Copyright. magazine. CFS Load Bearing Construction

Similar documents
Masonry and Cold-Formed Steel Requirements

ISSUE A Code Change # 2 Class 3 and Class 4 Buildings

Building Division Informational Handout

North Shore at Canton Baltimore, MD Beau Menard Technical Report 1

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity

Nabil A. Rahman, Ph.D., P.E.

ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC.

VARIOUS TYPES OF SLABS

Technical Report 1. Seneca Allegany Casino Hotel Addition. Salamanca, NY

Structural Technical Report #2 Pro/Con Study of Alternate Floor Systems

Stone and Masonry Veneer

Technical Report 1. Hakuna Resort Swift Water, Pennsylvania. Image Courtesy of LMN Development LLC

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC)

Earth and Engineering Sciences Building University Park, Pennsylvania

Rutgers University Law School Building Addition and Renovation Camden, NJ

MECHANICAL BRIDGING AND BRIDGING ANCHORAGE OF LOAD BEARING COLD-FORMED STEEL STUDS. Paul E. Lackey, EIT Nabil A. Rahman, Ph.D.

Footings GENERAL CONSIDERATIONS 15.2 LOADS AND REACTIONS 15.4 MOMENT IN FOOTINGS

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

[TECHNICAL REPORT 3] Lateral System Analysis

North Mountain IMS Medical Office Building

OVERALL STRUCTURAL SYSTEM

Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Consultant: Dr. Hanagan

SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series

COFS Mission. AISI Standards Hierarchy. North American Standards for Cold-Formed Steel Framing. Member versus System Design. Specification 10/21/2016

Strategies for mitigation of progressive collapse of corner panels in reinforced concrete buildings

OF THREE NEW BUILDINGS BEING CONSTRUCTED TO REPLACE THE EXISTING COMPLEX. THE FLOOR SYSTEM OF GEORGE READ HALL IS A HAMBRO COMPOSITE SYSTEM

John Jay College Expansion Project

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures

Table of Contents.2. Introduction...3 Gravity Loading and Deflections..4. Existing Structural System..8

Letter of Transmittal

Technical Assignment 3 December 3, 2007

William W. Wilkins Professional Building Columbus, Ohio

AREMA 2008 Annual Conference. LOW PROFILE RAILROAD BRIDGE Steve K. Jacobsen, PE NNW, Inc. Rochester, Minnesota

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5

4.6 Procedures for Connections

David A. Walenga Technical Assignment #1

Hyatt Place North Shore. Pittsburgh, PA T. Technical Assignment #1. Kyle Tennant. Kyle Tenn. Structural (IP) [Type the document subtitle]

Case Study in Steel adapted from Structural Design Guide, Hoffman, Gouwens, Gustafson & Rice., 2 nd ed.

SECTION COLD-FORMED METAL FRAMING

Pulaski County, Virginia Practical Wall Bracing

SECTION NON-STRUCTURAL METAL FRAMING

APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES

Thesis Proposal 12/13/06

STEEL STRUCTURAL SYSTEMS

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

Thesis Proposal Structural Redesign / Cost, Schedule and Coordination Analysis / Architectural Impact

Lateral Design of Mid- Rise Wood Structures

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC)

The Structural Redesign of Boyds Bear Country and its Related Systems. Boyds Bear Country, Pigeon Forge, Tennessee

Jackson Crossing Located in Alexandria, VA. Technical Report 1 Michael Bologna

Office Building-G. Thesis Proposal. Carl Hubben. Structural Option. Advisor: Dr. Ali Memari

Bijan Khaleghi, Ph, D. P.E., S.E.

111 MORGAN ST. Ryan Friis

ALTERNATE DESIGN METHODOLOGY FOR UNREINFORCED MASONRY BUILDINGS

Light Steel Framing Members. Table of Contents

Structural Redesign Gravity System

THE FORENSIC MEDICAL CENTER

Dead Loads (psf): Concrete Floor Slab on Metal Deck 45 psf Mechanical and Ceiling 7 psf Miscellaneous 5 psf Exterior Wall 80 psf

Light Steel Framing Members. Table of Contents

ADDENDA #9- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services

151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University

Investigation for the Removal of Steel Tie Rods in a Historic Segmental Arch Floor

R Code and Commentary for 2012 NC Residential Code final 03/06/13

Connect Easily to Insulated Concrete Forms

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania

Technical Report #2. Matthew R Peyton

Lateral System Analysis and Confirmation Design November 15, 2004

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2

CORPORATE HEADQUARTERS

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

Project. San Jose City College Physical Education Building. Prepared For. Prepared By PLACE IMAGE HERE. Ken Bauer, AIA Principal

