SECTION HVAC DUCTS AND CASINGS

SECTION METAL DUCTS

DIVISION 15-MECHANICAL PN SECTION DUCTWORK SYSTEMS PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Low, medium and high pressure ductwork.

B. Qualification Data: For installers specified in Quality Assurance article.

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

SECTION AIR DISTRIBUTION

A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field applied, if any), for each type of product indicated.

a gray co. SPIRAL, OVAL & RECTANGULAR DUCT CATALOG Lake Park, GA Coats, NC

RATING: Consult factory for availability Consult factory for availability

SECTION METAL DUCTS

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT. A. ASME B31.1 (American Society of Mechanical Engineers) - Power Piping

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION HVAC INSULATION

PROJ. NO SECTION HVAC DUCT INSULATION

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

Testing. Test drainage products according to the applicable AASHTO or ASTM specification, except as otherwise noted.

SECTION AIR OUTLETS AND INLETS

SECTION METAL STAIRS

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

LLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

installation instructions Combination Fire & Smoke Damper

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

Air Duct Metal Products

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System

SECTION HANGERS AND SUPPORTS FOR PLUMBING

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

SECTION MEDICATION CABINET. 1.1 SUMMARY A. Section Includes: 1. Medication cabinets with self-contained refrigerator and fixtures.

SECTION ALUMINUM HANDRAIL SYSTEMS

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

SECTION VIBRATION AND SEISMIC CONTROL FOR PLUMBING

Midwest Metal Fabricators LLC 712 Maple Street Wapakoneta, OH Phone (419) Fax (419)

E. Fume hood to have set baffling system. No adjustable baffles allowed.

Design & Construction Standards, Revised January

UNIVERSITY OF NORTH FLORIDA Arena HVAC Replacement

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

Union County Vocational - Technical Schools Scotch Plains, New Jersey

1. ARI 410 Standard for chilled water, hot water and steam coils. 2. ARI 430 Central Station Air Handling Units

This specification describes the minimum requirements for industrial thermal insulation.

Design and Construction Standards SECTION HYDRONIC PIPING

2.5" Min. Stud or Runner. 1.5" Mineral Fiber Blanket in Cavity, If Required. Wallboard. Retaining Angle. 1" Min. Damper Sleeve on 10" centers.

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION HYDRONIC PIPING

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19

Multi-Institutional Academic Health Science & Research Center Evansville, IN

K. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor.

SECTION HYDRONIC PIPING

Architectural Roof and Wall Products Guide Specifications

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

SUPPORT AND ANCHORS SECTION 15090

Duct Wrap Flexible Wraps

SECTION AIR TERMINAL UNITS

SECTION MECHANICAL INSULATION. A. Types of insulation specified in this section include the following:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SMACNA-01Accepted Industry Practice for Industrial Duct Construction. A. Duct work sizes on drawings state inside clear dimensions.

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

SECTION CHAIN LINK FENCES AND GATES

SECTION PRE-ENGINEERED BUILDING INSULATION

Division 15 INSULATION Section 15100

Mechanically Fasten Duct Sections. Code Reference: 2013 Title 24, Part 6 Standards 120.4(a) Sealed Openings. Drawbands

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

SECTION METAL DUCTS

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

FIRE STATION 55 June 14, 2010

Light-Metal Roof Edge, Raised

SECTION ACCORDION FOLDING PARTITIONS

SANITARY WASTE AND VENT PIPING

SECTION PLUMBING PIPING

SECTION HYDRONIC PIPING

BNIM ARCHITECTS 2460 PERSHING ROAD, SUITE 100 KANSAS CITY, MO

DIVISION 20 GENERAL SECTIONS FOR PLUMBING, FIRE SUPPRESSION & HVAC SECTION VIBRATION ISOLATORS

CERTIFICATE OF APPROVAL No CF 5073 LEMINAR AIR CONDITIONING INDUSTRIES L.L.C.

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.

