ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS.

Similar documents
Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions

Energy and Comfort in School Buildings in the South of Portugal

Indoor comfort and air quality in spaces equipped with eco-ventilation systems

Energy and Comfort in School Buildings in the South of Portugal

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Evaluation methods for indoor environmental quality assessment according to EN15251

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Energy and indoor temperature consequences of adaptive thermal comfort standards

IMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3)

Assessing thermal comfort of dwellings in summer using EnergyPlus

Thermal Environment evaluation in commercial kitchens

PREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Prediction of Thermal Comfort. mech14.weebly.com

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Cost-Benefit Analysis of Dwelling Retrofit Options

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece

On the performance of confluent jets ventilation system in office space

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

Assessment of thermal comfort near a glazed exterior wall

A Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment

Thermal Control in Buildings by John Straube (updated )

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

447 - Thermal Performance of Residential Buildings in Lisbon with Large Glazing Areas

125BEPM - Building energy performance modeling. Lecture handouts

Sustainable Designed Air-Conditioned Mosque For Thermal Comfort

Work Package 2: Performance of naturally ventilated buildings

Information paper 17. Prepared by: David Clark. book:

Research of Thermal Comfort for Side Air Supply Pattern in Office

Application of CFD Predictions to Quantify Thermal Comfort for Indoor Environments

IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE

Computational Fluid Dynamics and Building Energy Performance Simulation Nielsen, Peter Vilhelm; Tryggvason, T.

Adaptive thermal comfort explained by PMV

Buildings with large glazed surfaces: optimization of solar control strategies in relation to the building's thermal inertia

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

2006 Building Science Press All rights of reproduction in any form reserved.

Chapter 7. Passive Solar Contents

Thermal comfort recent challenges

Room-side Low-e Coating: As Good As It Sounds?

Personal Ventilation: from research to practical use

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

A Field Study of the Thermal Environment in Residential Buildings in Harbin

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

Experimental investigation of zero energy office under natural and forced ventilation

Thermal comfort in Lebanese residential unit case studies: a coastal region in Lebanon

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

Comparison between thermal comfort predictive models and subjective responses in Italian university classrooms

Advanced Ventilation Technologies

Evaluation of natural ventilation systems in a landscaped office.

THERMAL COMFORT ANALYSIS OF BUILDINGS USING THEORETICAL AND ADAPTIVE MODELS Hélder Silva Almeida

VARIABILITY OF THERMAL STRATIFICATION IN NATURALLY VENTILATED RESIDENTIAL BUILDINGS. Stephanie Gauthier 1, David Shipworth 1

ON THE ENERGY CONSUMPTION OF HIGH- AND LOW-LEVEL AIR SUPPLIES

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2

Thermal Comfort Zone for Thai People

362: Indoor climate control effect of AAC panels as determined by house model measurements and simulations

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

Energy simulation of traditional vs. adaptive thermal comfort for two

Designing Air-Distribution Systems To Maximize Comfort

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

Infiltration simulation in a detached house empirical model validation

Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions Hensen, J.L.M.; Hensen Centnerová, L.

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

CHAPTER 6 CONCLUSION

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

Thermal comfort study of naturally ventilated office

Analysis of the Window Side Thermal Environment Formed by Air Barrier. Technique in Winter Conditions and Its Economy

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Research on indoor thermal environment of stilted buildings in Chongqing, China

Passive house optimization for Southern Italy based on the New Passivhaus Standard

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

FIELD MEASUREMENT OF A RESIDENTIAL FLOOR COOLING SYSTEM AND EVALUATION OF HUMAN THERMAL COMFORT

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

Application of a Computer Model for Integrated Hygrothermal Building Analysis

SIMULATION OF THE PERFORMANCE OF A HYBRID VENTILATION SYSTEM IN DIFFERENT CLIMATES. Technicka 2896/2, Brno, Czech Republic

