Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields

Similar documents
PREPROCESSOR FOR THE GENERATION OF G-FUNCTIONS USED IN THE SIMULATION OF GEOTHERMAL SYSTEMS

PRELIMINARY INTERMODEL COMPARISON OF GROUND HEAT EXCHANGER SIMULATION MODELS

APPLICATIONS OF A DYNAMIC THREE-DIMENSIONAL NUMERICAL MODEL FOR BOREHOLE HEAT EXCHANGERS. M. He, S.J. Rees, L. Shao

A SIMPLE TOOL FOR SIMULATION OF GROUND SOURCE HEAT PUMP SYSTEMS

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Experimental Validation of a Numerical Model for the Thermal Response of a Borehole Field

IMPROVED DESIGN METHODS FOR GROUND HEAT EXCHANGERS RACHEL MARIE GRUNDMANN. Bachelor of Science in Mechanical Engineering. Oklahoma State University

This paper was presented at 12th REHVA World Congress (Clima 2016).

Pitfalls of Rules of Thumb in Geothermal Heat Pump Design

TEMPERATURE STRATIFICATION OF CIRCULAR BOREHOLE THERMAL ENERGY STORAGES

The correct citation for this paper is:

INCORPORATION OF GROUNDWATER FLOW INTO NUMERICAL MODELS AND DESIGN MODELS

Improvement of a Two-Dimensional Borehole Heat Exchanger Model

Bore field sizing : Theory and applications

SIMULATION AND OPTIMIZATION OF GROUND SOURCE HEAT PUMP SYSTEMS

Thermal Performances Of Three Types Of Ground Heat Exchangers In Short-Time Period Of Operation

IMPROVEMENTS IN DESIGN PROCEDURES FOR GROUND SOURCE AND HYBRID GROUND SOURCE HEAT PUMP SYSTEMS JAMES R. CULLIN

Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

A quasi-two-dimensional standing column well model for ground source heat pump systems

Numerical and analytical analysis of groundwater influence on the pile ground heat exchanger with cast-in spiral coils

Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers

MODELLING OF A LARGE BOREHOLE HEAT EXCHANGERS INSTALLATION IN SWEDEN

SIMULATION OF A DOMESTIC GROUND SOURCE HEAT PUMP SYSTEM USING A TRANSIENT NUMERICAL BOREHOLE HEAT EXCHANGER MODEL

Optimal Design for a Hybrid Ground-Source Heat Pump

Commercial Program Development for a Ground Loop Geothermal System: G-Functions, Commercial Codes and 3D Grid, Boundary and Property Extension

Parametric Study for Evaluation of Design Parameters of Standing Column Well

Finite Volume Based Computer Programs for Ground Source Heat Pump Systems

Commercial Program Development for a Ground Loop Geothermal System: G-Functions, Commercial Codes and 3D Grid, Boundary and Property Extension

Ground Loop Design. Thermal Conductivity Report - 2/15/2012. Calculation Results

ADVANCEMENTS IN THE SIMULATION OF GROUND SOURCE HEAT PUMP SYSTEMS JAMES R. CULLIN

This is a repository copy of The Average Temperature of Energy Piles.

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

MODELING THE VIABILITY OF UNDERGROUND COAL FIRES AS A HEAT SOURCE FOR ELECTRICAL POWER GENERATION

This is a repository copy of Validation of vertical ground heat exchanger design methodologies.

First Thermal Response Test in Libya Abstract 1. Introduction 2. Background

Thermal Performance and Design Guidelines of Thermo-Active Foundations

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

An Analysis on Cost Reduction Potential of Vertical Bore Ground Heat Exchangers Used for Ground Source Heat Pump Systems

A SIMPLE MODEL TO ACCOUNT FOR THERMAL CAPACITY IN BOREHOLES

Simulation of 2D Heat Transfer in a Horizontal Plane with Thermal Resistance-Capacitance Model

Field Validation of a Short Time Step Model for Vertical Ground-Loop Heat Exchangers

