DESIGN ASPECTS AFFECTING THE SEISMIC BEHAVIOUR OF STEEL MRF BUILDINGS: ANALYSIS OF THREE CASE STUDIES

Similar documents
INFLUENCE OF DIFFERENT TYPES OF FULLY RESTRAINED CONNECTIONS ON THE RESPONSE OF SMRF STRUCTURES

Seismic Evaluation of Steel Moment Resisting Frame Buildings with Different Hysteresis and Stiffness Models

Inelastic Torsional Response of Steel Concentrically Braced Frames

SYSTEM PERFORMANCE OF STEEL MOMENT RESISTING FRAME STRUCTURES

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

HYBRID MOMENT RESISTING STEEL FRAMES

STRUCTURAL APPLICATIONS OF A REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTION MODEL FOR EARTHQUAKE LOADING

Comparison of Chevron and Suspended Zipper Braced Steel Frames

CONTRIBUTION of GRAVITY FRAMES TO SEISMIC PERFORMANCE OF STEEL MOMENT RESISTING FRAMES

Evaluation of the ASCE 7-05 Standard for Dual Systems: Response History Analysis of a Tall Buckling-Restrained Braced Frame Dual System

COMPARISON OF LOW-RISE STEEL CHEVRON AND SUSPENDED ZIPPER BRACED FRAMES

APPLICATION OF ENERGY DISSIPATION TECHNOLOGY FOR RETROFITTING STEEL STRUCTURES WITH VULNERABLE PRE- NORTHRIDGE CONNECTIONS

COMPARATIVE PERFORMANCE OF BUCKLING-RESTRAINED BRACES AND MOMENT FRAMES

Seismic Performance and Design of Linked Column Frame System (LCF)

Seismic Performance Evaluation of an Existing Precast Concrete Shear Wall Building

Seismic evaluation of Hybrid steel frames with different patterns of semi-rigid connection

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

EVALUATION OF SEISMIC PERFORMANCE FACTORS FOR CHEVRON BUCKLING RESTRAINED BRACED FRAMES

ANALYSIS PROCEDURES FOR PERFORMANCED BASED DESIGN

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

Concept of Earthquake Resistant Design

MCEER Hospital Demonstration Project

Seismic Performance of Residential Buildings with Staggered Walls

STRENGTH REDUCTION FACTORS FOR MULTI-DEGREE-OF-FREEDOM SYSTEMS

SEISMIC PERFORMANCE OF STEEL MOMENT RESISTING FRAMES DESIGNED WITH: DISPLACEMENT-BASED AND STRENGTH-BASED APPROACHES

CUREe-Kajima Flat Plate 1 Kang/Wallace

EFFECTS OF COLUMN CAPACITY ON THE SEISMIC BEHAVIOR OF MID-RISE STRONG-COLUMN-WEAK-BEAM MOMENT FRAMES

Evaluation of Seismic Response Modification Factors for RCC Frames by Non Linear Analysis

THE BEHAVIOR OF ECCENTRICALLY BRACED FRAMES WITH SHORT LINKS

Evaluation of Seismic Behavior for Low-Rise RC Moment Resisting Frame with Masonry Infill Walls

Engr. Thaung Htut Aung M. Eng. Asian Institute of Technology Deputy Project Director, AIT Consulting

SEISMIC SIMULATION OF AN EXISTING STEEL MOMENT-FRAME BUILDING RETROFITTED WITH EXTERNAL CABLE-STAYED SYSTEM

National Information Service for Earthquake Engineering University of California, Berkeley

Seismic Evaluation of Infilled RC Structures with Nonlinear Static Analysis Procedures

Finite Element Model Calibration of An Instrumented Thirteen-story Steel Moment Frame Building in South San Fernando Valley, California

INFLUENCE OF HYSTERETIC DETERIORATIONS IN SEISMIC RESPONSE OF MULTISTORY STEEL FRAME BUILDINGS

Seismic Response of Low-rise Steel Frame Buildings

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

Pushover Analysis of Reinforced Concrete Structures with Coupled Shear Wall and Moment Frame. *Yungon Kim 1)

