The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions

Similar documents
Study on AC Flashover Performance for Different Types of Porcelain and Glass Insulators With Non-Uniform Pollution

Study on Pollution Flashover Performance of Short Samples of Composite Insulators Intended for ±800 kv UHV DC

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Pollution Performance of HVDC SiR Insulators at Extra Heavy Pollution Conditions

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Study on the dc flashover performance of standard suspension insulator with ringshaped non-uniform pollution

A Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators

COMPARISON OF THE SPECIFIC SURFACE CONDUCTIVITY AND ESDD APPROACHES TO ASSESSMENT OF SALT DEPOSITS ON NATURALLY POLLUTED INSULATORS. 1.

Comments on Document from Richard Martin, Canada

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

INSULATOR REQUERIMENTS:

Different Characteristics of Artificially Polluted High Voltage Composite Insulators

Flashover Performance of Pre-contaminated and Ice-covered Composite Insulators to be Used in 1000 kv UHV AC Transmission Lines

C Pollution measurement based on DDG method for different type s of insulator profile

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Simulation Study of the Pollution Deposition Characteristics of the Insulators on High-Voltage DC Transmission Lines

ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE

Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS

Study of Pre-polluting Methods on Artificial Icing Flashover Characteristics of Composite Insulators

The Effect of Severity and Location of Pollution on Leakage Current Characteristics of Porcelain Insulators under Different Humidity Condition

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments

Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method

Natural Contamination and Surface Flashover on Silicone Rubber Surface under Haze Fog Environment

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Development of Composite Line Spacers for Distribution Lines

Analysis of Leakage Current to Predict Insulator Flashover Using Artificial Neural Network

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy

PS2: Lifetime management, deterioration and ageing of substation equipment

Composite Insulator Components

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and

Prediction of flashover voltage of non-ceramic insulators under contaminated conditions

Investigation on the Process of Dry Ice Cleaning Insulators

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

High Quality Porcelain Insulators for Transmission Lines

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Artificial intelligence assessment of sea salt contamination of medium voltage insulators

Comparison of effects of Various Contaminations on SiR insulators

Mapping HV Insulators Pollution in the Mediterranean Island of Crete

ILMOS Insulator Leakage Current Monitor

Study on the Application of Advanced Power Electronics in Smart Grid

DL/T Translated English of Chinese Standard: DL/T

LIGHTNING IMPULE PERFORMANCE OF POLLUTED MEDIUM VOLTAGE INSULATORS

COPYRIGHTED MATERIAL INTRODUCTION CHAPTER SCOPE AND OBJECTIVES

Application of Decision Trees in Mining High-Value Credit Card Customers

CONDITION MONITORING OF INSULATORS UNDER POLLUTION ABSTRACT

Sediver High Resistivity insulators for HVDC applications

An Investigation Into The Methodology To Develop An Insulator Pollution Severity Application Map For South Africa

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Annex A: Measurement of ESDD and NSDD

Experimental Techniques to Simulate Naturally Polluted High Voltage Transmission Line Insulators

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test

Polluted Outdoor Insulators Maintenance and Washing

Are there any new or emerging trends in technology that will impact the scope and work activities of the TC? Please describe briefly.

High Resistivity toughened glass insulators for HVDC applications. Experts & Pioneers USA/CANADA

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

Panagiotis Charalampidis

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Si-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation

WILEY A JOHN WILEY & SONS, INC., PUBLICATION

Scientific Journal Impact Factor: (ISRA), Impact Factor: 2.114

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators

SC C3 System Environmental Performance

Factors Contributing to Haze Formation and the Influence on Power Equipments External Insulation

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION

Optimum Return Period of an Overhead Line Considering Reliability, Security and Availability with Respect to Extreme Icing Events

Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case

B2-00. SPECIAL REPORT FOR SC B2 (Overhead Lines) V. NAIDOO J. IGLESIAS S. ANSORGE. Special Reporters