Laurel School Upper Campus Building Features

Assessment of rammed earth as external cladding for thermal comfort and energy consumption of a low cost house in Bangladesh

NUMERICAL SIMULATION OF CAR COCKPIT HEATING DURING WINTER 1

Maarten G. Sourbron 1, Lieve M. Helsen 1. Corresponding SUMMARY

Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

Available online at ScienceDirect. Energy Procedia 78 (2015 )

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the

CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

Analysis of Night Ventilation Potential for Residential Buildings in Hot-Humid Climate of Malaysia

Transcription:

Eleventh International IBPSA Conference Glasgow, Scotland July -, 2009 ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS Eusébio. Z. E. Conceição 1, Margarida C. Lopes 1 and Mª. Manuela J. R. Lúcio 2 1 FCT, Universidade do Algarve, Campus de Gambelas, 8005-139 Faro, Portugal email: econcei@ualg.pt 2 Agrupamento Vertical Professor Paula Nogueira, R. Comunidade Lusíada, 8700-000 Olhão, Portugal ABSTRACT In this work a numerical model, which simulates the buildings thermal response with complex topology and evaluates the indoor environment comfort, in transient conditions, is used in the energy and thermal comfort evaluation for different passive solutions in a kindergarten, in Summer conditions. After the validation phase, this numerical model is applied in the evaluation of the building thermal behaviour, using the indoor temperature field, and the occupants thermal comfort levels, using the PMV and PPD indexes. The introduction of a roof placed in the top of the kindergarten, horizontal shading devices placed above the windows level facing South and external pyramidal opaque trees placed in front to the windows facing West and East, used to reduce the indoor temperature level and to increase the indoor thermal comfort level, in Summer conditions, are analyzed. INTRODUCTION The external air temperature and solar radiation values in the South of Portugal, in an environment with Mediterranean characteristics, in Summer conditions, are very high. In this season adequate shading devices, to reduce this direct solar radiation, as example, are used. This situation requires a detailed study of the building thermal behaviour, considering the buildings structural details and the surrounding buildings. The use of shading devices in school buildings is an efficient tool in order to reduce the internal air temperature, with low energy consumption level. Nevertheless, in particular situations, an additional ventilating and air-conditioning systems should be used. In this region, with a particular climate, is very important to develop adapted kindergartens, that can promote the occupants comfort conditions, namely the thermal and air quality levels, as well as to promote the reduction of buildings energy consumption levels. In this study, in order to develop shading devices adapted to particular kindergartens, a numerical model that simulates the buildings thermal response with complex topology and evaluates the indoor environment comfort, in transient conditions, is used. The numerical model, developed by the authors in the last years, considers the air (inside the several compartments and ducts system), the different windows glasses, the interior bodies (located inside the several spaces), the different layers of buildings main bodies, the water vapour (inside the several spaces, ducts system and in the interior surfaces) and the air contaminants (inside the several spaces and ducts system). In the evaluation of the indoor environment comfort, that an occupant feels in the different spaces, is important to evaluate the air temperature, air velocity, air relative humidity, mean radiant temperature, metabolic rate and clothing level (Fanger, 1970). The Predicted Mean Vote (PMV) and the Percentage of People Dissatisfied (PPD) indexes, used to evaluate the thermal comfort in steady state conditions, is usually used to integrate the environmental and personal parameters. The present numerical model was used not only in studies of comparison between numerical and experimental data in Summer conditions (see Conceição et al, 2008a) and in Winter conditions (see Conceição et al, 2008b), but also in particular numerical applications as, for example, in the study of the influence of surrounding buildings (see Conceição et al, 2007) and in the use of a greenhouse, in Winter conditions, to increase the internal air temperature and the occupants comfort levels (see Conceição et al, 2008c). In the present work, made in Summer conditions, the implementation of some shading devices, like the roof placed in the top of the kindergarten, horizontal shading devices placed above the windows level facing South and external pyramidal opaque trees placed in front to the windows facing West and East is studied. This kind of numerical model, used in the building thermal analysis, has been developed in the last years by several authors. In the numerical study of buildings thermal behaviour, for example, Ozeki et al. (1992), Cammarata et al. (1994), Mendes and Santos (2001) and Strand et al. (2001), present some studies applied to similar complex situations than the one here presented in this paper. - 24 -

