DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY

Similar documents
COMPUTER SIMULATION AND EXPERIMENTAL VALIDATION OF A MODERN HOTEL ON BUILDING ENERGY CONSERVATION

Waste Energy Recovery Including Pressure and Thermal Energy From LNG Regasification

Energy Conversion and Management

Heat Pump Efficiencies simulated in Aspen HYSYS and Aspen Plus

Refrigeration Kylteknik

Simulation Analysis of Shell Plate-Type Heat Exchanger Using Liquified Natural Gas Cold Energy for Refrigerated Warehouses

CHAPTER 1 BASIC CONCEPTS

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

Enhancement of LNG Propane Cycle through Waste Heat Powered Absorption Cooling

COMBINED HEAT AND POWER SYSTEMS IN LIQUEFIED NATURAL GAS (LNG) REGASIFICATION PROCESSES

Performance enhancement of a photovoltaic thermal (PVT) and ground-source heat pump system

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

Utilisation of LNG Cold Energy at Maptaput LNG Receiving Terminal

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Problems in chapter 9 CB Thermodynamics

Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

DETERMINING THE MAXIMUM LNG PRODUCTION RATE BY PROCESS SIMULATION MODELLING OF LOW TEMPERATURE NATURAL GAS SEPARATION UNIT

Low temperature cogeneration using waste heat from research reactor as a source for heat pump

Chapter 5: Thermodynamic Processes and Cycles

LIFE CYCLE COST ANALYSIS OF WASTE HEAT OPERATED ABSORPTION COOLING SYSTEMS FOR BUILDING HVAC APPLICATIONS

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS

Experimental investigation of solar-driven double ejector refrigeration system

Scientific Journal Impact Factor: (ISRA), Impact Factor: [Son, 3(10): October, 2014] ISSN:

Large scale hydrogen liquefaction in combination with LNG re-gasification

Design of onshore LNG regasification plant

MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE

Alexander Rattner MEAM-402 HW 2

ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE

A new re-liquefaction system of MRS-F (Methane Refrigeration System Full re-liquefaction) for LNG Carriers

Recovery of Waste Heat in Diesel Engine Coolant for Air Conditioning

Comparison of Different Gas Turbine Inlet Air Cooling Methods

Comparison of Different Gas Turbine Inlet Air Cooling Methods

Green FSRU for the future

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING

Heat pumps. WP5 Education and Economic Promotion

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

THE CONCEPT OF INTEGRATED CRYOGENIC ENERGY STORAGE FOR LARGE SCALE ELECTRICITY GRID SERVICES. Finland *corresponding author

Parametric Study of a Double Effect Absorption Refrigeration System

Critical exergy analysis of counterflow reversibly used cooling towers

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.

Sustaining thermal power plant production in low water supply regions using cooling towers

A novel CO 2 -capturing natural gas combined cycle with LNG cold energy utilization

GEOTHERMAL SPACE COOLING

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Efficiency enhancement of the ocean thermal energy conversion system with a vapor vapor ejector

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

A DUAL LOOP ORGANIC RANKINE CYCLE UTILIZING BOIL-OFF GAS IN LNG TANKS AND EXHAUST OF MARINE ENGINE. * Corresponding Author ABSTRACT 1.

Chapter 8. Vapor Power Systems

A discussion of"heat pumps as a source of heat energy for desalination of seawater"

Energy Mix Opportunity of Vapor Absorption Refrigeration System Integrated With Solar Collectors: A Case Study of Hotel Shangri-La

INTEGRATION OF A NEW CCGT PLANT AND AN EXISTING LNG TERMINAL AT BARCELONA PORT Abstract ID Number: 155

Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD

Energy Saving Report. Frigi-Tech Oil Additive. Application. In HKU Central Plant. Chiller No. 3

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

The Part-Load Efficiency Benefit of Oil-Free, High- Speed, Direct-Drive Centrifugal Compressors

Development of a New High efficiency Dual cycle Natural Gas Liquefaction Process

Modified Reverse-Brayton Cycles for Efficient Liquefaction of Natural Gas

Review Questions for the FE Examination

Chapter 10 POWER CYCLES. Department of Mechanical Engineering

Fluid Mechanics, Heat Transfer, and Thermodynamics. Design Project. Production of Acetone