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

Surface Roughness Effect on the Hydrophobicity Characteristic of Operating Composite Insulators

Dry reusing and wet reclaiming of used sodium silicate sand

SILICONE RUBBER INSULATORS WITH NOTCHED SURFACE

Pins Insulator. Composite/Polymers Insulators

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May 2010

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

Modeling Of River Flow For The Reservoir Routing

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

Electric Field and Current Density Characteristic of Contaminated Solid Insulator

Optimization of maintenance for power system equipment using a predictive health model

fire Charcoat Charcoat IC Passive Protection

Porcelain Insulator Performance under Different Condition of Installation around Aligarh

Robust and Decentralized Operations for Managing Renewable Generation and Demand Response in Large-Scale Distribution Systems

Comparative Investigation of Silicone Rubber Composite and RTV Coated Glass Insulators Installed in Coastal Overhead Transmission Lines

DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil

Influences of Agricultural Irrigation on Regional Salinity Balance in Arid Areas of Northwestern China

Materials Research for Power Products A review on Nanotechnology

Thermal analysis of recent crude oil transportation technologies in China

Single and Multiple Outage Statistics in Turkish National Power Transmission System

Integration of Photovoltaic Generation in a Microgrid: Spinning Reserve Analysis

RE-EVALUATION OF CREEPAGE DISTANCE REQUIREMENTS FOR OUTDOOR INSULATION IN SEC-ERB

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS

Chemical analysis of insulator contaminants and Reliability improvement of T&D line for smart operation of grid under chemically polluted environment

Transcription:

1 The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions Ying Long 1, Yan Xiao 1, Zhiyi Su 2, Dong Wu 3, Urban Astrom 3 Abstract--The reliability of DC lines is critical for the reliability of Ultra High Voltage (UHV) DC system operation. Being the main factor in determining the reliability of DC lines, the external insulation is designed mainly with the consideration of the pollution performance of DC insulators at the operating voltage in contaminated areas. Among the approaches for external insulation design, the statistical method would be a good candidate with the consideration of the statistical nature of the input variables. In order to use the statistical method with reasonable confidence for (U)HVDC projects, the influences of various potential inputs on the dimensioning results with statistical principles are studied and evaluated in a cooperative project between ABB and China EPRI. The results demonstrate that the interpretation from the natural conditions to artificial conditions or vice versa is most important for the reliability of the insulator dimensioning in the statistical method because it affects the insulator performance and consequently the dimensioning results significantly. It also shows that the different parameters have different effects on the design result. The study is the important step for input preparation for the statistical dimensioning of insulators with regard to pollution conditions on (U)HVDC lines. Index Terms Insulator Dimensioning, Pollution, Statistical Method, DC Lines, (U)HVDC, Reliability. I. INTRODUCTION Large-capacity HVDCs have been the popular solutions for power transmissions in various countries. The reliability of DC lines is critical for the reliability of (U)HVDC system operation, and the external insulation design with regard to pollution performance is the determining factor for the reliability of DC lines in the contaminated environment [1]. With the coming UHVDC project in China, the higher requirements are needed for external insulation, and more investigations are thereby motivated. The approaches for insulator dimensioning generally can be classified into the deterministic method and statistical method. The statistical method would be a promising candidate since it is applied for insulation dimensioning with 1 Y. Long and Y. Xiao are with Corporate Research, ABB China, 100016(e-mail: Emily-Ying Long@cn.abb.com). 2 Z.Y. Su is with China Electrical Power Research Institute, Beijing, 100085. 3 D. Wu and U. Astrom are with ABB, Power System, Ludvika, Sweden. the consideration of the statistical nature of the input variables. However, the approach is rarely accepted by the designers so far because more detailed and reliable input data is needed to describe the variables, most of which are often difficult to be available [1]. In spite of this, new efforts have been made recently to develop software applications with the statistical principles, in an attempt to help the designers with the line design or line performance assessment [2-4]. It is important to validate the applications with the existing projects. However, up to now, there is lack of clear guidance about the numerous and complicated inputs for the users. And it is not well known yet how and how much all variables have influences on the reliability of the dimensioning results. The preparation of the input data therefore becomes important for the reliability of benchmark, and also one of the important works before the statistical method can be used with reasonable confidence. In a cooperative project between ABB and China Electrical Power Research Institute (CEPRI), the influence of various parameters are studied and evaluated on the dimensioning results based on statistical principles. The results can be used as a reference/guide to inputs preparation for benchmark with existing HVDC projects. It is also one of the important steps in the reliability of the outdoor insulation design or assessment for (U)HVDC projects with statistical principles. A. Principles II. SOLUTION AND METHODOLOGY The optimal dimensioning results with statistical principles are obtained by the calculation of the line s risk-of-failure to an acceptable value at the specific operating voltage. The equation is given as follows [5-6]. R = M f ( x) P( x) dx (1) In which f(x) is probability density function of site severity at the start of a wetting event, P(x) is the cumulative function of insulator flashover probability, x is the site severity (Equivalent Salt Deposit Density (ESDD)), M is the number of wetting events in the calculated period, and R is the line s risk-of-failure. When the insulation with the higher strength is selected,