Numerical Modelling of Geothermal Borehole Heat Exchanger Systems Miaomiao He

EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS

Study on Heat Exchange Characteristics for PHC Energy Piles

DOE Task 99-4 Extension of Design and Simulation Models 3/24/00 EXTENSION OF EXISTING DESIGN AND SIMULATION MODELS

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing

NUMERICAL MODELLING OF MULTIPLE STANDING COLUMN WELLS FOR HEATING AND COOLING BUILDINGS

GEOTHERMAL HEAT PUMPS CONFIGURATIONS/INSTALLATION

Research on Ground Source Heat Pump Design

Enhancement of Heat Exchange Capacity of Ground Heat Exchangers by Injecting Water into Wells

Ground Source Heat Pumps: Testing three mediums surrounding the piping in geothermal field beds to evaluate performance

Temperature Response functions (G-Functions) for Single Pile Heat Exchangers

EVALUATION OF THE DESIGN LENGTH OF VERTICAL GEOTHERMAL BOREHOLES USING ANNUAL SIMULATIONS COMBINED WITH GENOPT

Horizontal Borehole Study

Hafiz M K U Haq 1, Birgitta J. Martinkauppi 1, and Erkki Hiltunen 1 1 Department of Energy Technology

A PILOT PROJECT OF THE CLOSED-LOOP GROUND SOURCE HEAT PUMP SYSTEM IN CHINA

Modeling a Novel Shallow Ground Heat Exchanger

Modeling of Standing Column Wells in Ground Source Heat Pump Systems

1 INTRODUCTION. Keywords: ground source heat pump; energy pile; geothermal; geophysics; ground temperature

Simulation of Hybrid Ground Source Heat Pump Systems and Experimental Validation

Technical University of Sofia, Department of Thermal and Nuclear Power Engineering, 8 Kliment Ohridski Blvd., 1000 Sofia, Bulgaria

A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

Multi injection rate Thermal response test

Measurement of COPs for Ground Source Heat Pump (GSHP) System in Heating and Cooling Mode

Report. Software for modelling and simulation of ground source heating and cooling systems WP2 INTERACT

DESIGN AND OPTIMUM CONTROL OF A SWEDISH DUAL- SOURCE (AIR AND GROUND) HEAT PUMP SYSTEM

February 20, 2014: The attached paper was presented at the 2014 ASHRAE Winter Meeting in New York City. It was published as a conference paper.

MULTI-DIMENSIONAL SIMULATION OF UNDERGROUND SPACES COUPLED WITH GEOENERGY SYSTEMS. Telephone: , Postal: CB2 1PZ

Performance Improvement on Water-cooled Cold-Plate

ENERGY SAVINGS, SIMULATIONS AND ECONOMIC ANALYSIS OF A GROUND SOURCE HEAT PUMP WITH VERTICAL BOREHOLE HEAT EXCHANGERS FOR A BELGIAN OFFICE BUILDING

Study on the change of soil temperature in Ground Source Heat Pump System Shili Han1, a*, Shunyu Su1,b, Lamei Liu1,c, Chuanhui Zhou1,d, Lei Shi2,e

CFD Analysis of Earth-Air Heat Exchanger to Evaluate the Effect of Parameters on Its Performance

Geothermal site selection based on varying thermal parameters using the finite cylinder source method

New Large Geothermal Storage Project in Zurich/Switzerland for Heating and Cooling

Water Resources Engineering. Prof. R. Srivastava. Department of Water Resources Engineering. Indian Institute of Technology, Kanpur.

