Seismic Analysis of Monolithic Coupling Beams of Symmetrical Coupled Shear Wall System

Similar documents
MODELLING OF SHEAR WALLS FOR NON-LINEAR AND PUSH OVER ANALYSIS OF TALL BUILDINGS

Earthquake-Resistant Coupling Beams without Diagonal Reinforcement

Modeling of Shear Walls for Nonlinear and Pushover Analysis of Tall Buildings

STRUCTURAL APPLICATIONS OF A REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTION MODEL FOR EARTHQUAKE LOADING

Seismic Performance of Residential Buildings with Staggered Walls

Implementation of High-Performance Fiber Reinforced Concrete Coupling Beams in High-Rise Core-Wall Structures

Exploring the Implication of Multi-plastic Hinge Design Concept of Structural Walls in Dual Systems

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING

Application of Buckling Restrained Braces in a 50-Storey Building

REINFORCED CONCRETE WALL BOUNDARY ELEMENT LONGITUDINAL REINFORCING TERMINATION

Seismic Behaviour of RC Shear Walls

A Comparative Study on Non-Linear Analysis of Frame with and without Structural Wall System

PUSHOVER ANALYSIS OF A 19 STORY CONCRETE SHEAR WALL BUILDING

Pushover Analysis of Reinforced Concrete Structures with Coupled Shear Wall and Moment Frame. *Yungon Kim 1)

Earthquake-resistant fibre-reinforced concrete coupling beams without diagonal bars

Basic quantities of earthquake engineering. Strength Stiffness - Ductility

The International Conference on Earthquake Engineering and Seismology. Naveed Anwar. ICEES April 2011 NUST, Islamabad Pakistan

Truss Analysis for Evaluating the Behavior of Reinforced Concrete Moment-Resisting Frames with Poorly Reinforcing Details

PUSHOVER ANALYSIS FOR PERFORMANCE BASED-SEISMIC DESIGN OF RC FRAMES WITH SHEAR WALLS

Design Example 2 Reinforced Concrete Wall with Coupling Beams

Modelling of RC moment resisting frames with precast-prestressed flooring system

Seismic Detailing of RC Structures (IS: )

LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS. Qiang SHEN Graduate Research Assistant. Yahya C. KURAMA Assistant Professor

In-plane testing of precast concrete wall panels with grouted sleeve

DESIGN OF HIGH-RISE CORE-WALL BUILDINGS: A CANADIAN PERSPECTIVE

Seismic Performance and Modeling of Post-Tensioned, Precast Concrete Shear Walls

EXPERIMENTAL INVESTIGATION ON THE INTERACTION OF REINFORCED CONCRETE FRAMES WITH PRECAST-PRESTRESSED CONCRETE FLOOR SYSTEMS

SEISMIC VULNERABILITY OF EXISTING RC BUILDINGS IN INDIA

Office Building-G. Thesis Proposal. Carl Hubben. Structural Option. Advisor: Dr. Ali Memari

SEISMIC DESIGN OF STRUCTURE

Interaction between ductile RC perimeter frames and floor slabs containing precast units

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

Seismic Design Principles for RC Structures

Seismic Behavior and Detailing of High-Performance Fiber- Reinforced Concrete Coupling Beams and Coupled Wall Systems

Lateral Force-Resisting Capacities of Reduced Web-Section Beams: FEM Simulations

Chapter 2 Notation and Terminology

CE 6071 Structural Dynamics and Earthquake Engineering UNIT -5 2 MARKS

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

Tests of R/C Beam-Column Joint with Variant Boundary Conditions and Irregular Details on Anchorage of Beam Bars

Reinforced Concrete Coupling Beams Part I: Testing

EFFECTS OF INTERACTION BETWEEN JOINT SHEAR AND BOND STRENGTH ON THE ELAST-PLASTIC BEHAVIOR OF R/C BEAM-COLUMN JOINTS

APPLICATIONS OF STRESS FIELDS TO ASSESS THE BEHAVIOR AND STRENGTH OF COUPLING BEAMS SUBJECTED TO SEISMIC ACTIONS

Effect of web reinforcement on shear strength of shallow wide beams

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

OPTIMUM LOCATION OF RC SHEAR WALL FOR A FIVE STOREY SYMMETRICAL FRAMED STRUCTURE FOR EFFICIENT SEISMIC DESIGN USING PUSHOVER ANALYSIS

Numerical study of shear wall behavior coupled with HPFRCC beam and diagonal reinforcements

Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units.

