HVAC SPECIFICATION DETAIL GUIDE. A guide to specifying ROCKWOOL insulations for HVAC applications

Similar documents
The thickness of ROCKWOOL insulation

DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks.

DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks.

Ductslab and Ductwrap

condensation condensation condensation condensation condensation surfa sur surfa surfa surfa surfa design cold face design cold face design cold face

Ductslab and Ductwrap

Guide to Enhanced Capital Allowances

RockLap H&V pipe sections

TECHWRAP2 AND TECHTUBE Acoustic solutions for pipework and equipment

KoolthermTM FM. Project Specification. HVAC & Building Services Pipe Insulation

FOR FURTHER INFORMATION ON THE KOOLTHERM RANGE OF PRODUCTS PLEASE TELEPHONE THE KINGSPAN TECHNICAL SERVICES DEPARTMENT (01457)

Kooltherm FM. Quick Guide HVAC & Building Services Pipe Insulation. UK & Ireland

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts.

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts.

Mechanical Services Standard Specification Thermal Insulation. May For ROYAL HOLLOWAY UNIVERSITY OF LONDON

Fire protection for timber frame & masonry cavity walls

Technical Submission Spiralite Pre-insulated Ductwork

RH & RV CAVITY BARRIERS

PIPEWORK INSULATION. 14/ Page 1 of 10 Pipework Insulation Rev D

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

TCB & PWCB CAVITY BARRIERS Fire Protection for timber/steel frame & masonry cavity walls

Revision:C Pipework Insulation Issued:14/11/2012 PIPEWORK INSULATION CU14. 14/11/2012 Page 1 of 10 Pipework Insulation - RevC

Product Data Sheet. Product: Benchmark Wall Liner System

Division 15 INSULATION Section 15100

Product Data Sheet (rev c 16/7/15) Product: BENCHMARK Roofliner System

This specification describes the minimum requirements for industrial thermal insulation.

EDITION RTI - UK & I - PUBLISHED 10/2013 NEW PRODUCT NAMES. PROROX Industrial insulation. Product catalogue UK & Ireland

Insulation TECHNICAL DATA SHEET. Low Energy Low Carbon Buildings. CI/SfB (57.9) In7 (M2) First Issue April 2016

Kooltherm FM. Quick Guide. HVAC & Building Services Pipe Insulation System. UK & Ireland

Date of update January 25, 2018 Valid until

B. Refer to Section : Air Distribution for lined ductwork requirements.

Light steel frame walls

Fire performance of curtain walls and rainscreens

KINGSPAN KOOLDUCT SYSTEM. Product. Scope. Building Regulations. Appraisal No. 771 [2017]

EXPERIENCE COUNTS! Specializing in more than just products we put the competitive advantage at your fingertips.

SP FIRESTOP VRB Open-state cavity fire barrier for use within building facades

Design & Construction Standards, Revised January

ACOUSTIC BARRIERS DWX SERIES FOR DUCTWORK

Kooltherm FM. Quick Guide. HVAC & Building Services Pipe Insulation System. UK & Ireland

K15 Rainscreen Board. Insulation INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS

CLIMAVER ductwork system. Saves valuable space, reduces installation time and is more cost-effective

EDITION: EXPORT - PUBLISHED: 11/2012 NEW PRODUCT NAMES. ProRox. Product catalogue. Industrial insulation

PRODUCT APPLICATION MANUFACTURER INTRODUCTION CERTIFICATION PROCEDURE. Date of update April 6, 2018 Valid until

PRODUCT TECHNICAL DATA SHEET WEATHER PRO TM INSULATION JACKET

Suspended timber upper floors

PRODUCT CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE

HP Partial Fill. Robust, long-lasting protection

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

SP FIRESTOP SYSTEMS The purpose-made solution for cavity fire stopping

EDITION: EXPORT - PUBLISHED: 11/2013 NEW PRODUCT NAMES. ProRox. Product catalogue. Industrial insulation

Insulation AN INTRODUCTION. Low Energy Low Carbon Buildings. Fourth Issue August 2018

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

RAINSCREEN DUO SLAB. Non-combustible thermal insulation

FIRE STATION 55 June 14, 2010

NEW. Product catalogue UK & Ireland. Wired Mat ASSORTMENT. PROROX Industrial insulation SEAROX Marine & Offshore Insulation. rockwool-rti.co.

CERTIFICATE OF APPROVAL No CF 5073 LEMINAR AIR CONDITIONING INDUSTRIES L.L.C.

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC INSULATION

Kooltherm FM. Quick Guide. HVAC & Building Services Insulation System

INSTALLATION GUIDELINES FOR CHILL WATER PIPE INSULATION

ROCKWOOL ABLATIVE COATING Improves the fire resistant properties for ROCKWOOL stone wool slabs

Process plant insulation and fuel efficiency

SP FIRESTOP OSCB 60 & 120 Open-state cavity barrier only for use with RAINSCREEN DUO SLAB

Gulf Cool Therm Polyisocyanurate (PIR) Insulation

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

BEAMCLAD SYSTEMS. Fire protection solutions for structural steel & soffit protection

MANUFACTURING TOLERANCES FOR PROFILED METAL ROOF AND WALL CLADDING

Insulation AN INTRODUCTION. Low Energy Low Carbon Buildings. Third Issue September 2017

Revolutionary Spacer Support Bar and Bracket System for Built Up, Twin Skin Roofing and Cladding Applications

RAINSCREEN CLADDING SOLUTIONS

.1 Thermal insulation for insulated piping and piping accessories affected by construction and new pipe sections as indicated on drawings.

SIDERISE SC cavity barriers & fire stops for suspended ceilings

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2

Addendum 1 Section THERMAL INSULATION FOR PIPING Burrow Avenue Pumping Station Upgrades Page 1 of 5

Sarnavap 5000E SA Vapour Control Layer

Jabfloor 70, 100, 150, 200, 250

EDITION: UK & I - PUBLISHED 02/2015. PROROX Industrial insulation SEAROX Marine & Offshore Insulation. Product catalogue UK & Ireland

Duct Insulation. Kingspan. Insulation RIGID INSULATION FOR OUTDOOR RECTANGULAR, CIRCULAR AND FLAT OVAL HVAC DUCTWORK. Low Energy Low Carbon Buildings

August 2008: Issue 1. Non - Residential New Build Built - up Metal Walls

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

WALL LINER PRODUCT DATA SHEET FAÇADE & ROOF SYSTEMS

Floors Walls Roofs. Jablite Premium board Jablite board. APPLICATION: Internally Lined Pitched Roof PRODUCTS: Vencel Resil Limited

Table of contents. Tapes 4. Fiberglass Cloth 9. Fastening Systems 11. Polyurethane Foam 17. Rockwool 19

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

Fire damper frequently asked questions for ASFP

Superior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803

Superior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803

RW SEMI-RIGID AND RIGID SLABS (RWA45, RW3, RW4, RW5 & RW6)

HVAC INSULATION. A. General Requirements for Flexible Elastomeric Insulation: 3. Use pre-molded roll on pipe sizes 3.5" and below.

WALLSPAN. Insulated Panels for a Clean World

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

CRYOGENIC SUPPORTS INTRODUCTION

Superior Performance Phenolic Insulation. SR/RS Insulation for Ventilated Rainscreen Cladding. Walls 10/4803

Jabfloor High Performance (HP) 70 and 100

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

Cold Work Insulation (Advanced)

60MM ABLATIVE COATED BATT Fire stopping solution for voids in walls and floors

Superior Performance PIR Insulation XO/FB. Insulaton for Steel & Timber Frame. Walls 12/4956

INTERPLANT STANDARD - STEEL INDUSTRY CODE OF PRACTICE FOR THERMAL. Based on IS 7240:1981 (Superseded by IS 14164:2008)

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED

Transcription:

HVAC SPECIFICATION DETAIL GUIDE A guide to specifying ROCKWOOL insulations for HVAC applications