Interior Hangers. Application

Mandatory Wood Frame Soft-story Retrofit Program STRUCTURAL DESIGN GUIDELINES

Caitlin Ferrell Structural Option Dr. Boothby, AE Faculty Consultant. Erie Convention Center and Sheraton Hotel

Belmont Executive Center; Building A

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California

DESIGN AND ANALYSIS OF PRECAST CONCRETE BRIDGES IN AREAS OF HIGH OR MODERATE SEISMICITY

STATEMENT OF SPECIAL INSPECTION FORM

RCKW Kneewall Connectors

Residential Deck Safety, Construction and Repair. Juneau Permit Center, 4 th Floor Marine View Center,(907) February 2016

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

Fairfield Inn and Suites Pittsburgh, PA

Atkinson Engineering, Inc.

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

Eric Alwine Structural Option George Read Hall The University of Delaware Dr. Boothby Technical Assignment #2 October 31, 2005 EXECUTIVE SUMMARY:

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading

S p a c e e l e v a t o r. Structure selection and design Prof Schierle 1

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Alexis Pacella Structural Option Dr. Schneider Lexington II, Washington D.C. Technical Report #3 November 21,

ENTRY FORM. DVASE 2014 Excellence in Structural Engineering Awards Program

Transcription:

Progressive Collapse Requirements Cold-Formed Steel Load Bearing Construction By Nabil A. Rahman, Ph.D., P.E., Michael Booth and Gary Bennett Figure 1: Cold formed steel load bearing mid-rise construction. In 2001, the Department of Defense (DoD) published its design guidelines to resist the progressive collapse of structures resulting from an extreme loading event in the Unified Facilities Criteria UFC 4-023-03 Design of Buildings to Resist Progressive Collapse. This document provides the design requirements necessary to reduce the potential of progressive collapse for new and existing DoD facilities. The use of UFC 4-023-03 is controlled by the applicability requirements of UFC 4-10-01 document DoD Minimum Antiterrorism Standards for Buildings. UFC 4-023-03 covers the design strategies and requirements for buildings made of reinforced concrete, structural steel, masonry, wood, and cold-formed steel (CFS). The criteria includes design examples and design details for all the above materials except cold-formed steel. It is the objective of this article to discuss the progressive collapse requirements in UFC 4-010-01 and UFC 4-023-03 as it relates to mid-rise construction using cold-formed steel load bearing walls. CFS Load Bearing Construction In the opinion of the authors, the use of CFS load bearing framing in typical mid-rise construction (Figure 1) brings the value of reducing associated construction cost in comparison to other structural framing systems such as reinforced masonry, structural steel and wood. A key component of the cost savings is the lighter mass of the structure relative to the design of the lateral force resisting system and the foundation. It is important to note that several types of floor systems can be integrated with CFS load bearing walls. Among these types are composite steel deck-concrete slabs, CFS joists or open bar joists with a concrete or wood floor diaphragm, and pre-cast hollowcore concrete planks. The structural system combining CFS load bearing walls and hollowcore planks is ideal for low and mid-rise construction of three to eight stories in height. Because precast hollowcore concrete planks provide the advantages of high stiffness-to-weight ratio and rapid field installation, this allows for a wide range of building usage including apartment buildings, office buildings, health care facilities, hotels, schools, and dormitories. Progressive Collapse Requirements UFC 4-010-01 requires that all new and existing buildings of three stories or higher be designed to avoid progressive collapse. UFC 4-023-03 offers two levels of design procedures to resist progressive collapse: The first level of progressive collapse design employs the Tie Forces method, which is based on the catenary (membrane tension) response of the structure. This design level may be used for buildings assigned Very Low and Low Levels of Protection (VLLOP and LLOP). ties only are required for buildings assigned VLLOP, while horizontal and vertical ties are required for buildings assigned LLOP. The second level of progressive collapse design employs the Alternate Path method, which is based on flexural performance of the floor system, as the building must bridge across removed vertical supporting elements. This design level must be used for building assigned Medium and High Levels of Protection (MLOP and HLOP). Tie Forces requirements and additional ductility requirements must be also satisfied for MLOP and HLOP. In the case that an adequate Tie Force cannot be developed in a vertical structural element, then the Alternate Path method is allowed to be used to verify that the building can bridge over the deficient element. DoD mid-rise building projects include, but are not limited to, housing facilities (barracks) in addition to dining, gathering, operations centers, administrative buildings, and health care facilities. These types of facilities are typically assigned VLLOP or LLOP (UFC 4-010-01, Table B-1). As a result, the Tie Forces method can be used by the designer to satisfy the progressive collapse resistance part of the design. The Tie Forces method is a simple, indirect design approach that enhances the continuity, ductility and structural redundancy of the building by requiring horizontal and vertical ties to mechanically keep the building together in the event of an extreme loading that causes local damage. Figure 2 (see page 10) Codes and Standards updates and discussions related to codes and standartds STRUCTURE 9 August 2007