SOLAR HEAT INJECTION INTO BOREHOLES. Case Postale 6079, succursale «centre-ville», Montréal, Québec, Canada

A Model for Annual Simulation of Standing Column Well Ground Heat Exchangers

SUPERVISED ROCK-MASS STORAGE OF THERMAL ENERGY PRODUCED BY A SOLAR THERMAL PANEL

REGRESSION ANALYSIS ON INFLUENCE OF VARIOUS FACTORS ON HEAT TRANSFER OF VERTICAL GROUND HEAT EXCHANGER

Long-term Effects of Ground Source Heat Pumps on Underground Temperature

Quenching steels with gas jet arrays

Groundwater Modeling Guidance

Transient and Succession-of-Steady-States Pipeline Flow Models

Optimization of NCG System Lineups

Computational Fluid Dynamic Analysis in De-staging of Centrifugal Pumps

Energy and Buildings

Long-Term Heating Test Using the Semi-open Loop Ground Source Heat Pump System

A NOVEL CONCEPT TO ENGINEERED GEOTHERMAL SYSTEMS

Dynamic thermal simulation of horizontal ground heat exchangers for renewable heating and ventilation of buildings

ABSTRACT INTRODUCTION

Influencing Factors on Ground Heat Balance of GSHP System Xiaohong Zhang1, a *, Zehua Liu2,b, Chao Zhang3,c and Long Ma4,d

A Simple Engineering Analysis Method to Evaluate the Geothermal Potential from a Hot Water Aquifer

Nanocomposite materials used for ground heat exchanger pipes

A Comprehensive Evaluation of Regression Uncertainty and the Effect of Sample Size on the AHRI-540 Method of Compressor Performance Representation

Numerical Investigation on Latent Heat Storage Unit of Different Configurations Manish K Rathod and Jyotirmay Banerjee

PERFORMANCE CHARACTERISTICS AND MODELLING OF CEMENTITIOUS GROUTS FOR GEOTHERMAL HEAT PUMPS

Optimizing Borehole Heat Exchanger Spacing to Maximize Advective Heat Transfer A THESIS SUBMITTED TO THE FACULTY OF UNIVERSITY OF MINNESOTA BY

Proofing Concept of Thermoinsulating Enclosure for Underground Heat Storage Systems

Transcription:

Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields Veera Malayappan 1, Jeffrey D. Spitler 2 1,2 Mechanical and Aerospace Engineering, Oklahoma State University Stillwater, Oklahoma, USA 1 veeram@okstate.edu 2 spitler@okstate.edu Abstract Models of ground heat exchangers and the surrounding ground are essential for design, optimization and energy analysis of ground heat exchangers (GHE) used with ground source heat pump (GSHP) systems. These models can account for ground thermal response of GHE in timescales ranging from hours to as long as years. A commonly used, computationally efficient method utilizes a dimensionless response function known as a g-function. The heat extraction and rejection loads on the GHE are devolved into a series of step inputs, then the g-function is used to determine the response due to each step input, and the temperature responses are superimposed to determine the evolution of borehole temperatures with time. G- functions for specific borehole configurations are calculated by superposition of single borehole responses and have been obtained with both numerical and analytical approaches. The numerical approach offers the most flexibility and does not require the approximation that all boreholes have uniform heat fluxes. However, the numerical approach requires significant computation time and the only practical approach at present is to pre-compute a library of g-functions. This paper examines the limitations of the uniform heat flux assumption as embodied in one analytical approach with a parametric study. Keywords - Ground Source Heat Pumps; Borehole Heat Exchangers; Finite Line Source Theory; g-functions 1. Introduction Ground source heat pump (GSHP) systems are a widely-used energyefficient technology for meeting the heating and/or cooling demands of residential and commercial buildings. Because of the long time constant of the ground, design tools that account for heat extraction and/or rejection over a number of years are required for sizing purposes. A computer simulation of the heat flow in the ground is used to predict the temperature rise and fall over time of the fluid temperature leaving the ground heat exchanger. One approach [1] involves the use of a dimensionless response function known as a g-function. The heat extraction and rejection loads on the GHE are devolved into a series of step inputs, then the g-function is used to determine

