Application of Variable Frequency Drives for Energy Savings

Similar documents
Energy Management Workshop

ADJUSTABLE-FREQUENCY drives (AFDs) provide

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

Calculate the Costs of Piping System Elements

Water-side Systems. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology

Large University Central Chiller Plant Design Considerations

TECHNICAL MANUAL TEH-375A. Pump & System Curve Data for Centrifugal Pump Selection and Application

Best Practice Pump Control

AR No. # Efficient Irrigation

Table of Contents. Foreword... xvii Executive Summary... xxi. Chapter One Pump Fundamentals, 1

AALSO Summary of Formulas needed for Levels I, II and III.

Optimizing Central Chilled Water Systems

VFD Facts: Discovering the True Potential of Smart Pump Technology

Peerless Pump Company Handbook of Engineering Data

Application Solution. Foreword. Figure 1. Affinity Laws for Centrifugal Pumps

Variable Speed Waste Water Pumping

6. PUMPS AND PUMPING SYSTEM

How the design of a cooling tower impacts energy usage and operating costs

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

Conflict Resolution: Pump & System Interaction. April 13, 2017

Section A: CUSTOMER INFORMATION. Customer Name Electric Account Number Rate Application Number. Facility Address City State Zip Code

Pump ED 101. Pump Selection for VFD Operation Part 3 Q / H Pump Down vs Level Control. Introduction. Pump Down vs Level Control

Module 9 : Sewage And Storm water Pumping Stations. Lecture 11 : Sewage And Storm water Pumping Stations

B. System Design and Performance Requirements

Ohio Energy. Workshop G. Best Practices in Energy Efficiency to Help You Reduce Your Energy Spend. Tuesday, February 21, :45 a.m.

AALSO Proficiency Program Level I, II & III

Chiller plant optimization

Pump System Optimization Checklist

Session 2 Pump Selection. Mark Markham, P.E. Gresham, Smith and Partners September 14, 2017

A SPREADSHEET FOR GEOTHERMAL DIRECT USE COST EVALUATION. Kevin Rafferty Geo-Heat Center

Preface to the First Edition Preface to the Second Edition. Acknowledgment

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

WATER DISTRIBUTION SYSTEM MATHEMATICS

Mechanical Project Proposal

FlowSet. Balancing Procedure

ABB drives for water Medium voltage drives for energy savings and life-cycle improvements

Water and wastewater treatment operations

Pumping Plant Detailed Evaluation Worksheet

Saving Energy with VFDs

Index USE OF VARIABLE SPEED DRIVES FOR ENERGY SAVING APPLICATIONS IN PULP & PAPER INDUSTRY BY : CHIRAG SHAH LARSEN & TOURBO LIMITED

Optimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017

PAYBACK GUIDE CENTRIFUGAL PUMPS

University Curriculum Development for Decentralized Wastewater Management

Variable Speed Drives: Reducing energy costs in meat processing plants

Booster Pump Fundamentals. By: Bill Baglot

Eco-Flow - C VARIABLE FREQUENCY DRIVE PRODUCT BROCHURE. for Commercial Swimming Pools & Water Feature Pumps. H flow 2. Pool & Spa Products Division

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL

Chilled Water Distribution Systems. APPA Institute for Facilities Management New Orleans, LA January 19, 2016

CUSTOMER FACILITY INFORMATION

Pump Performance Curves and Matching a Pump to a Piping System

ARMSTRONG DESIGN ENVELOPE FAQ

Pump Performance Curves and Matching a Pump to a Piping System

Pumps and Pumping Stations

Using Water-Cooled Chillers to Exceed ASHRAE Minimum Efficiency Standard by > 50%

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)

Secondary loop chilled water in super high-rise

7 th NATIONAL CERTIFICATION EXAMINATION Nov FOR ENERGY MANAGERS & ENERGY AUDITORS

2/24/2011. Energy Efficiency. Fluid Sealing Association. The Beginning. Fluid Sealing Association

ASSESSING PUMPING SYSTEM OPERATION FOR UPGRADING WORKS IN BUKIT KUDA WATER TREATMENT PLANT, LABUAN, MALAYSIA

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

Why use VSD in existing HVAC installations

ASHRAE All about T. Either control directly with a temperature reactive VFD pump or valves and a pressure reactive pump

(For ASllRAE Staff Use Only)

SECTION COOLING TOWER

Chilled Beams. The new system of choice?