Internal Ties (dotted lines) Corner Column Ties b) In each bay (one at a time) and at all floors and the roof, the slab/floor system must be able to withstand a net upward factored load of: 1.0D + 0.5L Eq. 3 Tie to External Column or Wall Internal Ties Floor/Roof Tie Force Requirements The requirements for floor and roof internal ties vary based on the construction material used. As a general rule: internal ties must be provided at each floor and roof level in two directions; they must be effectively continuous; and they must be anchored to peripheral ties at each end. Additionally, they may be spread evenly or grouped. In walls, these ties must be within 1.6 ft. of the top or bottom surface of the floor diaphragm. Vertical Peripheral Tie Tie For reinforced concrete and CFS floor (dashed lines) and roof systems, internal ties must have a required tensile strength (in kips/ft width) equal to the greater of: Figure 2: Tie forces in a frame structure (Reference UFC 4-023-03). (1.0D+1.0L)l shows the different types of ties that must Other additional design requirements that r 1.0 F Eq.4 8475.2 t or F 3.3 t be provided in the building design. There apply to all levels of protection (VLLOP are two main groups of ties; horizontal and through HLOP) are: vertical. ties include internal a) Multistory vertical load bearing Table 1: Unfactored Design Loads ties within the floor system, ties to edge elements must be capable of supporting columns or walls, ties to corner columns, the vertical load after the loss of lateral Dead Live Wind and peripheral ties around the perimeter of support at any floor level with an unsupported length (L u ) of: Load Load Load the building. While horizontal ties must Roof 20 psf 20 psf ±15 psf provide a straight continuous load path from L one building edge to the other, vertical ties u = 2 l s Eq. 1 Ceiling 15 psf must provide a straight continuous load path where l s is the floor height in (ft). This Typical Floor in columns and load bearing walls. Along a should be analyzed with the following (other than 80 psf 40 psf particular horizontal or vertical load path, factored load combination: Corridor) different structural elements may be used to (0.9 or 1.2)D + Corridor 80 psf 100 psf provide the required tie strength. Adequate (0.5L or 0.2S) + 0.2W Eq. 2 manufactured connections must be provided Exterior Walls 48 psf 25 psf between these structural elements to ensure where D is Dead Load, L is Live Load, the continuity of the load path. S is Snow Load and W is Wind Load. Interior Walls 12 psf 5 psf Exterior CFS Load Bearing Wall N Interior CFS Load Bearing Wall Corridor Beam 26-9 59-8 6-2 26-9 Direction C o r r i d o r Exterior CFS Load Bearing Wall Max. Panel = 25-8 Direction Columns Stairs 9-4 330-4 Figure 3: Typical floor plan. STRUCTURE 10 August 2007

