OIL / WATER SEPARATORS UNDERGROUND FIBERGLASS STORAGE TANKS MODELS: CSI-10 / CSI-15 / UL 2215

Similar documents
TANK SUMPS SINGLE WALL & DOUBLE WALL

Below Ground Oil Water Separators

RECOMMENDED SPECIFICATIONS FOR AREO-POWER 10 PPM OIL WATER SEPARATORS WITH THROUGH SHELL CONNECTIONS

RECOMMENDED SPECIFICATIONS FOR AREO-POWER 10 PPM OIL WATER SEPARATORS WITH THROUGH SHELL CONNECTIONS

FLOWTITE WATER STORAGE UNDERGROUND FIBERGLASS TANKS

SINGLE-WALL TANK SUMPS INSTALLATION INSTRUCTIONS & OPERATING GUIDELINES

Fiberglass Underground Water Tanks

SECTION GROUND STORAGE TANK

GGI-750. Gravity Grease Interceptor Technical Data. Submittal Special Precautions Specifications Installation

TechNews. Part 2: Creative Solutions to Secondary Containment at Electrical Substations December 2018

SPECIAL SPECIFICATION 3504 Septic Tank System

Specifications: Simplex Fiberglass Lift Station: Rail Pipe. Simplex Fiberglass Lift Station: Pre-Packaged Fiberglass Systems

Fibreglass Underground Waste-Water Tanks

Simplex Fiberglass Lift Station: Hard Piped

Adam Sweet 6,000 GALLON DW FRP UST FUEL STORAGE TANK BY XERXES 10/25/2017 False

GGI-750. Gravity Grease Interceptor Technical Data. Submittal Special Precautions Specifications Installation

DOUBLE-WALL TANK SUMPS INSTALLATION INSTRUCTIONS & OPERATING GUIDELINES

SAFE-TANK DOUBLE WALL TANKS HIGH DENSITY CROSSLINKED POLYETHYLENE STORAGE TANKS WITH OXIDATION RESISTANT LINING SYSTEM (NSF/ANSI 61)

San Antonio Water System Standard Specifications for Construction ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES

ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES

San Antonio Water System Specifications for Construction ITEM NO. 853 SANITARY SEWER GLASS-FIBER REINFORCED POLYESTER (FRP) MANHOLES

STANDARD SPECIFICATION FOR OIL GRIT SEPARATOR (OGS) STORMWATER QUALITY TREAMENT DEVICE

CITY OF ODESSA SPECIAL SPECIFICATIONS ITEM 1000 GLASS-FIBER REINFORCED POLYESTER (FRP) REHAB/REPLACEMENT MANHOLE

Tank shall be designed for possible relocation at a future date. Concrete encased tank designs are not equal and will NOT be permitted.

Tank shall be designed for possible relocation at a future date. Concrete encased tank designs are not equal and will NOT be permitted.

A. This section is intended to provide design guidelines for Utility Direct Buried Piping and Conduit Systems.

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

Arms Group Drainage System. 1. Swivel Joint Type 2. Pivot Joint Type 3. Flexible Hose Type 4. Swing Master Joint Type 5. Floating Check Valve

SPECIFICATION FOR FIBERGLASS REINFORCED PLASTIC CHEMICAL STORAGE TANKS

PREMIER Low Profile Induced Draft Cooling Tower Specifications

SECTION SANITARY WASTE INTERCEPTORS

STANDARD SPECIFICATION FOR OIL GRIT SEPARATOR (OGS) STORMWATER QUALITY TREAMENT DEVICE

GRS GRS. Model. Groundwater Remediation Systems 1-50 GPM

TYPICAL INSTALLATION INSTRUCTIONS

TAMDID PIPES ABOVE GROUND FIBERGLASS STORAGE TANKS

.1 All equipment, controls and accessories to be compatible with system design, and matched to the steam boiler(s) by the boiler Manufacturer.

SUPPLEMENTARY SECTION: STANDARD SPECIFICATIONS PAGE 1 STORMWATER MAINS & CULVERTS MAY 2018

List of products of harmonised standards Code 28: PIPES-TANKS AND ANCILLARIES NOT IN CONTACT WITH WATER INTENDED FOR HUMAN CONSUMPTION

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED

GB-25. Submittal Special Precautions Specifications Installation Application Specific Details

HIGH DENSITY CROSSLINKED POLYETHYLENE STORAGE TANKS WITH OXIDATION RESISTANT LINING SYSTEM (NSF/ANSI 61)

DIVISION 33 UTILITIES SECTION PACKAGED SEWAGE GRINDER PUMPING UNITS

TM Series Induced Draft Cooling Tower Specifications

GB-20. Submittal Specifications Installation Application Specific Details

POLLUTANT STORAGE CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION

Captor Containment DOUBLE WALL TANK SYSTEMS.