Total Cost of Ownership (TCO) for Variable Speed Pumping Systems

Application of Steam Turbine Driven Chillers in CHP/DES System

4th Class Power Engineering (PEN) Curriculum Mapping

The Latest Generation of VFDs

FLUID FLOW - PUMPS. Discharge Section. Section. Two main types of pumps: Positive Displacement pumps Centrifugal pumps.

Chilled Water Plant Design American Standard Inc.

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

Building Hydronic Systems Pressure Profile

ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS

AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL

Wood Products Energy Savings Guide

CONSTRUCTION REQUIREMENTS

Pump System Energy Saving Practices

Pepco C&I Energy Savings Program Custom Incentives Technical Resource Manual

NZQA registered unit standard version 1 Page 1 of 7. Demonstrate knowledge of pumps and pump selection for rural systems

NJ AIHA CIH Review Industrial Ventilation

Central Chilled Water Plant Sustainable Design. By : George Berbari, CEO DC PRO Engineering

COMPRESSED AIR SYSTEM DESIGNS BEGIN WITH THE DEMANDS

High Technology Energy Savings Guide

Abstract. 1 Introduction. Golder Associates Ltd, Canada

IRRIGATION PUMPS - PRESERVING PERFORMANCE

ENERGY EFFICIENCY IN FLOUR MILLS

Design Considerations For Artificial Lifting Of Enhanced Geothermal System Fluids

Aggregate Portal Asphalt Plant Case Study

Troubleshooting Piping Systems

Evaluation of theperformance of Centrifugal PumpType ( )

FRENIC4800VM5, a Water-Cooled High Capacity, High Voltage Inverter

Fluid Mechanics. The Energy Equation [7] Dr. Mohammad N. Almasri

Don t get caught in the chiller speed trap YORK OPTISPEED VARIABLE-SPEED DRIVE

Troubleshooting Piping Systems

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

SUSTAINABLE PUMPING HOW USING AC DRIVES CAN CONTRIBUTE TO FUTURE WATER SECURITY

Farm Energy IQ. Farms Today Securing Our Energy Future

PAPER-1: GENERAL ASPECTS OF ENERGY MANAGEMENT AND ENERGY AUDIT

Time-Tested Fiberglass Piping Systems for Water Applications From Smith Fibercast. Bulletin No. C3320 November 1,2005

Transcription:

Application of Variable Frequency Drives for Energy Savings Scott McGlamery,.E. Department of Electrical Engineering, Hixson, Cincinnati, OH Abstract- While almost any facility could potentially benefit from Variable Frequency Drives (VFDs), there are a variety of pitfalls that can lead to misapplication. Avoiding those pitfalls requires an understanding of the physical laws governing the system under consideration, and of the operational characteristics and efficiencies of the individual components. I. Introduction VFDs are typically utilized either to provide improved control or energy savings. This paper will describe the characteristics of systems with the potential for energy savings, and the parameters to consider when making energy savings calculations. The utilization of VFDs strictly for speed control is typically a function of the system requirements, and will not be the subject of this discussion. VFDs can provide energy savings primarily with variable torque centrifugal loads such as fans and pumps. Other types of loads typically do not provide energy savings, and will not be analyzed. II. ower Requirements for umps and Fans ump and fan power requirements are very similar, with liquids and gases following the same laws of fluid dynamics. We will examine pumps in detail, with the understanding that the same principles apply to fans. The fluid power, fl, measured in horsepower for a given pumping application is governed by the following equation: ( H ) sg / 3960 fl = Q KQ + s () where K is a system constant, Q is the flow rate (gpm), sg is the specific gravity of the fluid, and H s is the static head (ft). The KQ component represents the frictional head in the system. Static head is defined as the difference in elevation between the pump and the discharge location, typically measured in feet. Frictional head results from the friction between the fluid and the walls of the pipe, and is defined by the Darcy-Weisbach relation : L V H L = f D g () where f is a friction factor based on the characteristics of the pipe, L is the length of the pipe, D is the diameter of the pipe, and V is the average velocity of the fluid. Notice that for a given pipe, the frictional head is proportional to the square of the fluid velocity, which is reflected by the KQ component in the fluid power equation (). Equation () is critical for understanding the role of VFDs in energy savings. Equation () shows that for a system dominated by static head, fluid power is directly proportional to flow. fl = QH ssg / 3960 (3) In a system dominated by frictional head, fluid power varies with the cube of the flow rate. 3 fl = KQ sg / 3960 (4) Equation (3) shows a linear relationship between fluid power and flow rate in a static head dominated system, whereas equation (4) shows that fluid power is proportional to the cube of the flow rate in a frictional head dominated system. The pump in a static head system works to lift a liquid to a higher elevation by overcoming the force of gravity. In a frictional system, the pump works to overcome the force of friction. The greatest opportunity for energy savings is in frictional head dominated systems, because of the non-linear relationship between work and flow rate. In a static head dominated system, the work required is linearly dependent on the flow rate. VFDs in static head dominated Copyright 003 by Hixson Incorporated