Architectural Roof and Wall Products Guide Specifications

SAUDI AIR CONTROL SYSTEM INDUSTRIAL REGISTRATION NO.353 FIRE DAMPERS

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION HVAC PIPES AND TUBES

SECTION (15150) - SANITARY WASTE AND VENT PIPING

Addendum to Specifications

SECTION WALL AND DOOR PROTECTION

SECTION DUCT INSULATION

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

For Underground Burial or Under Slab Applications. Can Be Fabricated For Both Positive And Negative Pressure

PermaShield Pipe. Fab-Tech, Inc. SECTION 1589X Specification for Coated Corrosive Fume Exhaust Duct

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

DARTMOUTH COLLEGE DESIGN September 15, 2004 &CONSTRUCTION GUIDELINES

SECTION (15081) - HVAC INSULATION

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION SUPPORTS AND ANCHORS

SECTION PLUMBING INSULATION

SECTION AIR DUCT CLEANING

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

SECTION ROOF ACCESSORIES

DIVISION 15-MECHANICAL SECTION SUPPORTS AND ANCHORS PN PART 1 - GENERAL 1.01 SECTION INCLUDES. A. Pipe and equipment support systems.

PERMANENT PAVEMENT REPAIR NO SCALE

Transcription:

SECTION 23 31 00 HVAC DUCTS AND CASINGS PART 1 -GENERAL 1.1 SUMMARY A. Section includes metal ductwork, nonmetallic ductwork, casing and plenums, buried ductwork, kitchen hood ductwork, duct cleaning. 1.2 RELATED SECTIONS: A. Section 09 05 00 - Common Work Results for Finishes: Execution requirements for Weld priming, weather resistant, paint or coating specified by this section. 1.3 REFERENCES A. ASTM A36 - Structural Steel. B. ASTM A90 - Weight of Coating on Zinc-Coated (Galvanized) Iron or Steel Articles. C. ASTM A167 - Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip. D. ASTM A366 - Steel, Sheet, Carbon, Cold Rolled, Commercial Quality. E. ASTM A568 - Steel, Sheet, Carbon, and High-Strength, Low-Alloy, Hot-Rolled and Cold-Rolled. F. ASTM A569 - Steel, Carbon (0.15 Maximum, Percent), Hot-Rolled Sheet and Strip, Commercial Quality. G. ASTM B209 - Aluminum and Aluminum-Alloy Sheet and Plate. H. ASTM C14 - Concrete Sewer, Storm Drain, and Culvert Pipe. I. ASTM C443 - Joints for Circular Concrete Sewer and Culvert Pipe, Using Rubber Gaskets. J. NFPA 90A (National Fire Protection Association) - Installation of Air Conditioning and Ventilating Systems. K. NFPA 90B (National Fire Protection Association) - Installation of Warm Air Heating and Air Conditioning Systems. February 2009 Page 1 of 10 2017 FDG Section 23 31 00

L. NFPA 96 (National Fire Protection Association) - Installation of Equipment for the Removal of Smoke and Grease-Laden Vapors from Commercial Cooking Equipment. M. SMACNA (Sheet Metal Air Conditioning Contractors National Association) HVAC Air Duct Leakage Test Manual. N. SMACNA (Sheet Metal Air Conditioning Contractors National Association) HVAC Duct Construction Standards - Metal and Flexible. O. SMACNA (Sheet Metal Air Conditioning Contractors National Association) Fibrous Glass Duct Construction Standards. P. UL 181 (Underwriters Laboratories, Inc.) - Factory-Made Air Ducts and Connectors. 1.4 PERFORMANCE REQUIREMENTS A. No variation of duct configuration or sizes other than those of equivalent or lower loss coefficient is permitted except by written permission. When a rectangular or round duct shape is specified and there is no mention of alternate shape use then only shape specified shall be installed unless written permission is first obtained from responsible Stanford Facilities engineer. When alternate shape /configuration is permitted the replacement will have same or lower friction loss as the one originally specified. This will be measured per ASHRAE guidelines. When duct of one material is specified the alternate material can only be used with written permission from responsible engineer. B. Locations and routing shall be selected in such a way that ducts will not interfere with any access door, hatch or equipment. Duct shall not be installed in a way that it will be stepped on by maintenance personnel. In a situation where this is not possible provide cat walk over the duct. 1.5 SUBMITTALS A. Section 01 33 00 - Submittal Procedures: Submittal procedures B. Shop Drawings: Indicate duct fittings, gages, sizes, welds, and configuration for all systems. Submit shop drawings for approval before fabrication. C. Product Data: Submit data for duct materials, duct liner, duct connectors and other duct accessories.. If internal duct liner is specified it shall be of approved type, none fiber shedding and permanently secured to duct. D. Test Reports: Provide pressure tests. Include date, section tested, test pressure, and leakage rate, following SMACNA HVAC Air Duct Leakage Test Manual. February 2009 Page 2 of 10 2017 FDG Section 23 31 00

