ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE

Similar documents
EXPERIMENTAL AND THEORETICAL STUDY OF HEAT PUMP PERFORMANCE ENHANCEMENT BY USING A NANOREFRIGERANTS

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

Chapters 5, 6, and 7. Use T 0 = 20 C and p 0 = 100 kpa and constant specific heats unless otherwise noted. Note also that 1 bar = 100 kpa.

ANSYS, Inc. March 31, Phase Change Models in FLUENT

Thermodynamics: Homework A Set 6 Jennifer West (2004)

COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22

Eng Thermodynamics I: Sample Final Exam Questions 1

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

MECHANICAL ENGINEERING DEPARTMENT, OITM

PERFORMANCE IMPROVEMENT OF AIR CONDITIONING SYSTEM BY USING NANOREFRIGERANT

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

Department of Mechanical Engineering. MSc/PGDip/PGCert in Energy Systems and the Environment. Specialist Modules

Performance Investigation of Window Air Conditioner

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

The performance of a heat pump using nanofluid (R22+TiO 2 ) as the working fluid an experimental study

EXTRA CREDIT OPPORTUNITY: Due end of day, Thursday, Dec. 14

Flow analysis and noise reduction of discharge silencer by using cfd

S.E. (Mechanical) (First Semester) EXAMINATION, 2012 APPLIED THERMODYNAMICS (2008 PATTERN) Time : Three Hours Maximum Marks : 100

Code No: RR Set No. 1

Module 05 Lecture 35 : Low temperature process design Key words: Refrigeration system

Lecture No.3. The Ideal Reheat Rankine Cycle

Review Questions for the FE Examination

Center for Environmental Energy Engineering Department of Mechanical Engineering University of Maryland College Park, MD

Problems in chapter 9 CB Thermodynamics

Improvement of the Performance for an Absorption Refrigerating System with. Lithium bromide-water as Refrigerant by Increasing Absorption Pressure 1

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Pool Boiling Heat Transfer to Water/Lithium Bromide Mixture

Thermodynamic Performance Assessment of R32 and R1234yf Mixtures as Alternatives of R410A

Analytical model of a multichannel double tube CO2 gas-cooler for a water heater

Feedwater Heaters (FWH)

Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle

Eng Thermodynamics I - Examples 1

PAPER-I (Conventional)

NUMERICAL INVESTIGATION OF AN R744 LIQUID EJECTOR FOR SUPERMARKET REFRIGERATION SYSTEMS

Enthalpy Calculations. Change in enthalpy can occur because of change in temperature, change in phase, or mixing of solutions and reactions.

Eng Thermodynamics I - Examples 1

Natural Refrigerants in different applications

Multi-Stage Cascade Refrigeration System

EXPERIMENTAL STUDY OF ALTERNATIVE REFRIGERANTS TO REPLACE R134a IN A DOMESTIC REFRIGERATOR

Scientific Journal Impact Factor: (ISRA), Impact Factor: [Son, 3(10): October, 2014] ISSN:

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR

AE R1 November, 2003

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM IV (ME-41, 42,43 & 44)] QUIZ TEST-1 (Session: )

A NOVEL DESIGN OF COMPACT BRAZED PLATE HEAT EXCHANGER FOR CO2 TRANSCRITICAL APPLICATIONS

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

CONTROL VOLUME ANALYSIS USING ENERGY. By Ertanto Vetra

Thermodynamics: Homework A Set 3 Jennifer West (2004)

PI Heat and Thermodynamics - Course PI 25 CRITERION TEST. of each of the following a. it

MCG THERMODYNAMICS II. 22 April 2008 Page 1 of 7 Prof. W. Hallett

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

EXPERIMENTAL ANALYSIS OF TRIPLE FLUID VAPOUR ABSORPTION REFRIGERATION SYSTEM DRIVEN BY ELECTRICAL ENERGY AND ENGINE WASTE HEAT. Kancheepuram, India

Refrigeration Kylteknik

THERMAL ENERGY ANALYSIS OF SOLAR POWERED VAPOUR ABSORPTION COOLING SYSTEM

Practice Final Exam (A) Six problems. (Open-book, HW solutions, and notes) (Plus /minus 10 % error acceptable for all numerical answers)

A Review on Performance of Refrigeration System Using Nanofluids Mr. Nilesh S. Desai 1 Professor P.R. Kulkarni 2

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Heat and Mass Transfer Studies on 134 A-DMAC Based Falling Film Absorbers for Absorption Refrigeration System

Flow visualization at suction of a twin screw compressor

B.Tech. Civil (Construction Management) / B.Tech. Civil (Water Resources Engineering) B.Tech. (Aerospace Engineering) Term-End Examination

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector

flow work, p. 173 energy rate balance, p. 174 nozzle, p. 177 diffuser, p. 177 turbine, p. 180 compressor, p. 184 (4.4b) p. 166

ASSIGNMENT 2 Coal and Ash Handling System and Draught Systems

CHAPTER 1 BASIC CONCEPTS

Investigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics

CFD Analysis of VARS Component (Evaporator) on ANSYS Fluent

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system

Copyright 2012 Neal D. Lawrence

ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

W t. Strategy: We need to step through the equipments and figure out the inlets and outlets to allow us to calculate the work and heat terms.