Alternative Methods of Evaluating and Achieving Progressive Collapse Resistance

Evaluation Of Response Modification Factor For Moment Resisting Frames

Span Length Effect on Seismic Demand on Column Splices in Steel Moment Resisting Frames

Modeling of steel moment frames for seismic loads

A Comparison of Basic Pushover Methods

Design check of BRBF system according to Eurocode 8 Use of pushover analysis

SEISMIC DAMAGE CONTROL WITH PASSIVE ENERGY DEVICES: A CASE STUDY

LIGHTLY DAMPED MOMENT RESISTING STEEL FRAMES

Seismic performance of dual frames with composite CF-RHS high strength steel columns

EVALUATION OF ANALYSIS PROCEDURES FOR PERFORMANCE-BASED SEISMIC DESIGN OF BUILDINGS

RELIABILITY OF NONLINEAR STATIC METHODS FOR THE SEISMIC PERFORMANCE PREDICTION OF STEEL FRAME BUILDINGS

Evaluation of Response Reduction Factor and Ductility Factor of RC Braced Frame

ACCIDENTIAL TORSIONAL IRREGULARITY IN STEEL CONCENTRICALLY BRACED FRAMES

SYMMETRIC 3D R/C BUILDINGS SUBJECTED TO BI-DIRECTIONAL INPUT GROUND MOTION

ALUMINIUM SHEAR-LINK FOR SEISMIC ENERGY DISSIPATION

DEFLECTION AMPLIFICATION FACTORS FOR DUCTILE BRACED FRAMES

EVALUATION OF DESIGN METHODOLOGIES FOR STRUCTURES INCORPORATING STEEL UNBONDED BRACES FOR ENERGY DISSIPATION

Performance-based plastic design of a high rise moment resisting frame with friction dampers

Non Linear Static Analysis of Multi-storeyed Special Moment Resisting Frames

International Journal of Intellectual Advancements and Research in Engineering Computations

PERFORMANCE OF ECCENTRICALLY BRACED FRAMES UNDER THE ACTION OF LATERAL LOAD

Fragility Curves for Seismically Retrofitted Concrete Bridges

Simi Aboobacker 1 and Nisha Varghese 2

Response Evaluation of Braced Frames with Suspended Zipper Struts and Chevron Braced Frames in Near-Fault Earthquake Ground Motions

Assessment Response Reduction Factor of Elevated Tanks with Alternate RC Frame Staging Configurations

Study of Reduced Beam Section Connections with Web Opening

CYCLIC BEHAVIOR OF AN INNOVATIVE STEEL SHEAR WALL SYSTEM

Performance Based Seismic Design of Reinforced Concrete Building

Fragility Curves for Seismically Retrofitted Concrete Bridges

Effect of Interstorey Drift Limits on High Ductility in Seismic Design of Steel Moment Resisting Frames

STRUCTURAL DESIGN REQUIREMENTS (SEISMIC PROVISIONS) FOR EXISTING BUILDING CONVERTED TO JOINT LIVING AND WORK QUARTERS

A Performance Based Evaluation of a Wall- Frame Structure Employing the Pushover Analysis Tool

EVALUATION OF THE NEED FOR WEAK BEAM-STRONG COLUMN DESIGN IN DUAL FRAME-WALL STRUCTURES

POTENTIALLY PLASTIC ZONES CONFIGURATIONS IN BOTTOM COLUMNS OF ECCENTRICALLY BRACED FRAMES

TO STUDY THE PERFORMANCE OF HIGH-RISE BUILDING UNDER LATERAL LOAD WITH BARE FRAME AND SHEAR WALL WITH OPENINGS

OPTIMAL SEISMIC DESIGN METHOD TO INDUCE THE BEAM-HINGING MECHANISM IN REINFORCED CONCRETE FRAMES

LIMIT STATES FOR PERFORMANCE-BASED DESIGN

ON DRIFT LIMITS ASSOCIATED WITH DIFFERENT DAMAGE LEVELS. Ahmed GHOBARAH 1 ABSTRACT

Seismic Performance of Modular Braced Frames for Multi-Storey Building Applications

