Closed Bus Tie Systems Why to operate a DP vessel in closed bus tie configuration? Global Maritime 2013

Similar documents
On the Development of a Classification Guide for the Dynamic Positioning (DP) System

A Practical Approach to Managing DP Operations

Applying Agile to DP FMEAs

Grid Code Compliance. For India S.Balasubramoniam, Senior Consultant. 08 September September 2017 SAFER, SMARTER, GREENER

Methods for Reducing Frequency and Voltage Variations on DP Vessels

GUYANA POWER AND LIGHT INC

NavDP4000 Series Dynamic Positioning Systems

ENHANCED SYSTEM VERIFICATION (ESV)

NavDP4000 Series Dynamic Positioning Systems

Are All Generator Sets Integrated Equally?

12 tips. on selecting the right fraud protection solution

safe reliable affordable GENERATOR COMPLIANCE MONITORING PROGRAM REQUIREMENTS 1 21 September 2015 TITLE: PREPARED BY: SYSTEM ANALYSIS & SOLUTIONS

System Verification Helps Validate Complex Integrated Systems. American Bureau of Shipping (ABS) RELIABILITY SESSION.

Contents Certification, Training, Competency & Manning Introduction Certification and Competency Requirements...

TECHNICAL AND OPERATIONAL GUIDANCE (TECHOP) TECHOP_ODP_16_(P) COMPETENCY ELEMENTS FOR DP PROFESSIONALS - DP SMEs / DP FMEA PRACTITIONERS APPENDIX 1

QUALITY INTEGRATED ENGINEERING SERVICES to the energy sector

YES MARITIME SDN BHD

Shipboard Electrical Power

Seminar on African Electrical Interconnection. Module 8 - Interconnected Systems Operating Conditions

Scenario C-SS-1, Construction Vessel/Subsea Operation, number 1. Assessee Copy: Assessment Narrative:

Renewable energy connection requirements in Spain April 2012

Reference Document. Interconnected Operations Services

Technical Requirements for Distributed Generation Connection

Redundancy and Criticality Assessment (RCA) System Applied in Deep Water Operations

Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA. March 21, 2017

Arc Flash Risk in Wind Energy Systems. Guidelines for analysis, mitigation and management

UPS Electrical Design and. Installation. critica POWER SUPPLIES

Power and Energy Systems Engineering

RISK SESSION. DP Proficiency Development A Comprehensive Approach to Competency Assessment and Assurance

Unit Commitment of Generator Sets During Dynamic Positioning Operation Based on Consequence Simulation

BROCHURE. Projects and engineering Engineering expertise to enhance your operations

Machine Guards White Paper 9 Trapped Key Interlocking

FUNCTIONAL SAFETY CERTIFICATE. Topworx, Inc 3300 Fern Valley Road, Louisville, Kentucky, 40213, USA

SEASYacht INTEGRATED BRIDGE AND AUTOMATION SYSTEM. ENHANCED COMFORT, EFFICIENCY AND RELIABILITY.

INDUSTRY EXPERTISE IN AUTOMATION AND ELECTRONICS AUTOMATION

Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA

Generator Assessment & Roles During A Restoration

YOUR PREMIER ENGINEERING & TECHNICAL RECRUITMENT CONSULTANCY

RECRUITMENT.

On Board Use and Application of Computer based systems

Reliability of Safety-Critical Systems Chapter 2. Concepts and requirements

San Diego Gas & Electric Company FERC Order 717 Transmission Function Employee Job Descriptions June 25, Electric Grid Operations

Comparison of IV.A.M2 and IV.A.M3 to EOP-005-1

Standard EOP System Restoration from Blackstart Resources

ONSHORE WIND PART OF THE ALE WIND SERVICES DIVISION WORLDWIDE HEAVY TRANSPORTATION AND LIFTING

SIMARIS Software Tools

IEC Functional Safety Assessment

PROJECT SSDR ExD By FRIEDE & GOLDMAN, LTD

Offshore Supply, ROV Survey, Emergency Response and Rescue

TECHNICAL AND OPERATIONAL GUIDANCE (TECHOP) TECHOP_ODP_16_(P) (COMPETENCY ELEMENTS FOR DP PROFESSIONALS - DP SMEs / DP FMEA PRACTITIONERS) MARCH 2019