NUMERICAL MODEL This code, presented and used in this study, was developed and validated in the last years by the authors of this study (Conceição, 2003, Conceição et al., 2004, Conceição and Lúcio, 2006, Conceição et al., 2007 and Conceição et al., 2008a,b,c). The present numerical program calculates the internal air temperature (inside the several compartments and ducts system), the different windows glasses temperature, the interior bodies temperature (located inside the several spaces), the different layers of buildings main bodies temperature, the water vapour concentration (inside the several spaces, ducts system and in the interior surfaces), the air contaminants concentration (inside the several spaces and ducts system) and the global thermal comfort conditions, using the PMV and PPD indexes, that the occupants are subjected. The input data in the software are the building geometry (introduced in a three-dimensional design software), the boundary conditions, the materials thermal proprieties and other conditions (like the external environmental and geographical conditions, the initial conditions, the several heat and mass load, the occupation cycle, the occupant s clothing and activity levels and the air ventilation topologies). More details about this numerical model can be seen, for example, in Conceição (2003), Conceição et al. (2004), Conceição and Lúcio (2006), Conceição et al. (2007) and Conceição et al. (2008a,b,c). Balance integral equations The multi-nodal buildings thermal behaviour model, which operates in transient conditions, is based in energy and mass balance integral equations. The energy balance integral equations are developed for the air (inside the several compartments and ducts system), the different windows glasses, the interior bodies (located inside the several spaces) and the different layers of buildings main bodies. The mass balance integral equations are developed for the water vapour (inside the several spaces, ducts system and in the interior surfaces) and the air contaminants (inside the several spaces and ducts system). In the resolution of these integral equations system the Runge-Kutta-Fehlberg method with error control is used. Heat exchanges with the environment The model considers the conductive, convective, radiative and mass transfer phenomena: the conduction is verified in the building main bodies (doors, ceiling, ground, walls, etc.) layers, in convection the natural, forced and mixed phenomena are considered; in radiation, verified inside and outside the building, the short-wave (the real distribution of direct solar radiation in external and internal surfaces) and long-wave (heat exchanges between the buildings external surfaces and the surrounding surfaces as well as among the internal surfaces of each space) phenomena are considered. In radiative calculus the shading effect caused by the surrounding surfaces and by the internal surfaces is considered. Building simplified model In the numerical simulation of the kindergarten the compartments, the 498 building main bodies, the 15 trees (90 surfaces), the roof (4 surfaces), the 4 shading devices and the 42 windows glasses, as well as two schools and three residential surrounding main buildings, are considered. In the building main bodies double brick, in the external walls, simple brick, in the internal walls, coverage of cement, in the ceiling, several meters of ground, in the floor, and interior and exterior doors, that include several wood layers, are used. In the pyramidal opaque trees only the external surfaces are considered. These trees, with falling foliage, guarantee a large passage of solar radiation in Winter (not considered in this work) and no passage of solar radiation in Summer conditions (considered in this work). The roof bodies consider the tiles and a thickness of coverage of cement. Finally, the horizontal shading devices placed above the windows level, facing South, are dimensioned in order to guarantee a lower direct solar radiation in Summer conditions and a higher direct solar radiation in Winter conditions. This existing kindergarten, used in this study, located in Olhão (South of Portugal), has 10 spaces with higher occupation and 15 spaces with lower occupation. The idea is, in a first phase, to evaluate the actual buildings thermal behaviour and improve thermal comfort conditions that the occupants are subjected, using passive systems, which will be implemented in a second phase. As spaces with higher occupation are considered the classrooms (numbers 3, 13 and 16), for 3, 4 and 5 years old children, playground (number 10), office (number 23), kitchen (number 18), teachers room (number 7), non-teacher s staff room (number 11), corridors (numbers 19 and ), while in the spaces with lower occupation are considered the hall (number 2), storage rooms (numbers 5, 6, 8, 12, 17 and 20), WC (numbers 4, 9, 14, 15, 21, 22 and 24) and garret (). In Figure 1 the grid generation used in the numerical simulation of the kindergarten and considered surrounding buildings is presented. This numerical grid, used in the indoor and outdoor direct solar radiation determination, was spaced cm in both directions. The detailed grid generation used in the numerical simulation of the kindergarten and the space numeration are presented in figure 2. Finally, in figure 3 are presented the considered passive systems, namely the roof, the pyramidal opaque trees and the horizontal shading devices. - 25 -