SEISMIC FORCE RESISTING MECHANISM OF THE MULTI-STORY PRECAST CONCRETE SHEAR WALL SUPPORTED ON PILES

10NCEE REINFO FROM ABSTRACT. detailing without. end. For. 5 Lecturer, Ferzli, J. High-

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

SEISMIC BEHAVIOR OF RCS BEAM-COLUMN-SLAB SUBASSEMBLIES DESIGNED FOLLOWING A CONNECTION DEFORMATION-BASED CAPACITY DESIGN APPROACH

PEER Tall Building Seismic Design Guidelines

INELASTIC SEISMIC PERFORMANCE OF RC TALL PIERS WITH HOLLOW SECTION

Case Study: Challenges of a Single-layer Reticulated Dome

22. DESIGN OF STEEL BRACED FRAMES Eccentrically Braced Steel Frames

Engr. Thaung Htut Aung M. Eng. Asian Institute of Technology Deputy Project Director, AIT Consulting

CHAPTER 1: INTRODUCTION

Displacement-Based Seismic Analysis of A Mixed Structural System

VERIFICATION OF A REINFORCED CONCRETE COLUMN COMPUTER MODEL UNDER UNIAXIAL AND BIAXIAL BENDING LOADING CONDITIONS

Performance-Based Seismic Evaluation of Wind-Impacted Tall Buildings

Encased Beam with Variable Upper Steel Flange Position

Pushover Analysis Of RCC Building With Soft Storey At Different Levels.

Modeling of Coupled Nonlinear Shear and Flexural Responses in Medium-Rise RC Walls

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure

Index terms Diagrid, Nonlinear Static Analysis, SAP 2000.

Available at ISSN

Comparative Study and Seismic Analysis of a Multistorey Steel Building

Lateral Force Resisting Mechanism of a Multi-story Shear Wall and Peripheral Members

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress

Hyperstatic (Secondary) Actions In Prestressing and Their Computation

CUREe-Kajima Flat Plate 1 Kang/Wallace

Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower

User Elements Developed for the Nonlinear Dynamic Analysis of Reinforced Concrete Structures

PERFORMANCE-BASED PLASTIC DESIGN AND ENERGY-BASED EVALUATION OF SEISMIC RESISTANT RC MOMENT FRAME

SEISMIC VULNERABILITY OF REINFORCED CONCRETE BRIDGE COLUMNS IN CANADA

SEISMIC-FORCE-RESISTING MECHANISMS OF MULTI-STORY STRUCTURAL WALLS SUPPORTED ON PILES ABSTRACT

An Investigation on Bracing Configuration Effects on Behavior of Diagonally Braced Frames

Seismic Performance of RC Structural Walls with Slits: Analytical Study

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

EXPERIMENTAL STUDY ON SEISMIC BEHAVIOR OF REINFORCED CONCRETE COLUMNS UNDER CONSTANT AND VARIABLE AXIAL LOADINGS

PERFORMANCE OF EXTERIOR PRECAST UNDER CYCLIC LOADING. R. Vidjeapriya & K.P. Jaya Anna University, Chennai , India 1.

Types : Metal rockers, rollers or slides or merely rubber or laminated rubber, POT - PTFE

CODE RECOMMENDATONS FOR THE ASEISMIC DESIGN OF TALL REINFORCED CONCRETE CHIMNEYS

THE STUDY OF THE OVER STRENGTH FACTOR OF STEEL PLATE SHEAR WALLS BY FINITE ELEMENT METHOD

International Journal of Intellectual Advancements and Research in Engineering Computations

Modeling of Reinforced Concrete Folded Plate Structures for Seismic Evaluation Swatilekha Guha Bodh

NON-LINEAR STRUCTURAL INTEGRITY ANALYSIS

Seismic Performance Of R C Flat-Slab Building Structural Systems

ANALYSIS PROCEDURES FOR PERFORMANCED BASED DESIGN

Seismic performance assessment of reinforced concrete buildings using pushover analysis

International Journal of Engineering and Techniques - Volume 4 Issue 2, Mar Apr 2018

ANALYTICAL STUDY ON FLANGED SHEARWALL UNDER LATERAL LOADING

International Journal of Advance Engineering and Research Development REVISION OF IS: A REVIEW (PART 2)

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

Shear Behavior of Steel Fiber-Reinforced Concrete Beams without Stirrup Reinforcement

3-D FINITE ELEMENT ANALYSIS OF PILE-TO-PILE CAP CONNECTIONS SUBJECTED TO SEISMIC ACTION

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

AN ALTERNATIVE PROCEDURE FOR THE PERFORMANCE ASSESSMENT OF FRP-RETROFITTED RC BUILDINGS USING LUMPED PLASTICITY

Seismic Analysis of RC Shear Wall Frame Buildings with and Without Openings in Shear Wall