Performance Improvement of Tall Reinforced Concrete Structures with Multiple Tuned Mass Dampers (MTMD)

STRUCTURAL CALCULATIONS SEISMIC EVALUATION PEER REVIEW

SEISMIC PERFORMANCE STATES OF PRECAST CONCRETE CLADDING CONNECTIONS SUMMARY

SEISMIC PERFORMANCE EVALUATION

Performance-Based Seismic Evaluation of Wind-Impacted Tall Buildings

Base Shear Scaling. B. J. Davidson. Compusoft Engineering Ltd.

Displacement-Based Seismic Analysis of A Mixed Structural System

Improving the Seismic Response of a Reinforced Concrete Building Using Buckling Restrained Braces

ctbuh.org/papers Seismic Performance of High-Rise Intermediate Steel Moment Frames Title:

INNOVATIVE DESIGN AND TESTING OF A SEISMIC RETROFITTED STEEL DECK TRUSS BRIDGE

The International Conference on Earthquake Engineering and Seismology. Naveed Anwar. ICEES April 2011 NUST, Islamabad Pakistan

NONLINEAR PERFORMANCE OF A TEN-STORY REINFORCED CONCRETE SPECIAL MOMENT RESISTING FRAME (SMRF)

SEISMIC PERFORMANCE OF ECCENTRICALLY BRACED FRAMES DESIGNED FOR CANADIAN CONDITIONS

ctbuh.org/papers CTBUH Recommendations for the Seismic Design of High-Rise Buildings

Egyptian Code Seismic Load Design Provisions for Moment Resisting Frames

CHAPTER 8 THE DESIGN AND ANALYSIS OF MULTI-STORY BUILDINGS WITH LARGE MOMENT END-PLATE CONNECTIONS 8.1 INTRODUCTION

Seismic Response of RC Building Structures using Capacity Spectrum Method with included Soil Flexibility

COMPUTER AIDED DESIGN AND ANALYSIS OF RC FRAME BUILDINGS SUBJECTED TO EARTHQUAKES

NON LINEAR STATIC ANALYSIS OF DUAL RC FRAME STRUCTURE

Development of a New Steel Moment Connection

International Journal of Engineering and Techniques - Volume 4 Issue 2, Mar Apr 2018

Seismic performance of ductile shear wall frame systems

Transcription:

DESIGN ASPECTS AFFECTING THE SEISMIC BEHAVIOUR OF STEEL MRF BUILDINGS: ANALYSIS OF THREE CASE STUDIES E MELE 1, A DE LUCA 2 And L DI SARNO 3 SUMMARY The seismic performance of three partial perimeter and spatial moment resisting frames is analysed in order to establish if the perimeter configuration has a detrimental effect on the seismic behaviour of buildings. For these frames, designed for three different seismic areas, a comparison is presented in terms of ultimate capacity and inelastic demands, expressed through different parameters, i.e. interstory drifts, beam and column maximum plastic rotations, hysteretic energy. The results of both inelastic static and dynamic analyses allow to conclude that the behaviour of the perimeter and spatial MRFs is very similar, provided that design criteria are consistent. INTRODUCTION Following the recent earthquakes in California (Northridge, 1994) and Japan (Hyogoken-Nanbu, 1995), widespread and unexpected brittle fractures were detected in welded steel beam-to-column connections of several steel frame structures. Different opinions have been advanced on the causes of the poor performance observed during the earthquakes, also relating the erratic connection behaviour to global design choices, namely the lack of structural redundancy resulting from the U.S. current trend in the MRF design philosophy, consisting in the adoption of perimeter, or even partial perimeter configuration, for resisting lateral actions, while the interior elements support only gravity loads. A great deal of research activity is presently devoted to understand the causes of the observed behaviour. In U.S.A. the SAC Steel Project, was "formed specifically to address both immediate and long-term needs related to solving problems of the WSMF connections" (SAC, 1995). In this context some frame office buildings were designed according both to "pre-northridge" design practice (UBC, 1994) and to the Interim Guidelines (SAC, 1995) developed by the SAC. The present paper investigates on the seismic performance of partial perimeter and spatial MRFs in order to establish if the first structural configuration has detrimental effects on the seismic behaviour of buildings, giving rise to concentrations of rotation demands in the moment resisting beam-to-column connections. In particular the seismic behaviour of three frame buildings, designed within the SAC Steel Project (according to the pre- Northridge design practice) for three different seismic regions is assessed by performing nonlinear static and dynamic analyses. For the three buildings an alternative structural configuration, more close to the European design practice, i.e. spatial MRF, is also designed and analysed. For all frames is presented a comparison in terms of ultimate capacity and inelastic demands, expressed through different parameters, i.e. interstory drifts, beam and column plastic rotations, hysteretic energy. Structures and Ground Motions ANALYSED BUILDINGS The structures analysed in this paper are 3-story office buildings, designed according to UBC 1994 provisions for three different seismic zones, respectively Los Angeles (Seismic Zone 4), Seattle (Seismic Zone 2A) and Boston (Seismic Zone 2B). The three building structures have been designed by three U.S. professional firms, 1 2 3 Università degli Studi di Napoli Federico II, P.le Tecchio n 8, 8125, Napoli, Italy. E.mail: elenmele@unina.it Università degli Studi di Napoli Federico II, P.le Tecchio n 8, 8125, Napoli, Italy. E.mail: adeluca@unina.it Università degli Studi di Salerno, via Ponte don Melillo n), Italy. E.mail: luigi.disarno@mbox.diima.unisa.it

i.e. Brandow & Johnston Associates (Los Angeles building), KPFF Consulting Engineers (Seattle building) and LeMessurier Consultants (Boston building), and have been extensively analysed by several researchers (Gupta and Krawinkler, 1998) in the context of SAC studies on system performance. As shown in figure 1, all frames have the same rectangular floor plan (56.8x37.8 m): the structural geometry consists of six 9.15 m bays along major side and four 9.15 m bays in the orthogonal direction. The interstory height is 3.96 m. Figure 1 - Typical plan layout At each story level there is a floor system of 76.2 mm metal decking with 63.5 mm of NWC fill. These three buildings have MRF perimeter configuration along both directions and interior gravity frames with simple shear connections. In the Los Angeles perimeter frame there are only three moment resisting bays; this last frame has also a weak axis column. The governing design criterion of the alternative spatial MRF configurations has been: stiffness and strength close to the corresponding perimeter structure values. This condition (same fundamental periods and close yield strength capacity) is the fundamental requirement for consistent comparison between performances, as shown in next paragraphs. The frame elevations and the element cross sections are provided in figure 2. The non linear dynamic analyses have been carried out with three well-known historical records, characterised by different frequency contents and peak ground acceleration values (table 1). Table 1. Seismic inputs Earthquake Date Station Component Duration PGA [sec] [g] Imperial Valley 18.5.4 SE 53.8.348 Northridge 17.1.94 34N/118W 59.98.583 Hyogoken-Nanbu 17.1.95 EW3 56.4.834 Structural Models The non-linear dynamic analysis computer program DRAIN-2DX (Prakash et Al., 1993) was used to evaluate both the static and the dynamic responses of perimeter and spatial MRFs. The frames are modelled as twodimensional assemblages of plastic hinge (lumped plasticity) beam-column element, including bending-axial interaction and P- effects. In the SAC building design ASTM A36 steel, with nominal yield strength equal to 248 MPa (36 ksi) and Grade 5 steel (345 MPa=5 ksi) have been respectively adopted for beams and columns. The plastic hinges at the end of beam elements have been modelled with a linearized biaxial plastic domain (Bending Moment-Axial Load), with both horizontal and vertical branches corresponding to 1 of ultimate bending and axial force values. The analyses have been performed assuming material strain hardening of, while the equivalent structural damping has been fixed as of the critical value. 2