Performance Assessment of Large Vapor Absorption System

FEE, CTU in Prague Power Engineering 2 (BE5B15EN2) Exercise 3

Lecture No.1. Vapour Power Cycles

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

University of Strathclyde Faculty of Engineering

Chapter 1 STEAM CYCLES

Chapter 1 Basic Concepts

CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER

R13 SET - 1 '' ''' '' ' '''' Code No: RT31035

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS

R442A (RS-50) Features and uses of the R442A (RS-50) Lubricants TECHNICAL DATA SHEET. Barcelona Girona Madrid Zaragoza

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant

Low GWP Chiller Refrigerants: Weighing the Tradeoffs

2. (a) Determine the natural frequency of oscillation of spring mass system as shown below. 5

Energy and Buildings

Experimental investigation of solar-driven double ejector refrigeration system

Computational Modeling of Counter Flow Heat Exchanger for LMTD Analysis

Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222)

COP Improvement Of A CO2 Refrigeration System With An Expander-Compressor-Unit (ECU) In Subcritical And Transcritical Operation

1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option.

MUZAFFARPUR INSTITUTE OF TECHNOLOGY COURSE FILE OF THERMODYNAMICS FACULTY NAME: AMIT KUMAR ASSISTANT PROFESSOR DEPARTMENT OF MECHANICAL ENGINEERING

Practical Differences in Working With Low & High Glide Blends, and Implications for Retrofitting. Stephen V. Spletzer

A New Approach in Control Valve Design With a New Hybrid Flow Characteristic

Transcription:

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE Dr Venkata Ramana Reddy Mula 1, H.V.Harish 2 1 Professor and Head, Department of Aeronautical Engineering NMIT BANGALORE 2 Asst. Professor, Department of Aeronautical Engineering NMIT BANGALORE Abstract To Improve the Coefficient of Performance (COP), it is require decreasing the Compressor Work and increasing the Refrigerating Effect. Experimental analysis on vapour compression refrigeration (VCR) system with R134A (Tetra Fluro Ethane) refrigerant was done and their results were recorded. The effects of the main parameters of performance analysis are mass flow rate of refrigerant, suction pressure of compressor, delivery pressure of compressor, temperature of evaporator and condenser The results from vapour compression refrigerant plant was taken where the variables like suction pressure of compressor, delivery pressure of compressor,temperature of evaporator and condenser were noted and coefficient of performance (COP) was calculated. The results obtained will be validated through CFD simulation. Further diffuser has been introduced in between compressor and condenser so that power input to the compressor has been reduced there by enhancing COP. The enhancement will be done through CFD simulation; Modeling and meshing will be done in ICEMCFD, analysis in CFX and post results in CFD POST. KEY WORDS: Tetra Fluro Ethane, ICEMCFD 1. Introduction In thermodynamics Refrigeration is the major application area, in which the heat is transferred from a lower temperature region to a higher temperature region. The devices which produce refrigeration are known as Refrigerators and the cycle on which it operates are called refrigeration cycles. Vapour compression refrigeration cycle is the most regularly used refrigeration cycle in which the refrigerant is alternately vaporized and condensed and in the vapor phase it is compressed. Gas refrigeration cycle is the well-known refrigeration cycle in which cycle refrigerant remains in the gaseous phase throughout the cycle. Cascade refrigeration are the other refrigeration cycles discussed in this chapter; absorption refrigeration is the one more refrigeration cycle which is used where the refrigerant is dissolved in liquid before it is compressed. 49