Upgrading ductility of RC beam-column connection with high performance FRP laminates

Transcription:

Research Article International Journal of Current Engineering and Technology ISSN 2277-4106 2012 INPRESSCO. All Rights Reserved. Available at http://inpressco.com/category/ijcet Seismic Analysis of Monolithic Coupling Beams of Symmetrical Coupled Shear Wall System Islam M. Ezz EL-Arab a* a Structural Engineering Department, Faculty of Engineering Tanta University, Egypt Accepted 9 Nov.2012, Available online 1Dec. 2012, Vol.2, No.4(Dec. 2012) Abstract It is a well-known fact that the Coupled shear walls are common lateral load-resisting structural components in high-rise Reinforced Concrete (RC) buildings, in which the coupling beams spanning across the openings are normally the most critical elements. Because of architectural considerations and the need to accommodate service voids, these beams are usually of small dimensions and small stiffness as compared with the wall piers in turn. Therefore, the coupling beams often experience very high induced bending and shear stresses under lateral loads. The seismic response of high rise buildings with different height, 10, 20, and 40 stories building are investigated for the three real earthquake excitations, namely; El-Centro, 1940, Northridge, 1994, and Loma prieta, 1989 to analyze and evaluate the effect of the geometry parameters (Span/depth) ratios (1, 2, 4 and 6), and the aspect ratio of the shear wall height to building width effects on the monolithic reinforcement concrete coupling beams of symmetrical coupled shear wall system. Key words: Seismic response; coupling beams; coupled shear wall; high rise building. 1. Introduction 1 Concrete structural walls can be designed as efficient primary lateral load resisting systems particularly suited for ductile response with very good energy dissipation characteristics when regular patterns of openings (e.g., windows, doors, and/or mechanical penetrations) are arranged in a rational pattern (Park, R. and Paulay,T. 1975; Paulay, T.; and Binney, J.R, 1974; Liao, W. C., et al., 2006, Naish, D., et al., 2009) Examples are shown in Fig. 1; where wall piers are interconnected or coupled to each other by beams at the floor and roof levels. Fig. 1 Coupling wall structures. Coupling-beams can be thought of as large-scale shear connectors providing composite action between distinct sub-cores. First yield will often occur in coupling-beams and spread vertically. The span/depth ratio of these beams *Corresponding author: Islam M. Ezz EL-Arab Tel.:+201019998752, Fax: +2 0403351482 is determined by non-structural considerations and usually well into the 'deep beam' range prone to brittle behavior. The desired failure mechanism for a coupled wall structural system involves the formation of plastic hinges in most or all of the coupling beams and also at the base of each wall pier. In this manner, the dissipation of seismic input energy is distributed over the height of the structure (rather than being concentrated in a few stories), similar to the strong column-weak girder design philosophy for ductile moment resisting frames. The behavior and mechanisms of lateral resistance of a single (i.e., uncoupled) wall and two coupled wall systems are compared in Fig. 2. The gravity loads acting on the walls are ignored for this example and it is assumed that a lateral force in the plane of the walls is applied at the top. The base moment resistance, M w,unc of the uncoupled wall Fig. 2(a) is developed in the traditional form by flexural stresses, while axial forces as well as moments are resisted in the coupled shear wall systems Figs. 2(b) and 2(c). When a coupled shear wall system is pushed from left to right under lateral loads, tensile axial forces (N twb ) develop in the left wall pier and compressive axial forces (N cwb ) develop in the right wall pier due to the coupling effect. 2. Judging the efficiency of a coupled shear wall system The magnitude of these wall axial forces is equal to the sum of the shear forces of all the coupling beams at the upper floor and roof levels; and thus, depends on the stiffness and strength of those beams. 345