Figure 2 - Frame elevations Beam loads (self weight and exterior walls) and joint vertical loads, provided in figure 3, are the same for the two frame configurations. The floor mass values (table 2) have been computed by considering ½ floor tributary area in the case of the perimeter structures, while 1/7 of the total mass is attributed to each frame in the spatial frame configurations. The total masses are the same for the three buildings, namely 295 kn s 2 /m. The total seismic load (dead plus live loads without reduction) is W tot = 28926 kn. The fundamental vibration periods of the analysed frames, listed in the table 3 for both partial and perimeter frames, are higher (usually twice larger) than the values calculated with the empirical formula for steel MRFs suggested by UBC Method A: the code formula value, equal for all considered building structures, is.55 sec. The floor equivalent static forces and the design base shear provided by the UBC at T=.55 are provided in table 4. In the design of the spatial MRFs, the code drift limit of 1/4 under this force distribution, has been the most stringent requirement. Table 2. Floor masses Typology M 1 [kn s 2 /m] M 2 [kn s 2 / m] M 3 [kn s 2 /m] Perimeter 478.65 478.65 518.6 Spatial 136.5 136.5 148. Figure 3 - Dead plus live vertical loads. 3

Table 3. Fundamental vibration periods. FRAMES FRAMES Seismic Zone T [s] T 1 [s] T 2 [s] Seismic Zone T [s] T 1 [s] T 2 [s] Los Angeles 1.1.327.171 Los Angeles 1.12.331.171 Seattle 1.325.425.214 Seattle 1.321.422.227 Boston 1.771.563.296 Boston 1.777.529.38 Table 4. Equivalent horizontal loads. FRAMES FRAMES BUILDINGS Seismic Zone F 1 F 2 F 3 F 1 F 2 F 2 V UBC,BASE V UBC,BASE /W TOT [%] Los Angeles 189 378 596 54 18 17 2323 8.3 Seattle 95 189 297 27 54 85 1161 4.1 Boston 71 142 223 2 4 64 871 3.1 Building Resistance RESULTS The nonlinear static behaviour of the perimeter and spatial MRFs has been assessed through pushover analyses. The results of the analyses, carried out both on the single frames and on the complete buildings, are provided in figure 4, according to three seismic regions (L.A., Seattle, Boston). The charts provide the base shear V b versus the top displacement d top, normalised to the building height H. In the curves referring to the entire building structure, the base shear has been normalised to the seismic weight W tot. The curves point out that the yield strength capacity of the frames is quite higher than the relative design base shears. The nonlinear branch starts approximately at base shear values equal to 1 and 2 W tot, respectively for the Boston and L.A. building. The design (Allowable Stress Design) values of base shear are equal to 3. (Boston) and 8. (Los Angeles), thus considering the 1.5 ratio of yield to allowable stress, an overstrength factor of approximately 2 can be derived. The same ovestrength value is also reported by Osteraas and Krawinkler (199) with reference to low-rise steel frame building structures. This significant overstrength is expected to reduce the inelastic deformation demands in the structural elements. The pushover analyses results also evidence that the design of the buildings is mainly governed by stiffness requirements, as confirmed by the intersection of the vertical line at 1/4 and of the horizontal line at V UBC on approximately the same point of the curve. Finally, the comparison between spatial and perimeter MRFs curves in figure 4 underlines that the ultimate strength capacity of the spatial MRFs is consistently higher than the perimeter MRFs, though the yield displacements are similar. The close values of yield displacements is related to the approach in the design of spatial MRFs herein adopted, which was aimed to match the structural stiffness of the corresponding perimeter MRFs. Drifts and Plastic Rotations In the figures 5 and 6 the maximum values of top displacement (normalised to the building height H tot ) and of interstory drift d int (normalised to the interstory height h int ) obtained from the inelastic dynamic analyses are reported. The values of global drift are generally less than, both for perimeter and spatial frames. An exception is the case of the Seattle building perimeter frame under the seismic input, which gives 3.5. The maximum interstory drifts provided in figure 6 are generally lower than, which is the interstory drift capacity (IDC) required in (SAC, 1999) for SMRFs. The spatial frames experience slightly larger values than the corresponding perimeter frames, and under the signal, the interstory drift exceeds. 4