1. General Insulation materials should have a Euroclass of either A1, A2, or B, should have a FIGRA RCT of less than 1.0, and should not have a potential to flashover. The Lambda value of the Insulation must also be quoted, both manufactured and aged value. Insulation materials shall have a Global Warming Potential (GWP) of zero and an Ozone Depletion Potential (ODP) of zero. For all mineral wool insulation products, test evidence must be available showing that the fibres from which the products are made are not classified as a possible human carcinogen, as detailed by European Directive 97/69/EC and the Approved Supply List of CHIP98. 2. Specialist thermal insulation sub-contractor Include for all thermal insulation to be carried out by an approved Specialist Thermal Insulation Contractor selected from the list of preferred Specialist Contractors scheduled elsewhere in this specification. Specialist Thermal Sub- Contractor shall be a member of the :- Thermal Insulation Contractors Association TICA House Allington Way Yarm Road Business Park Darlington Co. Durham DL1 4QB Tel: 01325 466704 Fax: 01325 487691 3. Scope This specification covers the thermal insulation of pipes, ductwork and equipment generally in the temperature range of 0 C to 250 C. The specification is for guidance purposes only and should be read in conjunction with recommendations given in BS 5970 and BS 5422. The following British Standards are applicable to this thermal insulating specification: BS5422:2009 Method for specifying thermal insulating materials for pipes, tanks, vessels, ductwork and equipment operating within the temperature range -40 C to +700 C. BS 5970:2001 Code of practice for thermal insulation of pipework and equipment (in the temperature range 100ºC to +870ºC). BS 3533:1981 Glossary of thermal insulation terms. BS EN 14303:2009 Thermal insulation products for building equipment and industrial installations. Factory made mineral wool products (MW). BS 874:1986 Methods for determining thermal insulating properties with definitions of thermal insulating terms. BS 2972:1989 Methods of test for inorganic thermal insulating materials. BS 476 - Part 4:1970 Fire tests on building materials and structures. Non-combustibility test for materials. BS 476 - Part 6:1989 Fire tests on building materials and structures. Method of test for fire propagation of products. BS 476 - Part 4:1970 Fire tests on building materials BS 476 - Part 4:1970 Fire tests on building materials and structures. Method of test to determine the classification of the surface spread of flame of products. BS 1710 Specification for identification of pipelines and services. 2

4. Internal services - concealed from view (false ceilings/voids/chases) 4.1 Heating/HWS Pipes to be insulated with... *mm thick ROCKWOOL RockLap H&V Pipe Sections, having a nominal density not less than 120 kg/m 3, with a factory applied facing which is a laminate of close mesh reinforcement between two layers of foil including integral lap for fixing. The whole to comply with BS5422:2009 and BS 5970 water vapour permeance and Building Regulations Class O definition. Fixing to be in accordance with manufacturer s instructions, by peeling protective tape from self-adhesive lap and pressing lap smoothly over joint. Where adjacent Sections abut, approved 75 mm wide aluminium tape to be used to maintain integrity of the vapour barrier. *insert required 4.2 Chilled Water/CWS Insulation as 4.1. Attention to be paid to maintaining integrity of the vapour barrier. At termination points, insulation edges to be over-taped and returned to the piping surface. Where the insulation abuts pipe supports, the insulation is to be taped to all supports. 4.3 Ducting Insulation To be insulated with ROCKWOOL Ductwrap/Ductslab, nominal density 45 kg/m 3, having a factory applied reinforced aluminium foil facing. Joints to be securely taped with 75 mm minimum wide soft aluminium self adhesive tape. The insulation on the underside of the ducting to be additionally secured by suitable insulation hangers @ 300 mm centres. The whole to be further supported by means of:- 19-22 swg x 50 mm mesh galvanised wire netting. Where a vapour barrier is required, care to be taken when applying wire mesh support to avoid damaging the aluminium foil. or Aluminium Bands, circumferential at nominal 300 mm centres. Bands located over the outer surface typically 50 mm from the circumferential joint of the ROCKWOOL Ductwrap and Ductslab. Do not over tighten the aluminium bands, as this will locally reduce the of the insulation and reduce the thermal efficiency. N.B. Additional measures may be necessary to prevent sagging. For below ambient operating temperatures a vapour barrier is required, provision should be made, at exposed edges, to carry the aluminium foil to the duct surface. Where support pins/hangers puncture the foil, they should be sealed using aluminium foil tape to maintain the vapour barrier. Ductslab of the same density and facing as Ductwrap can be used where aesthetic or mechanical requirements prevail. For high velocity ductwork, insulation to be ROCKWOOL Lamella Mats. 4.4 Valve and Flange Insulation All valves and flanges on heating, HWS, CWS and chilled water pipework to be insulated with oversize ROCKWOOL RockLap H & V Pipe Sections. Finish and to be as adjacent pipework services. 5. Internal services exposed to view 5.1 Heating/HWS Generally as 4.1. Should the exposed pipework be liable to mechanical damage, i.e. sited at low level, the insulation to be protected with 22 gauge stucco embossed aluminium cladding secured with pop rivets. Aluminium securing bands may be omitted under cladding. 5.2 Chilled Water/CWS As specification 4.2. Where the insulation is protected with sheeting, care should be taken to ensure that the vapour barrier is not punctured by the rivets. Aluminium banding and seals may be used as an alternative to pop rivets. 5.3 Ducting Insulation As specification 4.3. Where aluminium cladding is used at low level, wire netting reinforcement to be omitted. 5.4 Valve and Flange Insulation As specification 4.4. Where insulation is finished with aluminium cladding, valve and flange boxes to be protected with purpose made aluminium covers. or Subject to the client s approval, alternative fixings can be used in place, or alongside the above. 3

6. Plant rooms/boiler houses/calorifier chambers 6.1 Heating/HWS To be insulated as specification 4.1, finished and protected with 22 gauge stucco embossed aluminium sheeting, secured by means of pop rivets at 225 mm centres. 6.2 Chilled Water/CWS To be insulated as specification 4.2, finished and protected with 22 gauge stucco embossed aluminium sheeting secured by means of aluminium banding and seals at 450 mm centres. Alternatively, if pop rivets are used, care should be taken to avoid puncturing the vapour barrier. 7. External services 7.1 Heating/HWS Generally as specification 4.1. Please select the finish from the list of alternatives below. 7.2 Chilled Water/CWS Generally as specification 4.2. Please select the finish from the list of alternatives below. 7.3 Ducting Insulation Generally as specification 4.3. Please select the finish from the list of alternatives below. 6.3 Ducting Insulation To be insulated with ROCKWOOL semi-rigid slabs, nominal density 45 kg/m 3, finished and protected with 22 gauge stucco embossed aluminium cladding secured with pop rivets at 225 mm centres. For high velocity and circular ductwork, insulation to be ROCKWOOL Lamella Mats. 6.4 Valve and Flange Insulation To be insulated with purpose made removable 22 gauge stucco embossed aluminium boxes, lined with ROCKWOOL ProRox WM960. 6.5 Heat Exchangers and HWS Calorifiers To be insulated with ROCKWOOL Lamella Mat finished and protected with 22 gauge stucco embossed aluminium cladding secured with pop rivets at 225 mm centres. Domed tops of calorifiers to be finished in segments. Manway chests, flanges and covers of heat exchangers to be enclosed in removable stucco embossed aluminium covers lined with ROCKWOOL ProRox WM960. 6.6 Boiler Flues Boiler flues and chimneys to be insulated as described in BS 5970 with a minimum of 50 mm thick ROCKWOOL ProRox WM960, finished generally as in Specification 6.1. 7.4 Valve and Flange Insulation Generally as specification 4.4. Please select the finish from the list of alternatives below. Alternative Finishes a) Flat Aluminium-Zinc Coated Steel Protection: Mild steel sheet continuously hot dipped with 185g/m 2 aluminium-zinc coating to BS EN 10326 and BS EN 10327, applied directly to insulating material. 0.4 mm thick flat sheet Fixed and installed in accordance with BS5790. b) Ribbed Aluminium-Zinc Coated Steel Protection: Mild steel sheet continuously hot dipped with 185g/m 2 aluminium-zinc coating to BS EN 10326 and BS EN 10327, applied directly to insulating material. 0.4 mm thick ribbed sheet Fixed and installed in accordance with BS5790. c) Aluminium Sheeting Protection: Apply flat (embossed) or profiled aluminium cladding directly to insulating material. 0.56 mm thick on pipework 0.71 mm thick on ductwork Fixed and installed in accordance with BS5790. 4