Fiberglass Basin Installation Reference Guide

Flygt Advanced Low Pressure Sewer System Package

Captor Containment. DOUBLE WALL TANK SYsTEMS.

A. Gravity-Flow, Nonpressure, Drainage-Piping Pressure Rating: 10-foot head of water (30 kpa).

D-10 OUTLINE SPECIFICATION FOR PRE FAB Undergrd Piping System

SECTION SANITARY WASTE INTERCEPTORS

SPECIFICATIONS FOR HONEYCOMB INTERNAL FLOATING ROOFS

A. This Section includes the following sump pumps and accessories, inside the building, for building storm drainage systems:

BuildingName The Description of the Project P DOCUMENTS

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Section 10 Design Criteria: Components

STANDARD SPECIFICATION STORMWATER QUALITY MEMBRANE FILTRATION TREATMENT DEVICE

San Antonio Water System Standard Specifications for Construction ITEM NO. 848 SANITARY SEWERS

GBHF Submittal Special Precautions Specifications Installation Application Specific Details

a tankage process. delivery. 4. Avoid 6x6 T-bar Page 1 of 7 POLY Tank

SECTION GROUND WATER STORAGE TANKS

Contents EN 14015:2004 (E) page

SAMPLE SPECIFICATIONS FOR PREFABRICATED FRP LIFT STATIONS

SECTION PLUMBING SPECIALTIES

2 5 0 P. S. I. G. AMERICAN DARLING 5 1 /4" B-84-B FIRE HYDRANT

Beacon Hill Water & Sewer District Standard Specifications

TABLE OF CONTENTS

CHEMICAL WASTE OVERVIEW CONTINUED

GB-50. Submittal Special Precautions Specifications Installation Application Specific Details

Industrial Separation & Process Solutions. CS SERIES Coalescing Oil/Water Separators

GB-75. Submittal Special Precautions Specifications Installation Application Specific Details

4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT

VSS-2 ½ D HIGH HEAD SUMP PUMP FREE STANDING

B. Fiberglass for construction in back lot easements placed on cast-in-place base.

Centricast CL-1520 Pipe Product Data

SECTION FIRE HYDRANTS

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS

Underground Steam Condensate Distribution Piping

WASTEWATER TREATMENT SYSTEMS

Underground Exhaust System

Roth MultiTank (RMT) Certified Installer Training

Weholite LIGHTWEIGHT PIPE SYSTEM

SV24. Submittal Special Precautions Specifications Installation. 12½" (31.8 cm) 12½" (31.8 cm) 12" (30.5 cm) 12" (30.5 cm) 12" (30.

Pioneer Forced Draft Cooling Tower Specifications

Pioneer Forced Draft Cooling Tower Specifications

1. B16.1 Cast Iron Pipe Flanges and Flanged Fittings, Class C 111 Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings

SEPTIC TANK CONSTRUCTION GUIDELINES

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

1DIVISION 15- MECHANICAL Section Fire Pumps. A. Single Stage, Double Suction, 9100 Series Horizontal Splitcase Fire Pump (Base Mounted)

Akiki Engineering Est.

AMERICAN DARLING 5 1 /4" B-62-B FIRE HYDRANT

Oil On Water A Novel Helon Habila

SECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.

Section 3 Fusible PVC Pipe Connections

TYPES OF SEWAGE PUMPS. Solids Handling Pumps: Grinder Pumps: Effluent Pumps:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

A. Codes and Standards that are Standard at the University: 1. AGA Compliance: LC 1-91 Interior Fuel Gas Piping Systems

SECTION HVAC WATER TREATMENT

SECTION CONCRETE ABOVE GROUND FUEL STORAGE

Transcription:

OIL / WATER SEPARATORS UNDERGROUND FIBERGLASS STORAGE TANKS MODELS: CSI-10 / CSI-15 / UL 2215

FIBERGLASS UNDERGROUND OIL/WATER SEPARATORS Containment Solutions, Inc. (CSI) provides a full range of dependable products for the oil/water separator industry. Our underground separators utilize the same fiberglass manufacturing technology the petroleum industry relies on for environmental protection. The inherently non-corrosive properties of fiberglass provide the most compatible option for your separator application, built by one of the most trusted brands in the world. CSI provides several options in both single and double-wall construction to meet your unique needs. CSI separators are constructed to remove hydrocarbons with a specific gravity up to 0.95 through the use of an enhanced oleophilic coalescer pack system. Oil/water separator designs vary based on required effluent quality and flow rates. An effluent quality of 10 parts per million (10ppm) is typical but the difference between continuous flow and intermittent flow will drastically alter the coalescer pack sequence. For intermittent flow applications we offer CSI-10 and CSI-15 models. The CSI-10 model provides an effluent quality of 10ppm, while the CSI-15 model provides an effluent quality of 15ppm. For continuous flow applications look no further than the CSI UL 2215 separator. For more information on the CSI UL 2215, please contact your CSI representative. SYSTEM PROCESS CSI fiberglass separators are buried and filled with water. Each separator includes a combination of baffles and coalescer packs, based on effluent requirements, to accelerate separation. Waste water enters through the inlet and gravity naturally settles heavier solids to the bottom of the tank as the oil floats to the top of the water level. The oily water then passes through the coalescing plates in a straight flow or cross flow direction depending on the tank model. The configuration of the packs efficiently coalesces or joins oil droplets together forming larger masses of oil that rise to the surface where it accumulates and can be removed. Gravity displacement discharges the effluent though the outlet at a lower point in the tank chamber. Separator systems can also be equipped with drop boxes, electronic monitoring with high oil level alarms and control panels, and oil stop valves. PERFORMANCE CLAIMS: Fiberglass construction provides corrosion resistance without coatings or protection systems. Enhanced coalescer system is comprised of oleophilic plates to maximize separation and minimize maintenance. Removable plates simplifies routine cleaning. All tanks are built to the stringent performance requirements of UL 1316. Removes free floating oils and settleable solids for oil/water mixtures to achieve 10ppm effluent quality (or 15 ppm if specified). Includes a 30-year internal / external corrosion and structural limited warranty. 1 FIBERGLASS OIL/WATER SEPARATORS

SEPARATOR DESIGN & SIZING Since each site is unique, the most effective approach is to analyze each situation and design the system accordingly. CSI s engineering staff can help determine the best fit for your technical considerations and site specific needs. The major design parameters include: Inlet flow rates Oil spill capacity Inlet/outlet concentration Oil storage capacity Effluent quality Temperature Specific gravity of contaminants CSI UL 2215 separators are sized primarily on flow rates. A complete list of flow rate plate pack options are available, contact your CSI representative for more information. INTERCEPTORS In addition to separators, interceptors are available in single, double, and triple basin designs. CSI interceptors reduce sand, settleable materials, and oil or grease prior to sewer discharge. CSI interceptors can be used as stand alone units or as the initial stage of a more efficient treatment system utilizing CSI oil/water separators. MODELS PERFORMANCE UL 2215 CSI-10 CSI-15 Interceptor Stokes Law UL 1316 API 1630 API 421 USCG 46CFR 162.050 15ppm 10ppm UL 2215 Continuous Flow ELECTRONICS / ACCESSORIES Oil/Water Separator monitoring and control systems can be configured to satisfy a wide range of customer requirements. Control panels, sensors, probes and gauges are available for double-wall and single-wall oil/water separator systems as well as for single-tank or multiple-tank installations. CSI carries a full line of pump controls, inlet and outlet pumps, and waste oil pumps. We can package the right model with the proper electronics so when the tank arrives the only thing left to do is connect the piping. APPLICATION: RAINWATER RUNOFF Oil drippings and spills from parking lots, driveways, oil terminals and other vehicular traffic surfaces are being washed into our water supplies by rainwater, creating serious environmental concerns. CSI Oil/Water Separators are designed to meet EPA guidelines for rainwater runoff control. F I B E R G L A S S O I L / WAT E R S E PA R AT O R S 2