Figure 1 Grid generation in the kindergarten and surrounding buildings. This geometry is based in the Kindergarten number 4 in Olhão. Figure 2 Identification of the indoor compartment of the kindergarten. Figure 2 Scheme of the considered passive systems, namely the roof, the pyramidal opaque trees and the horizontal shading devices, in the kindergarten. - 26 -

In this work typical pyramidal opaque trees, with similar dimensions and configurations, placed in accord to the windows positions, are used. These 15 trees, placed side by side, with pyramidal shape with six triangular plane surfaces (see figure 3), are characterized by the trees total height, the trees diameter and the trees main trunk height. In the present study trees with a total height of 8 m, a diameter of 4 m and a trunk height of 2 m were used. Comfort model In order to evaluate the thermal comfort level in moderate environments equipped with heating and air-conditioning systems, either in cold or in warm climates, during Winter or Summer conditions, the PMV (Predicted Mean Vote) and the PPD (Predicted Percentage of Dissatisfied) indexes are used (Fanger, 1970 or ISO 77, 2005). For acceptable thermal comfort conditions the ISO 77 (2005) defines three comfort categories (A, B and C), establishing limits for PMV and PPD indexes. In the category C, the limits of the suggested PMV values change between 0.7 and -0.7 (PPD=15 %). This classification allows the selection a priori of one thermal environment according to the required demands. Fanger and Toftum (2002), for non-air-conditioned buildings in warm climates, present an extension of the PMV model. This extension, that combines the static PMV model and the adaptive model, uses the traditional PMV model (Fanger, 1970) and the expected verified in the adaptive model (de Dear et al., 1997). The PMV index is calculated, by the software, for each space, using the numerical values of the indoor air temperature, indoor air velocity (obtained through the renovation and recycled airflow), indoor air relative humidity and indoor mean radiant temperature (obtained through the mean value of the compartment surrounding surfaces temperatures), for a pre-defined clothing and activity levels. In this calculus the Fanger (1970) model with the Fanger and Toftum (2002) extension are used. The PPD index is correlated with the PMV index using the Fanger (1970) model. NUMERICAL SIMULATIONS In these simulations the doors and windows are closed, the indoor curtains are open, the airconditioning systems were not considered, the occupation is not considered and the indoor radiative heat exchanges are also not considered. The airflow renovation rate values, considered in these numerical simulations, inside each compartment by infiltration, were experimentally obtained, using the tracer gas concentration method. In the school buildings numerical simulations, in order to evaluate the real building s thermal inertia, the previous 5 days are also simulated. In these simulations, made in this work in Summer conditions, external environmental information about th July 2007 are used. In figure 4 the evolution of external air temperature and relative humidity is presented. This day was selected as a typical day of Summer conditions in the Algarve (South Portugal). The considered clothing and the activity level are, respectively, 0.5 Clo. and 1.2 Met. 40 38 36 24 Tair Rhair 0 2 4 6 8 10 12 14 16 18 20 22 24 Figure 4 Evolution of external air temperature (Tair) and relative humidity (RHair) used in the numerical model as input. In these simulations the kindergarten and the surrounding buildings are considered. In accord to Conceição et al. (2007) the surrounding buildings should be considered in the numerical simulation, because the shading devices verified are very important in the kindergarten behaviour. In this study three kinds of numerical simulations were made: In the first one the existing kindergarten and the surrounding buildings, without particular shading devices are considered. This simulation, in accord to the previous validation tests, represent the actual kindergarten behaviour status; In the second one the kindergarten, the surrounding buildings, the horizontal shading devices placed above the windows level facing South and the external pyramidal opaque trees placed in front to the windows facing West and East are considered; In the third one the kindergarten, the surrounding buildings, the horizontal 46 45 44 43 42 41 RHair (%) - 27 -