the response due to each step input, and the temperature responses are superimposed to determine the evolution of borehole temperatures with time. G-functions for specific borehole configurations are calculated by superposition of single borehole responses and have been obtained with both numerical and analytical approaches. The numerical approach offers the most flexibility and does not require the approximation that all boreholes have uniform heat fluxes. However, the numerical approach requires significant computation time and the only practical approach at present is to pre-compute a library of g-functions. A number of analytical approaches [2-5] have been published in recent years. This paper examines the limitations of the uniform heat flux assumption as embodied in one such approach [5] with a parametric study. The analytical approach assumes that all boreholes have uniform heat flux. Therefore, as the heat flux in the different boreholes becomes more non-uniform, we expect that the analytical approach will become less accurate. In general, non-uniform heat fluxes are caused by edge effects - e.g. in densely packed rectangular grids, the outer boreholes will have higher heat fluxes, as time goes on, than the inner boreholes. Therefore, we might expect that the larger the number of boreholes in each direction, the higher the non-uniformity and the higher the error in the simplified analytical approach. Likewise, end effects create non-uniformity along the boreholes and we expect these to be more important as the borehole depth decreases. Claesson and Javed [5] verified their approach by comparing the response predicted with their analytical g-functions to those predicted with Eskilson s g-functions for configurations with 1, 3, and 9 boreholes. Small errors can be observed after 10,000 hours; the errors clearly increase with increasing number of boreholes and with increasing time. Fossa, et al. [4] also noted a discrepancy between their analytical solution and Eskilson s results; they surmised that it could be caused by the different assumptions regarding uniform heat flux. This paper further investigates the differences between the two approaches in order to characterize the error caused by using the simplified analytical approach. Ultimately, we hope to determine generally applicable guidelines that could indicate when the use of the simplified analytical approach is acceptable. This paper focuses mainly on rectangular arrays of boreholes, but also looks briefly at other shapes such as open rectangles and double L ( L2 ) configurations. 2. Methodology The methodology used for this comparison involves application of the analytical approach and the numerical approach to generate g-functions; the g-functions developed with both approaches are then used in a bore field sizing procedure. A parametric study then examines the differences for a

range of configurations. The numerical and analytical approaches, the bore field sizing procedure and the parametric study are described below. The numerical approach of Eskilson [1] for computing the long term response is based on a two dimensional finite difference model of heat extraction boreholes in radial-axial coordinates. Spatial superposition, which accounts for thermal interference between neighboring boreholes, was used for the analysis of multiple boreholes. The temperature response is then converted to non-dimensional form to be stored as a g-function for a specific borehole configuration. Because this process is time consuming, a library of g-functions is developed for different borehole configurations. For each configuration, g-functions are stored for different ratios of borehole spacing (B) to depth (H); to use these at other combinations, they are logarithmically interpolated by the sizing software. [7] The analytical approach described by Claesson and Javed [5] is implemented in a computer program. The non-dimensional form of the response is divided into two regions, a short numerical response, which is computed numerically as described by Javed and Claesson [6]. A suitable breaking time is chosen to connect the short term response to the long term response solution. Any time between 10 hours and 1000 hours can be chosen for the breaking time as explained in [5]; 50 hours was used here. The sizing procedure [7] simulates the temperature response of the ground heat exchanger using either the numerical or the analytical approach. It adjusts the required borehole length iteratively to meet the required maximum and minimum entering fluid temperature limits. The sizing requires the monthly total and monthly peak loads as inputs from the user. Three different building/location combinations presented in [8] were initially considered for this study a school building in Memphis, Tennessee and Burlington, Vermont, and an office building in Miami, Florida. After beginning the study, we found that the Miami office building, having the highest annual imbalance, also always had the highest errors in the sizing calculations. So, we only used the Miami office building for the parametric study in order to estimate the maximum likely error. The monthly loads are obtained from the building energy analysis program EnergyPlus. The peak load analysis tool developed by Cullin and Spitler [9] was used for determining the duration of the peak loads. Because a range of building loads are needed for this investigation, monthly loads and monthly peak loads determined from a sample building are scaled up and down with a multiplier, representing a larger or smaller office building. The heat pump entering fluid temperature limits for sizing the borehole heat exchanger fields were chosen to be 44 C maximum and 19 C minimum. Miami has an undisturbed ground temperature of 25 C and these limits are consistent with the recommendations provided in [10]. Because the building loads were scaled, the total system flow rate was also scaled automatically to 0.045 liters/second of water per kilowatt of peak