Cryogenic Carbon Capture

The efficiency of the heat pump water heater, during DHW tapping cycle

Eng Thermodynamics I: Sample Final Exam Questions 1

Reduce energy costs and create environmentally friendly hot water all year round

THERMAL ENERGY ANALYSIS OF SOLAR POWERED VAPOUR ABSORPTION COOLING SYSTEM

Modeling and simulation of a reclaimed water source heat pump system based on TRANSYS 1

PERFORMANCE EVALUATION OF HEAT PUMP SYSTEM USING R744/R161 MIXTURE REFRIGERANT

LNG REGASIFICATION PLANTS: CRYOGENIC ORC TO ENHANCE THE EFFICIENCY OF LNG TERMINALS

*Corresponding authors. Tel.: x415, address: (N. Zhu)

NUMERICAL APPROACH TO A LOW PRESSURE GAS-INJECTION SCROLL COMPRESSOR

Analysis of Solar Thermal Cooling System Using TRANSOL

Chapter 10. In Chap. 9 we discussed gas power cycles for which the VAPOR AND COMBINED POWER CYCLES. Objectives


EXTRA CREDIT OPPORTUNITY: Due end of day, Thursday, Dec. 14

Chapter 10. In Chap. 9 we discussed gas power cycles for which the VAPOR AND COMBINED POWER CYCLES. Objectives

Eng Thermodynamics I - Examples 1

Chapter 9: Vapor Power Systems

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Improvement of the Performance for an Absorption Refrigerating System with. Lithium bromide-water as Refrigerant by Increasing Absorption Pressure 1

Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222)

Eng Thermodynamics I - Examples 1

(52) U.S. Cl. 60/643

The Separation and Liquefaction of Oxygenated CBM Yang Kejian and Zhang Wu

THERMAL STORAGE AIR CONDITIONING FOR TROPICAL COUNTRIES ISSUES AND OPTIONS

HYSYS WORKBOOK By: Eng. Ahmed Deyab Fares.

Introduction to Condensate Recovery

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery

Reg. No. : Question Paper Code : B.E./B.Tech. DEGREE EXAMINATION, NOVEMBER/DECEMBER Second Semester

ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY

Separations and Reaction Engineering Spring Design Project. Production of Acetone

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

Chapter 6: Stationary Combustion Systems

Comparative Efficiency of Geothermal Vapor-Turbine Cycles

Research on a Magnetic Refrigeration Cycle for Hydrogen Liquefaction

What is District Energy

ENERGY RECOVERY IMPROVEMENT USING ORGANIC RANKINE CYCLE AT COVANTA S HAVERHILL FACILITY

A Investigation of the Performance of Two-Stage Compression Refrigeration/Heat pump System with Dual-cylinder Rolling Piston Compressor

Transcription:

, Volume 4, Number 1, p.14-23, 2003 DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY K.H. Yang and S.C. Wu Mechanical Engineering Department, National Sun Yat-Sen University, Kaohsiung, Taiwan 80424 (Received 27 September 2002; Accepted 9 January 2003) ABSTRACT An innovative design approach has been performed using latent heat of the Liquefied Natural Gas (LNG) during evaporation to provide cooling for 500 USRT cold storage warehouse. In compared with the conventional, mechanical cooling designs, tremendous energy savings can be experienced and is discussed in detail in the paper. 1. INTRODUCTION During the energy crisis in the 1970s, oil prices hiked to a record high of 42 USD per barrel, which imposed a lot of pressure economically on oil importing countries such as Taiwan. To diversify energy resources as a counter-measure, it was decided to import LNG from ASEAN countries such as Indonesia and Malaysia, so that most of the fossil-fueled power plants, which were burning coal and oil, would switch into natural gas (NG). Natural gas is a more environmentally friendly fuel, which contains over 92% of methane, depending on the source of product. When LNG is vaporized into NG, tremendous cooling capacity will be generated during this phase-changing process. Conventionally, this was done by pumping seawater through the open rack vaporizer (ORV), such that heat was transferred from seawater to LNG, and vaporized it into a gaseous state, for industrial and household usage. The chilled water was normally dumped into sea again. Fig. 1 shows the conventional process. LNG was pumped from the tanker A to the storage tank B. In order to maintain a steady flow condition, the boil-off gas (BOG) from the tank at point C was extracted and cooled by the cooler D and recharged into the tanker at point E to form a circulation loop. Part of the BOG at point F was re-compressed at the BOG compressor or point G, condensed and re-charged into the LNG supply loop at point J. While, part of the boil-off gas shown at point H, was incinerated at the burning tower. On the other hand, pump 1 located inside the storage tank transports LNG from the tank, through point I and J, boosted by the pump 2 to a higher pressure at point K, and vaporized at the ORV by the sea water loop shown by point M and N and supply to the customers at the gaseous state, denoted by the point L. During this process, only a few part of the LNG cold energy was recovered by re-condensing BOG. This open heat exchanger loop is not only a waste of huge cold energy or cooling capacity, but will cause thermal pollution to the coastal fishery area also when cold water was re-injected into the sea. In this project, an innovative design has been performed to reclaim the cold energy for a -35 o C cold warehouse. Conventionally, this was done by installing mechanical refrigeration systems, necessitating tremendous electrical power to drive the refrigerant compressor working in such a low temperature. In this study, a closed loop LNG heat exchanger system will be designed to replace the mechanical, or vapor-compression refrigeration (VCR) cycle, with a technical and economical feasibility study to justify its application. 2. EVALUATION OF LNG COLD ENERGY RECLAIM POTENTIAL LNG imported to Taiwan has a chemical composition of 90.5% CH 4, 6.2% C 2 H 4, and 2.33% C 3 H 8 in molar fractions. Its thermal properties can be calculated by the Redlich-Kwang-Soave (RKS) State equation [1]. However, to meet the demand side higher pressure at the local power utilities, it is necessary to pressurize LNG from -162 o C at 100 kpa atmospheric pressure, to around 8 Mpa, or 80 atm. Therefore, a calculation model with much broader range of temperature and pressure should be adapted, such as the Peng-Robinson (PR) state equations [2]. Both calculation models have similar accuracy on light hydrocarbons, but the RKS tends to over-estimate on density calculations, so the PR model is used in this study. PR state equations: P = RT a (1) (V b) (V(V + b) + b(v b)) 14

where P is the pressure of LNG, kpa; T is the temperature of LNG, K; V is the volume of LNG, M 3 ; and R is the gas constant, kpa.m 3 kg -1.K -1. a b a n = i n i x n = x i b i i = i a ci α i 0.5 i x j(a ia j) R T a c = 0.45724 P α 0.5 i 2 c 2 c = 1+ (0.37646 + 1.54226ωi + 0.26992ωi )(1 Tri ) R T b i = 0.07748 P ci ci where x is the mole fraction of each substance, ω is the acentric factor, T ri = T i /T ci. The subscript c means critical state. 2 The pressurization process will change the LNG boiling point, which in turn, will change the cold energy amount that can be reclaimed. The cold energy potential can be calculated from the enthalpy change of LNG across the ORV, or: Pin 162 C Pout t E = H H (2) where the subscripts stand for the enthalpy H at different temperature and pressure P in, P out. The temperature of LNG at liquid state is around -162 o C, while the temperature of NG at gaseous state is about 20 o C in maximum. And the reclaimed energy potential is expressed in E. The calculation result of the LNG cold energy potential under various temperature and pressure was shown in Fig. 2. It is noticed that the cold energy potential decreased while LNG was pressurized. For example, at 8 Mpa, LNG would have an enthalpy of 786 kjkg -1, only amounts to 88% of its value at atmospheric pressure. Based on statistics from September 1, 1998 to August 31, 1999, the annual LNG consumption rate in Taiwan is around 396.52 million metric tons, equivalent to a daily average of 10864.31 metric tons, or 452.67 tons.h -1. Fig. 1: A schematic diagram showing the conventional LNG transporting process using ORV for evaporation 15