2 the probabilistic flashover curve moves towards the right of the distribution function of ESDD, so that the risk-of-failure decreases, as shown in Figure 1 [1, 6-7]. B. Influencing factors Fig. 1 The principle of the statistical method According to the figure 1, both the pollution performance of DC insulators and the pollution severity in the areas where HVDC lines pass through are decisive factors for insulation design. However, the pollution performance, P(x), is obtained in laboratory tests under typical conditions; while the distribution function of pollution severity density is derived from the natural conditions. It has been recognized that there are significant differences in the behavior of insulators under these two conditions [1]. In order to make correctly use of the data from these two different sources, correction factors are needed for the conversion and unification. Such correction factors have mostly been obtained from artificial tests. As an example, Table 1 summarizes the major differences between natural conditions and laboratory test conditions (solid layer method) for the line insulators [8]. In addition to the factors listed in Table 1, there are some other differences between the natural conditions and test conditions, e.g. wetting method and intensity [1]. For insulator dimensioning with statistical principles, more parameters, e.g. the standard deviation of the probability density distribution of pollution severity (e.g., lognormal distribution, Ln(ESDD)), the standard deviation of insulator performance, number of strings in parallel and number of wetting events also have influences on insulator design. C. Equations and basic conditions A bind of equations for insulator dimensioning of DC lines in respect of polluted conditions is proposed to be evaluated with the operational data of the existing HVDC projects. To date, many studies have been conducted and reported on DC flashover voltages at various laboratories under different test conditions, e.g. different inert materials and different quantities [16-22]. Based on the results of literatures, the following equations are obtained by analyzing the data in numerical statistical way. The flashover characteristics as function of pollution severity (Salt Deposit Density (SDD)), under 0.1 mg/cm 2 of NSDD (Roger s Kaolin) and uniform distribution, for the DC porcelain insulators The conversion between SDD and ESDD with the consideration of calcium ion proportion in natural contamination The conversion between SDD and ESDD with the consideration of the organic component in natural contamination The correction of the type of NSDD The correction of the quantity of NSDD The correction of the contaminant distribution on the surface between the top and the bottom of the insulator The dimensioning results by the equations are then tested by the design data [16,17], and the maximum errors of the required number are 3% and 5% separately. In addition to the equations aforementioned, there are some assumed conditions used for the study in Section III as shown in Table 2. TABLE 1 THE DIFFERENCES BETWEEN NATURAL CONDITIONS AND STANDARD POLLUTION TEST CONDITIONS FOR PORCELAIN INSULATORS. Factors Different in shed profiles Top/bottom surface of a shed Along the insulator Type of salt Type of Non-Soluble Deposit Density (NSDD) Quantity of NSDD Installation in a nonvertical position Natural conditions Often different in pollution accumulation Often nonuniformly polluted Often nonuniformly polluted Different and site Can be various types and site Site Often accumulate less pollution Test Empirical conditions correction Same None uniform pollution for all type of sheds Uniform Available [9-12] Uniform Sodium Chloride (NaCl) Kaolin or Tonoko g in 1000g water Often not being considered Available [12] Available for some cases [10,11,13] Available between a few types used in artificial tests [9,12, 14,] Available [9-10,12-15] None TABLE 2 THE SPECIFIED VALUES FOR THE PARAMETERS IN STUDY Conditions Values and References Insulator type The specified DC porcelain insulator Line length 100km Number of strings 0 The maximum 515kV system operating voltage

