Bio-medical Wastes Disposal Incinerator Systems - Understanding, Criteria and Analysis For Comparative Selection, By Homi R. Mullan.

Similar documents
Incinerator Options. Surefire TS Fixed Hearth Incinerators. todaysurematthews.com +44 (0) Application. Throughput Capacities

Central Bio-Medical Waste Treatment Facility

An Experimental Approached to Investigate Keys Operating Parameters for Thermal Destruction of Major Components of Simulated Infectious Waste

ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT Air Division INSTRUCTIONS FOR COMPLETION OF DATA SHEET FOR WASTE DISPOSAL

APPROVAL FOR HAZARDOUS (BIOMEDICAL) WASTE INCINERATION PLANT FOR HOSPITALS

Legal Aspects and Process of Biomedical Waste Management Practices in India. *Prakash V **Dr. N. Palaniraj

Major changes proposed in the Bio- Medical Waste Management Rules, 2016 and its likely implication

Technical Session on Healthcare Waste Management - Treatment of infectious and sharp waste -

Title V Changes Regulatory Overview. New EPA Air Quality Standards

CHAPTER 3 STUDY OF EXISTING COMMON BIO-MEDICAL WASTE TREATMENT FACILITY (CBMWTF)

HOW PYROLYSIS WASTE TO ENERGY WORKS

INCINERATION. Combustion Efficiency. NACT Incinerators NACT 270. Incinerators. 3 T's Time (of residence) Temperature Turbulence

BIO-MEDICAL WASTE MANAGEMENT- CHALLENGES IN INDIA

Chapter 13. Thermal Conversion Technologies. Fundamentals of Thermal Processing

Technical Description Package Micro Auto Gasification System (MAGS )

MEDICAL WASTE MANAGEMENT STUDY NOTES

1.01 Development of the Air cross flow gasification-process

MP-500. The most thermally efficient, robust and reliable medical incinerators on the market. Simply Built Better!

FORM III (See Rule 10) AUTHORISATION No: 18BAZ Dated 25/01/2018 **********

MP-300. The most thermally efficient, robust and reliable medical incinerators on the market. Simply Built Better!


MP-400. The most thermally efficient, robust and reliable medical incinerators on the market. Simply Built Better!

1) ABSORPTION The removal of one or more selected components from a gas mixture by absorption is probably the most important operation in the control

Borregaard Case Study. Sarpsborg I & II

nc.us/swhome/

Table Of Contents. Preamble 2. Summary 2. Human Health Effects of Dioxin Emission from Incinerators. 3

Environmental Performance Test of Hazardous Waste Incinerator in Indonesia

Chapter Five Waste Processing, Treatment and Recycling Joe Green Dr Chris Wooldridge Cardiff University

VIRIDOR WASTE MANAGEMENT ARDLEY EFW PLANT EP APPLICATION - NON TECHNICAL SUMMARY

International experiences Healthcare Waste Mangement

A Burning Experiment Study of an Integral Medical Waste Incinerator

CHAPTER 6 BOILER EFFICIENCY

INDUCED-DRAFT RICE HUSK GASIFIER WITH WET SCRUBBER AND JET-TYPE BURNER: DESIGN AND PERFORMANCE

Health Care Waste Management - To Reduce the Burden of Disease, Health- Care Waste Needs Sound Management, Including Alternatives to Incineration

US APPROACH TOWARD MEDICAL WASTE MANAGEMENT. BY KRISTINA MESON, OSWER CHEN H. WEN, OPPTS US Environmental Protection Agency

3R approach towards bio-medical waste management

TRIAL BURN TECHNOLOGY FOR WASTE THERMAL PLANT

PEI Candlestick (Utility) Flaring Systems (Theoretical by-products of combustion & destruction efficiency)

Current Technologies, Treatment, and Disposal Issues

Electric Furnace Off-Gas Cleaning Systems Installation at PT Inco ABSTRACT

Application of CFB (Circulating Fluidized Bed) to Sewage Sludge Incinerator

BFB (bubbling fluidized bed) Power Plants (CHP) Fuel: RDF or Biomass CHP

Biomass Gasification

Chapter 5. Current Land-Based Incineration Technologies

DESIGN OF INCINERATOR FOR THE TREATMENT OF BIO-MEDICAL SOLID WASTE IN CHIKMAGALUR CITY

Sheffield s Energy Recovery Facility

SOURCE ACTIVITY TITLE: Incineration of Industrial Wastes

Transportable disease control units

GASIFICATION THE WASTE-TO-ENERGY SOLUTION SYNGAS WASTE STEAM CONSUMER PRODUCTS TRANSPORTATION FUELS HYDROGEN FOR OIL REFINING FERTILIZERS CHEMICALS

T-125 EVOLUTION OF THERMAL REMEDIATION. Technical Paper T-125. EVOLUTION OF THERMAL REMEDIATION by Wendell R. Feltman P.E.