Fig. 2 Wall systems- (a) Uncoupled wall; (b) Coupled wall with strong beams; and (c) Coupled wall with weak beams. As a result of the axial forces that develop in the walls, the lateral stiffness and strength of a coupled wall system is significantly larger than the combined stiffness and strength of the individual constituent walls (i.e., wall piers) with no coupling. The total base moment, Mw of the coupled wall structures in Figs. 2(b) and 2(c) can be written as: M w =M tw +M cw +N cwb L c (1) Where, M tw and M cw are the base moments in the tension and compression side walls, respectively, N cwb = N twb, and L c is the distance between the centroids of the tension and compression side walls. Then, the contribution of the wall axial forces from coupling to the total lateral resistance of the system can be expressed by the Coupling Degree, CD as: CD= (2) The coupling degree, which can be controlled by changing the strength and stiffness of the beams relative to the wall piers as shown in Figs. 2(b) and 2(c), is an important parameter for the seismic behavior and design of coupled wall structures. Too little coupling (i.e., too small a coupling degree) yields a system with behavior similar to uncoupled walls and the benefits due to coupling are minimal. Too much coupling (i.e., too large a coupling degree) will add excessive stiffness to the system, causing the coupled walls to perform as a single pierced wall with little or no energy dissipation provided by the beams, and will result in large axial forces in the foundation. The desirable range for the amount of coupling lies in between these two extremes and should be selected properly in seismic design as investigated by (El-Tawil et al., 2002). Although CD reflects a true judgment to the behavior of the coupled shear wall, it is a post analysis result which requires full analysis of the system. In other wards it is worth to have a pre-analysis coefficient depends only on the geometric characteristics of the coupled system of walls. This coefficient can simply be used to eliminate number of trials judge the system or going through to many sophisticated analysis procedure and calculations. In this paper the authors suggest two factors depend on the geometric configuration of the coupled shear wall system (constitute walls and coupling beams) and defined as follows: Stiffness Coefficient (K f ) = (3) Inertia Coefficient (I f ) = (4) Where: K b : Stiffness of each individual coupling beam acts as a beam fixed at both ends = K w : Stiffness of each individual wall acts as a cantilever subjected to concentrated load at the top of the building = I w : Second moment of inertia of each individual wall I gross : Second moment of inertia of each gross wall considering the overall dimensions of the system (i.e. considering the system as a single solid wall without any openings) Both K f and I f are dimension less factors that reflects the geometric configuration of the system. K f accounts for the geometric parameters of the system in the vertical direction such as beams depth, building height and number of coupling beams. On the other side I f accounts for the 346

Fig. 3 Diagonally oriented reinforcement for deep coupling beams spacing between walls and the width of the building which is the geometric parameters in the horizontal direction. Combining both together to produce Coupling Index (CI) as a dimension less pre-analysis coefficient depends on the geometric configuration of the coupled shear wall system and defined as follows: CI = K f x I f (5) An analytical discussion for the preceding factors and coefficients is presented in section 5 of this paper. More over some correlations between these factors and the induced forces in the beams and some tips for design are discussed also. 3. Behavior of cast-in-place concrete coupling beams Indeed coupling beam behaves as any laterally loaded element where load transfer mechanism governs the behavior and the failure mode of the element. In general reinforced concrete bending members (RC beams) are classified according their shear-span/depth ratio (a/h) into four categories as it was mentioned in (ACI 318M- 05,2005; Saatcioglu, M., et al., 1987), 1) deep (a/h 1); 2) short (1< a/h 2.5); 3) slender (2.5 < a/h 6); and 4) very slender (6 < a/h), where (a/h) is the shear span to depth ratio. Very slender beams fail in flexure, while slender beams without any stirrups experience diagonal tension failure. Short beams without any stirrups fail in either shear-tension (i.e. principal tensile stress exceeds allowable) or shear-compression (i.e. principal compression stress exceeds allowable) before their flexural capacity is reached. On the other hand, load transfer of deep beams without web reinforcement is carried out by tied-arch action. The most common mode of failure in deep beams is anchorage failure at the end of the tension tie combined with dowel splitting. For coupling beam, direct loads have no significant effect in the same time beam internal forces are induced mainly due to coupling action. According it is reasonable to consider that the shear span is the total length of the beam (i.e. a = L b ) and this can be only considered for coupling beams which governed mainly by coupling action. On the other side, (ACI 318R-08, 2008) identified a sharp threshold (L b /h = 4) to distinguish between shear and bending failure modes. According to ACI-318 requirements; coupling beams with aspect ratio, (L b /h) 4, have to satisfy the requirements of flexural members of Special Moment Frames (SMF). While coupling beams with aspect ratio, (L b /h) < 4, shall be permitted to be reinforced with two intersecting groups of diagonally placed bars symmetrical about the mid-span. Each diagonal element consists of a cage of at least four longitudinal bars confined with transverse reinforcement as shown in Fig. 3. From all the above it could be concluded that there are four main stations (L b /h) = 1, 2.5, 4 and 6. These stations control the behavior of the coupling beam and significantly affect the overall efficiency of the system. In this paper these stations are adopted to be the main parameter of the research as illustrated in details in the next section. 4. Case study The results of induced forces in the shear walls as well as shear force distributions in coupling beams are compared by a Finite element 3D nonlinear modeling regular building provided with symmetrical coupled shear walls. These walls are subjected to three real earthquakes excitations, (El-Centro, 1940, Northridge, 1994, and Loma prieta, 1989). Fig. 4 presents the response spectrum and 347