where D and L are in pounds-per-square-foot (psf) and l r is in feet. F t is the Basic Strength which is the lesser of (4.5 + 0.9 n o ) or 13.5 for reinforced concrete floor/roof systems and the lesser of (1.62 + 0.33 n o ) or 4.92 for CFS floor/roof systems. The variable n o is the number of stories. Cold-Formed Steel Walls Tie Force Requirements Peripheral Ties At each floor level and roof level, provide an effectively continuous peripheral tie capable of sustaining a required tensile strength equal to: 1.0 F t (kips) Eq. 5 This tie must be located within 3.9 ft. of building edges or within the perimeter wall. Ties to External Walls Every 3.3 ft. length of external load bearing wall must be tied horizontally into the structure at each floor and roof level with a tie having a required tensile strength equal to the greater of: a) Lesser of 2.0 F t or Eq. 6 8.2 F t l s or b) 3% of the total ultimate vertical load carried by the wall at that level where l s is in (ft). Where the peripheral tie is located within the wall, provide horizontal ties adequate to anchor the internal ties to the peripheral ties. Table 2: Required Tie Forces Tie Force Internal, TF i (Floor) Internal, TF i (Corridor) Peripheral TF p Basic Strength F t = lesser of (4.5 + 0.9 n o ) or 13.5 n o = 4 F t = 8.1 F t = lesser of (1.62 + 0.33 n o ) or 4.92 Reference Equation Equation (4) Equation (4) to External n o = 4 Equation (6) Walls TF e F t = 2.94 Vertical TF v (Walls) Vertical TF v (Columns) N/A ADVERTISEMENT For Advertiser Information, visit www.structuremag.org Vertical Ties Tie each column and load-bearing wall continuously from the lowest to the highest level. The tie must be capable of resisting a sile force equal to the maximum design Parameters D = 80 psf L = 40 psf l r (E-W) = 25 8 l r (N-S) = 26 9 D = 80 psf L = 100 psf l r (E-W) = 25 8 l r (N-S) = 6 2 Required Force TF i (E-W) = 2.94 kips/ft TF i (N-S) = 3.07 kips/ft TF i (E-W) = 4.41 kips/ft TF i (N-S) = 2.45 kips/ft Equation (5) TF p = 2.94 kips Equation (7), one story Equation (7), one story l s = 11 4 Max. 3.3-ft. wall load (E-W) = 27.2 kips Max. 3.3-ft. wall load (N-S) = 15.4 kips TF e (E-W) = 1.23 kips/ft TF e (N-S) = 1.23 kips/ft TF v (Interior) = 4.3 kips/ft TF v (Exterior-Sides) = 2.7 kips/ft TF v (Exterior-Long) = 2.3 kips/ft TF v (Columns) = 20.3 kips STRUCTURE 11 August 2007

ADVERTISEMENT For Advertiser Information, visit www.structuremag.org Simpson Strong-Tie Design Tip The New CTUD: A Unique Rod Coupling Take-Up Device The NEW Anchor Tiedown System (ATS) is designed to anchor stacked shearwalls in multi-story wood frame buildings while compensating for settling within the structure. The rods and bearing plates within the continuous rod tiedown system are joined together by the new Coupling Take-Up Device (CTUD). The CTUD is a spring-driven rod coupling device which contracts to compensate for rod movement caused by settling. This helps ensure that no slack develops in the system that could compromise its performance. The simplicity of the CTUD also simplifi es installation, reducing labor costs over other systems. For more information visit www.strongtie.com or call (800) 999-5099 to request a copy of the ATS Catalog (C-ATS07). 2007 Simpson Strong-Tie Company Inc. ATSDT07 Wall Bottom Track (Min. 54 Mil) Pour-Stop Angle Wall Top Track (Min. 54 Mil) Stiffener Plate ultimate dead and live load received by the wall or column from any one story: 1.2D + 1.6L (kips) Equation 7 This is the 2003 IBC factored load combination. Worked Design Example Building Description A four-story barracks building designed with CFS load bearing walls and hollowcore precast concrete planks for the floor slabs is considered in this example. The barracks building is assigned LLOP and is approximately 330 feet long and 60 feet wide, with an 11-foot, 4- inch floor to floor height and a CFS truss roof system. The building incorporates a normal weight brick veneer finish on the exterior walls. The typical structural system consists of interior and exterior load bearing walls in the N-S direction that have variable spacing between the bearing walls with a maximum span of 25 feet, 8 inches (Figure 3, see page 10). Exterior walls in the E-W direction are also load bearing walls, but only support the truss roof loads in addition to their self weight and the lateral wind pressure. The interior corridor is supported by corridor beams resting on individual CFS columns at the inside edges of the load bearing walls. Hollowcore planks are selected to be 8 inches thick to accommodate the maximum span of 25 feet, 8 inches between the N-S load bearing walls. The planks require a seating/ bearing width of 2 to 2.5 inches on top of the stud walls as recommended by the 1998 Design Manual of the Precast/Prestressed Concrete Institute. A minimum of 6-inch STRUCTURE 12 August 2007 6 Stud Wall Screw Connection 22 Bearing Figure 4: Peripheral tie and horizontal tie connection to external wall. #4 Reinforcement Bars Grouted in 6 Stud Wall width wall framing can accommodate the required plank seating width, but 8- inch walls are typically recommended for interior walls to allow enough gap between planks to insert diaphragm connectors. The unfactored design loads for this building are summarized in Table 1 (page 10). Required Tie Forces This barracks building is considered a composite construction since it has CFS walls and columns with hollowcore concrete slabs and CFS roof trusses. Hence, the floor system is required to meet the internal tie requirements for reinforced concrete design while the roof system is required to meet the internal tie requirements for CFS design. The walls and columns are required to meet the peripheral, external and vertical tie requirements for CFS design, as applicable. Appropriate over-strength factors (W) and strength reduction factors (F) must be used for different materials as given in UFC 4-023-03. The required horizontal and vertical tie forces for the typical floor and interior and exterior walls and columns for this building are calculated as given in Table 2 (see page 11) to generate tie schemes and mechanical connections. Tie Forces Schemes a) Internal Ties Hollowcore The required internal tie forces between hollowcore planks can be achieved using various connection details offered by the Precast/ Prestressed Concrete Institute to satisfy their structural integrity and diaphragm action requirements. Reinforcement steel continued on page 14