TYPICAL FEATURES A. Double-Wall Separator B. FRP Manway Extension C. Oil Draw Pipe D. Hydrostatic Reservoir E. Tank Sump F. Cross flow Baffle G. Coalescer Plate Packs H. Oil Stop Valve I. Anchor Straps J. Deadman Anchor System Corrugated plate packs coalesce, or join, oil droplets together forming larger masses of oil which rise to the surface. STANDARD TANK DIMENSIONS for CSI-10 & CSI-15 Models 10 Dia. 8 Dia. 6 Dia. 4 Dia. Nominal Capacity (gallons) Flow Rate (gpm) Oil Storage Capacity (gallons) Oil Spill Capacity (gallons Inlet / Outlet (sizes) Nominal Length Nominal Weight (lbs) Single-Wall Double-Wall Single-Wall Double-Wall 550 55 110 440 4 9 8 9 9 425 900 1,000 100 200 800 4 11 11 1 500 1,050 1,500 150 300 1,200 4 16 10 16 11 750 1,275 2,000 200 400 1,600 6 13 10 13 8 1,000 2,275 3,000 300 600 2,400 6 16 16 9 1,075 2,750 4,000 400 800 3,200 6 19 8 19 9 1,475 2,975 5,000 500 1,000 4,000 8 24 8 25 1,800 3,475 6,000 600 1,200 4,800 8 29 6 30 3 2,100 3,900 6,000 600 1,200 4,800 8 19 5 19 6 2,300 4,200 7,000 700 1,400 5,600 8 22 2 23 7 2,650 4,675 8,000 800 1,600 6,400 10 24 11 26 4 2,950 5,075 9,000 900 1,800 7,200 10 27 8 27 9 3,300 5,450 10,000 1,000 2,000 8,000 10 30 5 30 6 3,550 5,950 12,000 1,200 2,400 9,600 10 35 11 36 4,375 7,000 15,000 1,500 3,000 12,000 12 44 5 44 6 5,350 8,650 20,000 2,000 4,000 16,000 14 37 8 37 9 6,950 11,900 25,000 2,500 5,000 20,000 16 45 11 46 8,300 13,900 30,000 3,000 6,000 24,000 16 54 2 54 3 9,600 16,300 40,000 4,000 8,000 32,000 20 71 3 71 4 12,650 20,975 A 3 SEPARATOR SYSTEM OVERVIEW

B D E F H C F G I J Oleophilic coalescer plate packs are intended to be removed for cleaning. The number of plate packs will vary based on tank size and required effluent quality. SEPARATOR SYSTEM OVERVIEW 4

