Using Radiant Cooled Floors to Condition Large Spaces and Maintain Comfort Conditions

Similar documents
Using Radiant Cooled Floors to Condition Large Spaces and Maintain Comfort Conditions

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

Thermo Active Building Systems Using Building Mass To Heat and Cool

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

Monitoring of Advanced Facades and Environmental Systems

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Assessing the energy performance of modern glass facade systems

COMFORT-PRODUCTIVITY Building costs COMFORT-PERFORMANCE. Radiant Heating and Cooling Systems for Better Comfort and Energy Efficiency INDOOR - OUTDOOR

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy

CASE STUDY HOW COULD WE OPTIMIZE THE ENERGY-EFFICIENT DESIGN FOR AN EXTRA-LARGE RAILWAY STATION WITH A COMPREHENSIVE SIMULATION?

Cost-Benefit Analysis of Dwelling Retrofit Options

CAE 331/513 Building Science Fall 2017

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

Design guidelines for direct ground cooling systems in different climates

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing

Two Examples for Corporate Identity by intelligent building design

Italcementi Center for Research and Innovation

Case Studies for Radiant Cooling in Hot & Humid Climate

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

Chapter 2 Literature Review

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the

Slab cooling system design using computer simulation

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

FULL YEAR PERFORMANCE SIMULATION OF A DIRECT-COOLED THERMAL STORAGE ROOF (DCTSR) IN THE MIDWEST

Part 1 Review Questions on material covered in Midterms I & II

THE PTM ZEO BUILDING

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Understanding "Heat Load & Psychometric. by Djunaidi HS

Evaluation of Underfloor Air Distribution

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

Thermal Control in Buildings by John Straube (updated )

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Radiant Slab Cooling for Retail

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario

Figure 1: Uncovered and covered PVT collectors

2006 Building Science Press All rights of reproduction in any form reserved.

DISPLACEMENT VENTILATION

Lecture 3: Utilization of Passive Solar Technology

Sustainable Building Façade and Advanced Fenestration Systems

Paper for Phoenics Benelux User Meeting Eindhoven the Netherlands 24 th May 2005

IESVE Compliance for ASHRAE IES Virtual Environment

Field Measurements of Thermal Comfort Conditions in Buildings with Radiant Surface Cooling Systems

CHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Innovative Solutions for Energy Efficient Buildings

Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones

Introduction to basics of energy efficient building design

AN ADVANCED GLAZING CASE STUDY FROM THE IMAGE PROJECT

Simulation Study of Discharging PCM Ceiling Panels through Night - time Radiative Cooling

Federation of European Heating, Ventilation and Air-conditioning Associations

The Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2

GLASS SELECTION GUIDE

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing

Higher Education Energy Efficiency Partnership Program BEST PRACTICES AWARDS

Thermal Characteristics of a Vernacular Building Envelope

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

SOLAR ENGINEERING OF THERMAL PROCESSES

Passive houses for the Northern climate

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate

Energy Analysis of Using Thermal Mass in a Hot Humid climate

Demonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass

CASE STUDIES - CENTRE FOR SUSTAINABLE BUILDING (ZUB) KASSEL, GERMANY

SOLAR PHOTOVOLTAIC ENERGY

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House

Room-side Low-e Coating: As Good As It Sounds?

DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE

Practitioner Modeling Competition

Student Modeling Competition

CONTENTS. Abbreviations: LT: Daylight Transmittance LR ext: Reflectance Outdoor SF: Solar Factor

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Improving Comfort in Microbrigada Buildings in Cuba

Performance of Glazing Materials for Atrium in Hot & Humid Climate

Assessment of thermal comfort near a glazed exterior wall

The Bahen Centre for Information Technology. Glazing Studies of the Gallery. Introduction. University of Toronto ~ Toronto, Ontario, Canada

Chapter 5 Glazing Properties

Practitioner Modeling Competition

ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS

Pearl River Tower. Guangzhou, China. AEI Professional Project Awards January 2014 PHOTO CREDIT: TIM GRIFFITH

Chapter 4. Analysis of Building Energy Performance

125BEPM - Building energy performance modeling. Lecture handouts

Ventilation Approaches for Shopping Malls An Examination of Natural and Hybrid Strategies

Improving Glass Walls Thermal Resistance in Air Conditioned Buildings. A. M. Kaluib, A. Al-Ansary, R. Alajmi, M. Abuzaid, and T.