bar ties may be run inside the core of the planks in their longitudinal direction and in the connection joint between the planks in their perpendicular direction. Grouting is used to provide the bond between the steel bars and the planks. Reinforcement steel bars can also be used in the concrete topping in the longitudinal direction of the planks, in addition to shorter anchored bars to tie adjacent planks in the perpendicular direction. Using #4 Grade 60 rebar (60 ksi yield strength) spaced 2 feet on center satisfies all the internal tie force requirements (Maximum required strength = 4.41 kips/ft). b) Peripheral Ties The required peripheral ties around the perimeter of the building can be achieved through the steel runner tracks bounding the exterior load bearing CFS stud walls. 6-inch exterior stud walls are recommended along with a minimum of 54 mil (0.0566-inch design thickness) runner tracks (Figure 4, see page 12). A single 33 ksi yield strength standard track (1.25-inch flange) provides an ultimate tensile strength of 14 kips, which exceeds the required strength of 2.94 kips. Care must be taken at splice locations of runner tracks in order to provide a splice connection capable of resisting the required tensile strength. Another method to provide the required peripheral ties is to use longitudinal steel bars embedded in the end grout. Two #4 Grade 60 rebar provide an ultimate tensile strength that exceeds the required tie strength. c) Ties to External Walls The required horizontal ties to external walls can be achieved by using reinforcement steel bars grouted into the hollowcore planks from A325 2 Bolts one side and anchored to the runner tracks of the CFS stud walls from the other side. Figure 4 (see page 12) shows these ties where the planks are supported by the stud wall and transferring vertical loads (E-W direction of the barracks building). Similar ties should be provided where the planks are only resting on the stud wall but not transferring any vertical loads (N-S direction of the barracks building). Anchorage of the horizontal ties to the runner tracks ensures the continuity between internal ties and peripheral ties as required by UFC 4-023-03. Number 4 Grade 60 rebar can be used at spacing 2 feet on center, which provides a tensile strength that exceeds the required strength of 1.23 kips/ foot. If steel bars are used as peripheral ties, the horizontal ties must extend to overlap with the peripheral ties to provide the required anchorage between the two sets of ties. d) Vertical Ties The specifications for vertical ties are the most critical requirements in this building s structural system due to the relatively heavy weight of the floor slab. For interior load bearing walls, mechanical connectors are T- shape steel sections made of d-inch thick plates welded together with stiffeners and attached to both the bottom and top studs of the wall with ½ inch bolts (Figure 5). The T- shape connectors are tied together using two ½-inch through bolts that run through the separation gap between the planks. A tested T-shape connector with the same dimensions provides a tensile strength of about 21.8 kips. Use of this connector to tie every third stud (every 4 feet) in interior walls would satisfy the required tensile strength of 4.3 kips/foot Min. 6 Stud Wall 8 Recommended A (4.3 kips/ft x 4 ft = 17.2 kips < 21 kips). The tensile capacity of two 2-inch through bolts exceeds the required tensile strength. The number of ½-inch bolts required to connect the T-shape to the studs (acting in shear) is dependant on the thickness of the stud. For example, a stud that is 54 mils thick and 50 ksi yield strength requires eight ½-inch bolts to develop connection shear strength of 17.8 kips. The stud itself must also be checked to resist the same strength in tension. Similar or lighter mechanical connectors can be used for exterior load bearing walls in the N-S and E-W directions of the barracks building since the required tensile strength is significantly less. Corridor beams are typically designed as structural steel W-or WT-shape resting on top of the corridor columns. The columns are built-up CFS studs attached together with weld or screws, and capped from each end with a welded closure plate (Figure 6). The hollowcore planks rest on top of the structural steel beam. The required vertical ties for the columns can be achieved, as shown in Figure 6, first by welding the closure plate of the bottom CFS column to the W-shape steel beam. Then, four ½-inch through bolts (two on each side of the column) run through the hollowcore planks and are fastened at one end to the top flange of the W-shape beam and at the other end to the closure plate of the top CFS column. Stiffener plates for the W-shape steel beam are provided to connect the beam flanges together at the vertical tie location. The tensile capacity of four ½-inch through bolts exceeds the required tensile strength of 20.3 kips for the vertical tie. Stud Wall Wall Bottom Track Grout Stiffener Plate Screw Connection (2) 2 Through Bolts A325 2 Bolts T-Section Connector Wall Bottom Track Wall Top Track T-Section Connector Hollowcore A (2) Stiffener Plates 22 Bearing (A-A) Figure 5: Vertical tie connection in internal wall. STRUCTURE 14 August 2007

