Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Similar documents
Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

INTRODUCTION SPECIMEN DESCRIPTION

KINETICS NOISE CONTROL TEST REPORT #AT001052

B Page 1 of 21-

KINETICS NOISE CONTROL TEST REPORT #AT001021B

KINETICS NOISE CONTROL TEST REPORT #AT001067

KINETICS NOISE CONTROL TEST REPORT #AT001049

KINETICS NOISE CONTROL TEST REPORT # AT001084

KINETICS NOISE CONTROL TEST REPORT #AT001032

KINETICS NOISE CONTROL TEST REPORT #AT001035

KINETICS NOISE CONTROL TEST REPORT #AT001110

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E.

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

This page was. intentionally. left blank

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ACOUSTICAL LABORATORIES

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM

NRC Publications Archive Archives des publications du CNRC

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

ICF/Building System FSTC Test Report

KINETICS NOISE CONTROL TEST REPORT #AT001073

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

FLOOR CEILING ASSEMBLY

Intertek Testing Services

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC.

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to US ARCHITECTURAL PRODUCTS, INC.

DIRECT FIX TO STEEL STUD Toll Free (866) RAL Assembly STC 58

Testing Procedure: AS ISO

RSIC ACOUSTIC ASSEMBLY

SPEEDPANEL. Fire & Acoustic Rated Wall Systems. Speedpanel. Intertenancy systems SPEEDPANEL

Report Number BTC 14020A

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF 2MM ECHOPANEL WALL TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

Testing Procedure: AS ISO

A L I O N Technical Center. Test Report

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK, 13045

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Forest rx

A L I O N Technical Center. Test Report

RSIC ACOUSTIC ASSEMBLY

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

RSIC ACOUSTIC ASSEMBLY

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to KOLAY FLOORING INTERNATIONAL, LLC

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM

Testing Procedure: AS ISO

Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Expona

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4005

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4002

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

A L I O N Technical Center. Test Report

RSIC ACOUSTIC ASSEMBLY

CJ Buma. To: Steelform Building Products Inc. Wednesday, 2007 May Avenue Edmonton, AB, T6B 2V2. Attn: Mr.

RSIC ACOUSTIC ASSEMBLY

Design of a standalone, modular test facility for measuring sound transmitted through a common ceiling plenum

-Letter - Tables 1 and 2 - Figure 1 - Exhibits 1 through 6

A L I O N Technical Center. Test Report

Report Number BTC 13505A

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

TECHNICAL DOCUMENT - SOUND INSULATION R9 SYSTEM. Dated: 30 August 2013

RIVERBANK ACOUSTICAL LABORATORIES

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP. Series/Model: Protecto Wrap Whisper Mat CS

A L I O N Technical Center. Test Report

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS

Roomtmove 3/9 Church Road MAddington WA 6109

RIVERBANK ACOUSTICAL LABORATORIES

A L I O N Technical Center. Test Report

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels, Pole Moss

Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation. Prepared for:

FLOOR CEILING ASSEMBLY

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

A L I O N Technical Center. Test Report

Airbourne Sound Transmission Test

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

A L I O N Technical Center. Test Report. RAL -A CONDUCTED: Page 1 of 9 ON: BioMontage Panels - Reindeer Moss

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System

Transcription:

Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure and legal name changed through the years from Quiet Solution, Inc. to Serious Materials, Inc to Serious Energy, Inc. The acquisition of the QuietRock business by PABCO Gypsum includes the products, technical data, test reports and other intellectual property. For the avoidance of confusion, references to Quiet Solution, Serious Materials, or Serious Energy used within test reports, in general, should be understood as references to PABCO Gypsum as of August 1, 2013. QuietRock by PABCO Gypsum 37851 Cherry Street Newark, CA 94560 1.800.797.8159 www.quietrock.com

INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on both sides of a single row of 38 mm x 89 mm wood studs, spaced 610 mm on center with 90 mm of glass fibre batts. For report purposes, this wall assembly is identified as Specimen B3414-4. A complete description of the tests procedure is outlined in the Test Procedure Section. Construction on the wall assembly began on 17-June-04. The airborne sound transmission loss test was performed on 18-Jun-04. The wall assembly comprised the following elements, listed from one side of the wall to the other. Specimen B3414-4 Table 1: Element breakdown of Specimen B3414-4 Element Surface weight (kg/m 2 ) Mass (kg) 16 mm QuietRock QR-530 Serenity 13.45 120.0 38mm x 89mm wood studs, 610mm oc (on center) including headers 36.7 90 mm glass fibre batts, R12 0.9 8.0 16 mm QuietRock QR-530 Serenity 13.40 119.5 TOTAL 284.2 Total thickness: 121 mm The Specimen B3414-4 was mounted in the IRC acoustical wall test opening which measures 3.66 m x 2.44 m. The area used for the calculation of the airborne sound transmission loss was 8.92 m². The wood studs were spaced at 610mm on center. The glass fibre batts with a thickness of 90 mm was installed in the single wood stud cavity. A single layer of 16mm QuietRock QR-530 Serenity was installed vertically on both sides and attached to the wood studs with Type S drywall screws, B3414.4 -Page 1 of 6-

41mm long and spaced at 406mm oc along the edges and in the field. A product identified by the client as QuietSeal is used to seal all the joints of the QuietRock QR-530 Serenity, then covered with metal tape. The QuietSeal was also used to cover all previous screw holes on the QuietRock QR-530 Serenity. The perimeter of the specimen was also caulked with QuietSeal and covered with metal tape. The measured temperature and relative humidity in the large chamber during testing were 21.0 o C and 63.7%, respectively. The measured temperature and relative humidity in the small chamber during testing were 22.0 o C and 59.3%, respectively. RESULTS Results of the airborne sound transmission loss measurements for Specimen B3414-4 are given in Table 2 and Figure 2. B3414.4 -Page 2 of 6-