d) Mild Steel Sheet Mild steel sheet continuously hot dipped with aluminium-zinc coating to BS EN 10326 and BS EN 10327, applied directly to insulating material. Fixed and installed in accordance with BS5790. e) Self Adhesive Weather Resistant Zero Perm Multi-Layer Laminate: Apply multi-layer laminate directly over ducts and pipework, ensuring 75 mm overlap for a complete vapour barrier. Fixed and installed in accordance with BS5790. f) Polyisobutylene: Polyisobutylene, minimum 0.8 mm. Fixed and installed in accordance with BS5790. g) Roofing Felt Protection: Secure in position with galvanized wire netting, of 1 mm x 25 mm mesh. Finish with two coats of black bituminous paint. Fixed and installed in accordance with BS5790. 8. Insulation tables BS5422:2009 Method for specifying thermal insulating materials for pipes, tanks, vessels, ductwork and equipment operating within the temperature range -40 C to +700 C. One of the most significant changes to BS 5422 is that the es of insulation shown for pipe-work, ducts, plant and equipment are based on practical limits for all applications. For H&V applications, BS 5422 has adopted the es of insulation published by TIMSA (Thermal Insulation Manufacturers and Suppliers Association) as part of its guidance for achieving compliance with Part L of the Building Regulations - Domestic and Non-Domestic Heating, Cooling And Ventilation Guide (relevant to England, Wales and Northern Ireland). Scotland It should be noted that the Scottish Building Standards Authority (SBSA) Editions of the Technical Handbooks (Domestic & Non Domestic) to the Building Standards (Scotland) Regulations 2013, Sections 6, Energy, still refer directly to BS 5422:2009. ROCKWOOL stone wool insulation does not thermally age and therefore the es shown can be relied upon to provide the required insulation performance for the lifetime of the host structure. BS 5422 is not a prescriptive document and recognises that there are many reasons why the insulation of pipes, tanks, vessels, ductwork and equipment may be required. It is therefore important that specifiers state the criteria or specific clause or reference in this standard in any specification. Insulation es are given for a range of thermal conductivities appropriate to the usual materials used for the application; es for intermediate thermal conductivities and pipe sizes may be deduced by calculation or interpolation. For guidance in selecting appropriate types of insulation and suitable methods of application, reference should be made to BS 5970. BS 5422 is arguably the most important industry-wide standard for determining and specifying the requirements for thermal insulation used on pipe-work and equipment. Importantly, the appropriate insulation es taken from BS 5422 and used on pipe-work will be eligible for enhanced capital allowances (ECAs). In January 2009, BS 5422:2001 was superseded by BS 5422:2009. The new version of this standard is relevant to H&V and process work undertaken on sites across the UK, although additional factors may apply to building works undertaken in accordance with the Building (Scotland) Regulations, which still refer to BS5422:2001 as outlined below. 5

Table 6 (BS5422:2009) Minimum insulation for chilled and cold water steel pipes to control condensation on a high emissivity outer surface (0.9) with an ambient temperature of +25 C and a relative humidity of 80% Temperature of contents ( O C) Outside diameter of steel pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section +10 +5 0 17 8 20 11 20 14 20 21 9 20 12 20 15 20 27 9 20 13 20 16 20 33 10 20 13 20 16 20 42 10 20 14 20 17 20 48 10 20 14 20 18 20 60 11 20 15 20 18 20 76 12 25 16 25 20 25 89 12 25 16 25 21 25 102 12 25 17 25 21 25 114 12 25 17 25 22 25 140 13 25 18 25 23 25 169 13 25 18 25 24 25 219 13 25 19 25 24 25 245 14 25 19 25 24 25 273 14 25 19 25 24 25 324 14 25 20 25 25 25 356 14 30 20 30 25 30 406 14 30 20 30 26 30 456 14 40 20 40 26 40 508 15 40 20 40 26 40 558 15 40 21 40 26 40 610 15 40 21 40 27 40 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. In situations where the ambient air temperature is greater than 25ºC and/or the relative humidity exceeds 80%, these es will not be sufficient to control condensation. NOTE 2 These es only apply where the vapour barrier has a dark, matt finish. Table 7 (BS5422:2009) Minimum insulation for chilled and cold water copper pipes to control condensation on a high emissivity outer surface (0.9) with an ambient temperature of +25 C and a relative humidity of 80% Temperature of contents ( O C) Outside diameter of copper pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section +10 +5 0 10 7-10 - 12-12 8-10 - 13-15 8-11 - 14-22 9 20 12 20 15 20 28 9 20 13 20 16 20 35 10 20 13 20 17 20 42 10 20 14 20 17 20 54 11 20 14 20 18 20 76 12 25 16 25 20 25 108 12 25 17 25 21 25 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. In situations where the ambient air temperature is greater than 25ºC and/ or the relative humidity exceeds 80%, these es will not be sufficient to control condensation. NOTE 2 These es only apply where the vapour barrier has a dark, matt finish. 6

Table 8 (BS5422:2009) Minimum insulation for chilled and cold water steel pipes to control condensation on a low emissivity outer surface (0.05) with an ambient temperature of +25 C and a relative humidity of 80% Temperature of contents ( O C) Outside diameter of steel pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section +10 +5 0 17 16 20 22 25 28 30 21 17 20 24 25 30 30 27 19 20 26 30 32 35 33 20 20 27 30 34 35 42 21 25 29 30 37 40 48 22 25 31 35 39 40 60 24 25 33 35 41 45 76 26 30 36 40 46 50 89 28 30 38 40 48 50 102 29 30 40 40 50 50 114 30 30 41 45 52 60 140 31 35 43 45 55 60 169 33 35 46 50 58 60 219 35 35 49 50 62 70 245 36 40 51 60 64 70 273 37 40 52 60 66 70 324 39 40 55 60 70 70 356 40 40 56 60 71 75 406 41 45 58 60 74 80 456 43 45 60 60 76 80 508 44 45 61 70 78 80 558 45 45 63 70 80 80 610 46 50 64 70 82 90 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. In situations where the ambient air temperature is greater than 25ºC and/or the relative humidity exceeds 80%, these es will not be sufficient to control condensation. Table 9 (BS5422:2009) Minimum insulation for chilled and cold water copper pipes to control condensation on a low emissivity outer surface (0.05) with an ambient temperature of +25 C and a relative humidity of 80% Temperature of contents ( O C) Outside diameter of copper pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section +10 +5 0 10 14 N/A 19 N/A 24 N/A 12 15 N/A 20 N/A 25 N/A 15 16 N/A 22 N/A 27 N/A 22 18 20 24 25 30 30 28 19 20 26 30 33 35 35 20 20 28 30 35 35 42 21 25 29 30 37 40 54 23 25 32 35 40 40 76 26 30 36 40 46 50 108 29 30 40 40 51 60 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. In situations where the ambient air temperature is greater than 25ºC and/or the relative humidity exceeds 80%, these es will not be sufficient to control condensation. 7

Table 10 (BS5422:2009) Indicative of insulation for cooled and chilled water systems to control heat gain Low emissivity outer surfaces ( = 0.05) Outside diameter of steel pipe on which insulation has been based Temperature of contents ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section +10 +5 0 Heat gain (W/m) Heat gain (W/m) Heat gain (W/m) 17.2 13 20 2.48 17 20 2.97 21 25 3.47 21.3 14 20 2.72 18 20 3.27 22 25 3.81 26.9 15 20 3.05 20 20 3.58 24 25 4.18 33.7 16 20 3.41 21 25 4.01 25 25 4.60 42.4 17 20 3.86 22 25 4.53 27 30 5.11 48.3 18 20 4.11 23 25 4.82 28 30 5.45 60.3 18 20 4.78 24 25 5.48 29 30 6.17 76.1 20 25 5.51 27 30 6.30 36 40 6.70 88.9 20 25 6.17 28 30 6.90 33 35 7.77 114.3 21 25 7.28 28 30 8.31 34 35 9.15 139.7 21 25 8.52 29 30 9.49 35 35 10.45 168.3 21 25 9.89 29 30 10.97 37 40 11.86 219.1 22 25 12.27 29 30 13.57 37 40 14.61 273.0 22 25 14.74 29 30 16.28 37 40 17.48 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at 25ºC, emissivity of outer surface of insulated system as specified. NOTE 2 Thicknesses derived solely against the criteria noted in this table may not necessarily satisfy other design requirements such as control of condensation. NOTE 3 Heat gain relates to the specified and temperature. Table 11 (BS5422:2009) Indicative of insulation for cooled and chilled water systems to control heat gain High emissivity outer surfaces ( = 0.9) Outside diameter of steel pipe on which insulation has been based Temperature of contents ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section +10 +5 0 Heat gain (W/m) Heat gain (W/m) Heat gain (W/m) 17.2 18 20 2.48 23 25 2.97 26 30 3.47 21.3 19 20 2.72 24 25 3.27 27 30 3.81 26.9 20 20 3.05 27 30 3.58 29 30 4.18 33.7 22 25 3.41 27 30 4.01 31 35 4.60 42.4 23 25 3.86 28 30 4.53 33 35 5.11 48.3 24 25 4.11 29 30 4.82 35 35 5.45 60.3 24 25 4.78 31 35 5.48 36 40 6.17 76.1 27 30 5.51 34 35 6.30 43 45 6.70 88.9 27 30 6.17 35 35 6.90 40 40 7.77 114.3 28 30 7.28 35 35 8.31 42 45 9.15 139.7 29 30 8.52 36 40 9.49 43 45 10.45 168.3 29 30 9.89 37 40 10.97 44 45 11.86 219.1 29 30 12.27 37 40 13.57 45 45 14.61 273.0 30 30 14.74 37 40 16.28 45 45 17.48 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at 25ºC, emissivity of outer surface of insulated system as specified. NOTE 2 Thicknesses derived solely against the criteria noted in this table may not necessarily satisfy other design requirements such as control of condensation. NOTE 3 Heat gain relates to the specified and temperature. 8