cooling. Typical parameters were chosen for the ground properties and ground heat exchanger: Ground thermal conductivity: 1.73 W/m K Ground volumetric heat capacity: 2160 KJ/K-m 3 A single U-tube with standard bentonite grout in a 110 mm diameter borehole, with borehole resistance of 0.208 K/(W/m) 3. Results The section presents comparisons of the numerical and analytical g- functions for different borehole configurations. Then, uncertainties in the sizing results are discussed. The parametric study then looks at the effects of borehole heat exchanger field size, borehole spacing and borehole depth on the error. Finally, an error caused by interpolation between database entries with the numerical method is discussed. As discussed in the introduction, the analytical approach is expected to over predict the ground thermal response for more densely packed borehole fields. Figure 1 shows g-functions for square arrays of boreholes with a ratio of borehole spacing (B) to depth (H) of B/H=0.0625. The g-functions are the temperature responses of the borehole heat exchanger field to a step heat input, multiplied by the ratio of 2πk to the step heat input magnitude, where k is the thermal conductivity. The time is non-dimensionalized by dividing by the steady-state time scale, t s [1] which is H 2 /9 divided by the thermal diffusivity. As expected, as the number of boreholes in each dimension increases, and hence the uniformity decreases, the difference between the analytical g-function and the numerical g-function increases. Before presenting the sizing comparisons, a brief discussion of the uncertainties in the sizing calculations is necessary. We have identified three types of uncertainties that can affect these comparisons. 1. The convergence criteria on fluid temperature limits to which bore field is sized. By using sensitivity analysis, the uncertainty in the sized depth due to the convergence criteria (± 0.01 C) was quite small; - ±0.3% or less. 2. Uncertainty due to the interpolation of g-functions in the numerical approach. As mentioned above, the numerical approach relies on a database of g-functions for specific configurations and discrete values of B/H which are interpolated logarithmically. In the results shown below in Figures 2-6, only these discrete values of B/H have been used to eliminate any uncertainty due to this interpolation. 3. Resolution of the time domain in the numerical integration of finite line source solution. The number of intervals used for integrating the weighting function was also found to affect the magnitude of the computed analytical g-functions. For a 10x10 array of boreholes with 5 m spacing and 100 m depth, 400 intervals were sufficient. However, for cases with much deeper boreholes, more intervals

were needed. In the present study, 1000 intervals were used to precisely compute the g-function, and the resulting uncertainty is negligible. In practice, it may be desirable to use fewer intervals in order to speed computation time. The uncertainty in the oversizing shown in Figures 2-6 is then ±0.3%. Figure 1 Long time step g-function comparisons (B/H=0.0625) Figure 1 showed the deviation between numerically-calculated and analytically-determined g-functions for a range of square borehole arrays increases as the number of boreholes in close proximity increases and as time goes on. Figure 2 shows the resulting increase in sizing error with an increase in both the number of boreholes and the number of years considered for sizing. An acceptable limit on oversizing of a simplified method may depend on the situation, but if we take 5% as an acceptable limit, we can see that the simplified analytical approach would be acceptable, for a 20 or 30 year sizing period, for arrays up to 5x5 in size, at 5 m spacing and 100 m depth. The oversizing error was also found to vary with borehole depth. In general, the deeper the borehole field, the less the error in the finite line source-derived g-functions. Figure 3 shows these errors for a 10x10 rectangular borehole array and two other configurations that would have same outer dimensions, but that have fewer boreholes, and, hence, less borehole-to-borehole interference. The 10x10 rectangular configuration shows the highest sensitivity to the borehole depth. It is expected that the end effects, which are treated approximately by the finite line source method, are