Spectral Acceleration (g) 1.3 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 El-Centro,1940 Northridge, 1994 Lomaprieta, 1989 Mean 0 1 2 3 4 5 Time Period, (sec) Fig. 4 The response spectrum curves and mean for three real earthquakes. mean response spectrum for these earthquakes, respectively. 7.0 5.8 5.0 D w =4.0 L b =1.8 (H/B). In other words (H/B) varied (3.06, 6.12 and 12.24) based on n (10, 20 and 40) respectively. Note that the breadth of coupling beam is equal to the corresponding wall thickness in all cases. Also it is assumed that young`s modulus of the used concrete E c = 27 GPa and young`s modulus of steel E s =200 GPa. The case study geometry description has been given in Figs.5 and 6. The main geometry parameters corresponding to the various coupling beam clear span to depth ratio (L b /h) are shown in Table 1 and Figs. 7 and 8. In the current case study the opening width to the total length of the coupling system ratio (W open /B) = 18.4%. Therefore the corresponding I f (as defined in Eqn 4) for this system is 13.6%. This value is a characteristic value for the system used to determine the CI factor as defined in Eqn 6. CI = 0.184 x K f (6) 7.0 9.0 9.0 Fig. 5 Plan view of coupled shear wall building system The dimensions are length of wall L w = 4.0 m, Length of beam L b =1.8 m. Therefore the total length of the coupling system B = 9.8m. The depth of beam h will be varied based on (L b /h) as shown in Table 1, total wall height H= n (floor number) x 3.0 m (floor height); Three wall heights were adopted based on number of floors [n=10, 20, and 40], and wall thickness t w = 200, 400-200, and 800-400- 200mm; respectively. In order to generalize the study, building height is reflect in terms of aspect ratio of the coupling system Fig. 6 Section elevation of coupled shear walls 348

Coupling Index (CI) X 10-3 Stiffness Coefficient (Kf) X 10-3 1600 1400 1200 H/B= 3.06 H/B= 6.12 H/B= 12.24 1000 800 600 400 200 0 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 Fig. 7 Stiffness coefficient (Kf) versus coupling beam span to depth () ratio. 200 180 160 H/B= 3.06 H/B= 6.12 H/B= 12.24 140 120 100 80 60 40 20 0 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 Fig. 8 Coupling index (CI) versus coupling beam span to depth () ratio. Table 1: Geometric parameters and factors that were used in the parametric study. Coupling beam aspect ratio (L b /h) Coupling beam depth (h) (mm) Stiffness coefficient (Kf) x10-3 Coupling Index (CI) x 10-3 H/B= 3.06 H/B= 6.12 H/B= 12.24 H/B= 3.06 H/B= 6.12 H/B= 12.24 1.0 1800 84.38 337.50 1350.00 11.475 45.899 183.597 2.5 720 5.40 21.60 86.40 0.734 2.938 11.750 4.0 450 1.32 5.27 21.09 0.179 0.717 2.869 6.0 300 0.39 1.56 6.25 0.053 0.212 0.850 349

5. Modeling of monotonic cast-in-suite concrete coupled wall systems As shown in Fig. 9, previous researches (Lequesne, R. D., et al., 2010; Parra-Montesinos, G. J., et al., 2010; Fintel, M. and Ghosh, S., 1982; Wallace, J., 2007, Weldon, B. and Kurama, Y., 2006.), has often adopted an equivalent frame analogy for the nonlinear inelastic hysteretic modeling and analysis of coupled wall structural systems. The properties of the wall piers and the beams are concentrated at the cetroid of each member. In the analytical model, rigid end zones (or kinematic constraints) are typically necessary to model where the coupling beams frame into the walls. Rigid end zones may also be needed in the wall piers depending on the stiffness of the coupling beams. It is emphasized that the validity of the frame analogy used to model the behavior of coupled wall structures can vary considerably depending on the stiffnesses assumed for the members and the lengths of the rigid end zones. Furthermore, nonlinear shear deformations in deep coupling beams and the axial elongation and shortening of the tension and compression side wall piers due to axial-flexural interaction cannot be represented using frame analogy,( Park, H. and Eom, T., 2007). Base on the above mentioned analog model, the paper presents a 3-D finite element model (FEM) for the whole and 12 present a perspective view of 3-D finite element model for 10, 20, 40 stories buildings, respectively. Fig. 10 Perspective view for 3-D finite element model for 10 stories building. Fig. 11 Perspective view for 3-D finite element model for 20 stories building. Fig. 9 Equivalent frame analytical models, as presented by M. Fintel, and S. Ghosh (1982). building is adopted to simulate the behavior of the predefined case study to take into consideration the elongation and shortening of the tension and compression side wall piers which failed in the simulation for frame analogy. In the FEM walls and slabs are modeled using fournodded shell element, while columns and beams are modeled as two nodded frame elements. Coupling beam was modeled as a shell element to ensure joint connectivity and to account for shear deformations in the coupling beam. Walls and coupling beams are defined as piers and spandrels respectively in order to simplify extracting the induced straining actions as calculated at the centroid of each member of these members. Figs. 10, 11, The cracked behavior of shear walls and other objects are modeled in ETABS (Nonlinear Ver.9.7.1, 2010), by using property modifiers to adjust their stiffness. ACI-318, recommendations for (EI) modifiers are correlated with either I 22 or I 33 for beams and columns, both M 11 and M 22 for slabs and either f 11 or f 22 for walls. Default settings align shear walls such that their 1-axis is horizontal and their 2-axis is vertical. As a result, the flexural modifier (EI) is applied to f 22 for wall piers and f 11 for spandrels (i.e. coupling beams). No recommendation is made for shear. Fig. 12 Perspective view for 3-D finite element model for 40 stories building. 350