2. Litreature Survey Amit Prakash [1] worked on the topic of Improving the performance of Vapor compression refrigeration system by using sub- cooling and diffuser. He found that COP of Vapor Compression Cycle is increased by lowering the power consumption /work input or increasing the refrigerating effect. By using sub-cooling and using a diffuser at condenser inlet refrigerating effect increases and power consumption or work input decreases. Thus performance of cycle is increased. High velocity refrigerant has various serious affect on vapor compression refrigeration system such as liquid hump, undesirable splashing of the liquid refrigerant in the condenser and damage To the condenser tubes by vibration, pitting and erosion. 3. Methodology Actual Vapour Compression Cycle (T-S Diagram) R. Reji Kumar et.al [2] worked on the topic of Heat transfer enhancement in domestic refrigerator using R600a/mineral oil/nano-al2o3 as working fluid They found that the R600a refrigerant and mineral oil mixture with nanoparticles worked normally. Freezing capacity of the refrigeration system will be more with mineral oil + alumina nanoparticles oil mixture compared the system with POE oil. When the nanolubricant is used instead of conventional POE oil the power consumption of the compressor reduces by 11.5% when the conventional POE oil is replaced with nanorefrigerant the coefficient of performance (COP) of the refrigeration system also increases by 19.6 %. h 4 h f = Enthalpy at condenser temperature h 5 h 4 c p (T 4 T 5) h 7 h g = Enthalpy at evaporator temperature h 1 h 7 c p (T 1 T 7) h 3 is h g at condenser temperature h 2 h 3 c p (T 2 T 4) COP = = (h1 h6)/ (h2 h1) m r refrigeration capacity/refrigeration effect in kg/s 50

Refrigeration capacity=m (h1-h6) Q mr cp dt Watts Compressor power=m (h2-h1) kw Result taken from refrigeration kit is validated through CFDFurther Diffuser has been used to decrease power input to the compressor which will enhance COP DIFFUSER LENGTH = (D1- D2)/tanθ Different D/L ratio of 0.5 and 0.6 for divergence angle of 15o has been carried so as to decrease power input of the compressor which will result in increasing COP Modeling and meshing done in ICEM-CFD, analysis in CFX and post result in CFD POST 4. Experimental setup Experimental Set Up (Refrigeration Test Rig) 51

LINE DIAGRAM Specifications Refrigerator Capacity 220 lts. Pipe Diameter of the Evaporator =11 mm = 0.011 m Length of the evaporator coil =1539 mm = 1.539 m Observations T1 = Temperature at Compressor Inlet T2 = Temperature at Compressor outlet T3 = Temperature at Condenser outlet T4 = Temperature at Evaporator Inlet P1 = Upstream pressure of the Compressor P2 = Downstream pressure of the Compressor Refrigerant used - R134A (Tetra Fluoro Ethane) Suction pressure of the compressor = Low Pressure Discharge pressure of the compressor = High Pressure Suction temperature of the compressor 52

= Outlet temperature of the evaporator Discharge temperature of the compressor = Temperature at Compressor Outlet Evaporator temperature = Temperature at Evaporator Inlet After condensation temperature = Temperature at Condenser Outlet CALCULATIONS FOR COP Experiments T 1 T 2 T 3 T 4 H.P (P 2 ) L.P. (P 1 ) Kg/cm 2 KPa lb/in 2 KPa 1 8 60.4 37.1-6.2 7.8 764.9 20 137.9 2 4.7 61.2 34.1-12.6 7.2 706.1 12.5 86.18 3 3.5 61.8 35-13.8 7 686.5 10 68.95 Values of Enthalpy, Saturation temperature were taken from the table for R134A. Actual Vapour Compression Cycle EXPERIMENT 1. 53

For P1 = 137.89 KPa saturation temp. is ts1 = -19.15 o C. But observed temperature is 8 o C. Therefore the condition of the refrigerant before compression is Superheat. H 1 = h g1 + c p (t sup-t s1) = 238.98 + 0.958 (8-(-19.15)) = 264.99 KJ/Kg For P 2 = 764.9 KPa saturation temp. is t s2 = 29.69 o C. But observed temperature is 60.4 o C. Therefore the condition of the refrigerant after compression is Superheat. H 2 = h g2 + c p (t sup-t s2) = 266.53 + 0.958 (60.4-29.69) = 295.95 KJ/Kg h3 = h4 = 93.155 KJ/Kg Coefficient of Performance = C.O.P. = Refrigeration Effect / Work Done = (H 1 h 4) / (H 2 H 1) = (264.99 93.155) / (295.95 264.99) = 5.55 Heat Flux Refrigeration Capacity = 0.220 X 3.5 = 0.77 KJ/s Refrigeration Effect (EXP -1) = 171.835 KJ/Kg m = mass flow rate in = = 0.77 / 171.835 = 0.00448 Kg/S Heat transferred = Q = m C p dt = 0.00448 * 0.958 * (8-(-6.2) = 0.06094 KW = 60.94 W Heat Flux = Q/A = = 1146 W/m 2 For P 2 = 686.5 KPa saturation temp. is t s2 = 25.986 o C. But observed temperature is 61.8 o C. Therefore the condition of the refrigerant after compression is Superheat. H2 = hg2 + cp (tsup-ts2) = 264.722 + 0.958 (61.8-25.986) = 299.03 KJ/Kg h 3 = h 4 = 89.202 KJ/Kg Coefficient of Performance = C.O.P. = Refrigeration Effect / Work Done = (H 1 h 4) / (H 2 H 1) 54