3 Acceptable risk-offailure The standard deviation for Ln(ESDD) Calcium ion proportion 0.02/(100km yr) 0. or 0.3-0.8 [5,23] %-90%, according to the measurements along Gezhouba- Nanqiao HVDC lines [10] NSDD/ESDD 4-6 [10] Top to bottom ratio 1/3 when The number of wetting events III. SENSITIVITY STUDY A. Calcium ion 1/5 when ESDD=0.05mg/cm 2 1/8 when 1/10 when ESDD 0.1mg/cm 2 [10] 10-100, estimated according to the regional navigation information along Yangtse River The influence of the calcium salt on the dimensioning results is studied and the results are shown as in Figure 2. It shows that the dimensioning results are affected significantly by the calcium ion proportion. The required number estimated without consideration of the correction is over 10 pieces more than the estimation with % of calcium ion proportion. And the difference of the results between % and % of the calcium ion proportion is about 5-7 pieces. It is evident that the design needs to be optimized with the consideration of the salt type of ESDD. The salt type and proportion, e.g. the calcium ion proportion, should be measured and estimated. 35 25 -* % % 90% Calcium ion proportion (* without consideration of the correction) Fig. 2 The influence of calcium ion proportion on insulator dimensioning of DC lines (The number of wetting events is 1) B. NSDD The influence of different quantity of NSDD on dimensioning results is shown as in Figure 3. According to the results, there is a remarkable difference between the result with and without the correction of NSDD by 17% of the average difference. The ratio of NSDD to ESDD does not have a significant effect on the results. For instance, at 0.08mg/cm 2, the required number is 49 and 52 for the ratio of 4 and 6 respectively. The difference is not influenced significantly by the wetting events. One ratio reasonably estimated from on site measurement, e.g. 5, can be adopted. 10 0 ESDD=0.05mg/cm 2 0.1 4*ESDD 6*ESDD NSDD, mg/cm 2 Fig. 3 The influence of NSDD quantity on the estimation of dimensioning (The number of wetting events is 1) C. Non-uniform distribution Figure 4 shows the influence of non-uniform distribution between the top and bottom of the insulator s surface. The results differ remarkably between with uniform distribution (1/1) and non-uniform distribution (1/10). The average difference is larger than %. However, the difference is not significant between 1/10 of the top to bottom ratio and the values given in Table 2, especially at moderate and heavy pollution levels. The non-uniform distribution on the surface of insulators should be considered in design. Typical value, e.g. 1/10, can be used. 100 90 10 0 >100 1/1 1/10 values in Table 2 Top to bottom ratio ESDD=0.05mg/cm 2 Fig. 4 The influence of the non-uniformity distribution on the estimation of dimensioning (The number of wetting events is ) D. Standard deviation of probability density distribution of pollution severity Usually, lognormal/normal distribution function is used to describe the pollution accumulation. Both the mean and variance are derived by the measurement. The influence of