Coupling Degree (CD) Coupling Degree (CD) 86% 84% 82% 80% 78% 76% 74% 72% 10 Floors 20 Floors 40 Floors 1 2 3 4 5 6 Fig. 13 Coupling degree (CD) versus beam (span/depth) ratio under El-Centro, 1940 earthquake 86% 84% 82% 80% 78% 76% 74% 72% 10 Floors 20 Floors 40 Floors 1 2 3 4 5 6 Fig. 14 Coupling degree (CD) versus beam (span/depth) ratio under Northridge, 1994 earthquake.. 6. Discussion of analysis outputs of finite element 3-d model Induced Normal force in the individual shear wall Induced Bending moment in the individual shear wall In order to assess the behavior of the coupled shear wall and the influence of the size of the coupling beam on the system, the following parameters are selected to be studied and discussed in this section: Coupling Degree (CD) Induced shear force in the coupling beam Building drift 6.1 Coupling degree Figs. 13, 14, and 15 present the coupling degree (CD) percentage versus to beam (span/depth), (L b /h) ratio for different buildings stories numbers 10, 20, and 40, respectively. The seismic analysis for these cases was 351

Coupling Degree (CD) Coupling Degree (CD) 86% 84% 82% 80% 78% 76% 74% 72% 10 Floors 20 Floors 40 Floors 1 2 3 4 5 6 Fig. 15 Coupling degree (CD) versus beam (span/depth) ratio under Loma prieta, 1989 earthquake 86% 84% 82% 80% 78% 76% 74% = 1.0 = 2.0 = 4.0 = 6.0 72% 10 Floors 20 Floors 30 Floors 40 Floors Fig. 16 Coupling Degree (CD) versus number of building stories. done under different real earthquakes El-Centro 1940, Northridge, 1994, and Loma prieta, 1989. Fig. 16 presents the same relation between the CD versus to different building stories number of different coupling beam (span/depth) ratio in trial to expect the optimum value of beam (span/depth) with high coupling degree percentage. All the above mentioned three figures have the same trend, where the Coupling degree is inversely proportional to the beam stiffness. The efficiency of the coupled shear wall systems increases by the increase of the slenderness ratio (H/B) of the building system until a certain value (in this study until slenderness of 6.12. i.e. 20 stories building, as it was cleared in Fig. 16) after this value the system 352

Height (m) 120 10 FLOORS BUILDING 20 FLOORS BUILDING 40 FLOORS BUILDING 114 108 102 96 90 84 ( = 1.0) 78 ( = 2.0) 72 ( = 4.0) 66 ( = 6.0) 60 54 48 42 36 30 24 18 12 6 0 0% 10% 20% 30% 40% 50% Vb/V 0% 10% 20% 30% 40% 50% Vb/V 0% 10% 20% 30% 40% 50% Vb/V Fig. 17 Coupling shear ratio (Vb/V) versus building height. showed much lower efficiency. To conclude there is an optimum slenderness ratio for coupling beam system depends on the dimensioning of the system and door openings size and location.otherwise, the coupling shear wall as lateral resistance system of seismic load will be not sufficient to improve the performance of building system and may be it will be necessary to adding additional system to resist lateral load of building depend on the building slenderness ratio (H/B). 6.2 Induced shear force in the coupling beam In this study and in order to generalize the concept, induced shear for in the coupling beam (V b ) is proportioned to the applied base shear of the building (V). As shown in Fig. 17, coupling beam exhibits the maximum shear at the second floor. For the current case study the maximum (V b /V) is 45%. It is worth to note that the maximum ratio of (V b /V) do not affected by the slenderness of the building system, in other words maximum (V b /V) is constant for a particular coupling beam system whatever it s height where in the current case study the opining with to the total length of coupling system ratio (W open /B) has a constant percent for all cases. 6.3 Building drift 353