5 LOS ANGELES [single frames] 5 LOS ANGELES [building] 45 4 V b 4 V b / W tot [%] 35 3 1/4 3 1/4 25 2 2 15 V UBC - perimeter 1 5 V UBC - spatial d top / H [%]..5 1. 1.5 2. 2.5 3. 3.5 1 V UBC - perimeter = V UBC - spatial d top / H [%]..5 1. 1.5 2. 2.5 3. 3.5 5 SEATTLE [single frames] 5 SEATTLE [building] 45 V b V b / W tot [%] 4 4 35 3 25 1/4 3 1/4 2 2 15 1 5 V UBC - perimeter V UBC - spatial d top / H [%],,5 1, 1,5 2, 2,5 3, 3,5 1 V UBC - perimeter = V UBC - spatial d top / H [%],,5 1, 1,5 2, 2,5 3, 3,5 5 BOSTON [single frames] 5 BOSTON [building] 45 V b V b / W tot [%] 4 4 35 3 25 2 15 1 5 1/4 V UBC - perimeter V UBC - spatial d top / H [%],,5 1, 1,5 2, 2,5 3, 3,5 3 2 1 V UBC - perimeter = V UBC - spatial d top / H [%],,5 1, 1,5 2, 2,5 3, 3,5 1/4 Figure 4 - Push-over curves for single frames and the buildings The maximum plastic rotations in the beam and column elements deriving from the time history analyses are provided in figure 7. The values of plastic rotation demands at the beam ends of the perimeter and spatial MRFs are quite close and do not generally exceed the value of.3 rad, defined within the SAC Steel Project as the target plastic rotation of beam-to-column connections. The response under the earthquake induces the largest plastic rotations in the beam elements, up to values of.5 rad. The rotation demands in the columns are lower than the beam ones, since Strong Column Weak Beam design philosophy has been adopted for both the MRF configurations. Larger rotations are required to the spatial configuration columns than to the perimeter frame columns. The location of the plastic hinges is usually at the base of the first story columns or, in few cases, at the top of the third story columns. As already noticed in (Mele et Al., 1995), the comparison between interstory drifts and plastic rotations shows close values, particularly in the case of perimeter MRFs, thus confirming the potential of plastic rotation prediction starting from the interstory drift values. Since inelastic interstory drift can be related to the elastic interstory drift by means of displacement amplification factor C d, thus a reasonable prediction of plastic rotation demands can be obtained by means of a simple elastic analysis. 5

FRAMES FRAMES [d top / H tot] max [d top / H tot] max Figure 5 - Maximum top displacements FRAMES FRAMES [d int / h int ] max [d int / h int] max Figure 6 - Maximum interstory drifts BEAMS FRAMES BEAMS FRAMES FRAMES FRAMES COLUMNS COLUMNS Figure 7 - Maximum plastic rotations Dissipated Hysteretic Energy The inelastic time history analyses also provide the hysteretic energy dissipated during the ground motion. In figure 8 the hysteretic energy histories in the three perimeter and in the three spatial MRF buildings, under the and seismic inputs, are respectively provided. It can be observed that the energy dissipated by the three pairs (L.A., Seattle, Boston) of buildings configurations (perimeter, spatial) is quite close. Therefore, also in terms of hysteretic energy, the dynamic response of the perimeter and spatial MRFs is very similar, pointing out their equivalent behaviour. 6