E. Manufacturer's Installation Instructions: Submit special procedures for glass fiber ducts. F. Manufacturer's Certificate: Certify that installation of glass fiber ductwork meet or exceed specified requirements. Glass fiber duct or flexible duct shall be used only if approved for the project. 1.6 CLOSEOUT SUBMITTALS A. Section 01 77 00 Closeout Procedures: Closeout procedures. B. Project Record Documents: Record actual locations of ducts, sizes, and duct fittings. Record changes in fitting location and type. Show additional fittings used. Flexible ducts shall be insulated type unless used for exhaust air where permitted by codes. Insulation shall be fiber glass with factory assembled outer vapor barrier. All material shall be fire retardant. 1.7 QUALITY ASSURANCE A. Perform work in accordance with SMACNA - HVAC Duct Construction Standards - Metal and flexible. B. Construct ductwork to NFPA 90A, NFPA 90B and NFPA 96 standards. C. Maintain one copy of each document on site. 1.8 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience. B. Installer: Company specializing in performing work of this section with minimum three years documented experience. 1.9 ENVIRONMENTAL REQUIREMENTS A. Do not install duct sealant when temperatures are less than those recommended by sealant manufacturers. B. Maintain temperatures during and after installation of duct sealant. 1.10 FIELD MEASUREMENTS A. Verify field measurements prior to fabrication. February 2009 Page 3 of 10 2017 FDG Section 23 31 00

1. Find out clearances are available for duct installation and that ducting will not interfere with maintenance of any existing or new equipment or obstruct any access. PART 2 -PRODUCTS 2.1 DUCT MATERIALS A. Galvanized Steel Ducts: ASTM A525 and ASTM A527 galvanized steel sheet, lockforming quality, having G90 zinc coating in conformance with ASTM A90. B. Steel Ducts: ASTM A366, A569 or A568. C. Aluminum Ducts: ASTM B209; aluminum sheet, alloy 3003-H14. Aluminum Connectors and Bar Stock: Alloy 6061- T6 or of equivalent strength. D. Stainless Steel Ducts: ASTM A167, Type 304 or 316. E. Concrete Ducts: ASTM C14; hub and spigot concrete sewer pipe with ASTM C443 joints, rubber gaskets. F. Fasteners: Rivets, bolts, or sheet metal screws. G. Hanger Rod: ASTM A36; steel or galvanized; threaded both ends, threaded one end, or continuously threaded. 2.2 DUCTWORK FABRICATION A. Fabricate and support in accordance with SMACNA HVAC Duct Construction Standards - Metal and Flexible, and as indicated. Provide duct material, gages, reinforcing, and sealing for operating pressures indicated. Seams shall be formed and assembled with proper dimension and proportion for tight and secure fit-up. Longitudinal seems shall be either Double Corner Seam (Slide Lock Seam) or Pittsburgh Seam with Pocket depth of 3/8 minimum. B. For round ducts, use spiral seam, butt weld or lapped & seam welded. C. Transverse joints shall be flange type with gaskets, Ductmate or approved equal or capped flanged type, drive slip with reinforcement. The sheet metal ends shall be brought up between 2 vertical sides of the angles ½ inch high before ended. All bolts with flanged joints must be 5/16 minimum dia. at 6 maximum spacing. For higher pressure joints must be spot welded, riveted or bolted to duct wall at 6 max. spacing centers beginning and ending with fasteners at corners. All flanged joints shall have sheet metal cap. Seal all joints with SMACNA approved water tight sealant. February 2009 Page 4 of 10 2017 FDG Section 23 31 00