shading devices placed above the windows level, facing South, and the roof, with four sides, placed above the kindergarten are considered. RESULTS AND DISCUSSION In this study, the developed numerical software that simulates the building thermal response, with complex topology, in transient conditions, and evaluates the indoor thermal comfort and indoor air quality levels, is used. This software was validated not only in school buildings with complex topology without surrounding buildings in Winter conditions (Conceição et al., 2004) and Summer conditions (Conceição and Lúcio, 2006), but also in kindergartens, with surrounding buildings presence, in Winter conditions (Conceição et al., 2008b) and Summer conditions (Conceição and Lúcio, 2008a) From figures 5 to 9 the evolution of the calculated indoor air temperature, respectively, for the compartment 3 (classroom equipped with windows facing South), 10 (playground equipped with windows facing East), 13 (classroom equipped with windows facing North and East), 16 (classroom equipped with windows facing North and West) and 18 (kitchen equipped with windows facing West) is presented. In these figures the obtained results are shown without passive system (1), with horizontal shading devices (placed above the windows level facing South) and pyramidal opaque trees (placed in front to the windows facing East and West) (2) and with horizontal shading devices (placed above the windows levels facing South) and roof (placed above the kindergarten) (3). In all simulations the surrounding buildings are considered. The evolution of the calculated PMV are presented from figures 10 to 12, respectively, for spaces occupied mainly by children (1), for spaces occupied mainly by teachers and non-teachers staff (2) and for transition spaces (corridors) (3). In these figures the kindergarten, the surrounding buildings, the horizontal shading devices placed above the windows level, facing South, and the roof, with four sides, placed in the top of the kindergarten are considered. In accordance with the obtained results is possible to conclude that the shading devices placed above the windows level, facing South, reduces more than 0.5 ºC the air temperature inside the associated shaded space. Nevertheless, the pyramidal opaque trees presence, located in front to the windows facing East and West is not very efficient in the air temperature reduction inside the associated shaded space, because in the beginning of the morning and in the end of the afternoon, when the pyramidal opaque trees can shade the windows, the surrounding buildings, placed in East and West, also promote shading effect in the kindergarten. With Horizontal Shading Devices and Pyramidal Opaque Trees With Horizontal Shading Devices and Roof Figure 5 Evolution of air temperature (Tair) calculated in the space number 3 (with windows facing South). and Pyramidal Opaque Trees and Roof Figure 6 Evolution of air temperature (Tair) calculated, in the space number 10 (with windows facing East). The introduction of the roof (see figure 3) reduces, in general, more than 1 ºC in all spaces. Nevertheless, in spaces also influenced by horizontal shading devices located above the windows level, facing South, the air temperature reduction is, in general, more than 1.5 ºC. - 28 -