8 [building] 8 [building] 7 6 5 4 hysteretic energy [knm] KOBE L. A. SEATTLE BOSTON 7 6 5 4 hysteretic energy [knm] KOBE 3 2 NEWHALL 3 2 NEWHALL 1 1 time [s] Figure 8 - Hysteretic energy dissipated by the buildings CONCLUSIONS time [s] The results of the static analyses show similar level of global strength capacity of the perimeter and spatial MRF buildings. The inelastic dynamic analyses evidence that the behaviour of the perimeter and spatial buildings is practically equivalent also from the point of view of the inelastic demand under different seismic inputs. Both the perimeter and the spatial frames show a good seismic behaviour, since they provide a global distribution of the plastic deformation within the entire frame, proved by the fact that the interstory drift ratios are comparable to the maximum plastic rotations and that the maximum plastic rotation values are generally smaller than.3 radians. The value of.3 rad, already found in (Mele et Al., 1995; De Luca & Mele, 1997) as an upper limit of plastic rotation demand in SCWB frames and identified in (SAC, 1995) as a reference capacity value for moment resisting welded connections, is confirmed. The results provided in terms of building ultimate capacity and global and local inelastic demands allow to conclude that the behaviour of the perimeter and the spatial MRF buildings is very similar, provided that the designs are consistent. On the basis of these results, it seems therefore possible to state that: - even though the partial perimeter buildings have a smaller number of plastic regions, there is no concentration of plastic rotation requirements. This is mainly due to the different relative capacity of the member cross-sections, which leads to the same hysteretic energy globally dissipated by the buildings; - the reason of the poor performance of the welded steel MRFs, observed in the Northridge earthquake, is not attributable to the design choice of the perimeter frames. Among others, a possible cause of the observed damage can be the large strain demand in the very deep beams used in the perimeter frames. ACKNOWLEDGEMENTS: This research has been supported by MURST. The authors would like to thank dr. J.O. Malley (Project Director) and dr. P.Clark (Project Technical Office) for having provided the data of the SAC Steel Project model buildings, prof. S.Mahin (Project Manager) for having illustrated the building designs, and prof. B. Stojadinovic for having provided updates of the building designs. REFERENCES De Luca A., Mele E. (1997). Seismic behaviour of steel frame buildings: comparison of perimeter and spatial frame solutions, Proc. XVI Congresso C.T.A., 2-5 Ottobre 1997, Ancona, Italy. Gupta A., Krawinkler H. (1998). Influence of design parameters on connection demands, Structural Engineering World Wide. Gupta A., Krawinkler H. (1998). Quantitative performance assessment for steel moment frame structures under seismic loading, 11th European Conference on Earthquake Engineering. Gupta A., Krawinkler H. (1998). Modeling issues in evaluating non linear response for steel moment frame structures, 11th European Conference on Earthquake Engineering. Mele E., D Amore E., De Luca A. (1995). Design criteria and plastic rotation requirements in steel frames subjected to seismic loadings, Proc. XV Congresso C.T.A., 15-18 Ottobre 1995, Riva del Garda, Italy. Osteraas J. and Krawinkler H. (199). Seismic design based on strength of structures. Proc. Of Fourth U.S. National Conference on Earthquake Engineering, May 2-24, Palm Springs, California, U.S.A. Prakash V., Powell G.H., Campbell S. (1993). DRAIN- 2DX Base program description and user guide - Version 1.1, Technical Report, University of California, USA. SAC Joint Venture (1995). Interim Guidelines: Evaluation, Repair, Modification and Design of Welded Steel Moment Frame Structures, Report No. SAC-95-2. FEMA 267/August SAC Joint Venture (1999). Seismic Design Criteria for New Moment-Resisting Steel Frame Construction (5 Draft), FEMA/January UBC 1994. Uniform Building Code, International Conference of Building Officials, Whittier, California. 7