D. Construct T's, bends, and elbows with minimum radius 1-1/2 times centerline duct width. Where not possible and where rectangular elbows are used, provide airfoil turning vanes. Where acoustical lining is indicated, provide turning vanes of perforated metal with glass fiber insulation. Elbows, vaned elbows, branch connections, transitions, splitters, etc. shall conform to Section II, SMACNA LPDCS. Test holes shall be airtight and noncorrosive with screw cap and gasket. All elbows shall have inside radius not less than the width of the duct in direction of the curve. Full duct cross section areas shall be maintained through out the transition E. Increase duct sizes gradually, not exceeding 15 degrees divergence wherever possible; maximum 30 degrees divergence upstream of equipment and 45 degrees convergence downstream. F. Fabricate continuously welded round and oval duct fittings two gages heavier than duct gages indicated in SMACNA Standard. Minimum 4-inch cemented slip joint, brazed or electric welded. Prime coat welded joints. Use flexible ducts to connect rigid ducts to outlets or terminals in locations accessible for service only. Flexible ducts shall have no plastic exposed to either the inside or outside surface of the duct core. Flame test 25 maximum and smoke developed 50 maximum. Maximum length of each connecting flex duct shall not exceed 8 ft. G. Provide standard 45-degree lateral wye takeoffs unless otherwise indicated where 90-degree conical tee connections may be used. H. Flexible Ducts 1. Two ply vinyl film supported by helical wound spring steel wire. a. Pressure Rating: 10 inches wg positive and 1.0 inches wg c. Temperature Range: -10 degrees F to 160 degrees F. d. Attach with three sheet metal screws equally spaced. 2. UL Label, black polymer film supported by helical wound spring steel wire. a. Pressure Rating: 4 inches wg positive and 0.5 inches wg c. Temperature Range: -20 degrees F to 175 degrees F February 2009 Page 5 of 10 2017 FDG Section 23 31 00

3. UL labeled multiple layers of aluminum laminate supported by helical wound spring steel wire. a. Pressure Rating: 10 inches wg positive and 1.0 inches c. Temperature Range: -20 degrees F to 210 degrees F 4. UL 181, Class 1, aluminum laminate and polyester film with latex adhesive supported by helical-wound spring steel wire. a. Pressure Rating: 10 inches wg positive and 1.0 inches wg b. Maximum Velocity: 4000 fpm c. Temperature Range: -20 degrees F to 210 degrees 5. UL 181, Class 0, interlocking spiral of aluminum foil. I. Insulated Flexible Ducts a. Pressure Rating: 8 inches wg positive or b. Maximum Velocity: 5000 fpm c. Temperature Range: -100 degrees F to 432 degrees 1. Two ply vinyl film supported by helical wound spring steel wire; fiberglass insulation; polyethylene or aluminized vapor barrier film. a. Pressure Rating: 10 inches wg positive and 1.0 inches wg c. Temperature Range: -10 degrees F to 160 degrees F. 2. Black polymer film supported by a helical-wound spring steel wire; fiberglass insulation; polyethylene aluminized vapor barrier film. a. Pressure Rating: 4 inches wg positive and 0.5 inches wg c. Temperature Range: -20 degrees F to 175 degrees F February 2009 Page 6 of 10 2017 FDG Section 23 31 00

3. Multiple layers of aluminum laminate supported by helical wound spring steel wire; fiberglass insulation; polyethylene aluminized vapor barrier film. a. Pressure Rating: 10 inches wg positive and 1.0 inches c. Temperature Range: -20 degrees F to 210 degrees F 4. UL 181, Class 1, aluminum laminate and polyester film with latex adhesive supported by helical wound spring steel wire; fiberglass insulation; polyethylene aluminized vapor barrier film. a. Pressure Rating: 10 inches wg positive and 1.0 inches wg b. Maximum Velocity: 4000 fpm c. Temperature Range: -20 degrees F to 210 degrees 5. UL 181, Class 0, interlocking spiral of aluminum foil; fiberglass insulation; polyethylene aluminized vapor barrier film. J. Flat Oval Ducts a. Pressure Rating: 8 inches wg positive or b. Maximum Velocity: 5000 fpm c. Temperature Range: -20 degrees F to 250 degrees F 1. Machine made from round spiral lock-seam duct with light reinforcing corrugations; fittings manufactured of at least two gages heavier metal than duct. K. Double Wall Insulated Flat Oval Ducts 1. Machine made from round spiral lock-seam duct with light reinforcing corrugations, galvanized steel outer wall, 1 inch thick fiberglass insulation, perforated galvanized steel inner wall; fittings manufactured with solid inner wall. L. PVC Coated Steel Ducts 1. UL 181, Class 1, galvanized steel duct coated with polyvinyl chloride plastic, 4 mil thick on both sides. M. Slab Duct Ventilation System February 2009 Page 7 of 10 2017 FDG Section 23 31 00