With passive systems the internal air temperature results, in general, is lower than without passive systems. These results, in transient conditions, that also consider the five previous days, are associated to the considered building thermal mass (namely, indoor and outdoor main building bodies, ceiling coverage of cement and tiles, floor with ground, roof and others bodies) and the low airflow renovation rate. The internal air temperature, mainly in the playground (number 10) and in the classroom (number 13), present a peak around 11 a.m. These values are associated to the inlet solar radiation through the windows facing East and simultaneously to the external air temperature peak. Nevertheless, due to the external air temperature peak the other internal air temperatures also show a little peak. In accordance with the previous results is possible to conclude that the thermal comfort level, in accord to Fanger (1970) and Fanger and Toftum (2002), in spaces occupied by children, are acceptable, in accord to the Category C of ISO 77 (2005), during the afternoon in the playground (when the children are having lunch) and in the North classroom (when the children are in lessons). and Pyramidal Opaque Tree and Roof Figure 7 Evolution of air temperature (Tair) calculated in the space number 13 (with windows facing North and East). In the South classroom, the internal thermal comfort conditions are not acceptable, nevertheless these thermal conditions are near the acceptable conditions in accordance with the category C of ISO 77 (2005). and Pyramidal Opaque Trees and Roof Figure 8 Evolution of air temperature (Tair) calculated in the space number 16 (with windows facing North and West). and Pyramidal Opaque Trees and Roof Figure 9 Evolution of air temperature (Tair) calculated in the space number 18 (with windows facing West). The spaces occupied by the teacher and non-teacher staff, during all day, are generally thermally comfortable and the kitchen in the morning (when is occupied) is also comfortable in accordance with the category C of the ISO 77 (2005). The office, with window facing West, is thermally uncomfortable mainly in the afternoon. - -

Finally, the main corridor (number ), that the occupants use during all day, is also thermally comfortable. Nevertheless the corridor (number 19) is thermally uncomfortable during the main occupation time. 1,4 PMV PMV-19 PMV- 1,4 PMV PMV-3 PMV-13 PMV-10 PMV-16 0,7 0,7 0,0 0,0 Figure 10 Evolution of PMV calculated inside the spaces (numbers 3, 10, 13 and 16) occupied by children. 1,4 PMV 0,7 0,0 PMV-7 PMV-18 PMV-11 PMV-23 Figure 10 Evolution of PMV calculated inside the spaces occupied mainly by teachers and nonteachers (numbers 7, 11, 18 and 23). Figure 11 Evolution of PMV calculated inside the transition spaces (numbers 19 and ) occupied by all occupants. CONCLUSION In this study, the numerical software that simulates the building thermal response, with complex topology, in transient conditions, and evaluates the indoor thermal comfort and indoor air quality levels, is used in the energy and thermal comfort evaluation for different passive solutions, in a kindergarten, in Summer conditions. The introduction of a new roof in the top of the kindergarten, horizontal shading devices placed above the windows level, facing South, and external pyramidal opaque trees placed in front to the windows facing West and East, are numerically analysed. In accord to the obtained results, the new roof and the horizontal shading devices are thermally efficient, nevertheless the external pyramidal opaque trees are not thermally efficient due to the surrounding buildings presence. When the kindergarten, the surrounding buildings, the horizontal shading devices and the roof are considered the thermal comfort level, in general, is acceptable in accord to the Category C of the ISO 77 (2005). However, in some spaces, like South classroom, complementary corridor, office room, for example, the comfort level can be improved, for PMV values lower than 0.7. Is suggested, for example, the introduction of forced ventilation. In the future this numerical model will be used in the implementation of other thermal solutions in the actual kindergarten, in order to improve the occupant s thermal comfort level and the energy savings. This kindergarten geometry will also be analysed in other geographical locations. Special - 20 -