Experimental Study on Combustion Characteristics of Unused Biomasses in Compact Combustor

Design of Biomedical Waste Incinerator

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

2. How can the University have an expansion of the Cogeneration Facility without an increase in the amount of coal used?

Oil Lakes Monitoring and Assessment Report. High-Temperature Thermal Desorption System Preliminary Design

Incineration (energy recovery through complete oxidation) Mass Burn Refuse Derived Fuel Pyrolysis Gasification

Lecture (6) on. Schematic of a Thermal Power Plant. By Dr. Emad M. Saad. Mechanical Engineering Dept. Faculty of Engineering.

Pharmaceutical product means a restricted drug under the Health (Drugs and Poisons) Regulation 1996.

ECO-FRIENDLY UTILIZATION FOR RESPONSIBLE BUSINESS

MultiZon incinerator for batch operation

COMPREHENSIVE MSW PROCESSING STEPS BIO COKE METHOD

In the UK, the most common disposal method is landfill. Incineration, anaerobic digestion and other disposal methods are also used.

Air Pollution Control For

Thermal Oxidation plants February 2016

a long-term sustainable solution for waste

Checklist of Authorization for handling Bio Medical Waste

State of the Art (SOTA) Manual for Stationary Gas Turbines

OPERATION AND PERFORMANCE TESTING OF THE HAZARDOUS (BIOMEDICAL) WASTE INCINERATION PLANT FOR HOSPITALS

Acid Gas Control Systems. Spray-Dry Scrubbers and Dry Injection Systems. United McGill products. a McGill AirClean product

FREQUENTLY ASKED QUESTIONS (FAQS)

Glossary of terms used in the book

On-site Incineration Area Source Category Calculation Methodology Sheet

1119. Optimisation of Cooking Stoves for Humanitarian Purposes

Incinerators for hazardous materials Safety and reliability with newest technology

CONTROLLED PYROLYSIS CLEANING OVENS

Commercial and Industrial Solid Waste Incinerator (CISWI) Rules Final Reconsidered Rules Requirements Summary

CEMENT PLANT ENVIRONMENTAL TECHNOLOGY FOR ACHIEVING HIGH SO 2 REMOVAL

Comparison of Dry Sorbent Injection of Sodium Bicarbonate, Lime, and Carbon and Their Control of Dioxins/Furans, Mercury, Chlorides and Sulfur Dioxide

Project Summary Products of Incomplete Combustion from Direct Burning Of Pentachlorophenol-treated Wood Wastes

Chapter page 1

Chapter 2.6: FBC Boilers

Waste-To-Energy New Technologies

The Preferred option of Co-processing for greening the nations backyard

GENERAL APCD PERMIT INFORMATION REQUIREMENTS LIST

Ms. Kiki KAMANU Director Shiraan Limited NIGERIA SHIRAAN ÇIRAĞAN

Green Incinerators Brand. Scan & Surf

Gas Measurements and Characterization of Wood Combustion in Two Moving Grate Boilers

GM2000. The most thermally efficient, robust and reliable medical incinerators on the market. Simply Built Better! GM2000. Touch Screen.

INSTRUMENTATION SYSTEMS FOR MUNICIPAL REFUSE INCINERATORS

GUIDANCE NOTE ON THE BEST PRACTICABLE MEANS FOR

Hospital Waste Characterization and Proposal of Management Technique for Onsite Disposal in Ujjain City

Pre-treatment plant. Plant BIOROT 200 CC. General description

TREATMENTAND DISPOSAL METHOD OF HOSPITAL WASTE MANAGEMENT IN AMRAVATI CITY

Waste treatment technologies I

RECENT CHANGES TO REGULATORY REQUIREMENTS FOR LOW LEVEL RADIOACTIVE WASTES INCINERATION AT FUEL FACILITIES IN CANADA

This is a draft revision of the briefing, and any comments are welcome please them to Becky Slater on

Effectiveness of briquetting bio mass materials with different ratios in 10 kw down draft gasifier