Table 12 (BS5422:2009) Minimum insulation for condensation control on ductwork carrying chilled air in ambient conditions: indoor still air temperature +25 C, relative humidity 80%, dewpoint temperature 21.3 C Table 12 - Ductwrap External surface emissivity Minimum of ROCKWOOL Ductwrap Minimum temperature inside duct (OC) 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint) 15 26 30 13 25 9 25 10 45 50 23 25 15 25 5 64 70 33 40 21 25 0 83 90 42 50 27 30 Table 12 - Ductslab Minimum temperature inside duct (OC) External surface emissivity Minimum of ROCKWOOL Ductslab 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint) 15 26 30 14 25 9 25 10 47 50 24 25 15 25 5 67 70 34 40 22 25 0 86 90 44 50 28 30 NOTE 1 Thicknesses given are calculated in accordance with BS EN ISO 12241:2008 based on 0.6m vertical flat surface of rectangular duct but are also adequate for horizontal surfaces. NOTE 2 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. NOTE 3 Refer to Annex B, Table B. 1 for surface emissivities of common finishing materials. In situations where the ambient air temperature is greater than 25ºC and/or the relative humidity exceeds 80%, these es will not be sufficient to control condensation. Table 13 (BS5422:2009) Indicative of insulation for ductwork carrying warm air to control heat loss. Table 13 - Ductwrap Max Heat Loss (W/m 2 ) External surface emissivity Minimum of ROCKWOOL Ductwrap 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint) 16.34 31 40 37 40 39 40 Table 13 - Ductslab Max Heat Loss (W/m 2 ) External surface emissivity Minimum of ROCKWOOL Ductslab 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint) 16.34 32 40 38 40 41 50 NOTE 1 Heat loss relates to the specified and temperature. NOTE 2 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal duct at 35 C, with 600 mm vertical sidewall in still air at 15 C, emissivity of outer surface of insulated system as specified. 9

Table 14 (BS5422:2009) Indicative of insulation for chilled and dual-purpose ducting to control heat transfer Table 14 - Ductwrap Max Heat Loss (W/m 2 ) External surface emissivity Minimum of ROCKWOOL Ductwrap 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint) 6.45 50 50 58 60 61 70 Table 14 - Ductslab Max Heat Loss (W/m 2 ) External surface emissivity Minimum of ROCKWOOL Ductslab 0.05 (eg bright aluminium foil) 0.44 (eg dusty galvanised steel) 0.90 (eg black paint) 6.45 52 60 59 60 63 70 NOTE 1 Heat loss relates to the specified and temperature. NOTE 2 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal duct at 13ºC, with 600 mm vertical sidewall in still air at 25ºC, emissivity of outer surface of insulated system as specified. Table 15 (BS5422:2009) Indicative of insulation for non-domestic heating services to control heat loss low emissivity outer surfaces ( =0.05) Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 75 100 125 Heat gain (W/m) Heat gain (W/m) Heat gain (W/m) 17.2 24 25 8.90 24 25 13.34 24 25 17.92 21.3 28 30 9.28 30 30 13.56 30 30 18.32 26.9 31 35 10.06 37 40 13.83 37 40 18.70 33.7 33 35 11.07 44 45 14.39 46 50 19.02 42.4 35 35 12.30 48 50 15.66 64 70 19.25 48.3 37 40 12.94 49 50 16.67 67 70 20.17 60.3 39 40 14.45 57 60 18.25 71 80 21.96 76.1 44 45 16.35 60 60 20.42 76 80 24.21 88.9 45 45 17.91 62 70 22.09 79 80 25.99 114.3 47 50 20.77 65 70 25.31 85 90 29.32 139.7 48 50 23.71 68 70 28.23 89 90 32.47 168.3 49 50 26.89 70 70 31.61 92 100 36.04 219.1 50 50 32.54 72 80 37.66 96 100 42.16 273.0 50 50 38.83 74 80 43.72 99 100 48.48 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at 15 C, emissivity of outer surface of insulated system as specified. NOTE 2 Heat loss relates to the specified and temperature. NOTE 3 The es in this table are applicable to pipes serving commercial solar hot water panels. 10

Table 16 (BS5422:2009) Indicative of insulation for non-domestic heating services to controlheat loss high emissivity outer surfaces ( = 0.9) Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 75 100 125 Heat gain (W/m) Heat gain (W/m) Heat gain (W/m) 17.2 28 30 8.90 28 30 13.34 28 30 17.92 21.3 33 35 9.28 33 35 13.56 33 35 18.32 26.9 36 40 10.06 41 45 13.83 41 45 18.70 33.7 38 40 11.07 49 50 14.39 55 60 19.02 42.4 40 40 12.30 57 60 15.66 69 70 19.25 48.3 42 45 12.94 58 60 16.67 72 80 20.17 60.3 44 45 14.45 62 70 18.25 77 80 21.96 76.1 49 50 16.35 65 70 20.42 82 90 24.21 88.9 50 50 17.91 67 70 22.09 84 90 25.99 114.3 53 60 20.77 71 80 25.31 91 100 29.32 139.7 54 60 23.71 74 80 28.23 95 100 32.47 168.3 55 60 26.89 76 80 31.61 98 100 36.04 219.1 56 60 32.54 79 80 37.66 102 120 42.16 273.0 57 60 38.83 81 90 43.72 106 120 48.48 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at 15 C, emissivity of outer surface of insulated system as specified. NOTE 2 Heat loss relates to the specified and temperature. NOTE 3 The es in this table are applicable to pipes serving commercial solar hot water panels. Table 17 (BS5422:2009) Indicative of insulation for non-domestic hot water service areas to control heat loss Low emissivity outer surfaces Outside diameter of steel pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section Heat Loss (W/m) 17.2 23 25 6.60 21.3 25 25 7.13 26.9 27 30 7.83 33.7 29 30 8.62 42.4 30 30 9.72 48.3 32 35 10.21 60.3 33 35 11.57 76.1 35 35 13.09 88.9 35 35 14.58 114.3 38 40 17.20 139.7 39 40 19.65 168.3 40 40 22.31 219.1 40 40 27.52 273.0 41 45 32.40 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60 C in still air at 15 C, emissivity of outer surface of insulated system as specified. NOTE 2 Heat loss relates to the specified and temperature. 11

Table 18 (BS5422:2009) Indicative of insulation for non-domestic hot water service areas to control heat loss high emissivity outer surfaces Outside diameter of steel pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section Heat Loss (W/m) 17.2 27 30 6.60 21.3 29 30 7.13 26.9 32 35 7.83 33.7 33 35 8.62 42.4 35 35 9.72 48.3 37 40 10.21 60.3 35 35 11.57 76.1 43 45 13.09 88.9 43 45 14.58 114.3 44 45 17.20 139.7 45 45 19.65 168.3 46 50 22.31 219.1 47 50 27.52 273.0 48 50 32.40 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60 C in still air at 15 C, emissivity of outer surface of insulated system as specified. NOTE 2 Heat loss relates to the specified and temperature. Table 19 (BS5422:2009) Indicative of insulation for domestic heating and hot water systems having low emissivity outer surfaces Outside diameter of copper pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section Heat Loss (W/m) 8.0 - - 7.06 10.0 - - 7.23 12.0 - - 7.35 15.0 - - 7.89 22.0 15 20 9.12 28.0 17 20 10.07 35.0 18 20 11.08 42.0 19 20 12.19 54.0 20 20 14.12 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60 C in still air at 15 C, emissivity of outer surface of insulated system as specified. NOTE 2 Heat loss relates to the specified and temperature. NOTE 3 This table is applicable to pipes serving solar hot water panels. 12