more important when the boreholes are shorter. Our interpretation of these results is that the end effects are also more important in more densely packed borehole fields. 25 Sizing Error (%) 20 15 10 10 Years 20 Years 30 Years 40 Years 50 Years 5 0 0 10 20 30 40 50 60 70 80 90 100 Number of Boreholes Figure 2 Sizing error for square borehole fields (5m spacing, 100 m deep boreholes) Figure 4 shows the impact of spacing on the oversizing error. Decreasing the spacing increases the error, and increasing the number of boreholes in close proximity exacerbates this effect. Beyond showing the effects of borehole spacing, depth, and number of boreholes, we sought a method to quantify these effects and looked at derived parameters that might help better characterize the errors. Three parameters were investigated: The mean spacing computed by obtaining the average distance of separation between the individual boreholes. The aspect ratio i.e. the ratio of the number of boreholes in one direction to the number of boreholes in the other direction. The ratio of the number of interior boreholes (InteriorBH) to total number of boreholes (TotalBH).

40 35 30 10x10 Rectangular Array 36 Boreholes - L2 Configuration 36 Boreholes - Open Rectangular Configuration Sizing Error(%) 25 20 15 10 5 0 50 100 150 200 250 Borehole depth (meters) Figure 3 Sensitivity of sizing error to borehole depth (50 years, 5m spacing) 25 20 10x10 Rectangular Array 10x10-L2 configuration 10x10-Open Rectangular Configuration Sizing Error(%) 15 10 5 0 2 4 6 8 10 12 14 Borehole spacing (meters) Figure 4 Error for three configurations (80 m deep boreholes, 50 years) The oversizing error correlated most closely to the third parameter, the ratio of the interior boreholes to total boreholes. Figure 5 shows oversizing errors for a 20-year sizing period for a range of different rectangular configurations; they are grouped into different ranges of borehole numbers. E.g., the 35-36 range includes 2x18, 3x12, 4x9, and 5x7 configurations. This comparison is made for a 20-year sizing period. A horizontal bar has been drawn at the 5% oversizing level. While there is some variance between the

different groups of boreholes, we might say that, roughly, if a maximum 5% oversizing is acceptable, then the analytical g-functions would be acceptable for fields of up to 64 boreholes with ratios of interior to total boreholes of less than 0.4. A similar analysis for a 30-year sizing period (Figure 6) suggests that the analytical g-functions would be acceptable for fields of up to 64 boreholes with ratios of 0.3 or less if the acceptable oversizing limit were taken as 6%. It should be kept in mind that these errors are for a worstcase annual ground heat exchange imbalance of a cooling-only office building in Miami. Errors for more balanced cases would be much smaller. 12.5 Sizing Error (%) 10.0 7.5 5.0 2.5 80-84 Boreholes 60-64 Boreholes 48-50 Boreholes 35-36 Boreholes 0.0 0.0 0.1 0.2 0.3 0.4 0.5 0.6 InteriorBH/Total BH Figure 5 Sizing error versus interior to total borehole ratio (20 yrs., 5 m spacing, 100 m depth) 15.0 Sizing Error(%) 12.5 10.0 7.5 5.0 80-84 Boreholes 60-64 Boreholes 48-50 Boreholes 35-36 Boreholes 2.5 0.0 0.0 0.1 0.2 0.3 0.4 0.5 0.6 InteriorBH/Total BH Figure 6 Sizing error versus interior to total borehole ratio (30 yrs., 5 m spacing, 100 m depth)