attention will be given in the new local geographical location, in the new external conditions, in the new external surrounding buildings and bodies and in the new kindergarten orientation. ACKNOWLEDGEMENT This research activity is being developed inside a project financed by the City Council of Olhão. This research activity is being also developed inside a project approved and financed by the Portuguese Foundation for Science and Technology and POCI 2010, sponsored by the European Comunitary Fund FEDER. REFERENCES Cammarata, G., Fichera, A., Forgia, F., Marletta, L. and Muscato, G. 1994, Thermal Load Buildings General Models and Reduce Models. Healthy Buildings 94, In Proceedings of the 3 rd International Conference, Budapest, Hungary. Conceição E. Z. E., Lopes M. C., Lúcio Mª. M. J. R. 2008a, Indoor Environment Comfort in a Kindergarten School Building in the South of Portugal in Summer Conditions, In Proceedings of the Indoor Air 2008, Copenhagen, Denmark, 17 to 22 August of 2008. Conceição E. Z. E., Lopes M. C., Lúcio Mª. M. J. R. 2008b, Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions, In Proceedings of the 4 th WSEAS/IASME International Conference on Energy, Environment, Ecosystems and Sustainable Development (EEESD '08) and 1 st WSEAS International Conference on Landscape Architecture (LA '08), Faro, Portugal, 11 to 13 June 2008. Conceição E. Z. E., Lúcio Mª M. J. R. and Lopes M. C. 2008c. Application of an Indoor Greenhouse in the Energy and Thermal Comfort Performance in a Kindergarten School Building in the South of Portugal in Winter Conditions", WSEAS Transactions on Environment and Development, Issue 8, Volume 4, August 2008, pp. 644-654. Conceição E. Z. E., Lúcio Mª. M. J. R., Vicente V. D. S. R., Lopes M. C. and Teixeira A. R. P. A. 2007. Thermal Comfort Level and Energy Consumption in School Buildings in South of Portugal, In Proceedings of the REHVA World Congress CLIMA 2007 WellBeing Indoors, Helsinki, Finland, 10 to 14 June of 2007. Conceição, E. Z. E. 2003. Numerical Simulation of Buildings Thermal Behaviour and Human Thermal Comfort Multi-node Models. In Proceedings of the 8 th International IBPSA Conference - Building Simulation 2003. Eindhoven, Vol. 1, pp. 2-2. Conceição, E. Z. E. and Lúcio. M.ª M. J. R. 2006. Numerical Study of Thermal Response of School Buildings in Summer Conditions. In Proceedings of the Healthy Buildings 2006. Lisbon, Vol. 3, pp. 195-200. Conceição, E. Z. E., Silva, A. and Lúcio. Mª M. J. R. 2004. Numerical Study of Thermal Response of School Buildings in Winter Conditions. In Proceedings of the 9 th Conference on Air Distribution in Rooms - RoomVent 2004. Coimbra, 5 to 8 September of 2004. de Dear, R. de, Brager, G. and Cooper, D. 1997. Developing an Adaptive Model of Thermal Comfort and Preference. ASHRAE RP-884. Fanger, P. O. 1970. Thermal Comfort. Copenhagen: Danish Technical Press. Fanger, P. O. and Toftum, J. 2002. Extension of the PMV Model to Non Air-Conditioned Buildings in Warm Climates. Energy and Buildings,, PP. 5-536. ISO 77, 2005. Ergonomics of the Thermal Environments Analytical Determination and Interpretation of Thermal Comfort using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria. International Standard. Switzerland. Mendes, N. and Santos, G. 2001, Dynamic Analysis of Building Hygrothermal Behavior. In Proceedings of the 7 th Int. IBPSA Conference Building Simulation, Vol. 1, pp. 117-123. Ozeki, Y., Yamamoto, M., Saito, T., Ohgaki, S. and Sonda, Y., 1992, Simulation on Temperature and Flow Field in the Atrium (Part 1. Computation of Solar Radiation, Radiative Heat Transfer, Air Flow, and Temperature). In Proceedings of the RoomVent 1992 3 rd International Conference on Air Distribution in Rooms, Aalborg, Denmark. Strand, R., Pedersen, C. and Crawley, D. 2001, Modularization and Simulation Techniques for Heat Balance Based Energy and Loads Calculation Programs: The Experience of the ASHRAE Loads Toolkit and EnergyPlus. In Proceedings of the 7 th International IBPSA Conference, Rio de Janeiro, Brazil. - 21 -