TECHNICAL AND OPERATIONAL GUIDANCE (TECHOP) TECHOP_ODP_16_(P) (COMPETENCY ELEMENTS FOR DP PROFESSIONALS - DP SMEs / DP FMEA PRACTITIONERS) APRIL 2018

DESIGN AND DEVELOPMENT

Call for Papers. August 16-17, Melbourne Park Function Centre Melbourne, Australia. Australian. Submit your abstract by March 28

Critical POWER Supplies Projects Support

Techlift International Limited Capability Statement

Competence in dynamic positioning for key technical personnel

Electrical Networks Principles and Performance

tradition. knowledge. responsibility. ADVANCED CONDITION MONITORING SYSTEMS FOR ROTATING MACHINES

Type and component certification of wind turbines

Flexible integrated transformer SOLUTION

CBTC (Communication Based Train Control): system and development

Transient Stability Analysis of an Industrial Cogeneration System

IEC Functional Safety Assessment

electrical requisition engineering an interactive integrating interface

Today s vessels are advanced constructions

Energy Efficiency. Technical Solutions for Operational Challenges

Standard EOP System Restoration from Blackstart Resources

WELMEC European cooperation in legal metrology Guide for the testing of automatic catchweighing instruments

HPC for Maritime SMEs

Standard TPL Transmission System Planning Performance Requirements

DRAFT RAMBOLL-SUBC END-TO-END EPCIC SOLUTIONS FOR ENERGY PROJECTS

DOCUMENT A-11 DU NPCC

We distribute energy Safe. Reliable. Innovative - since more than 45 years

Transmission Interconnection Requirements. Table of Contents

Addressing System Restoration Issues for the ISO New England System. Michael I. Henderson ISO New England Inc. PES General Meeting July 2015

Standard Development Timeline

FUGRO GROUP LNG FIELD DEVELOPMENT AND FACILITIES. TACKLING your complex challenges. UNDERSTANDING your operational objectives

Electromagnetic compatibility

AESO System Operating Limits Methodology for the Planning Horizon (R1 FAC-010-AB-2.1)

Multi-Agent Model for Power System Simulation

Doing things differently to deliver genuine efficiency.

GAC Australia Shipping Services Delivering shipping services with you in mind

Sticklers for Safety. Sep 17, 2014Van Wilkins Electrical Construction and Maintenance

MAKING GLOBAL REACH A REALITY.

exceptional Deep Sea

Information Document Protection System Information ID# R

We in Siraj Marine Services aspire to far surpass expectations through consistency and high level of professionalism.

Medium Voltage UPS Solutions - When and Why? Frank Herbener, Piller Group GmbH, Germany

Proposal for categorization of Significant Users

Marine Growth Anti-Fouling Systems Cuprion CAnDU SEAWATER PUMP FOULING PREVENTION

IEC Functional Safety Assessment

Standard MH-TPL Transmission System Planning Performance Requirements

Reliable Power in the Offshore Drilling Industry

End-to-end electrical solutions for the biggest challenges involved with connecting wind energy to the grid. Solutions for Wind Energy Integration

69/12KV SUBSTATION DESIGN

Beier IVCS 4000 Dynamic Positioning System

The 3VM molded case circuit breaker.

A. Introduction. B. Requirements and Measures

SimSci APC. Model Predictive Control to Improve Your Process Economics

Transcription:

Closed Bus Tie Systems Why to operate a DP vessel in closed bus tie configuration? 1

Why to operate a DP vessel in closed bus tie configuration? Conceptual design. 6 Contracts agreements and purchasing support...7 Design verification. 8 FMEA gap analysis. 9 DP FMEA report and sea trials... 10 Transient stability analysis.11 Short circuit and earth fault live tests...12 2