Wall normal force to base shear ratio (NWALL/V) Building drift (mm/m) 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 10 Floors 20 Floors 40 Floors 1 2 3 4 5 6 Fig. 18 Building drift versus beam span-to-depth ratio for Elcentro, 1940. 6.00 5.00 4.00 3.00 2.00 1.00 10 Floors 20 Floors 40 Floors 0.00 1 2 3 4 5 6 Fig. 19 Wall normal force to base shear ratio versus beam span-to-depth ratio for Elcentro, 1940. In order to generalize the concept, the term building drift is defined as the ratio between lateral displacements at top divided by the total height of the building. Fig. 18 presents the building drift ratio versus to coupling beam span to depth ratio (L b /h) for different building height under seismic analysis. For short buildings (in this study 10 stories building), coupling beam slightly enhances building drift. On the other hand it does not enhance building drift for medium and high rise buildings (in these study 20 and 40 stories, respectively); which can be explained based on the aspect ratio between shear wall heights values to the coupled shear wall width (H/B). In the short building the (H/B) ratio was less than 4.0 but for the medium and high rise buildings increase to 6.12 and 12.44 based on the study assumption as shown in Table 1. 6.4 Induced Normal force in the individual shear wall Induced normal force in the individual wall (N w ) is proportioned to the applied base shear of the building (V). As shown in Fig. 19, the induced normal force is much higher that applied base shear force. In the current study the induced normal force is ranging from 3 to 6 times the base shear. In the same time it is important to note that the capacity of the individual wall is much higher in case of normal force than shear force. So it is beneficial to make a 354

Wall bending moment to base moment ratio (Mwall/M) 14.0% 12.0% 10.0% 8.0% 6.0% 4.0% 2.0% 10 Floors 20 Floors 40 Floors 0.0% 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 Fig. 20 Wall bending moment to base moment ratio versus beam span-to-depth ratio for Elcentro, 1940. system that resist lateral loads by the minimum of axial resistance of the members. The induced normal force in the individual wall is directly proportional to the beam size. As the efficiency of the coupled shear wall systems increases by the increase of the slenderness ratio (H/B) of the system until a certain value, the induced normal force to base shear ratio also increased in the same manner until it reaches an optimum value at a critical slenderness ratio after that this ratio of the induced normal force to base shear started to decrease. The optimum value of normal force and the critical slenderness ratio for coupling beam system varies from system to another depending on the dimensioning of the system and door openings size and location. 6.5 Induced Bending moment in the individual shear wall In order to generalize the concept, induced bending moment in the individual wall (M w ) is proportioned to the applied base moment of the building (M). As shown in Fig. 20, the induced bending moment is ranging from 8% to 12% the base moment. The induced bending moment in the individual wall is inversely proportional to the beam size. As the efficiency of the coupled shear wall systems increases by the increase of the slenderness ratio (H/B) of the system until a certain value, the induced bending moment in the individual wall to base moment ratio also decreased until it reaches a minimum value at a critical slenderness ratio after that this ratio of the induced bending moment to base moment started to increase again. The minimum value of induced bending moment in the individual wall and the critical slenderness ratio for coupling beam system varies from system to another depending on the dimensioning of the system and door openings size and location. Conclusion The seismic response of high rise buildings with different height, 10, 20, and 40 stories building are investigated for the three real earthquake excitations, to analyze and evaluate the effect of the geometry parameters (Span/depth) ratios (1, 2, 4 and 6), and the aspect ratio of the shear wall height to coupled shear wall width (H/B) effects on the monolithic reinforcement concrete coupling beams of symmetrical coupled shear wall system. The main value points can be summarized in the following points: 1- There is an optimum slenderness ratio for coupling beam system depends on the dimensioning of the system and door openings size and location. 2- The maximum ratio of (V b /V) ratio does not affected by the slenderness of the system. Where, the coupling beam exhibits the maximum shear force at the second floor level. The maximum (V b /V) is 45%. It is worth to note that the maximum ratio of (V b /V) does not affected by the slenderness of the building system. 3- For short buildings, coupling beam slightly enhances building drift. On the other hand it does not enhance building drift for medium and high rise buildings. Building drift affected by the slenderness of the wall building height to the coupled shear wall width (H/B) ratio. 4- The induced normal force in the individual wall is directly proportional to the beam size. Also, the induced normal force is ranging from 3 to 6 times the base shear. In the same time it is important to note that the capacity of the individual wall is much higher in case of normal force 355