Heat and electricity from waste Sysav s waste-to-energy plant

John Vijgen, International HCH and Pesticides Association, Fellowship report: New and emerging techniques for the destruction and treatment of

Emission Criteria for Biomedical Waste Incinerators

Transcription:

.Page 1 of 9 BIO-MEDICAL WASTES DISPOSAL INCINERATOR SYSTEMS - UNDERSTANDING, CRITERIA AND ANALYSIS FOR COMPARATIVE SELECTION. Preamble The Bio-medical waste (Handling and Management) Rules, 1998, promulgated by Ministry of Environment & Forests (MoEF) permits Incineration of selected categories of Bio-Medical Wastes (BMW) as one of the Treatment & Disposal options. The permissible categories of wastes for Incineration included are Category No.1 (Human Anatomical Waste); Category No.2 (Animal Waste); Category No.3 (Microbiology & Biotechnology Waste); Category No.5 (Discarded Medicines and Cytotoxic Drugs); and, Category No.6 (Soiled waste - items contaminated with blood, and body fluids). The Standards for BMW Incinerators shall comply with MoEF Rules as per Schedule V which includes: a) Operating Standards, and, b) Emission Standards, and these are prescribed as per Central Pollution Control Board (CPCB) guidelines. The Rules permit these Incinerators, meeting with operating standards requirements, to be operated on-site or as well as off-site. Since then many BMW Incinerators have been, and are continuing to being, installed and operated on-site, whilst very limited off-site centralised Incinerator plants have been set-up. Though these BMW incinerators have been installed in accordance with the 'letter-of-the-law', they certainly are not being operated in the 'spiritof-the-law'. This is a major environmental and public health concern. Incineration process is rather a final waste disposal option to be compared with other disposal options such as sanitised landfill and deep burial. Incineration should not be considered as a waste treatment option, and is not a comparable waste treatment option such as steam Sterilizer / autoclave / hydroclave, Chemical disinfection and Microwave system. The objective of this paper is not to encourage the usage of incinerators where economic and safe alternative preferences are available for treatment and disposal of BMW. But, where the decisions have been made to opt for BMW incinerator, then this paper should enlighten the Selectors, Decision makers, Operators and other stakeholders in proper understanding and criteria for optimum selection of Incinerator system. A poor selection of Incinerator system could only result in an ongoing health hazard or scrapping off a huge investment, in short span of time, made into incineration system. The paper is confined to some of the selected basic understanding of BMW incineration that will be useful in proper selection as well as proper operation of BMW incinerator system. However, the incinerator operation is not covered in this paper, and interested readers may refer to Technical Papers, Hand Books, US EPA Guidelines and various articles referenced at the end of this paper for further reading for implementations.

.Page 2 of 9 The experience has shown that the purchasers and operators of incinerator systems, have more often than not, know very little about the fundamentals of Incinerators and intricacies and hazards involved with Bio-medical waste incineration, which otherwise would have helped them in opting for, selecting and operating a better choice of incineration system. It is not intended that this paper covers high technical jargon nor does it go into the depth of this very vast subject, but to arouse adequate interest to make use of proper selection of incineration system with the design selection parameters listed in this paper. This paper should interest users to refer to hand books and specialists in Incineration business. Fundamentals of Incineration 'Incinerate': In Greek it is 'Burn to ashes'. It is also known as Thermal Oxidation. The (1) CLAVIN other forms of thermal destruction include Pyrolysis and Starved Air Combustion R. BRUNNER. Incineration is a process by which combustible materials are burned, producing combustion gases and, non-combustible residue and ashes (2) USEPA O&M HMWI. Incineration is combustion or burning process, involving the chemical reaction of combustible waste materials with air, in which the primary purpose is the destruction and reduction, in size and mass, of the combustible material. A secondary purpose may be (3) California EPA the sterilization or destruction of pathological or hazardous waste materials Compliance Assistance Program on Incinerators. Combustion is a rapid chemical reaction process between oxygen (available in air) and combustible elements (such as carbon or hydrogen). Good combustion can produce invisible gases. Poor combustion can produce acrid smoke. Incineration process is to convert solid and liquid waste to Gas to allow combustion process to take place. No combustion process occurs instantly. The incineration process involves steps of Heating and drying; Volatilisation; Ignition; and heat release. The greater the air (oxygen) supply, the greater likelihood of complete burnout. The Temperature required for Ignition of gases to take place varies with that of the combustible material being incinerated. For gases from Paper the ignition will take place at 232C; for gases from Charcoal the ignition will take place at 350C; for gases from Coal the ignition will take place at 480C; for gases from Carbon monoxide the ignition will take place at 650C; for gases from Methane the ignition will take place at 630C to 750C. The greater the Air Supply, there is the greater likelihood of complete burnout. The amount of excess air required varies with the nature of combustible material. For Gaseous wastes the excess air required varies between 110% to 115%; for Liquid wastes the excess air required varies between 120% to 130%; For the Solid (medical) wastes the excess air required varies between 175% to 300%; For combustion to take place, besides Temperature, the air (oxygen) has to adequately mix with the hot gases from heated wastes, and such a mixing process is achieved through sufficient Turbulence by means of mechanical and manual mixing. Turbulence in secondary chamber assists complete combustion in