Column Closure Plate Welded to Column Wall Bottom Track Grout Wall Top Track (2) Stiffener Plates Welded to Beam W-Shape Beam Column Closure Plate Welded to Column and Beam 3-Stud Built-Up CFS Column (Weld Attached) Figure 6: Vertical tie connection in corridor column. Design for Loss of Lateral Support Loss of lateral support for load bearing walls and columns necessitates that these load bearing elements be designed at any floor level with an un-supported length (L u ) that is twice the floor height (Equation 1). For CFS walls, the lateral direction of the wall is the strong-axis direction of the studs. Therefore, only the strong-axis unsupported length of the studs should be doubled when design is performed to satisfy this requirement. In addition, the loss of the lateral support in exterior walls subjected to lateral wind pressure requires that the connection between wall sections must be capable of resisting the resulting bending moment; otherwise the wall system becomes unstable under lateral wind loads. The governing factored load combination to design this condition is given in Equation 2 and the factored design load would be (0.2W). For the barracks building under consideration, if this connection detail is used every third stud (every 4 feet), the maximum factored moment to be resisted for a continuous 22 feet, 8 inches beam is 15.4 in-kips. Conclusions This article summarizes the progressive collapse requirements in UFC 4-010-01 and UFC 4-023-03 as it relates to mid-rise construction using CFS load bearing walls. A worked design example for a four-story barracks building with CFS load bearing walls and hollowcore precast concrete slabs assigned LLOP has been used to demonstrate that all the tie forces requirements can be achieved through existing structural elements of the building or added mechanical connections. Special requirements such as Wall Typical Stud Stiffener Plate Hollowcore (4) 2 Through Bolts (2 per Side of Column) loss of lateral support in exterior walls have also been discussed. Design details have been proposed for all the tie forces requirements and special requirements. If CFS load bearing walls are used with other floor systems (such as composite steel deck or CFS joists), some of the presented design details will need to be adjusted accordingly; however, the same method of achieving the tie forces requirements would still apply. come work with us www.kpff.com Nabil A. Rahman, Ph.D., P.E. is the Director of Engineering & Research for The Steel Network, Inc. Dr. Rahman currently serves as the Chairman of the Wall Stud Task Group of the Committee on Framing Standards (COFS) of the American Iron and Steel Institute (AISI). He is also a member of the ASCE-SEI Committee on Cold-Formed Steel, as well as the AISI Committee on Specification. He can be reached via e-mail at nabil@steelnetwork.com. Michael Booth is the Director of Project Management at The Steel Network, Inc. Mr. Booth has held the titles of Regional Sales Manager and National Manager of Technical Services, in addition to 20+ years experience within the construction industry. He can be reached via e-mail at mbooth@steelnetwork.com. Gary Bennett is the Engineering Services Manager for the Steel Network, Inc. Mr. Bennett has extensive experience in design and analysis of cold formed steel structures. Mr. Bennett is a member of several sub-committees for AISI-Committee on Specification (COS). He can be reached via e-mail at gbennett@steelnetwork.com. Southwest Washington Medical Center Vancouver, Washington Photo: Denny Sternstein Seattle, WA Tacoma, WA Portland, OR Sacramento, CA San Francisco, CA Los Angeles, CA Irvine, CA San Diego, CA Phoenix, AZ Denver, CO St. Louis, MO New York, NY ADVERTISEMENT For Advertiser Information, visit www.structuremag.org STRUCTURE 15 August 2007