Thermal performance of concrete wall panel with advanced coating materials: a sustainable design

Window Options. Keeping cool in summer, warm in winter, comfortable all the time,... and saving energy too

McCarran International Airport Terminal 3

Solar cooling design: a case study

Transcription:

DA-00-8-3 Using Radiant Cooled Floors to Condition Large Spaces and Maintain Comfort Conditions Peter Simmonds, Ph.D. Member ASHRAE Stefan Holst ABSTRACT Stephanie Reuss This paper describes the development of a hybrid conditioning system that creates a comfortable indoor environment in a building. The operation of a variable-volume displacement conditioning system and a radiant cooled floor have been optimized to reduce the building load. Control strategies were developed that optimize energy consumption and contain moisture levels within specified limits. The development of conditioning-only occupied zones is shown and how the overall energy consumption is reduced. Its application in a large airport is described. INTRODUCTION Radiant cooled floors have been successfully used to maintain comfort conditions in many buildings, but their use as part of a hybrid system to condition a large airport has not yet been undertaken. To further complicate matters, the airport is in Thailand, which necessitates a careful control of humidity within the conditioned spaces. Another complexity added to the design was the load fluctuation due to the diversity of the airport. In recent years, several studies have been made on the concept of radiant cooled floors. Borressen (1994) and Simmonds (1993, 1994) reported on a radiant cooled floor design for a museum, and Schlappman (1996) reported on the functioning of the radiant floor system two years after it started operating. Holmes and Wilson (1996) reported on a slab cooling system being used to condition a building in London. Many papers have been written on improved comfort conditions using radiant systems for both heating and cooling. (Olesen 1997; Simmonds 1993, 1994). Large areas have Wayne Gaw Associate Member ASHRAE previously been conditioned using radiant systems, but a 200,000 m 2 radiant cooled floor of the 500,00 m 2 International Airport in Bangkok proved quite a challenge. Traditionally, airports are conditioned by ventilation systems that vary either flow or temperature or both to the space. Simmonds (1996a, 1996b) described the design process for the displacement ventilation system proposed for this airport. Holst et al. (1998a, 1998b) described the advantages of using a radiant cooled floor together with a variable-volume displacement system. This report also showed how the envelope design was optimized to reduce the heat guide to the space and reduce energy consumption. BUILDING CONFIGURATION The main terminal building is rectangular in shape and is constructed from single clear glazing and PTFE materials. The roof of the terminal and parts of the concourses are shaded, or partly shaded, by solar shading devices and roof overhangs. However, a majority of the concourses have no external shading devices. The PTFE material does provide a sufficient barrier for direct solar, but the single clear glazing offers very little resistance. The thermal resistance of both PTFE and single glazing is relatively low, and the conductive heat gain to the space would be quite high if traditional indoor temperatures of 24 C were to be maintained. During April, the warmest month, ambient temperatures vary from 34 C to 36 C and there would be a C to 12 C temperature difference across the envelope. A variable-volume displacement system was designed to maintain the required temperature in the occupied zone (24 C). Stratification would be enhanced by this system so that temperatures on the inside of the building envelope would be Peter Simmonds and Wayne Gaw are with Flack+Kurtz Consulting Engineers, San Francisco, Calif. Stefan Holst and Stephanie Reuss are with Transsolar Energietechnik GmbH, Stuttgart, Germany. ASHRAE Transactions: Symposia 695