.Page 3 of 9 shorter time. Besides Temperature and Turbulence requirement for combustion, the third important parameter is the 'Solids Residence Time' required for burnout of solids in the primary chamber producing combustible gases; and the 'Gas Retention Time' in the Secondary chamber, which ensures that the gas discharge from it controlled at 871C to 1093C. Usually the gas retention time in the secondary chamber is designed for 1- second to 2-second. You will therefore commonly hear about the 3-T's of combustion: Temperature, Turbulence and Time. For control of complete combustion and adequate incineration, the 3-T's have inter relationship which has to be balanced. 'Retention Time' cannot be controlled directly once the incinerator is designed and built. Residence time is a function of Chamber Volume and Volumetric Flow Rate. Planning for increased 'Retention Time' would result in Increased Size of an Incinerator and thereby resulting in Increased Capital Cost and Increased operating Heat loss. Indirect control of retention time is achieved by: controlling waste feed rate; by controlling Temperature within Incinerator. 'Temperature': Even though Temperature at some location is high, if sufficient oxygen (air) and Turbulent mixing are not provided, no reasonable amount of Residence Time can achieve complete combustion. Temperature can be easily achieved. 'Retention time' and 'turbulence' are more difficult to control. 'Incomplete Combustion': The reasons for it are: - Temperature: Not high enough in Secondary chamber. - Oxygen: Not enough (air starvation). - Mixing (Turbulence): Not enough. - Residence Time: Insufficient in the Secondary chamber. - Waste Feed Rate: Excessive. 'Combustion Air': Too much combustion air may be just as bad as too little air, as it will cool the combustion reaction and cause incomplete combustion. Too much excess air may make it necessary to burn auxiliary fuel in order to maintain temperature. 'Hospital Waste Characteristics': Understanding of waste characteristics is of prime importance as the basic purpose of Incinerator is for safe and efficient destruction of these wastes. Hospital wastes are heterogeneous mixtures of general refuse; laboratory & pharmaceutical chemicals and containers; and, pathological wastes. Heat Content and moisture content of waste being charged to the Incinerator, will affect the operators

.Page 4 of 9 ability to maintain good combustion conditions in the incinerator without the use of auxiliary fuel. Incinerators are to be sized based on Heat Liberated from hospital waste in combustion process. Two major impacts that moisture has on the combustion system are increased volumetric flow and reducing Residence Time of the combustion gases. Halogentaed plastics, such as polyvinyl chloride, will produce acid gases such as HCl. The presence of chlorinated wastes also may contribute to the formation of Toxic polycyclic organic material such as dioxins and furans under poor operating conditions. Segregation, removal and control of unwanted waste components for Incinerator system from the Hospital waste stream is of utmost importance. There are statutory regulations to this effect. Incinerator Construction The basic Incinerator system construction has following components. - Waste Feed: The waste can be manually fed, by mechanical arrangement such as feed trolley, or by an automatic feed arrangement. Manual waste feed is the most commonly practiced for small and medium capacity on-site incinerator, and its capital cost is low, but the operating efficiency is reduced. The waste bag size should match with the waste feed door size of the incinerator. - Primary Combustion Chamber: The waste is first fed into the primary chamber where the vaporisation of volatile matter takes place. The waste is ignited and moisture driven-off by the aid of auxiliary burners. The waste is placed on the Grate in the primary combustion chamber. The air (oxygen) supply is made by means of a Forced Draft (FD) fan. The size of the chamber volume and the grate area some of the factors which determines the incinerator capacity. - Secondary Combustion Chamber: The hot volatile and combustible gasses liberated from waste in the primary chamber, passes through the ducts into the secondary chamber. Complete burnout of combustibles should take place in this secondary chamber by means of secondary burners. The hot gases may be allowed to pass through a tertiary chamber where it will allow heavy particulate matter to settle down. - Ash Removal: the ash collection chamber is located at the bottom of Primary chamber, and the provision for ash removal from secondary chamber is also provided for. The holding capacity of the ash collection chamber determines the operating hour capacity of the incinerator, after which the ash chamber has to be cooled for removal of ash. Ash collection chamber of large holding capacity increases the overall size of the incinerator and thereby its cost.