Table 20 (BS5422:2009) Indicative of insulation for domestic heating and hot water systems having high emissivity outer surfaces Outside diameter of copper pipe on which insulation has been based Thickness of ROCKWOOL RockLap H&V Pipe Section Heat Loss (W/m) 8.0 - - 7.06 10.0 - - 7.23 12.0 - - 7.35 15.0 - - 7.89 22.0 19 20 9.12 28.0 21 25 10.07 35.0 22 25 11.08 42.0 24 25 12.19 54.0 25 25 14.12 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe at 60 C in still air at 15 C, emissivity of outer surface of insulated system as specified. NOTE 2 Heat loss relates to the specified and temperature. NOTE 3 This table is applicable to pipes serving solar hot water panels. Table 22 (BS5422:2009) Minimum insulation to control the surface temperature of a non-metallic surface with a surface emissivity of 0.90 and design cold face temperature of 59 C Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 100 150 200 250 17 3 20 6 20 10 20 13 20 21 3 20 7 20 10 20 14 20 27 3 20 7 20 11 20 15 20 33 3 20 7 20 11 20 16 20 42 4 20 8 20 12 20 17 20 48 4 20 8 20 12 20 17 20 60 4 20 8 20 13 20 18 20 76 4 25 9 25 14 25 20 25 89 4 25 9 25 15 25 21 25 102 4 25 9 25 15 25 21 25 114 4 25 9 25 15 25 22 25 140 4 25 10 25 16 25 23 25 169 4 25 10 25 16 25 23 25 219 5 25 10 25 17 25 24 25 245 5 25 10 25 17 25 25 25 273 5 25 11 25 17 25 25 25 324 5 25 11 25 18 25 26 25 356 5 30 11 30 18 30 26 30 406 5 30 11 30 18 30 27 30 456 5 40 11 40 19 40 27 40 508 5 40 11 40 19 40 27 40 558 5 40 11 40 19 40 28 40 610 5 40 12 40 19 40 28 40 flat 5 40 12 40 18 40 27 40 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at 20 C. Surface emissivity corresponding to outer surface specified. NOTE 2 Maximum heat loss values for intermediate operating temperatures may be deduced by interpolation. NOTE 3 Heat loss measured in Watts per metre (W/m) relates to the specified and temperature. NOTE 4 The thermal conductivity of insulation materials increases with mean temperature, and for any given material the use of a different thermal conductivity can be required for each operating temperature. NOTE 5 These es may not satisfy other design requirements, in particular those for control of surface temperature (see Table 22, Table 23 and Table 24). NOTE 6 To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow. 13

Table 23 (BS5422:2009) Minimum insulation to control the surface temperature of a metallic surface with a surface emissivity of 0.05 and design cold face temperature of 50 C Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 100 150 200 250 17 7 20 14 20 22 25 31 35 21 8 20 15 20 24 25 33 35 27 8 20 17 20 26 30 36 40 33 9 20 18 20 27 30 38 40 42 10 20 19 20 29 30 41 45 48 10 20 20 20 31 35 43 45 60 10 20 21 25 33 35 46 50 76 12 25 24 25 37 40 52 50 89 12 25 25 25 39 40 55 60 102 13 25 26 30 41 45 57 60 114 13 25 27 30 42 45 59 60 140 14 25 28 30 45 45 63 60 169 14 25 30 30 47 50 67 70 219 15 25 32 35 51 60 72 80 245 16 25 33 35 52 60 74 80 273 16 25 34 35 54 60 77 80 324 17 25 35 35 56 60 80 80 356 17 30 36 40 58 60 83 90 406 18 30 37 40 60 60 86 90 456 18 40 39 40 62 70 88 90 508 19 40 40 40 64 70 91 100 558 19 40 41 45 65 70 91 100 610 19 40 41 45 65 70 91 100 flat 19 40 41 50 62 70 82 90 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at 20 C. Surface emissivity corresponding to outer surface specified. NOTE 2 Maximum heat loss values for intermediate operating temperatures may be deduced by interpolation. NOTE 3 Heat loss measured in Watts per metre (W/m) relates to the specified and temperature. NOTE 4 The thermal conductivity of insulation materials increases with mean temperature, and for any given material the use of a different thermal conductivity can be required for each operating temperature. NOTE 5 These es may not satisfy other design requirements, in particular those for control of surface temperature (see Table 22, Table 23 and Table 24). NOTE 6 To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow. 14

Table 24 (BS5422:2009) Minimum insulation to control the surface temperature of a non-metallic surface with a surface emissivity of 0.90 and design cold face temperature of 50 C Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 100 150 200 250 17 5 20 9 20 13 20 18 20 21 5 20 9 20 14 20 19 20 27 5 20 10 20 15 20 20 20 33 5 20 10 20 15 20 21 25 42 5 20 11 20 16 20 22 25 48 6 20 11 20 17 20 23 25 60 6 20 11 20 18 20 24 25 76 6 25 13 25 19 25 27 30 89 6 25 13 25 20 25 28 30 102 7 25 13 25 21 25 29 30 114 6 25 13 25 21 25 30 30 140 7 25 13 25 22 25 31 30 169 7 25 14 25 23 25 32 30 219 7 25 15 25 23 25 33 35 245 7 25 15 25 24 25 34 35 273 7 25 15 25 24 25 35 35 324 8 25 16 25 25 25 35 35 356 8 30 16 30 25 30 36 40 406 8 30 16 30 26 30 37 40 456 8 40 16 40 26 40 37 40 508 8 40 16 40 26 40 38 40 558 8 40 17 40 27 40 38 40 610 8 40 17 40 27 40 39 40 flat 8 40 17 40 27 40 39 40 NOTE 1 Insulation es in this table have been calculated according to BS EN ISO 12241:2008 using standardised assumptions: horizontal pipe in still air at 20 C. Surface emissivity corresponding to outer surface specified. NOTE 2 Maximum heat loss values for intermediate operating temperatures may be deduced by interpolation. NOTE 3 Heat loss measured in Watts per metre (W/m) relates to the specified and temperature. NOTE 4 The thermal conductivity of insulation materials increases with mean temperature, and for any given material the use of a different thermal conductivity can be required for each operating temperature. NOTE 5 These es may not satisfy other design requirements, in particular those for control of surface temperature (see Table 22, Table 23 and Table 24). NOTE 6 To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow. 15

Table 24 (BS5422:2009) Minimum insulation to control the surface temperature of a metallic surface with a surface emissivity of 0.05 and design cold face temperature of 55ºC Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 100 150 200 250 17 6 20 12 20 18 20 26 30 21 6 20 13 20 20 20 27 30 27 7 20 14 20 21 25 30 30 33 7 20 14 20 23 25 32 35 42 7 20 15 20 24 25 34 35 48 8 20 16 20 25 25 35 35 60 8 20 17 20 27 30 38 40 76 9 20 19 25 31 35 43 45 89 9 20 20 25 32 35 46 50 102 10 20 21 25 33 35 48 50 114 10 25 21 25 34 35 49 50 140 10 25 23 25 37 35 52 60 169 11 25 24 25 39 40 55 60 219 12 25 26 30 41 45 59 60 245 12 25 26 30 43 45 61 70 273 12 25 27 30 44 45 63 70 324 13 25 28 30 46 50 66 70 356 13 30 29 30 47 50 68 70 406 13 30 30 30 49 50 71 80 456 14 40 31 40 50 50 73 80 508 14 40 32 40 52 60 75 80 558 14 40 32 40 52 60 75 80 610 15 40 32 40 52 60 75 80 flat 15 40 32 40 52 60 75 80 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table, Adopting these es may not necessarily satisfy other design requirements. NOTE 2 To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow. 16

Table 24 (BS5422:2009) Minimum insulation to control the surface temperature of a metallic surface with a surface emissivity of 0.18 and design cold face temperature of 55 C Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 100 150 200 250 17 5 20 11 20 16 20 23 25 21 6 20 11 20 18 20 24 25 27 6 20 12 20 19 20 26 30 33 6 20 13 20 20 20 28 30 42 7 20 14 20 21 25 30 30 48 7 20 14 20 22 25 31 35 60 7 20 15 20 24 25 33 35 76 8 25 16 25 27 30 38 40 89 8 25 18 25 28 30 39 40 102 8 25 18 25 29 30 41 45 114 9 25 19 25 30 30 42 45 140 9 25 20 25 31 35 45 45 169 9 25 20 25 33 35 47 45 219 10 25 22 25 35 35 50 50 245 10 25 22 25 36 40 52 60 273 10 25 23 25 37 40 53 60 324 11 25 24 25 38 40 55 60 356 11 30 24 30 39 40 57 60 406 11 30 25 30 40 40 58 60 456 11 40 25 40 41 45 60 60 508 12 40 26 40 42 45 61 70 558 12 40 26 40 43 45 61 70 610 12 40 26 40 43 45 61 70 flat 12 40 26 40 43 50 61 70 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table, Adopting these es may not necessarily satisfy other design requirements. NOTE 2 To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow. 17