Finally, one of the unexpected findings of this study is related to the logarithmic interpolation between different B/H ratios of the database of numerical g-functions. When we investigated this interpolation, we first made an estimate of the error by comparing the g-function values at various times by plotting the values vs. the B/H ratio on a log scale; comparing a smooth curve to the straight-line logarithmic interpolation suggests that the logarithmic interpolation may overestimate values of g-functions by as much as 4%. While any peak temperature prediction will depend on quite a few values of g-function, a 4% overprediction of g-function suggests that the resulting size of the ground heat exchanger could be oversized by as much as 4%. Then, when compared to the analytical g-function, an overestimate of numerically-determined size could lead to a 4% underprediction in the sizing error. This is illustrated in Figure 7, which shows the oversizing for a 10x10 array. Here, +4%/-0.3% error bars are shown on the interpolated points. It appears that the 4% estimate of possible error is probably too high, but this is a subject for further investigation. 40 35 30 10x10 Rectangular Array (interpolated) 10x10 Rectangular Array (No interpolation) Sizing Error(%) 25 20 15 10 5 0 50 100 150 200 250 Borehole depth (meters) Figure 7 Sizing error due to interpolation 4. Conclusions This paper has investigated maximum errors in sizing of ground heat exchangers due to use of a simpler analytical approximation (the finite line source method) for computing g-functions. While the actual errors will depend on the annual imbalance of heating and cooling loads, the maximum errors for a worst case load profile depend on borehole depth, spacing, and

overall density. For borehole fields of up to 64 boreholes, with a borehole depth of around 100 m and borehole spacing of 5 m, the maximum oversizing error will be around 5% when the ratio of interior to total boreholes is less than 0.4 for a 20-year sizing period. For a 30-year sizing period, the error will be around 6% or less if the ratio is 0.3 or less. However, for many real life cases, the error will be substantially less and the analytical g-functions could be used for a wider range of configurations. A recommendation for future research is that this error be quantified for a larger number of cases and an equation-fit be developed that can estimate the error as a function of borehole spacing, depth, configuration, and the building load profile. This will allow better judgment as to when the finite line source method is appropriate. An unexpected finding of this work is that interpolating between database entries of g-function values leads to an error in sizing, perhaps as high as a few percent. This should be corrected by improving the interpolation scheme. Finally, it should be noted that this work is narrowly focused on the differences between methodologies used to analyze pure conduction heat transfer with uniform soil thermal properties. There are many other realworld effects that have some (usually minor) effect on the performance. These include groundwater movement, moisture transport in unsaturated soils, and depth varying ground thermal properties. References [1] Eskilson, P. Thermal Analysis of Heat Extraction Boreholes. 1987.Doctoral Thesis. University of Lund, Lund. [2] Zeng, H. Y., N. R. Diao and Z. H. Fang. A Finite Line-Source Model for Boreholes in Geothermal Heat Exchangers. Heat Transfer Asian Research 31.7(2002) 558-567. [3] Lamarche, L. and B. Beauchamp. A New Contribution to the Finite Line-Source Model for Geothermal Boreholes. Energy and Buildings 39.2(2007) 188-198. [4] Fossa, M., O. Cauret and M. Bernier. Comparing the Thermal Performance of Ground Heat Exchangers of Various Lengths. Proceedings of 11th International Conference on Thermal Energy Storage, Effstock,Stockholm. 14-17 June 2009. [5] Claesson, J. and S. Javed. An Analytical Method to Calculate Borehole Fluid Temperatures for Time Scales from Minutes to Decades. ASHRAE Transactions 117.2(2011) 279-288. [6] Javed, S. and J. Claesson. New Analytical and Numerical Solutions for the Short Term Analysis of Vertical Ground Heat Exchangers. ASHRAE Transactions 117.1(2011) 3-12. [7] Spitler, J. D. GLHEPRO-A Design Tool for Commercial Building Ground Loop Heat Exchangers. Proceedings of the Fourth International Heat Pumps in Cold Climates Conference, Aylmer, Québec. 17-18 August 2000. [8] Spitler, J. and J. Cullin. Misconceptions Regarding Design of Ground-source Heat Pump Systems. Proceedings of the World Renewable Energy Congress, Glasgow, Scotland. 20-25 July 2008. [9] Cullin, J. R. and J. D. Spitler. A Computationally Efficient Hybrid Time Step Methodology for Simulation of Ground Heat Exchangers. Geothermics 40.2(2011) 144-156. [10] Kavanaugh, S. P. A 12-Step Method for Closed-Loop Ground Source Heat Pump Design. ASHRAE Transactions 114.2(2008) 328-337.