than shear force. So it is beneficial to make a system that resist lateral loads by the minimum of axial resistance of the members. The optimum value of normal force and the critical slenderness ratio for coupling beam system varies from system to another depending on the dimensioning of the system and door openings size and location. 5- The induced bending moment in the individual wall is inversely proportional to the beam span to beam depth ratio (L b /h). 6- The coupling shear wall as a lateral resistance system of seismic load will be not sufficient to improve the performance of building system and may be it will be necessary to adding additional resistance lateral load for building system depend on the building slenderness ratio (H/B). In other wards it is worth to have a pre-analysis coefficient depends only on the geometric characteristics of the coupled system of walls. This coefficient can simply be used to eliminate number of trials judge the system or going through to many sophisticated analysis procedure and calculations. References ACI Committee 318(2005), Building Code Requirements for Structural Concrete (ACI 318M-05) and Commentary (ACI 318RM-05), American Concrete Institute, Farmington Hills, MI. ACI Committee 318 (2008), Building Code Requirements for Structural Concrete (ACI 318-05) and Commentary (ACI 318R-08), American Concrete Institute, Farmington Hills, MI. S. El-Tawil, C. Kuenzli and M. Hassan (2002), Pushover of Hybrid Coupled Walls I: Design and Modeling, Journal of Structural Engineering, Vol. 128, No. 10, pp. 1271-1281. ETABS, Nonlinear version 9.7.1 (2010), Computers and structures, Inc. 1995 University Ave. Berkeley, CA 94704, web: www.csiberkeley.com, M. Fintel, and S. Ghosh (1982), Case Study of Seismic Design of a 16 Storey Coupled Wall Structure Using Inelastic Dynamic Analysis, ACI Structural Journal, American Concrete Institute, Vol. 79, No. 3, pp. 171-179, May-June 1982. Coupling Beams With High-Performance Fiber Reinforced R. D. Lequesne, M. Setkit, G. J. Parra-Montesinos, and J. K. Wight (2010),Seismic Detailing and Behavior of Concrete, Antoine E. Naaman Symposium Four decades of progress in prestressed concrete, fiber reinforced concrete, and thin laminate composites, SP-272, American Concrete Institute, Farmington Hills, MI, 14 pp 205-222. W. C. Liao, S. H. Chao, S. Y. Park, and A. E. Naaman (2006), Self-Consolidating High Performance Fiber Reinforced Concrete (SCHPFRC) Preliminary Investigation, Report No. UMCEE 06-02, University of Michigan, Ann Arbor, MI, 68 pp.130-139 D. Naish, J.W. Wallace, J.A.Fry, and R. Klemencic (2009), Reinforced concrete link beams: alternative details for improved construction, UCLA-SGEL Report 2009-06, Structural & Geotechnical Engineering Laboratory, University of California at Los Angeles, pp. 103-110 H. Park, and T. Eom (2007), Truss Model for Nonlinear Analysis of RC Members Subject to Cyclic Loading, Journal of Structural Engineering, American Society of Civil Engineers, Vol. 133, No. 10, pp. 1351-1363. R. Park, and T. Paulay, Reinforced Concrete Structures, John Wiley & Sons, New York, 1975. G. J. Parra-Montesinos, J. K. Wight, and M. Setkit (2010), Earthquake-Resistant Coupling Beams without Diagonal Reinforcement, Concrete International, 32(12), pp. 36-40. T. Paulay, and J.R. Binney (1974), Diagonally Reinforced Coupling Beams, Special Publication SP-42, American Concrete Institute, Detroit, Michigan, pp. 579-598 M. Saatcioglu, A. Derecho, and W. Corley (1987), Parametric Study of Earthquake-Resistant Coupled Walls, Journal of Structural Engineering, American Society of Civil Engineers, Vol. 113, No. 1, pp. 141-157. J. Wallace (2007), Modeling Issues for Tall Reinforced Concrete Core Wall Buildings, The Structural Design of Tall and Special Buildings, Vol. 16, pp. 615-632 B. Weldon, and Y. Kurama (2006), Post-tensioned Precast Coupling Beam Systems, 8 National Conference on Earthquake Engineering, San Francisco, CA, April 18-22, pp.10-16. 356