4 different standard deviations of Ln(ESDD) on insulation dimensions is shown in Figure 5 for of the number of wetting events. The results are affected by the standard deviation remarkably by about 2 pieces and 4 pieces per 10% increase of the standard deviation, at 0.03 and 0.08 mg/cm 2 respectively. The standard deviation of Ln(ESDD) has more influence on the results under the heavier pollution condition. 75 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Standard deviation of pollute severity distribution (Lognormal) Fig. 5 The influence of standard deviations of pollution severity distribution on the dimensioning results (pollution severity as lognormal distribution with design ESDD as 2% maximum value) E. Standard deviation of insulator performance According to the results in Figure 6, the influence of the variance of flashover voltages on the dimensioning results is remarkable and the dimensioning results increase with the increase of standard deviation by about 2 pieces per 1% of the deviation change. SDD=0.05mg/cm 2 0.06 0.07 0.08 0.09 0.10 Standard deviation of flashover voltage Fig. 6 The influence of standard deviations of flashover performance on the dimensioning results F. Number of strings The study with different number of strings in parallel shows that the results are not sensitive to the string number if the number is greater than 100 (Figure 7). Since the number of strings is often more than 100 for a line section longer than 25km. A typical value between 100 and 1000 can be used in design, without leading to a significant difference. With the shorter line section, the actual number should be adopted, in particular at the moderate and heavy pollution areas. 35 0 0 0 0 1000 Number of strings in parallel, strings Fig. 7 The influence of strings in parallel on dimensioning estimation G. Number of events As shown in Figure 8, the number of wetting events has a significant influence on the dimensioning results when the number is below. The effects of the number of wetting events are involved with other parameters, e.g. pollution level, the standard deviation of pollution severity distribution. The joint effect of the wetting events with other parameters are not described in detailed in the paper. Required Number of Units (pieces) 90, standard deviation of Ln(ESDD)=0., standard deviation of Ln(ESDD)=0., standard deviation of Ln(ESDD)=0.75 0 100 1 1 1 1 0 Wetting event number Figure 8 The influence of wetting event number on dimensioning estimation H. Other parameters Other parameters, which may have an impact on insulator dimensioning, are not included in the paper and need to be further studied. IV. DISCUSSION AND CONCLUSION To apply the statistical method in (U)HVDC projects, the selection of the inputs has significant influences on the reliability of the results. In order to make proper preparation of the inputs, the sensitivity of the dimensioning results to the inputs are investigated and analyzed. The results are summarized as follows. (1) It is critical for the reliability of the insulator dimensioning to convert and unify the data from both natural