Table 24 (BS5422:2009) Minimum insulation to control the surface temperature of a metallic surface with a surface emissivity of 0.26 and design cold face temperature of 55 C Outside diameter of steel pipe on which insulation has been based Hot face temperature ( O C) Thickness of ROCKWOOL RockLap H&V Pipe Section 100 150 200 250 17 5 20 10 20 16 20 22 25 21 5 20 11 20 17 20 23 25 27 6 20 11 20 18 20 25 25 33 6 20 12 20 19 20 26 30 42 6 20 13 20 20 20 28 30 48 6 20 13 20 21 25 29 30 60 7 20 14 20 22 25 31 35 76 7 25 16 25 25 25 35 35 89 8 25 16 25 26 30 37 40 102 8 25 17 25 27 30 38 40 114 8 25 17 25 28 30 39 40 140 8 25 18 25 29 30 41 45 169 9 25 19 25 30 30 43 45 219 9 25 20 25 32 35 46 50 245 9 25 20 25 33 35 47 50 273 9 25 21 25 34 35 48 50 324 10 25 21 25 35 35 50 50 356 10 30 22 30 36 40 51 60 406 10 30 22 30 37 40 53 60 456 10 40 23 40 37 40 54 60 508 11 40 23 40 38 40 55 60 558 11 40 24 40 39 40 55 60 610 11 40 24 40 39 40 55 60 flat 11 40 24 40 39 40 55 60 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table, Adopting these es may not necessarily satisfy other design requirements. NOTE 2 To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow. 18

Table 25 (BS5422:2009) Heat loss from bare surfaces calculated in accordance with BS EN ISO 12241:2008 (black steel pipes) Operating temperature ( Outside O C) diameter of 50 100 150 200 250 steel pipe Heat loss (W/m pipes, W/m 2 flat) 12.0 17 57 110 176 257 15.0 20 69 133 214 313 17.2 23 78 150 241 353 21.3 27 93 180 290 427 22.0 28 96 186 299 439 26.9 33 114 221 356 525 28.0 35 118 229 369 544 33.7 41 139 269 435 641 42.0 49 168 326 528 781 42.4 50 169 329 532 788 48.3 56 190 369 598 885 54.0 61 209 407 660 979 60.3 68 230 448 728 1081 67.0 74 253 492 800 1188 76.1 83 283 551 896 1333 80.0 87 295 576 938 1395 88.9 95 324 632 1031 1535 101.6 107 365 712 1162 1733 108.0 113 385 752 1228 1832 114.3 119 405 791 1292 1929 139.7 142 484 947 1549 2316 168.3 167 571 1119 1833 2746 219.1 212 722 1419 2330 3498 273.0 258 880 1731 2848 4283 323.9 301 1027 2021 3331 5016 OPERATING CONDITIONS: Ambient still air: 20 C Surface emissivity: 0.90 Height of flat surfaces: 0.6m Surface orientation: horizontal 19

Table 26 (BS5422:2009) Heat loss from bare surfaces calculated in accordance with BS EN ISO 12241:2008 (copper pipes commercial grade, scoured to a shine) Outside diameter Operating temperature ( O C) of copper pipe 50 100 150 200 Heat loss (W/m pipes, W/m 2 flat) 12.0 11 36 66 100 15.0 12 43 79 119 17.2 14 47 87 132 21.3 16 56 103 156 22.0 17 57 105 160 26.9 19 66 123 186 28.0 20 69 127 192 33.7 23 79 146 222 42.0 27 93 173 263 42.4 28 94 174 265 48.3 31 104 192 292 54.0 33 113 210 319 60.3 36 123 228 347 67.0 39 134 248 377 76.1 43 148 273 416 80.0 45 153 284 432 88.9 49 166 308 469 101.6 54 184 341 520 108.0 57 193 358 545 114.3 59 202 374 570 139.7 69 236 437 666 168.3 80 272 505 770 219.1 98 334 619 946 273.0 116 396 735 1123 323.9 133 452 840 1284 flat 119 647 1244 1938 OPERATING CONDITIONS: Ambient still air: 20 C Surface emissivity: 0.07 Height of flat surfaces: 0.6m Surface orientation: horizontal 20

Table 27 (BS5422:2009) Heat loss from bare surfaces calculated in accordance with BS EN ISO 12241:2008 (copper pipes oxidised) Outside diameter Operating temperature ( O C) of copper pipe 50 100 150 200 Heat loss (W/m pipes, W/m 2 flat) 12.0 15 52 99 158 15.0 18 63 120 191 17.2 21 70 135 215 21.3 25 84 162 258 22.0 25 87 166 265 26.9 30 103 197 315 28.0 31 106 204 326 33.7 36 124 239 383 42.0 44 150 289 464 42.4 44 151 292 468 48.3 50 169 326 524 54.0 55 186 359 578 60.3 60 205 395 636 67.0 66 224 433 698 76.1 73 250 484 781 80.0 77 261 505 816 88.9 84 286 554 895 101.6 94 321 623 1007 108.0 99 339 657 1063 114.3 104 356 691 1118 139.7 124 424 824 1336 168.3 146 499 971 1577 219.1 184 629 1226 1997 273.0 224 763 1491 2432 323.9 261 888 1737 2837 flat 245 1076 2125 3464 OPERATING CONDITIONS: Ambient still air: 20 C Surface emissivity: 0.70 Height of flat surfaces: 0.6m Surface orientation: horizontal 21

Table 28 (BS5422:2009) Minimum insulation to protect steel pipes against freezing under selected industrial process conditions Outside diameter of pipe Inside diameter of pipe (bore) Initial temperature: +5 C Minimum ambient air temperature: -10 C Evaluation period: 12 hours Permitted ice formation nil Initial temperature: +5 C Minimum ambient air temperature: -10 C Evaluation period: 12 hours Permitted ice formation 10% Thickness of ROCKWOOL RockLap H&V Pipe Section 21.3 16.0 - - - - 26.9 21.6 - - - - 33.7 27.2 - - 251-42.4 35.9 - - 89 90 48.3 41.8 452-59 60 60.3 53.0 173-34 35 76.1 68.8 87 90 23 25 88.9 80.8 62 70 19 20 114.3 105.3 40 40 13 25 168.3 158.6 23 25 9 25 219.1 207.9 17 25 6 25 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. NOTE 2 Some of the insulation es given are too large to be applied in practice but a selection is included to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by circulating the water or heat tracing. NOTE 3 Assumed densities (r) and heat capacities (c p ) are as follows: r water = 1,000 kg/m³, c p water = 4,200 J/kg.K; r steel = 7,840 kg/m³, c p steel = 455 J/kg.K Table 29 (BS5422:2009) Minimum insulation required to give protection against freezing under specified commercial and institutional conditions Outside diameter of pipe COPPER PIPES Inside diameter of pipe (bore) Initial temperature: +2 C Minimum ambient air temperature: -6 C (indoor unheated) Evaluation period: 12 hours Permitted ice formation 50% Initial temperature: +2 C Minimum ambient air temperature: -10 C (indoor unheated) Evaluation period: 12 hours Permitted ice formation 50% Thickness of ROCKWOOL RockLap H&V Pipe Section 15.0 13.6 66-315 - 22.0 20.2 19 20 47 50 28.0 26.2 12 20 24 25 35.0 32.6 9 20 16 20 42.0 39.6 7 20 12 20 54.0 51.6 5 20 8 20 76.1 73.1 4 25 6 25 108.0 105.0 3 25 4 25 STEEL PIPES 21.3 16.0 40 40 142-26.9 21.6 19 20 43 45 33.7 27.2 13 20 25 25 42.4 35.9 8 20 15 20 48.3 41.8 7 20 12 20 60.3 53.0 5 20 9 20 76.1 68.8 4 25 6 25 88.9 80.0 3 25 5 25 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. NOTE 2 Some of the insulation es given are too large to be applied in practice but a selection is included to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by circulating the water or heat tracing. NOTE 3 Assumed densities (r) and heat capacities (c p ) are as follows: r water = 1,000 kg/m³, c p water = 4,200 J/kg.K; r steel = 7,840 kg/m³, c p steel = 455 J/kg.K 22

Table 30 (BS5422:2009) Minimum insulation to protect against freezing for domestic cold water systems [12 h] Outside diameter of pipe COPPER PIPES Inside diameter of pipe (bore) Normal installation inside the building inside the envelope of the insulation Initial temperature +7 C Minimum ambient air temperature -6 C Evaluation period 12 hours Permitted ice formation 50% Extreme installation - inside the building but outside the envelope of the insulation Initial temperature +2 C Minimum ambient air temperature -6 C Evaluation period 12 hours Permitted ice formation 50% Thickness of ROCKWOOL RockLap H&V Pipe Section 15.0 13.6 49-66 - 22.0 20.2 17 20 19 20 28.0 26.2 11 20 12 25 35.0 32.6 8 20 9 20 42.0 39.6 6 20 7 20 54.0 51.6 5 20 5 20 76.1 73.1 3 25 4 25 108.0 105.0 2 25 3 25 STEEL PIPES 21.3 16.0 32 40 40 40 26.9 21.6 16 20 19 20 33.7 27.2 11 20 13 20 42.4 35.9 7 20 8 20 48.3 41.8 6 20 7 20 60.3 53.0 5 20 5 20 76.1 68.8 4 25 4 20 88.9 80.0 3 25 3 25 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. NOTE 2 Some of the insulation es given are too large to be applied in practice but a selection is included to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by circulating the water or heat tracing. NOTE 3 Assumed densities (r) and heat capacities (c p ) are as follows: r water = 1,000 kg/m³, c p water = 4,200 J/kg.K; r steel = 7,840 kg/m³, c p steel = 455 J/kg.K 23