3

Why to operate a DP vessel in closed bus tie configuration? Operating a DP vessel in closed bus tie configuration introduces unquestionable benefits in terms of operational and maintenance costs of the equipment throughout the entire lifespan of the vessel, as well as in terms of lower environmental impact. Moreover a closed bus tie power system provides superior tolerance to plant faults, increasing the overall system reliability. Indeed, if compared against open bus tie mode of operation, closed bus tie gives a better operational availability and less running hours and higher efficiency working conditions of the main engines. All these benefits are counterbalanced by additional challenges in the design of the control, protection and management systems of the power plant. The designer shall be aware of single point / common source failures which can lead to total black-out or loss of all thrusters when the bus tie breakers are closed. Examples of those type of failures are: short circuit, earth fault, AVR or excitation fault, governor fault, etc. 4

Utilizing 30 years of consultancy experience in the offshore business, Global Maritime can offer the best fit for purpose package of services, supporting designer and owners from the conceptual phase of closed bus tie DP2 and DP3 projects, through the acceptance tests, to the operational phase. 5

Conceptual design Conceptual design is vital to the successful development of closed bus tie DP2 and DP3 projects. Global Maritime conceptual design and Front End Engineering Design (FEED) studies guide our customers in taking the right choice between different design solutions and available technologies, in order to lay the foundations for an affordable and effective design. 6

Contracts agreements and purchasing support Basing on decades of experience in offshore industry, Global Maritime can lead complex procurements involving teams with experienced engineers who blend equipment expertise with in-depth DP systems knowledge. Global Maritime can either integrate into customer s team, or can fully handle a procurement project. When negotiating for our clients or providing negotiation advice, we ensure that our clients will achieve the best solutions and outcomes. 7

Design verification Basic and detailed designs are the most crucial part of closed bus tie projects execution. Global Maritime design verification will ensure that the subsystem comprised in the power plant will be in compliance with the applicable Classification Societies rules, International Association guidance as well as best industries practice. Global Maritime specialists will support the design phase with our comprehensive overall understanding of closed bus tie DP systems, taking particular care of the interfaces between different subsystems, often supplied by different vendors, where show stoppers usually arise at later stages of the project. 8

FMEA gap analysis Often FMEA reports approved by Classification Societies are not at the technical detailed level required by charterers. Global Maritime can provide gap analysis of FMEA reports in line with the best industry practices (e.g. Class Rules, IMCA and MTS guidelines). 9

DP FMEA report and sea trials DP FMEA and sea trials for closed bus tie systems are much more complex and much more demanding than traditional FMEA for open bus tie power plants. Global Maritime analysts will not only evaluate the single point/common source of failures, but, assuming the possible presence of hidden failures, will also address and analyse primary and secondary barriers in place for each failure mode. Global Maritime DP FMEAs and sea trials are developed by multidiscipline teams of experts, including machinery, electrical, instrumentation and control engineers. The final result will comply with the best industry practices, latest standards and newest international guidelines. 10

Transient stability analysis According to leading class societies requirements, for DP vessels operating in closed bus tie mode, the designer shall provide a transient stability evaluation of the power system, supported by a computer based model of the plant. System stability is a concern when two or more generators operate in parallel. Sudden disturbances such as short circuits, impact loads and switching conditions will cause transient speed changes on the generators, which may prevent the system from remaining in synchronous operation. Global Maritime can provide the proper tailor made analysis able to simulate all the failure modes required by the applicable rules: analysis work is carried out using tried and proven computer programs. 11

Short circuit and earth fault live tests Leading class societies rules (e.g. ABS and DNV GL) introduced a live short circuit test requirement for DP3 plant operating in closed bus tie configuration. The purpose of the test is not only to evaluate the voltage dip ride through capability of the essential consumers, but also to validate the dynamic model of the system used in the transient stability study. The short circuit live test is a potential harmful test: during this tests high currents are released from the generators, which represent a possible danger for the personnel involved. Moreover the equipment is subjected to electromechanical stresses which might compromise their functionality or reduce their expected lifespan. Global Maritime supports the customer with tailor made: risk evaluation study, detailed test procedures including test results measurement strategy, test results analysis for model validation. 12

13

14

For more information please contact: Piotr Gussmann Manager Global Maritime Poland Tel: +48 586 888 000 Mob: +48 788 36 36 43 Email: piotr.gussmann@globalmaritime.com 15

16