nearly equal to the ambient conditions, virtually eliminating the convective heat gain to the space. The design and evaluation of the variable-volume displacement system have been discussed by Simmonds (1996a, 1996b). BUILDING LOAD The calculation of peak loads for a building of this magnitude are obviously complex. In total, four building load and simulation tools were used to determine and cross-reference the loads. The load to the concourse was 97 W/m 2. Holst and Welfouder (1998) showed that the radiant cooled floor can absorb up to about 50 W/m 2 of short- and longwave radiation. Convection and conduction components provide another 30 W/m 2 of cooling from the radiant floor. Designing a radiant floor to handle a capacity of 80 W/m 2 is critical. The water supply temperature is limited to 13 C because of floor surface condensation risk. Preliminary analysis using a 17 C return temperature showed that the mass flow and temperature differential were inadequate for the required 80 W/m 2 capacity. The Bangkok climate, which has high air temperatures and solar radiation, leads to enormous solar gains and, therefore, to high cooling loads and low comfort because of high operative temperatures in highly transparent buildings. The optimization process for the membrane roof construction and the glazing leads to a highly reduced solar transmission and, therefore, to low solar-induced cooling loads in the concourses of the new Bangkok International Airport. Table 1 describes the material properties. Table 2 lists the solar radiation, longwave radiation, and air flows between zones. Table 3 notes the internal loads. DESIGN PROCEDURE The design approach was rather unique in that two authors (Holst and Reuss) were working with a team in Germany and Simmonds and Gaw and a team were working in America on the practical design of the airport. Holst used TRNSYS and CFD to simulate the indoor environmental conditions and to model envelope design. The envelope of the concourses consists of a PTFE membrane and glass section. Special attention was paid to the coating of the glazing. The inside surface of the laminated glass had a lowe coating. The low emissivity would redirect the cool radiation effect from the floor back into the space. This can be identified as follows: A 1 1 T 1 4 = A 2 2 T 2 4 where A 1 = area of surface 1, A 2 = area of surface 2, 1 = emissivity of surface 1, 2 = emissivity of surface 2, = Stefan-Boltzmann constant, T 1 = temperature of surface 1, T 2 = temperature of surface 2. Floor TABLE 1 Material Properties Element Construction U-Factor Wall (Glass Concourses) Wall (Glass Terminal) 5 cm insulation, conductivity 0.04 W/m K Laminated glass with low-e coating inside Single glazing Wall (Glass Offices) Insulated glass (Glass Concourses) (Membrane Concourses) (Glass Terminal) (Glass Offices) Laminated glass with low-e coating inside Glass fiber PTFE + baffles + inner membrane Laminated glass with low-e coating inside + insulated glass TABLE 2 Solar Radiation, Longwave Radiation, and Air Flow Between Zones 0.66 W/m 2 K 4 W/m 2 K 5 W/m 2 K 1.5 W/m 2 K 4 W/m 2 K 2.5 W/m 2 K 4 W/m 2 K 0.91 W/m 2 K Peak external solar radiation 10 W/m 2 Mean solar transmission, membrane 0.02 Mean solar transmission, fritted glass (roof) 0.035 Mean solar transmission, typical concourse 0.028 roof (membrane + fritted glass) Mean solar transmission, airside center roof 0.026 (membrane + fritted glass) Mean solar transmission, airside center cross 0.037 section roof (fritted glass) Mean solar transmission, 0.009 terminal skylights + louvers Mean solar transmission, 0.65 IGU roof office block Emissivity of low-e coated glass 0.17 Emissivity of scratch-resistant low-e coated 0.37 foil on membrane roof Mean emissivity of typical concourse roof 0.32 (glass + membrane) Mean emissivity of airside center cross section 0.17 roof (glass) Mean emissivity of terminal skylights 0.25 (glass + construction) Coupling between conditioned zone and upper 30 C unconditioned stratified zone 1 air exchange per hour (Terminal Hall, Level 4 Arrivals Hall) 0.2 air exchanges per hour 696 ASHRAE Transactions: Symposia

Circulation Corridor - with people mover - without people mover Description TABLE 3 Internal Loads for Typical Sections Persons Light Equipment (m 2 /person) (W/m 2 ) (W/m 2 ) (W/m 2 ) 19 19 Holdroom 3 30 0 Office 14 6.43 15 20 Retail 3 30 35 Atrium Transfer Lounge Business Lounge Central Waiting Lounge (like Holdroom) 5 3 Employee Facilities 14 6.43 15 Concessions 5 18 15 15 Bus Gate Vest. 9 0 Bus Gate 3 30 0 Airline Office 9 15 15 Arrival Hall/Baggage Reclaim 5 18 15 5 Baggage Re-check 15 6 15 15 Hotel 5 18 15 Custom Gate 9 15 15 Custom Office 9 15 15 Departure Hall 4 22.5 5 Gallery 5 18 5 Kitchen 15 6 15 30 Meeter/Greeter Lobby 5 18 15 5 Lobby 19 4.74 0 Ramp 9 0 Restaurant 5 18 15 5 Restaurant/Lounges/Shops 6 18 20 4.74 4.74 9 9 18 30 15 5 0 0 5 0 The reduction in emissivity of surface 2, the glazing, from 0.84 to 0.12 improves the radiation effect from the floor. Once the heat load to the space had been determined, the conditioning system was developed. The loads for the concourse were 97 W/m 2, and the conditioning systems to remove this heat from the space was divided as follows: Radiant floor, 80W/m 2 Ventilation air, 17W/m 2 * The ventilation air volumetric supply rate was calculated using a supply temperature of 18 C. The coils for the airhandling units could produce 16 C, which could be supplied to the space by increasing the temperature difference between required space conditions and air supply temperatures any fluctuation in the space load could be quickly picked up by the air system while the radiant floor followed. The extra cooling capacity of the air could also be used as a safety measure in the event that the humidity levels were too high. Results of the analysis provided by Holst show that the floor can absorb up to about 50 W/m 2 of short- and long wave radiation; convection and conduction components provide the other 30 W/m 2 of cooling from the floor. Because 50 W/m 2 could be absorbed into the floor, the pipe layout and mass flow of water became critical. The water supply temperature was limited to 13 C because of the condensation risk at the radiant floor surface. ASHRAE Transactions: Symposia 697