systems can save energy only by eliminating less efficient flow control devices, such as throttling valves, though the reduction in power consumption is significantly less than in frictional systems. Many pump installations in industrial facilities are frictional head dominated systems. All closed loop systems, such as glycol loops and chilled water loops, are frictional head dominated. Refer to Figure for a simple example. Note that while the fluid in this example changes elevation, the net change is zero, resulting in zero static head. frictional losses in the system via a reduced flow rate. Other means of flow control, such as throttling valves or bypass valves, do not take full advantage of the reduced frictional losses, and therefore consume more energy at reduced flow rates than a VFD equipped system. This analysis focuses on systems that are either static or frictional head dominated. Many systems, particularly in HVAC applications, have both static and frictional components, and require a detailed analysis to assess the impact of VFDs on the system. III. Affinity Laws A set of equations known as the affinity laws are typically used for energy savings calculations. The equations can be derived from equation (4), and are defined as follows: Q N = (5) Q N N = N (6) Figure : Frictional Head Dominated System A system with static head would be one in which a fluid is being pumped from one elevation to a higher elevation. An example would a product pump used to fill a tank, or an evaporative condenser water makeup pump. Refer to Figure for an example. H H Where: N = N N = Speed Q = Flow = ressure H = Horsepower 3 (7) STATIC HEAD Equation (7) is frequently used to justify installation of VFDs. Comparing equation (7) to equations (3) and (4), it is apparent that the affinity law relating horsepower to speed assumes a frictional head dominated system, and does not take into account any static head. This assumption can lead to significant errors if applied to systems that do include a static head component. Figure : Static Head Dominated System In frictional head dominated systems where a variable rate flow is required, VFDs have the potential to save energy by reducing the Carlson s paper 3 explains this error in detail. In Carlson s sample calculation, a pump with initial conditions of 4000 gal/min flow, 38 ft head, and 405 bhp (brake horsepower) is slowed to provide 000 gal/min in a system with both static and frictional head. Using the affinity laws, the required brake horsepower at the Copyright 003 by Hixson Incorporated

reduced flow rate would be 63 bhp. When the analysis accounts for the static head in the system, the actual brake horsepower at the reduced flow rate is 47 bhp. The actual power requirements are more than six times greater than the affinity laws suggest. Understanding the difference between static and frictional head is essential to avoid errors in energy savings calculations. The affinity laws may be used in closed loop systems, but should not be used in systems with a static head component. IV. System Efficiency The previous discussion focused on fluid power requirements, which define the power output requirements of a pump. When considering application of a VFD to such a system, the efficiency of the VFD, motor and pump should be considered to determine the total power input required to operate the system. Efficiencies for VFDs, motors and pumps all vary with speed. VFDs and motors decrease in efficiency as speed decreases, while pumps may increase or decrease in efficiency depending on the pump and application. According to Bernier and Bourret, this causes the total input power to be significantly higher than the pump affinity laws would predict. The efficiency of a VFD is affected by it s rated horsepower, carrier frequency, and torque rating. Efficiency is lower in smaller drives, for higher carrier frequencies, and for variable torque drives. Table lists efficiencies for variable torque drives with a carrier frequency of 5kHz 7. VFD ercentage of Full Operating Speed H Rating 5% 50% 75% 00% 9.4% 44.% 70.5% 8.5% 5 9.6% 74.7% 88.3% 9.4% 0 35.3% 79.0% 90.3% 93.5% 5 35.6% 79.4% 90.6% 93.8% 50 43.3% 83.5% 9.% 94.4% 00 54.8% 89.% 95.0% 96.6% 50 6.% 9.3% 96.% 97.3% Table : VFD Efficiency Isolation transformers or line reactors are frequently included in VFD installations, and the losses from these components further reduce the overall efficiency of the system. Component efficiency is important to consider not only in evaluating energy savings, but also to avoid applications where a VFD actually increases the cost of operating a motor. For example, a conveyor motor that has a VFD for providing soft starts and stops will cost more to operate than the same motor controlled by a soft start controller with a bypass contactor. The input power to the VFD in this example would be: = shaft input (8) ( Motor Efficiency )( VFD Efficiency ) where input is the power input to the VFD and shaft is power output of the motor. The input power to the soft start controller would be: = shaft input (9) ( Motor Efficiency ) Assume we have a conveyor motor with an output of 700W and an efficiency of 90%. The VFD efficiency from Table for a H rated VFD operating at full speed is 8.5%. The VFD power input in this example would be 943W, versus 778W for the soft start, a difference of.%. V. Quick Screening for ayback Given the complexities in accurately calculating energy savings with a VFD, a simple screening tool can help by eliminating scenarios that are unlikely to show a payback. The Electric ower Research Institute (ERI) publishes ASDMaster 5 software, which assists the user in determining whether or not a VFD will pay for itself in a specific application. One feature of the software is a screening routine, which provides a quick analysis of whether or not a VFD is financially justified, based on energy savings alone, for typical applications. The screening characteristics are derived from the analysis of hundreds of VFD applications, and are intended only as a guide. ERI recommends a complete energy analysis prior to proceeding with a VFD installation. The application characteristics employed by the screening routine are listed in Table, and Figure 3 is the corresponding decision tree. Copyright 003 by Hixson Incorporated