1. ASTM A527 galvanized steel, corrugated, with support brackets, connecting couplings, elbows, end caps, spin-in-collar, wall discharge head, and soffit discharge head; designed for installation in cast-in-place concrete floor assemblies. N. Double Wall Insulated Round Ducts 1. Round spiral lock-seam duct with galvanized steel outer wall, 1 inch thick fiberglass insulation, galvanized steel inner wall; fitting with solid inner wall. O. Transverse Duct Connection System 2.3 CASINGS 1. SMACNA "E" rated SMACNA "F" rated or SMACNA "J" rated rigidity class connection, interlocking angle and duct edge connection system with sealant, gasket, cleats, and corner clips. A. Fabricate casings in accordance with SMACNA HVAC Duct Construction Standards - Metal and Flexible and construct for operating pressures indicated. B. Mount floor mounted casings on 6-inch high concrete curbs. At floor, rivet panels on 8-inch centers to angles. Where floors are acoustically insulated, provide liner of 18 gage galvanized expanded metal mesh supported at 12 inch centers, turned up 12 inches at sides with sheet metal shields. C. Reinforce access door frames with steel angles tied to horizontal and vertical plenum supporting angles. Install hinged access doors where indicated or required for access to equipment for cleaning and inspection. D. Fabricate acoustic casings with reinforcing turned inward. Provide 16 gage back facing and 22 gage perforated front facing with 3/32 inch diameter holes on 5/32 inch centers. Construct panels 3 inches thick packed with 4.5 lb./cu ft minimum glass fiber media, on inverted channels of 16 gage. 2.4 BURIED UNDERGROUND DUCTS A. Buried ducts may be concrete encased sheet metal or PVC jacketed sheet metal, fiberglass reinforced plastic or concrete as indicated. B. Fabricate metal ductwork in accordance with SMACNA Low Pressure Duct Construction Standards, except as indicated. Fabricate using two gages heavier material than indicated for 2 inch wg pressure class. February 2009 Page 8 of 10 2017 FDG Section 23 31 00

2.5 KITCHEN HOOD EXHAUST DUCTWORK A. Fabricate in accordance with SMACNA HVAC Duct Construction Standards - Metal and Flexible and NFPA 96. B. Construct of 18 gage stainless steel, using continuous external welded joints welded by a Certified Welder. PART 3 -EXECUTION 3.1 EXAMINATION A. Verify sizes of equipment connections before fabricating transitions. 3.2 INSTALLATION A. Install and seal ducts in accordance with SMACNA HVAC Duct Construction Standards - Metal and Flexible. B. During construction provide temporary closures of metal or taped polyethylene on open ductwork to prevent construction dust from entering ductwork system. C. Use crimp joints with or without bead or beaded sleeve couplings for joining round duct sizes 8 inch and smaller. Use (3) #8 sheet metal screws and duct sealer. D. Use double nuts and lock washers on threaded rod supports. E. Slope underground ducts to plenums or low pump out points at l:500. Provide access doors for inspection. F. Paint buried metal ductwork without factory jacket with one coat and seams and joints with additional coat of asphalt base protective coating. G. Connect flexible ducts to metal ducts with draw bands. H. Set plenum doors 6 to 12 inches above floor. Arrange door swing so that fan static pressure holds door in closed position. I. Provide residue traps in kitchen hood exhaust ducts at base of vertical risers with provisions for clean out. Use stainless steel for ductwork exposed to view and stainless steel or carbon steel for ducts where concealed. J. Duct supports, unless specified otherwise elsewhere, shall be per SMACNA and seismic supports to be installed for Seismic Zone IV gravity forces for horizontal and vertical movement. February 2009 Page 9 of 10 2017 FDG Section 23 31 00

3.3 INTERFACE WITH OTHER PRODUCTS A. Provide openings in ductwork where required to accommodate thermometers and controllers. Provide Pitot tube openings where required for testing of systems, complete with metal can with spring device or screw to ensure against air leakage. Where openings are provided in insulated ductwork, install insulation material inside a metal ring. B. Connect diffusers or light troffer boots to low pressure ducts directly or with 5 feet maximum length of flexible duct held in place with strap or clamp, per design. C. Connect terminal units to supply ducts directly or with five foot maximum length of flexible duct, per design. Do not use flexible duct to change direction. 3.4 CLEANING A. Section 01 77 00 Closeout Procedures: Final cleaning. B. Clean duct system and force air at high velocity through duct to remove accumulated dust. To obtain sufficient air, clean half the system at a time. Protect equipment that may be harmed by excessive dirt with temporary filters, or bypass during cleaning. C. Clean duct systems with high power vacuum machines. Protect equipment that may be harmed by excessive dirt with filters, or bypass during leaning. Provide adequate access into ductwork for cleaning purposes. END OF SECTION February 2009 Page 10 of 10 2017 FDG Section 23 31 00