5 and artificial conditions into the same working reference. The correction factors have significant influences on the insulator performance, consequently affect the design results remarkably. (2) The salt type and proportion should be measured and estimated carefully, since significant deviations may be caused. (3) The quantity of NSDD needs to be considered in the design. (4) The correction of non-uniform of pollution distribution on the insulator should be applied. (5) The standard deviation of probability density distribution of pollution severity has a significant influence on the dimensioning results, especially at the moderate and heavy pollution level. (6) The standard deviation of flashover voltage has an impact on the design results. (7) The influence of the number of strings in parallel is not significant on the insulator dimensioning when it is greater than 100. A typical value between 100 and 1000 can be used in the design. (8) The influence of the number of wetting events is remarkable on the insulator dimensioning when it is low, e.g. below. The influence of the wetting events is involved with other parameters, which should be further studied. The study provides some guidance for the input preparation for the insulator dimensioning in statistical method. There is still a need for the further research work on these and other parameters. V. REFERENCES [1] TF 33-04-01, Polluted insulators: A review of current knowledge, CIGRE Brochure 158, September, 1999 [2] I. Gutman, K. Halsan, D. Hubinette, et al. New developed insulator selection tool (IST) software: results of application using known Russian service experience, Proceedings of the 12 th Asian conference on electrical discharge, Graduate school of Shenzhen, Tsinghua University Shenzhen, China, Nov. 04 [3] E.A. Solomonik, N.N. Tikhodeev, L.L. Vladimirsky, I. Gutman, Methods of statistical dimensioning of the outdoor insulation with respect to polluted conditions, IEEE Power Tech 05, St. Peterburg, Russia, Jun. 05, paper 6. [4] I. Gutman, K. Halsan, L. Wallin, et al. Line performance estimator software: calculations of lightning, pollution and ice failure rates compared with service records, CIGRE, B2-5, Paris, 06 [5] K. Naito, Y. Mizuno, W. Naganawa, A study on probabilistic assessment of contamination flashover of high voltage insulator, IEEE Transaction on Power Delivery, Vol 10, No 3,Jul 1995 [6] C.S. Engelbrecht, R. Hartings, J. Lundquist, Statistical dimensioning of insulators with respect to polluted conditions, IEE Proc.-Gener. Transm. Distrib., Vol 151, No 3, May 04 [7] Insulation co-ordination Part 2: Application guide, IEC071-2, Dec 1996 [8] D. Wu, U. Astrom, Z.Y. Su, W.M. Ma, Critical issues on the dimensioning of external insulation for UHVDC converter stations, Paper Selection of 06 International Conference of UHV Transmission Technology, Beijing, China, Nov 28-. 06 [9] CIGRE TF33.04.04, Artificial pollution testing of HVDC insulators: Analysis of factors influencing performance, Electra, No1, Feb 1992, pp99-113 [10] Z.Y. Su, X.D. Liang, Y. Yin, J.Zhou, W.F.Li, P. Li, Important correction factors in HVDC line insulation selection, Proceedings of the XIVth International Symposium on High Voltage Engineering, Tsinghua University, Beijing China, August 25-29 05 [11] L. E. Zaffanella, H.M. Schneider, J.H. Dunlap, Performance of contaminated insulators for HVDC lines, CIGRE 33-05, 1986 [12] K. Naito, External insulation design of HVDC transmission lines and stations, NGK, Mizuho, Nagoya, Japan, Tech. Rep. TN-847, May 1985 [13] Technical Report, Contamination withstand voltage characteristics of insulators in inland areas, Institute of Electrical Engineering of Japan, Vol 1, No137, 1984 [14] R. Matsuoka, K. Kondo, K. Naito, M. Ishii, Influence of nonsoluble contaminants on the flashover voltage of artificially contaminated insulators, IEEE Transactions on Power Delivery, Vol 11, No 1, January 1996 [15] NGK Technical Guide, Cat. No. 91R [16] Z.Y. Su, X.D. Liang, Y. Yin, J.Zhou, W.F.Li, P. Li, Outdoor insulation selection method of HVDC lines, Proceedings of the XIVth International Symposium on High Voltage Engineering, Tsinghua University, Beijing China, August 25-29 05 [17] NGK, The external insulation design in HVDC transmission lines, TN-00043R3, Jan, 04 [18] Y. Hasegawa, K. Naito, K. Arakawa, H.M. Schneider, L.F. Zaffanella, A comparative program on HVDC contamination tests, IEEE Transactions on Power Delivery, Vol 3, No 4, October 1988 [19] R.Y. Zhang, Pollution Flashover of External Insulation, Beijing: Hydraulic Power Publish, 1994 (in Chinese) [] Y. Yamamoto, K. Kawabata, Y. Maekawa, Design of the Anan- Kihoko DC trunk line, CIGRE SC22, 1997 [21] W.F.Li, P. Li, Z.Y. Su, J.B. Fan, Contamination flashover performance of insulator strings and post insulators used for ±0kV HVDC system, Proceedings of the XIVth International Symposium on High Voltage Engineering, Tsinghua University, Beijing China, August 25-29 05 [22] T. Kawamura, T. Seta, S. Minemura, K. Naito, Rationalized antipollution insulation designs of DC transmission lines and stations, International Conference on Large High Voltage Electric Systems, CIGRE, Paris, 1986 [23] C.S. Engelbrecht, I. Gutman, R. Hartings, A practical implementation of statistical principles to select insulators with respect to polluted conditions on overhead AC lines, IEEE Power Tech 05, Russia, 05