1000 LNG pressure=1atm LNG pressure=30atm LNG pressure=50atm LNG pressure=80atm 800 energy (kj/kg) 600 400 200 0-200 -150-100 -50 0 50 LNG temperature(c) Fig. 2: Calculation result of the LNG cold energy potential under various temperature and pressure When LNG was imported from ASEAN countries, it was pumped from the tanker and stored in the 60 m-diameter storage tank at -162 o C liquid state. Pumped out at -148 o C, it was pressurized in two stages, from atmospheric pressure to 3 atm, and then to 83 atm while entering the ORV. It leaves ORV at 15 o C with a pressure drop of around 20 atm, and stays at 63 atm. Therefore, the calculation yields a total heat exchange capacity of 743Mj per ton of LNG across the ORV. Combining with the daily LNG utilization rate in our study, which is around 10,864 ton/day, then it accounts for 1932 Gcal cold energy wasted per day, or equivalent to 26,662 Refrigeration Tons (USRT) cooling capacity, enough to provide residential cooling for around 8800 families during the summer. This has been validated by an experimental investigation through measuring the sea water loop with flow rate and temperature differences entering and leaving the ORV. As shown in Fig. 3, T1 and T2 denote the measuring points of the sea water inlet and outlet temperatures at the ORV, resulting at 27.3 o C and 23.5 o C respectively. The point F denotes the sea water flow rate measuring location, resulting at 2123.8 ton.h -1. The accumulated heat exchange capacity is 26682 USRT. Compared with our estimation, the deviation is within 3%. Furthermore, Fig. 4 shows a statistics and prediction of the LNG import to Taiwan. Following the completion of the second phase of LNG storage extension project in 1996, the annual import rises from 150 metric tons to 450 metric tons, and expected to reach 900 metric tons at the year of 2020. The huge amount of cold energy to be reclaimed is beyond doubt and waiting to be explored. 3. SYSTEM DESIGN FOR COLD WAREHOUSE USING LNG RE- CLAIMED COLD ENERGY In order to reclaim cold energy during LNG evaporation process, it is necessary to construct a closed heat exchange (HX) loop using secondary refrigerant, as shown in Fig. 5. In addition, the ORVs are still needed as a means for adjusting the appropriate portion of heat to be reclaimed without interrupting the normal NG supply to the power utilities. In other words, either the closed-loop heat exchanger or the ORV, each will provide a certain percentage of evaporation heat needed to vaporizer LNG into NG, and can be adjusted subject to the cooling load of the warehouse. On the ORV side, residual LNG was evaporated accordingly so that NG at its outlet still maintains the normal temperature and pressure needed for the power utilities. In this project, LNG cold energy will be utilized to supply cooling to a 110 RT cold storage warehouse operating at -35 o C, another 390 RT warehouse at -20 o C, and to provide 146 RT cooling capacity for air-conditioning in preparative rooms at around 15 o C. Fig. 6 shows a flow chart of the complete warehouse system using cold energy reclaimed from LNG, named the LNGCW system, with major design parameters indicated. 16

Computer simulation has been performed following the first law of thermodynamics along the flow process. Heat and mass balance of the system was calculated as shown in Fig. 7 where each component, including heat exchangers, pumps, and storage tanks were connected according to the system flow chart. After an iterative design and simulation process, the system schematics has been finalized. Fig. 8 gives an outlook of the completed LNG cold warehouse architectural design. denotes the measuring point, T for temperature, F for mass flow rate of sea water Fig. 3: The schematic diagram of the full-scale experiment in measuring the LNG cold energy released by ORV through sea water 11 The Import of LNG 10 9 8 1x10 6 ton 7 6 5 4 3 1995 2000 2005 2010 2015 2020 2025 year Fig. 4: Prediction of LNG import quantity from ASEAN countries to Taiwan in next decades 17

Fig. 5: A schematic diagram indicating cold energy reclaimed from LNG evaporation process for cold warehouse application Fig. 6: A schematic diagram showing the LNGCW system flow 18

Fig. 7: An energy and mass balance simulation result of the LNGCW system Fig. 8: An outlook of the completed LNGCW architectural design 19