.Page 5 of 9 - Gas cleaning system: The hot gases discharged from the secondary / tertiary chamber are latter are passed through dry particulate separators and / or Wet scrubber system. The different types and varying efficiencies of Gas cleaning system would determine the cost of the system. - Chimney: The cleaned and cooled gases from the gas cleaning system are discharged into a chimney. The gases are discharged by means of an Induced drafted fan. The cost of the chimney is determined by the construction standards. For tall chimneys (of 30 meter height) there is a considerable cost involved with regards to laying of chimney base support civil foundation work. - Monitoring & Control: Monitoring and control measures are needed for incinerator combustion control as well as for environmental monitoring and control. - Incinerator Building, housing the Incinerator as well as the gas cleaning system, should be very well ventilated to ensure that the incinerator combustion in not starved due to insufficient rate of combustion air (oxygen). The overall size of the incinerator building is a significant cost component of the Incinerator plant costs. Incinerator Types There are various explanations to various types of incinerators, and they can be grouped under: i) CATEGORY WISE: Batch feed type, Intermittent type, and, Continuous feed type; ii) CAPACITY WISE: Small, Medium, and Large; and, iii) DESIGN WISE: Single chamber, Multiple chamber, Controlled air, and Rotary Kiln. Batch Type: In this type a fixed quantity of waste is fed into the incinerator. The incineration cycle lasts for a period of six to eight hours. These are usually of small capacity having a single chamber, fixed grate. They usually operate at temperature of 600C to 800C. The waste is ignited and burned with oil fired or by Electric heating. They are such that neither waste charging nor ash removal can occur during combustion. Over many decades, these types of incinerators were widely and successfully used in U.K, Europe and North America, for Hospital waste Disposal. However these types of incinerators do not meet the New Operating Standards and do not meet with the New Environmental Standards. Modern Batch type incinerators are of two-chamber construction, having high temperature operation of 800C to 1000C, combustion efficiency of 99.9999%, invisible smoke and meet with the New environment emission standards.

.Page 6 of 9 Intermittent Type: In Intermittent Type of incinerators the waste is fed at intermittent intervals of every 10 to 15 minutes. They are usually of multiple chamber design (primary, secondary and tertiary) and operate at 800C to 1000C. They are of the fixed grate type and the ash build up has to be manually pushed into the ash collection chamber below the primary combustion chamber. They are suited for small and medium capacity incineration. The incinerator operating cycle is limited to the holding capacity of the ash collection chamber. Larger the ash collection chamber, longer is the operating cycle, thereafter the incinerator has to be cooled, ash removed before the next incinerator cycle starts. They usually operate for 12 to 14 hours before final burn down. These types of incinerators have been widely used in India in the 600C to 800C operating range. The current incinerators being installed are constructed for 800C to 1000C operations, meeting with the Central Pollution Control Board (CPCB) standards. They are limited to intermittent operation by virtue of the manual movement and removal of ash. Continuous Type: In these types of incinerators the grate is of moving type, which progressively moves the ash into the ash collection chamber. The ash removal is continuous by an automatic removal system. These systems are more economical for large capacity incinerators. They are available in Multiple Chamber or Rotary Kiln designs. Small Capacity: Maximum design waste burning capacity is less than or equal to 90 kg/hour (200 pounds per hour). Medium Capacity: Maximum design waste burning capacity is from 90 kg/hour (200 pounds per hour) to 220 kg/hour (500 pounds per hour). Large Capacity: Design waste burning capacity is above 220 kg/hour (500 pounds per hour). Single Chamber: Incinerators used for small quantity batch incineration for on-site waste disposal. It has features that of the 'Batch type' incinerators described above. Multiple Chambers: Incinerator described in 'Incinerator Construction' above, is that for a typical multiple chambers incinerator. Rotary Kiln: These incinerators are widely used in the treatment of hazardous waste. They are versatile and are suitable for most types and forms of waste including solids, sludge, liquids, and gases. Later these systems have been applied to the burning of medical waste. A rotary kiln incinerator is a cylindrical primary combustion chamber,