= (265.67 89.202) / (299.03 265.67) = 5.29 5. Experimental results Evaporator Flow Analysis Modeling and meshing of evaporator coil Modeling and meshing Analysis Carried Through CFX Model Imported From ICEM CFD Boundary Condition Experimental Validation Result 55

Temperature Plane Pressure Plane Temperature Contour inlet Temperature Contour outlet 56

Wall Heat Flux Contour ENHANCEMENT OF COP BY PROVIDING DIFFUSER BETWEEN COMPRESSOR AND CONDENSER WITH DIVERGENCE ANGLE OF DIFFUSER 15 0 Vapour Compression Refrigeration Cycle Along With Diffuser Block Diagram 57

6. Results and Discussions GEOMETRY OF DIFFUSER (D/L=0.5) INNER DIA= 15 mm ANGLE OF DIVERGENCE=15 0 LENGTH OF DIFFUSER= 30 mm Diffuser Model Meshing of Diffuser 58

Inlet Pressure of the diffuser Outlet Pressure of the diffuser Inlet Temperature of the diffuser 59

Outlet Temperature of the diffuser WITH DIFFUSER For P 1 = 137.89 kpa saturation temp. is t s1 = -19.15 o C. But observed temperature is 8 o C. Therefore the condition of the refrigerant before compression is Superheat. H 1 = h g1 + c p (t sup-t s1) = 238.98 + 0.958 (8-(-19.15)) = 264.99 kj/kg For P 2 = 764.9 KPa saturation temp. is t s2 = 29.69 o C. But observed temperature is 60.4 o C. Therefore the condition of the refrigerant after compression is Superheat. H 2 = h g2 + c p (t sup-t s2) = 266.53 + 0.958 (60.4-29.69) = 295.95 kj/kg h 3 = h 4 = 93.155 kj/kg Coefficient of Performance = C.O.P. = Refrigeration Effect / Work Done = (H 1 h 4) / (H 2 H 1) = (264.99 93.155) / (295.95 264.99) = 5.55 60

Pressure Enthalpy diagram When diffuser added pressure from 2 to 2 1 i.e. from bar to bar. But, if diffuser is not there compressor take additional power input to reach bar WITHOUT DIFFUSER Therefore Compressor input = h2 1 - h1 Refrigeration effect = h 1 - h 6 For P 1 = 137.89 kpa saturation temp. is t s1 = -19.15 o C. But observed temperature is 8 o C. Therefore the condition of the refrigerant before compression is Superheat. H 1 = h g1 + c p (t sup-t s1) = 238.98 + 0.958 (8-(-19.15)) = 264.99 kj/kg Final pressure = P2 1 = 770KPa Final Temperature = 348 K = 348 273 = 75 o C. For P 2 1 = 770 KPa saturation temp. is t 3 1 = 29.92 o C. The condition of the refrigerant after compression is Superheat. H 2 1 = h 3 1 + c p (t sup-t 3 1 ) = 266.64 + 0.958 (75-29.92) = 309.83 kj/kg H 6 = h 5 = 93.155 kj/kg Coefficient of Performance = C.O.P. = Refrigeration Effect / Work Done = (H 1 h 6) / (H 2 1 H 1) = (264.99 93.155) / (309.83 264.99) = 3.83 Enhancement of COP = = 0.31 = 31 % 61

7. Conclusion and Discussion SL REFRIGERATION COMPRESSOR REFRIGERATIO COMPRESSOR NO EFFECT WITHOUT INPUT WITHOUT N EFFECT WITH INPUT WITH DIFFUSER KJ/Kg DIFFUSER KJ/Kg DIFFUSER KJ/Kg DIFFUSER KJ/Kg 1 171.84 44.84 171.84 30.96 SL POWER INPUT TO POWER COP COP WITH % NO COMPRESSOR WITHOUT DIFFUSER KW INPUT TO COMPRESSOR WITH DIFFUSER WITHOUT DIFFUSER DIFFUSER OF ENHANCEMENT OF COP KW 1 0.2 0.14 3.83 5.55 31% 8. Conclusion From above analysis following conclusion has been arrived. With the addition of diffuser pressure inlet of refrigerant to the condenser is increased. Work input to the compressor is decreased Since work input to the compressor decreased Coefficient of Performance (COP) of refrigerator has been increased. With the addition of diffuser Coefficient of Performance (COP) enhancement has been increased by 31 % when compared without diffuser. Power input to the compressor obtained without diffuser is 0.2 KW. Power input to the compressor with diffuser obtained is 0.14KW Finally conclusion drawn is Coefficient of Performance (COP) can be enhanced by placing diffuser. 62