4. ECONOMIC FEASIBILITY STUDY Based on the design analysis shown above, major components were sized accordingly enabling an economic feasibility evaluation of the LNGCW systems vs. a conventional mechanical refrigeration (CMR) system. The LNGCW system necessitates 3 specially designed close-loop heat changers and storage tanks etc., introducing higher initial investment at the cost of 12.8 million USD. On the other hand, the CMR system consists of huge refrigerant compressors and condensers, etc. at a cost of around 8.3 million USD. In this way, the operation cost plays a key role in justifying economic feasibility. The CMR system suffers from operating in low evaporator temperature causing reduced refrigerant mass flow rate and smaller cooling capacity. In addition, the high compression ratio between condenser and evaporator demands higher power consumption which worsens the case. The operation power demand is around 2321 kw. On the other hand, the LNGCW system, with an inherent low evaporative temperature of -162 o C, can easily provide cooling capacity at a higher temperature of -30 o C by way of a simple heat exchanging process. The operation power demand is 379 kw, or 16% of that of the conventional CMR system. Based on the outdoor design temperature of 34 o C, the average partial cooling load (APCL) of the cold warehouse was calculated as shown in Fig. 9. It indicated that the APCL ranged from 91% during the summer and down to 76% in the winter. Assuming 330 operation days a year, the LNG consumption rate of the LNGCW system can be calculated as shown in Fig. 10, where the daily average flow rate is 11.2 ton.h -1 and reached its peak of 12.3 ton.h -1 in July. Steady state energy estimation method is used for the cooling load calculation, energy analysis and the power consumption of refrigeration system in this project. It can be calculated for different values of outdoor temperature and multiplied by the corresponding numbers of hours. This method can be accurate if the indoor temperature and internal gains are relatively constant and if the systems are to operate for a complete season as recommended by the ASHRAE Handbook [3]. The calculated power consumption and energy savings of the LNGCW system was plotted in Fig. 11, indicating a monthly energy savings of 1,050 MWh on the average. Economic assessment is performed using the life cycle cost (LCC) method by calculating the present worth during each period of time. n (1 + i) 1 Pv = A (3) n i (1 + i) where Pv is the present worth, A is the annual money saving by reduce electricity consumption, i is the effective discount rate, and n is the total number of years. average partial cooling load % 95 90 85 80 75 70 65 1 2 3 4 5 6 7 8 9 10 11 12 month Fig. 9: Annual cooling load estimation of the cold warehouse in this study 20

average LNG flow rate for LNGCW(ton/h) 12.5 12 11.5 11 10.5 10 9.5 9 1 2 3 4 5 6 7 8 9 10 11 12 month Fig. 10: Annual LNG consumption rate of the LNGCW system LNGCW power saving per month(mwh) 1200 1150 1100 1050 1000 950 900 850 1 2 3 4 5 6 7 8 9 10 11 12 month Fig. 11: Annual operational power savings estimation of the LNGCW system 21

The input parameters include annual inflation rate at 1%, rediscount rate at 4%, assuming an double declining depreciation rate for 15 years of major equipment and no residual value left after that. Local power tariff was inputted at 6.5 cents per kwh. Fig. 12 indicated that the monthly average operation cost savings is about 70,000 USD. Fig. 13 furthers shows the simulation result, indicating that the payback is at around 3.5 years. This represents a promising project with both technical and economical feasibility. 5. CONCLUSIONS During its vaporization process, tremendous cooling capacity can be reclaimed. In this study, the feasibility to design and construct a refrigerated warehouse by using LNG cold energy has been demonstrated both technically and economically. The payback of the 500 USRT cold warehouse is expected to be within 3.5 years, which is now funded by the Chinese Petroleum Corporation of Taiwan for construction. saving electricity cost 1000 USD 78 76 74 72 70 68 66 64 62 60 58 56 1 2 3 4 5 6 7 8 9 10 11 12 month Fig. 12: Annual operational cost savings estimation of the LNGCW system 8000 Net Present Value( 10 3 US dollars) 6000 4000 2000 0-2000 Payback Year 0 2 4 6 8 10 12 14 16 year Fig. 13: The life cycle cost analysis of the LNGCW system in this study 22

REFERENCES 1. H.T. Liu and L.X. You, Characteristics and applications of the cold heat exergy of liquefied natural gas, Energy Conversion & Management, Vol. 40, pp. 1515-1525 (1999). 2. W.C. Edmister, Applied hydrocarbon thermodynamics, Vol. 1, Gulf Publish Company (1984). 3. ASHRAE Handbook - fundamentals, Chapter 28, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, USA (2001). 23