.Page 7 of 9 which rotates about a horizontal axis. It is tilted at a slight incline to the horizontal from 40 to 80 mm per meter of length. It is rotated slowly, approximately 1 revolution per minute. Waste is charged at the upper end of the kiln and its rotation moves the waste slowly towards its opposite end. Waste will burn within the kiln and by the time the burning waste has reached its far end it will be burned out to an ash and will be discharged to an ash sump. A separate secondary combustion chamber is located downstream of the kiln to complete combustion of organics in the off-gas, providing Temperature, Time and injecting air to obtain the Turbulence required for good combustion. The Rotary Kiln incinerators are not being used in India for Bio-medical waste disposal. Incinerator Design Aspects Following design aspects will enable you to check and compare during the competitive selection of Incinerator offers. 1. Length-to-Width Ratio of Primary Combustion Chamber: a.) For Multiple chamber incinerator of capacity less than 230 kg/hour is 2.0 to 1 b.) For Multiple chamber incinerator of capacity greater than 230 kg/hour is 1.75 to 1 c.) For Multiple chamber incinerator of capacity less than 340 kg/hour is 1.65 to 1 d.) For Multiple chamber incinerator of capacity greater than 340 kg/hour to less than 907 kg/hour is 1.1 to 1 2. Grate Loading a.) b.) Acceptable Grate loadings for incinerator capacity 11.3 to 340 kg/hour capacity range from 73 to 122 kg/(m 2 h). Acceptable Grate loadings for incinerator capacity greater than 340-kg/hour capacity range from 122 to 146 kg/(m 2 h). c.) A number of incinerators have designed for grate loadings of 244 to 342 kg/(m 2 h).

.Page 8 of 9 3. Arch Height and Grate Loading Relationship Optimum Arch height and Grate Area can be estimated. The relationship between arch height and grate area can be calculated from the empirical equation: Arch Height in meter (H A ) = 0.9643 (A G ) 4/11 Where, A G is the Grate Area of horizontal cross-sectional area of the ignition (Primary) chamber in square meter. 4. Optimum Design Velocities for Gas Flow: GAS FLOW PATH VELOCITY IN M/S Flame Port 13.7 to 19.8 Mixing Chamber 6.1 to 10.7 Curtain-wall Port 3.0 to 4.6 Secondary Combustion Chamber Less than 3.0 The above velocities enable to maintain required Turbulence required for combustion and incinerator operation. Conclusion: The choice of selection of the type of incinerators available in India is very limited. The above guideline and information available from the below listed reference list would enable administrators to take an educated purchase decision. References: 1. 'Medical Waste Disposal': Calvin R. Bruner, P.E., DEE, ISBN 0-9621774-1-5 2. 'Operation and Maintenance of Hospital Medical Waste Incinerators'. United States Environmental Protection Agency, Centre for Environmental Research Information Cincinnati OH 45268, EPA/625/6-89/024.

.Page 9 of 9 3. 'Medical and Institutional Waste Incineration: Regulations, Management, Technology, Emissions, and Operations'. Seminar publication of USEPA, EPA/625/4-91/030 of December 1991 4. 'Bio-medical Waste (Management and Handling) Rules, 1998, MoEF. 5. Infectious Waste Incineration', Gordon F. Blizard, Jr., Standard Handbook of Hazardous Waste Treatment and Disposal, The McGraw-Hill Companies, Inc., 1998. 6. "Waste Incineration Handbook", by Paul Cheremisinoff, Butterworth Heinemann -1992. 7. "Planning & Selection Guidelines, Hospital Medical Infectious Waste Incinerators (HMIWI)". Prepared by: Homi R. Mullan, Consultant, Hospital & Medical Waste Management. 8. "Indian Perspective of Hospital /Medical / Infectious Waste INCINERATOR Operation drawbacks and suggested corrective measures", By: Homi R. Mullan,. Second National Seminar on, "Hospital Clinical Waste, Hazards Management, and Infection Control", April 12-15, 2000, at Banglore. Organised By: INDIAN SOCIETY OF HEALTH ADMINISTRATORS (ISHA) Homi R. Mullan Consultant: Energy & Environment Conservation Cell: +91-9820811308; Home: +91-22-23865290 homi-mullan@hotmail.com mullan.hts@gmail.com website: www.mullanconsultants.com