Table 31 (BS5422:2009) Minimum insulation to protect against freezing for domestic cold water systems [8h] Outside diameter of pipe COPPER PIPES Inside diameter of pipe (bore) Normal installation inside the building inside the envelope of the insulation Initial temperature +7 C Minimum ambient air temperature -6 C Evaluation period 8 hours Permitted ice formation 50% Extreme installation - inside the building but outside the envelope of the insulation Initial temperature +2 C Minimum ambient air temperature -6 C Evaluation period 8 hours Permitted ice formation 50% Thickness of ROCKWOOL RockLap H&V Pipe Section 15.0 13.6 22-26 - 22.0 20.2 10 20 11 20 28.0 26.2 7 20 7 20 35.0 32.6 5 20 6 20 42.0 39.6 4 20 4 20 54.0 51.6 3 20 3 20 76.1 73.1 2 25 2 25 108.0 105.0 2 25 2 25 STEEL PIPES 21.3 16.0 17 20 20 20 26.9 21.6 10 20 11 20 33.7 27.2 7 20 8 20 42.4 35.9 5 20 5 20 48.3 41.8 4 20 5 20 60.3 53.0 3 20 4 20 76.1 68.8 3 25 3 25 88.9 80.0 2 25 2 25 NOTE 1 Thicknesses given are calculated specifically against the criteria noted in the table. These es may not satisfy other design requirements. NOTE 2 Some of the insulation es given are too large to be applied in practice but a selection is included to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by circulating the water or heat tracing. NOTE 3 Assumed densities (r) and heat capacities (c p ) are as follows: r water = 1,000 kg/m³, c p water = 4,200 J/kg.K; r steel = 7,840 kg/m³, c p steel = 455 J/kg.K 24

Ductwork 9. Braithwaite tank insulation within buildings Insulated with an initial layer of 40 mm thick ROCKWOOL HVAC/RWA45 Slabs secured by manufacturer approved adhesive and insulation hangers, followed by a further layer of 40 mm thick ROCKWOOL Ductslab secured to the first layer by adhesive and previously applied insulation hangers. Finish to insulation to be factory applied reinforced aluminium foil, joints in surface covering to be secured with 75 mm wide aluminium foil self adhesive tape, to maintain a vapour barrier. Particular attention to be given to the vapour barrier where the self adhesive insulation hangers protrude through the mineral wool insulation and its factory applied finish (second layer). Further finish should be according to location i.e. external as specification 7.2; plant rooms as specification 6.2. 10. Tank insulation Cold water tanks, including feed and vent tanks to be insulated with ROCKWOOL Ductslab 50 mm thick. Insulation to be secured by manufacturer approved adhesive and further supported by means of 50 mm, 19-22 swg galvanised wire mesh netting. Care to be taken when applying the wire netting to avoid damage to the foil facing. 11. Fire protection to ductwork Fire Duct Systems (previously Conlit Ductwork System) materials can be used to provide ½, 1, 1½ and 2 hour fire protection to rectangular and circular ventilation and smoke extract steel ductwork. The fire protection provided is in accordance with BS 476-24: 1987, duct types A & B. The Fire Duct system protects horizontal and vertical ductwork against both fire break out and fire break in. Kitchen extract ducts, which are subject to separate BS 476-24 requirements, are additionally covered for ½ and 1 hour protection periods. Full guidance relating to ductwork fire requirements and the Fire Duct System are available from the ROCKWOOL Technical Department. The ROCKWOOL publication Fire Duct System is available on request. Typical specification Ductwork shall be in accordance with B&ES Specification DW/144. Ducts to be fire protected with the correct of high density single layer ROCKWOOL fire rated ductwork system. Insulation system shall be independently tested and carry current valid certification to provide fire protection fully in accordance with the requirements of duct Type A and duct Type B of BS476: 24. (The fire resistance of test specimens shall be the duration, in minutes, of heating in accordance with 5.1.1 until failure occurs according to one or more of the performance criteria, i.e. stability, insulation, integrity, or until the test is terminated, whichever is the shortest time). And in accordance with BS9999 (The fire resistance of ductwork, when tested from either side, should be not less than the fire resistance required for the elements of construction in the area through which it passes. The supporting hangers should be capable of supporting the ductwork for not less than the period of fire resistance of the ductwork). 25

Welded pin fixing method 1 1. All ductwork to be insulated with..*mm ROCKWOOL Fire Duct slab, having a factory applied reinforced aluminium foil to one face and complying with Building Regulations Class O requirements. 2. The Fire Duct Slab to be affixed to the duct using 2.5 mm diameter welded steel pins and 38 mm spring steel washers in accordance with ROCKWOOL manual Fire Duct System. 3. The foil facing is to be removed from any surface to which Firepro glue is to be applied. 4. All corner joints are to be fixed with pigtail screws at 250 mm maximum centres. Screw length is to be 2 x slab. 5. All cross joints are to be filled with Firepro Glue and held tightly closed. 6. For duct sizes up to 1500 x 1500 mm, drop rods and bearers are to be at 1500 mm maximum centres and to be M10 steel rod and 30 x 30 x 3 mm steel angle respectively. Ductwork is to be in accordance with B&ES Specification DW144. 7. Drop rods and exposed bearers are to be insulated with mm Fire Duct Slab or Fire Duct Hanger Strip, as appropriate. Rebates or cover pieces are to be used at duct flange and bearer locations according to site conditions and subject to ROCKWOOL approval. 8. Where a vapour barrier is required, all exposed Fire Duct edges and penetrations through the foil should be sealed using soft self-adhesive aluminium foil tape. Welded pin fixing method 2 1. All ductwork to be insulated with..*mm ROCKWOOL Fire Duct slab, having a factory applied reinforced aluminium foil to one face and complying with Building Regulations Class O requirements. 2. The Fire Duct Slab to be affixed to the duct using 2.5 mm diameter welded steel pins and 38 mm spring steel washers in accordance with ROCKWOOL manual Fire Duct System. 3. All corner joints are to be fixed with pigtail screws at 250 mm maximum centres. Screw length is to be 2 x slab. 4. All joints are to be filled with Firepro Glue and held tightly closed. Nails to be used at corner joints for this purpose. 5. For duct sizes up to 1500 x 1500 mm, drop rods and bearers are to be at 1500 mm maximum centres and to be M10 steel rod and 30 x 30 x 3 mm steel angle respectively. Ductwork is to be in accordance with B&ES Specification DW144. 6. Drop rods and exposed bearers are to be insulated with mm Fire Duct Slab or Fire Duct Hanger Strip, as appropriate. Rebates or cover pieces are to be used at duct flange and bearer locations according to site conditions and subject to ROCKWOOL approval. 7. Where a vapour barrier is required, all exposed Fire Duct edges and penetrations through the foil should be sealed using soft self-adhesive aluminium foil tape. 26

Joint Option A - Rebated protection Joint Option B - Protection using T section Joint Option C - Protection using block cover strip Fire resistance - Performance summary Fire Duct Slab, Section and PSM Fire Resistance (hours) Duct type Required Fire Duct Joint options (see Fig.2 below) Hanger protection Fire Duct Slab Hanger protection Hanger Section Max. duct size for mitre-joint, glued system ½ HVAC & smoke extract 40 BC 40 17 x 30 1500 x 1500 ½ Kitchen extract 40 BC 40 17 x 30 1500 x 1500 1 HVAC & smoke extract 40 BC 40 17 x 40 1000 x 1000 1 Kitchen extract 90 ABC 40 17 x 40 1500 x 1500 1½ HVAC & smoke extract 70 ABC 50 17 x 50 1200 x 1200 2 HVAC & smoke extract 90 ABC 60 17 x 70 1000 x 1000 Welded pin fixing method 3 1. All ductwork to be insulated with..*mm ROCKWOOL Fire Duct slab, having a factory applied reinforced aluminium foil to one face and complying with Building Regulations Class O requirements. 2. The Fire Duct Slab to be affixed to the duct using 2.5 mm diameter welded steel pins and 38 mm spring steel washers in accordance with ROCKWOOL manual Fire Duct System. 3. All corner joints are to be fixed with pigtail screws at 250 mm maximum centres. Screw length is to be 2 x slab. 4. All cross joints are to be covered with centrally positioned 100 mm wide strips of Fire Duct Slab of the same as the insulation. The cover strips are to be fixed along both edges using pigtail screws, as described above. 5. For duct sizes up to 1500 x 1500 mm, drop rods and bearers are to be at 1500 mm maximum centres and to be M10 steel rod and 30 x 30 x 3 mm steel angle respectively. Ductwork is to be in accordance with B&ES Specification DW144. 6. Drop rods and exposed bearers are to be insulated with mm Fire Duct Slab or Fire Duct Hanger Strip, as appropriate. Rebates or cover pieces are to be used at duct flange and bearer locations according to site conditions and subject to ROCKWOOL approval. 7. Where a vapour barrier is required, all exposed Fire Duct edges and penetrations through the foil should be sealed using soft self-adhesive aluminium foil tape. Alternatively the ROCKWOOL Fire Duct system can be fixed using the mitre-joint fixing method-please see ROCKWOOL Fire Duct System brochure for further information. 27