FIBERGLASS OIL/WATER SEPARATOR SPECIFICATIONS Specifications for Models CSI-10 / CSI-15 Long form specifications for the UL 2215 model oil/water separator or oil/sand/grit interceptor are available on the CSI website. SHORT FORM SPECIFICATION The contractor shall provide fiberglass underground Oil/Water Separators, in types (single-wall or double-wall) and sizes as shown on the drawings. The separators shall be manufactured by Containment Solutions. Separators shall be tested and installed with pea gravel or crushed stone or approved alternate backfill material, according to the current installation instructions (Containment Solutions Pub. No. INST 6001 and OWS 2013 provided with the tank). LONG FORM SPECIFICATION 1. GENERAL 1.1. Related Work 1.1.1. Containment Solutions, Inc. Fiberglass Drop out Box: Contractor to furnish and install (1) Fiberglass drop out box. 1.1.2. Plastic pipe: Contractor to furnish and install all necessary PVC drainage pipe and fittings. Contractor shall install a butterfly valve between the drop out box and tank inlet, as well as one between the outlet of the separator and the effluent pipe. 1.2. Quality Assurance 1.2.1. Acceptable Manufacturer: Containment Solutions, Inc., Conroe, TX 1.2.2. Governing Standards 1.2.2.1. U.L. 1316 Underwriters Laboratories, Inc. Glass Fiber Reinforced Plastic Underground Storage Tanks for Petroleum Products. 1.2.2.2. National Fire Protection Assoc. (NFPA 30 Flammable and Combustible Liquids Code, (NFPA 30A) Automotive and Marine Service Station Code, (NFPA 70) National Electrical Code. 1.2.2.3. All tanks and piping shall be properly installed in accordance with the manufacturer s instructions and either Petroleum Equipment Institute Publication RP100; Recommended Practices for Installation of Underground Liquid Storage Systems or American Petroleum Institute Publication 1615; Installation of Underground Petroleum Storage Systems. 1.2.2.4. API manual on disposal of refinery wastes 1.2.2.5. API bulletin no. 1630 first edition 1.2.2.6. API bulletin no. 421 1.3. Submittals 1.3.1. Oil/Water separator tank(s) shall be wall fiberglass tank(s) constructed in strict accordance with UL-1316. 1.3.2. Shop Drawings: Contractor shall submit copies of shop drawings for each OWS tank. Drawings shall include all critical dimensions, locations of fittings and accessories, i.e.: manways, hold-down straps, secondary containment collar, manway extensions, etc. 1.3.3. Contractor shall submit copies of manufacturer s literature including copies of manufacturer s current installation and maintenance instructions to the Owner. 2. PRODUCTS 2.1. Oil/Water Separator Tanks 2.1.1. Provide wall fiberglass reinforced plastic underground oil/water separator tank with fittings and accessories as denoted on the drawings. 2.1.2. Loading Conditions - Tanks shall meet the following design criteria: 2.1.2.1. External hydrostatic pressure: Buried in ground with 7 of over burden over the top of the tank, the excavation fully flooded and a safety factor of 5:1 against general buckling. 2.1.2.2. Surface Loads: When installed according to manufacturer s current installation instructions, tanks shall withstand surface HS-20 axle loads (32,000 lbs/axle). 2.1.2.3. Internal Load: Primary and secondary tanks shall withstand 5 psig (35kPa), or 3 psig for 12 diameter tanks, air pressure test with 5:1 safety factor. 2.1.2.4. Tanks shall be designed to support accessory equipment such as heating coils, ladders, drop tubes, etc. when installed according to manufacturer s recommendations and limitations. 2.1.3. Product Storage Requirements 2.1.3.1. Tank must be separately vented at the influent tee, oil/ water separator chamber and at the effluent tee. 2.1.3.2. Tank shall be capable of storing liquids with specific gravity of up to 1.1. 2.1.3.3. Tank shall be capable of storing grease and oils at temperatures not to exceed 150ºF at the tank interior face. Operating temperatures of the influent oil/water mixture shall range from 40 F to 150 F. 2.1.3.4. Tank shall be chemically inert to petroleum products. 2.1.4. Materials 2.1.4.1. The tank shall be manufactured as a matrix of premium resin, glass fibers and silane-treated silica that together result in a composite providing improved corrosion protection. 2.1.4.2. Tank inner wall shall be fabricated against a mold to produce a non-air inhibited and high gloss laminate to provide a fully cured inner surface without the need for wax coats, a low coefficient of friction and a natural resistance to the build-up of algae or other contamination on the surface. Wax and wax resin coatings cannot be used to achieve full surface cure on tank shells and endcaps. 2.1.5. Capability and Dimensional Requirements 2.1.5.1. Nominal volume of the separator shall be gallons. 2.1.5.2. Nominal outside diameter of the separator shall be feet. 2.1.5.3. Intermittent flow rate shall be GPM. 2.1.5.4. Total spill capacity shall be gallons. 2.1.5.5. Total oil storage capacity shall be gallons. 2.1.5.6. Inlet oil specific gravity shall range between and. 2.1.5.7. Inlet oil concentration shall be no more than 200,000 parts per million. 2.1.5.8. Effluent discharge quality shall be ppm free oil and grease. 2.1.6. Monitoring Capabilities 2.1.6.1. Double-wall tanks shall have a monitoring space between the walls to allow for the free flow and containment of leaked product from the primary tank. The monitoring space shall provide equal communication in all directions. 2.1.6.2. The following continuous monitoring conditions shall be compatible with the cavity between the inner and outer tanks: Vented to atmosphere Vacuum 5 psig maximum Positive air pressure (3 psig maximum) External hydrostatic pressure 7 maximum groundwater head pressure over tank top 5 SPECIFICATIONS