TABLE 4 Cooling Power of Radiant Floor Description Peak Power of Floor Cooling Refer. to Cooled Area (W/m 2 ) Tube Spacing (mm) Cooled Area to Total Floor Area (%) Peak Power of Floor Cooling Refer. to Total Area (W/m 2 ) Holdrooms 80 150 80 64 Circulation Level 2 70 200 64 45 Circulation Level 3 80 150 69 55 Waiting Lounges 80 150 91 72 Terminal Level 4 70 200 86 60 Terminal Level 6 70 200 84 59 Terminal Level 7 70 200 90 63 Preliminary analysis simulated a system using a 17 C return temperature. The mass flow and temperature differential were inadequate for the 80 W/m 2 capacity. The maximum return water temperature was increased to 19 C and the internal pipe diameter was 20 mm. This resulted in lower mass flow and improved heat transfer to the water flowing through the floor. To control the cooling output from the radiant floor, a controller would only control the supply water temperature at a constant 13 C. The return water temperature can vary between 13 C (no load) and 19 C (full load). The flow through the floor will be constant. Table 4 shows the different radiant cooled floor capacities. Design temperatures were: Design air temperature 24 C Ambient design temperature 36 C Mean floor temperature (mix of cooled + noncooled areas) 27 C Design mean inside surface temperature of roof construction concourses 55 C Design mean inside surface temperature of roof construction terminal skylights 45 C inside glass pane is tinted and low-e coated on the surface facing the room. The fritting pattern varies from 76% fritting to 20% from the roof panes to the vertical panes. The low-e coating on the inside glass pane is a standard pyrolytic coating, which is a state-of-the-art coating used for heat protection glass. Due to the low-e coating on the inside surface, the total solar energy reaching the floor surface is reduced dramatically. Figure 1 shows the effect of low-emission IR coating on the internal conditions. The standard situation without floor cooling and low-e coating has a PMV of 1.85 and PPD of 70%. A low-e coating does not improve conditions. The addition of floor cooling improves conditions to PMV = 1.05 and PPD = 31%. Results obtained from simulating a radiant cooled floor and a low-e coating on the inside of the glass improve conditions to PMV = 0.44 and PPD = %. RESULTS To simplify calculating the thermal load for the entire airport, the complex was divided into representative zones. The outside air demand was: Open areas Enclosed areas Airline offices 17 m 3 /h per person 26 m 3 /h per person 34 m 3 /h per person MATERIALS DEVELOPMENT The glazing system for the concourses consists of two 6 mm glass layers. A clear float glass on the outside with a double ceramic fritting reduces the solar transmission. The fritting is white toward the outside to reach a high solar reflection and black toward the room side. The laminate layer contains a coated sun protection foil to achieve a better selectivity (i.e., daylight/solar transmittance). The Figure 1 The effect of low emission IR coating. 698 ASHRAE Transactions: Symposia