12. Acoustic treatment of ducts and pipes Techwrap2 GENERAL - 25 mm ROCKWOOL Techwrap2 to be applied to ducts. The polymeric mass layer should be positioned outermost from the sound source and overlapped at all joints. Techwrap2 should be cut 25 mm oversize and a 25 mm strip of ROCKWOOL stone wool removed to create an overlap. All cutting operations can be completed using a sharp knife. 75 mm wide plain aluminium foil self-adhesive tape should be used to seal the joints. FIXINGS - Welded steel pins should be used to fix Techwrap2 to the duct. However, subject to the manufacturer s approval, adhesive applied insulation hangers may be used in place of welded pins. Particular attention should be paid to support of the Techwrap2 at joint locations and where sagging may occur, eg in soffit areas. The number of pins required will depend upon size and orientation of the duct. However, where pins are employed at Techwrap2 edges, 4 number are recommended at 1000 mm edges and 7 number at 2000 mm edges. Additional lines of pins should be at nominal 300 mm spacings. Where a vapour barrier is required, support pins and hangers, which penetrate the foil, should be sealed using aluminium tape. 13. Construction type pipework and trunking penetrations - insulated fire sleeves ROCKWOOL Insulated Fire Sleeves supplied 300 mm long and cut to the desired length. The sleeve must fully cover the part of the pipe that is located within the depth of the compartment wall or floor. The sleeve may be flush fitting or may protrude from the wall/floor by 25mm (typ.) to facilitate sealing of the outer foil facing onto adjacent insulation. Figure 2 For soil-vent and rainwater pipes, ductwork etc. where they pass within a building and a high level of acoustic insulation is required use ROCKWOOL Techtube. All joints to be taped with self-adhesive foil tape, including the joints where the insulated fire sleeve butts to existing insulation. To maintain the fire rating stated above, the minimum allowable length of sleeve is 50 mm. Insulated Fire Sleeves can accommodate irregularities in the division opening and the pipe O.D.up to 15 mm. Multiple pipe penetrations can be accommodated in conjunction with intumescent coated batts. On metal pipes pipe insulation can be used to meet the insulation requirement for fire protection. Installation to be fully in accordance with manufacturer s instructions. 28

14. Firestop solution for large voids in walls and floors - ROCKWOOL Ablative Coated Batt FirePro Ablative Coated Batts are manufactured by spraying specially produced, high density ROCKWOOL insulation with an additional fire protection ablative coating. This is a fully automated process to ensure an even coating. ROCKWOOL Ablative Coated Batts are available in either 50mm or 60mm es. Installation FIREPRO Ablative Coated Batts are manufactured by spraying specially produced, high density ROCKWOOL insulation with an additional fire protection ablative coating. This is a fully automated process to ensure an even of coating. To install, the Batts are simply cut and a bead of Acoustic Intumescent Sealant applied around the external edges. They are then friction fitted between the services and the wall or floor edges to completely seal the void. Where butt joints are required between cut sections of adjacent batts, Acoustic Intumescent Sealant and/or FIREPRO Glue is applied to both mating edges in order to form a fire tight bond between individual pieces of insulation. Contact the Technical Solutions team on 01656 862621 for specific details on blank seals and dampers. All joints, including those around the perimeter of the Batt, are then pointed with FIREPRO Acoustic Intumescent Sealant to complete the seal. Plastic pipes (PVC, ABS and HDPE etc) must be sleeved with FIREPRO Insulated Fire Sleeves at the point at which they pass through the Ablative Coated Batt. Similarly, to achieve fire resistance insulation (I) with metal pipes such as steel or copper, the pipes must be lagged with a 1m length of ROCKWOOL Fire Tube or Pipe Section (minimum 40mm wall ) protruding equal distances from both faces of the Ablative Coated Batt. The joint between the Ablative Coated Batt and the pipe insulation must be pointed with the FIREPRO Sealant. Where the pipe has been thermally lagged with a combustible insulation, this must be cut away and replaced with the ROCKWOOL insulation, as above. Ensure the integrity of any vapour control layer is re-instated as necessary. The joint between the Batt and Fire Sleeve or Fire Tube must be pointed with the FIREPRO Sealant. Load Bearing Seals FIREPRO Ablative Coated Batts are not intended for use as load-bearing seals. Where a load-bearing seal is required, ROCKWOOL Firestop Compound should be considered. Fire performance ROCKWOOL Ablative Coated Batt has been tested to the dedicated fire resistance standard for penetration seals - pren 1366-3. The independently prepared assessment, detailing the full scope of fire performance, is available from the ROCKWOOL Technical Solutions Team. Ablative Coated Batt fire resistance tests were conducted using ROCKWOOL Acoustic Intumescent Sealant Sealant and/or ROCKWOOL FIREPRO Glue. Independant tests have proved the capability of a single 50mm Batt to provide up to 2 hours fire resistance integrity, insulation ratings are dependent upon the service penetration. Where 4 hour integrity and insulation are required we recommend the use of our 60mm Coated Batt. Independent tests have proved the capability of a single 60 mm Batt to provide up to 4 hours fire resistance integrity and up to 2 hours insulation when used with all of the services listed in the Ablative Coated Batt Datasheets and also as a blank seal. Even for extreme requirements, where 4 hours integrity and insulation are required to maintain the performance of a masonry wall, a solution can also be accomplished with a double Batt solution. 29

Acoustic data 60mm batt: Tested for head of wall: Rw = up to 52db (2 x Coated Batts) Rw = up to 38db (1 x Coated Batts) The correct use of Coated Batt within concealed cavities and voids will reduce the level of transmitted sound: Rw = up to 52 db (2 x Coated Batts) incorporating 48mm O/D PVC /15mm copper pipe penetrations. Rw = up to 34 db (1x Coated Batts) incorporating 48mm O/D PVC /15mm copper pipe penetrations. 50mm batt: Tested for head of wall: Rw = up to 48db (2 x Coated Batts) Rw = up to 37db (1 x Coated Batts) The correct use of Coated Batt within concealed cavities and voids will reduce the level of transmitted sound: Rw = up to 52 db (2 x Coated Batts) incorporating 48mm O/D PVC /15mm copper pipe penetrations. Rw = up to 34 db (1x Coated Batts) incorporating 48mm O/D PVC /15mm copper pipe penetrations. Further acoustic test data is available for use in facefix applications. Contact the ROCKWOOL Technical Solutions Team. 30

Sustainability As an environmentally conscious company, ROCKWOOL promotes the sustainable production and use of insulation and is committed to a continuous process of environmental improvement. All ROCKWOOL products provide outstanding thermal protection as well as four added benefits: Fire resistance Acoustic comfort Sustainable materials Durability Environment Made from a renewable and plentiful naturally occuring resource, ROCKWOOL insulation saves fuel costs and energy in use and relies on trapped air for its thermal properties. ROCKWOOL insulation does not contain (and has never contained) gases that have ozone depletion potential (ODP) or global warming potential (GWP). ROCKWOOL is approximately 97% recyclable. For waste ROCKWOOL material that may be generated during installation or at end of life, we are happy to discuss the individual requirements of contractors and users considering returning these materials to our factory for recycling. Health & Safety The safety of ROCKWOOL stone wool is confirmed by current UK and Republic of Ireland health & safety regulations and EU directive 97/69/EC:ROCKWOOL fibres are not classified as a possible human carcinogen. A Material Safety Data Sheet is available and can be downloaded from www.rockwool.co.uk to assist in the preparation of risk assessments, as required by the Control of Substances Hazardous to Health Regulations (COSHH). Interested? For further information, contact the Technical Solutions Team on 01656 868490 or email technical.solutions@rockwool.co.uk Visit www.rockwool.co.uk to view our complete range of products and services. Copyright ROCKWOOL January 2017. 31