Table 2: Airborne sound transmission loss measurements of Specimen B3414-4, TLA-04-036. Frequency (Hz) Airborne Sound Transmission Loss (db) 95% Confidence Limit 1 Deviation Below the STC Contour 50 19 63 16 80 16 100 25 125 35 ±2.2 3 160 39 ±1.5 2 200 39 ±0.9 5 250 43 ±1.1 4 315 45 ±0.8 5 400 47 ±0.6 6 500 53 ±0.5 1 630 57 ±0.5 800 61 ±0.4 1000 64 ±0.4 1250 66 ±0.3 1600 67 ±0.4 2000 69 ±0.4 2500 70 ±0.4 3150 71 ±0.5 4000 71 ±0.5 5000 68 Sound Transmission Class (STC) 2 = 54 Weighted Sound Reduction (R W ) 3 =53 1 Acoustical measurement in rooms is a sampling process and as such has associated with it a degree of uncertainty. By using enough microphone and loudspeaker positions, the uncertainty can be reduced and upper and lower limits assigned to the probable error in the measurement. These limits are called 95% confidence limits. They are calculated for each test according to the procedures in ASTM and must be less than upper limits given in the standards. These confidence limits do not relate directly to the variation expected when a nominally identical specimen is built, installed and tested (repeatability). Nor do they relate to the differences expected when nominally identical specimens are tested in different laboratories (reproducibility). 2 Sound Transmission Class (STC) calculated according to ASTM E413. 3 Weighted Sound Reduction (R w ) calculated according to ISO 717. B3414.4 -Page 3 of 6-

100 TLA-04-036 90 Frequency (Hz) Airborne Sound Transmission Loss (db) Airborne Sound Transmission Loss, db 80 70 60 50 40 30 20 10 50 19 63 16 80 16 100 25 125 35 160 39 200 39 250 43 315 45 400 47 500 53 630 57 800 61 1000 64 1250 66 1600 67 2000 69 2500 70 3150 71 4000 71 5000 68 0 63 125 250 500 1000 2000 4000 Frequency, Hz STC 54 Figure 1: Airborne sound transmission loss results for Specimen B3414-4. The solid line is the experimental data and the dotted line is the STC 54 contour. B3414.4 -Page 4 of 6-

NOTES ON THE SIGNIFICANCE OF TEST RESULTS Sound Transmission Class And Weighted Sound Reduction Index The Sound Transmission Class (STC) and Weighted Sound Reduction Index (R w ) are single-figure rating schemes intended to rate the acoustical performance of a partition element under typical conditions involving office or dwelling separation. The higher the value of either rating, the better the wall performance. Thus, the rating is intended to correlate with subjective impressions of the sound insulation provided against the sounds of speech, radio, television, music, office machines and similar sources of noise characteristic of offices and dwellings. In applications involving noise spectra that differ markedly from those referred to above (for example, heavy machinery, power transformers, aircraft noise, motor vehicle noise), the STC and R w are of limited use. Generally, in such applications it is desirable to consider explicitly the noise spectra and the insulation requirements. Extended Frequency Range Standard test procedures require measurements in 1/3- octave bands over a specified frequency range (125 to 4000 Hz for ASTM E90). Within those ranges, reproducibility has been assessed by inter-laboratory round robin studies. The standards recommend making measurements and reporting results over a larger frequency range, and this report presents such results, which may be useful for expert evaluation of the specimen performance. The precision of results outside the standard ranges has not been established, and is expected to depend on laboratory-specific factors such as room size and specimen dimensions. FACILITIES AND EQUIPMENT The acoustics wall test facility comprises two reverberation rooms with a moveable test frame between the two rooms. One room has a volume of 138 m 3. The volume of the other room is 250 m 3. In this report they are referred to as the small and large chambers, respectively. Measurements are controlled by a desktop PC-type computer interfaced to a Bruel & Kjaer 2144 real time analyser. Each room has a calibrated Bruel & Kjaer condenser microphone with a type 4166 cartridge that is moved under computer control to nine positions used for the acoustical measurements. Each room has four loudspeakers B3414.4 -Page 5 of 6-

driven by separate amplifiers and noise sources. To increase the randomness of the sound field, there are also fixed diffusing panels in each room. TEST PROCEDURE Airborne Sound Transmission Loss Airborne sound transmission measurements were conducted in accordance with the requirements of ASTM E90, Standard Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions, and of ISO 140-3, Laboratory Measurement of Airborne Sound Insulation of Building Elements. The Sound Transmission Class (STC) was determined in accordance with ASTM E413, Classification for Rating Sound Insulation. The Weighted Sound Reduction Index (R w ) was determined in accordance with ISO 717-1, Rating of Sound Insulation in Buildings and of Building Elements, Part 1: Airborne Sound Insulation. One-third octave band sound pressure levels were measured for 32 seconds at nine microphone positions in each room and then averaged to get the average sound pressure level in the room. Five sound decays were averaged to get the reverberation time at each microphone position in the receiving room. These times were averaged to get the average reverberation times for the room. The average sound pressure levels of both the source and receiving rooms and the average reverberation times of the receiving room were used to calculate sound transmission loss values. Airborne sound transmission loss tests were performed in the forward (receiving room is the large room) and reverse (receiving room is the small room) directions. Results presented in this report are the average of the tests in these two directions. A complete description of the test procedure, information on the flanking limit of the facility and reference specimen test results are available on request. B3414.4 -Page 6 of 6-