Typical Annual Flow as % Operating Application of Maximum Motor Size Hours Centrifugal fans, Over 6,000 Good pumps, blowers, Under 75% Over 75H Hours and compressors. Other fluid,500 to Fair handling equip. 75% to 90% 30 to 75H 6,000 hours (blenders, screw compressors.) Conveyors, 90% Less than oor grinders, rollers. or higher Under 30H,500 hours Table : ASDMaster Screening 5 Any oor More than two Fair ratings? ratings? Yes Yes No ayback not likely Energy analysis required ayback likely the harmonics do not pose a problem, other times mitigating solutions should be provided. Misapplication of utility rate structures frequently leads to errors in energy savings calculations. Even measured results can be misleading; for example, measuring reduced power consumption and calculating savings with an average rate can overstate the savings significantly. Refer to the Hixson white paper Electrical Energy Savings Calculations for a detailed discussion of the topic. VII. Conclusions The application of VFDs for energy savings can be very complex. Understanding the physical laws governing the system under consideration and the efficiencies of the equipment involved is essential for proper application. Figure 3: ASDMaster Decision Tree 5 VI. Other Considerations While energy savings or the need for speed control typically determine whether or not a VFD will be used, other factors should be considered prior to installation. VFDs require a cleaner environment than single speed starters. The electronic components in a VFD require cooling, which is accomplished by a ventilated enclosure, and sometimes fans. It is important that the air passing through is relatively clean, to prevent the buildup of dust on the electronic components, which can cause overheating. VFDs emit a significant amount of heat. An electric room with a large number of VFDs may require mechanical cooling to prevent the drives from overheating and shutting down. The fast switching characteristics of VFDs can cause a voltage spike at the motor, leading to motor failure. Voltage spikes can be mitigated by application of filters, proper branch circuit design, and use of inverter duty motors. The electronic switching in VFDs produces harmonics. The impact of harmonics should be considered on a case-by-case basis. Sometimes Copyright 003 by Hixson Incorporated

References. ASHRAE Handbook, 98 Fundamentals, pp. 4.-4.8.. Bernier, Michel A. and Bernard Bourret. umping Energy And Variable Frequency Drives. ASHRAE Journal, December 999, vol. 4, no.. 3. Carlson, Ron. The Correct Method of Calculating Energy Savings to Justify Adjustable-Frequency Drives on umps. IEEE Transactions on Industry Applications, vol. 36, no. 6, November/December 000. 4. Casada, Don. Energy and Reliability Considerations for Adjustable Speed Driven umps. Industrial Energy Technology Conference, 999. 5. Electric ower Research Institute. ASDMaster User s Guide, Adjustable Speed Drive Evaluation Methodology and Applications Software. 996. 6. Mukherjee, Subrankar, Richard G. Hoft and James A. McCormick. Digital Measurement of the Efficiency of Inverter-Induction Machines. IEEE Transactions on Industry Applications, vol. 6, no. 5, September/October 990. 7. U.S. Department of Energy Office of Industrial Technologies. Energy Matters, Winter 00. Hixson Incorporated 659 Van Meter Street Cincinnati, Oh 450 (53) 4-30 www.hixson-inc.com Contact Information Copyright 003 by Hixson Incorporated