Figure 2 New Bangkok International Airport, Case 1 37/119 segments. Figure 3 SBIA concourse, case 1. Figure 2 shows the first typical concourse examined. The section shows the holdrooms and the arrivals corridor at the highest level. Level 1 has floor cooling over 71% of its area, and level 2 has floor cooling over 58% of the floor area. At ambient temperatures of up to 34 C, the maximum internal temperature underneath the roof reaches 50 C, but when the floor cooling system is being supplied with a constant inlet water temperature of 13 C, the operative temperature in the occupied zone is 27 C and the air temperature is 24 C (see Figure 3). The peak cooling load for the segment being investigated is 165 kw, whereby the floor cooling removes 90 kw of heat from the space. The latent load for dehumidifying the outside air is 35 kw. There is 17 m 3 /h fresh air per person, and the sensible load to cool outdoor air and recirculating air and maintain space conditions at 24 C is 150 kw (see Figure 4). The result of this simulation for an area of 1593 m 2 shows that the peak load per square meter is 3 W/m 2 because there is 82 m 2 of floor cooling in this segment and the radiant cooled floor removes 83 W/m 2 of the load. For the terminal building, the total cooling load has its maximum at 9500 kw and the floor cooling does not exceed 3000 kw because of the external shading of the trellis roof (Figure 5). The maximum operative temperature is only 26 C because the roof is shaded by the trellis roof blades and does not get as warm as the roof in the concourses (Figure 6). The average operative temperature is about 24 C throughout the day, which provides a very comfortable indoor environment. For this large area, the combination of floor cooling and variable-volume displacement ventilation consumes a considerably lower amount of energy and provides a higher degree of comfort. Compared to the original concept (Figure 7), the peak cooling load was reduced by 35% in the optimized concept (Figure 8).For the entire airport, a cooling energy consumption of 191 GWh per year is estimated, which means 513 kwh Figure 4 SBIA concourse, case 2. Figure 5 SBIA terminal building cooling loads. ASHRAE Transactions: Symposia 699

for each conditioned square meter of floor area per year. This is a reduction of 226 kwh/m 2 energy savings per year. Bearing in mind that the airport has a total floor area of 550,000 m 2, the total annual savings are considerable. Figure 6 Figure 7 Figure 8 SBIA terminal building upper level. SBIA comparison of cooling loads for the entire airport. Optimized energy concept concourses for SBIA. CONCLUSION The Bangkok climate and the architectural design of the new airport would normally lead to enormous solar and heat gains requiring high cooling loads and producing low comfort conditions. Therefore, the operation of a variable-volume displacement conditioning system and a radiant cooled floor were developed and optimized to reduce the building load. The introduction of a floor cooling system covers one part of the cooling load, which leads to a reduction of air changes for the circulating air cooling system and also leads to lower surface and operative temperatures. Since the floor cooling removes the solar gains absorbed on the floor, it allows the anticipated stratification of the hot air in the upper volume of the concourse. The thermal comfort is improved and the infrared energy transport from the roof to the bottom level is lowered by introducing low-e coatings on the inside surface of the hot concourse building envelope. An optimized concept for the concourses with an operative temperature of 27 C was developed. The placing of the air inlets and the air exhausts makes the stratification work for the standard concourse C (see Figure 8). REFERENCES Borresen, B. 1994. Floor cooling in atrium. Velta Congress, St. Christophe, Austria (in German). Holmes, M., and A. Wilson. 1996. Assessment of the performance of ventilated floor thermal storage system. ASHRAE Transactions 2 (1). Holst, S., and T. Welfouder. 1998. Calculation of peak cooling loads. Murphy/Jain Architects, 29 May. Holst, S., T. Lechner, S. Reuss, and M. Selulen. 1998a. Concept and verification by material and function evaluation. Murphy/Jain Architects, 29 January. Holst, S., T. Lechner, S. Reuss, and M. Selulen. 1998b. Climate and energy concept, concourses. Murphy/Jain Architects, 4 October. Olesen, B.W. 1997. Possibilities and limitations of radiant floor cooling. ASHRAE Transactions 3 (1). Simmonds, P. 1993. Thermal comfort and optimal energy use. ASHRAE Transactions 99 (1): 37-48. Simmonds, P. 1994. Control strategies for combined heating and cooling radiant systems. ASHRAE Transactions 0 (1). Simmonds, P. 1996a. Using CFD to analyze temperature stratification in a large airport building. ASME Fluid Conference, San Diego. 700 ASHRAE Transactions: Symposia

Simmonds, P. 1996a. Creating a micro-climate in a large airport building to reduce energy consumption. ASHRAE Conference on Buildings in Hot and Humid Climates. Ft. Worth. Schlappman. 1996. Report on the Groninger Museum radiant floor system. University of Stuttgant (in German). DISCUSSION Philip Haves, Lawrence Berkeley National Laboratory, Berkeley, Calif.: When calculating the floor cooling from direct absorption of solar radiation in worst cases, where there is a very high occupant density, did you allow for shading of the floor by the occupants and their hand baggage, etc.? Did you modify you comfort calculation procedure to allow for the radiant coupling between occupants when the occupant density is very high, e.g. in check-in lines? Is there a need for new calculations and design tools to deal with such situations? Bernard Blazewicz, Principal Engineer, Merck and Co., Sommerset, NJ: At what floor temperature did condensation occur? ASHRAE Transactions: Symposia 701