FIBERGLASS OIL/WATER SEPARATOR SPECIFICATIONS 2.1.6.3. The monitoring system shall be capable of detecting a breach in the inner and outer tank under the following installed conditions: When the primary tank is empty. When the primary tank is partially or completely full and the ground water table is below tank bottom. When the primary tank is partially or completely full and the tank is partially or completely submerged in groundwater. 2.1.6.4. The leak detection performance of the monitoring system shall be listed as a continuous interstitial monitoring method (liquid filled) by the National Work Group on Leak Detection Evaluations (NWGLDE). The system should be capable of detecting leaks in the primary or secondary tank walls as small as 0.10 gallons per hour within one-month. 2.1.6.5. The hydrostatic monitoring system shall be capable of a precision tank test that is listed by the National Work Group on Leak Detection Evaluations (NWGLDE). 2.1.6.6. If hydrostatically monitored, any solution used in the monitoring space shall be compatible with the tank and be of a contrasting color to the tank. 2.2. Accessories 2.2.1. Coalescer plates and associated internal mounting hardware shall be rust-proof and removable through a 22 x 29 oval access manway. 2.2.2. Provide fiberglass anchor straps, turnbuckles and concrete deadmen as provided by tank manufacturer. 2.2.3. Threaded fittings on tank shall be of a material of construction consistent with the requirements of the U.L. label. Fittings to be supplied with temporary PVC plugs. Standard threaded fittings are 4 in diameter. Reducers are to be used for smaller sizes where specified and provided by Contractor. See contract drawings for size and locations of fittings. 2.2.4. Oil Draw Off 2.2.4.1. Tank shall have a PVC factory installed oil draw off assembly. 2.2.5. Liquid Sensor Drawstring 2.2.5.1. Galvanized steel drawstring shall be factory installed at the monitoring fitting to facilitate field insertion of sensor. 2.2.6. Flanged Manways 2.2.6.1. (1) 22 x 29 oval or access manway will be provided with each tank. Tanks greater than 3,000-gallon total capacity will also include one 22 flanged manway. 2.2.6.2. All manways will be furnished complete with U.L. listed gaskets, bolts and covers. 2.2.6.3. Location - refer to drawings for location. 2.2.6.4. Optional manway extensions shall be fiberglass and feet long. 2.2.7. Flanged Nozzles 2.2.7.1. Inlet and outlet nozzles shall be of fiberglass or PVC construction. The nozzles shall have standard 150# ANSI Flange. 2.2.7.2. Nozzles shall be of sufficient size for inlet flow rate. 2.2.8. Secondary Containment Collars 2.2.8.1. The secondary containment collar shall be 42 diameter for containment around the 22 (or the 22 X 29 oval) manway on the tank. 2.2.8.2. The collar shall be factory installed. 2.2.8.3. The collar shall include an internal adhesive channel. 2.2.9. Tank Sumps 2.2.9.1. Provide fiberglass reinforced plastic tank sump as shown on the drawings. 2.2.9.2. The height for the tank sump shall be feet high. 2.2.9.3. The tank sump top and lid assembly shall be sealed watertight with factory supplied adhesive. 2.2.10. Oil/Water Separator Electronics 2.2.10.1. Provide control panel and required sensors, probes and gauges as provided by tank manufacturer. Model CPF Oil/Water Separator Control Panels Model FOWS Oil/Water Separator Interface Sensor Model FHRB 810 Reservoir Sensor for Hydrostatically Monitored Double-Wall Tanks Model FDAS 710 Annular Space Sensor for Dry Monitored Double-Wall Tanks Model FCBS 700 Collar, Bulkhead, Sump Float Switch 3. EXECUTION 3.1. Installation of FRP Tanks 3.1.1. Contractor s personnel involved with tank system installation shall be educated by tank manufacturer. 3.1.2. Contractor shall test and install tank, and accessories, according to all current installation instructions provided with tank. 3.1.3. Contractor is to complete the installation checklist provided by the manufacturer. A copy of the installation checklist must be retained by the tank Owner and/or installation Contractor to validate any future warranty claim. 3.1.4. Tanks shall be tested and installed according to the current installation and start-up instructions provided with the tank (refer to Containment Solutions pub. no. s INST 6001 and OWS 2013). 3.2. Maintenance Instructions 3.2.1. See Containment Solutions Pub. No. 2012 for maintenance requirements. 4. LIMITED WARRANTY 4.1. Limited Warranty 4.1.1. Warranty shall be Containment Solutions limited warranty in effect at time of delivery. While Containment Solutions has taken every precaution as to the accuracy of content and data presented herein, Containment Solutions cannot be held responsible for the individual interpretation of the data presented, any loss or damage to any property whatsoever, injury or death to any persons whatsoever, or any claims, demands, actions, complaints, proceedings, judgement, losses, damages, compensation, liabilities, costs or charges, however arising from the unauthorized undirected used of this handbook or the data it contains. SPECIFICATIONS 6

CONTAINMENT SOLUTIONS MANUFACTURES: Underground and Aboveground Storage Tanks Urea DEF Storage Tanks Automotive Oil and Lubricant Storage Tanks Flowtite Water Tanks Chemical Storage Tanks Fiberglass Manholes and Wetwells 333 North Rivershire Dr, Suite 190 Conroe, Texas 77304 Phone: (936) 756-7731 www.containmentsolutions.com Copyright Containment Solutions, Inc. All Rights Reserved September 2017 Pub. No. OWS 2001K