EVALUATION OF STANDARD SOLAR COMBI PLUS SYSTEMS FOR SMALL SCALE APPLICATIONS

Similar documents
3rd International Conference Solar Air-Conditioning Palermo 2009

Identification of Standard System Configurations

IEE Solar Combi + WP3 Virtual Case Studies

IEE Solar Combi + WP3 Virtual Case Studies

SorTech package solution description

Description and Visual Representation of Most Promising Markets

SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

Innovative Solar thermal systems for heating and cooling

DESIGN, INSTALLATION AND OPTIMIZATION OF TWO SMALL SCALE SOLAR HEATING AND COOLING SYSTEMS

Influence of the control strategy on the heat rejection potential and electricity consumption of air-to-water condensers for solar cooling systems

Solar Heating and Cooling & Solar Air-Conditioning

EVASOLK. Evaluation of Solar Cooling in Comparison to Reference Technologies

Inventaire des installations de climatisation solaires en Europe Inventory of solar cooling installations in Europe

Solar Combi+ Alexander Thür, Charlotta Winkler. Kick Off Meeting 27/9-2007, Bolzano. Workplan for: WP 6: Dissemination and Communication

Content. State of the Art in Solar Cooling. Solar cooling technology developments. Market developments & barriers

Experiences from design studies, simulation studies and installations

Solar Air-Conditioning Systems in small - medium scale applications

SolarCoolingOpt Austrian R&D project

New developed solar thermal systems for heating and cooling Budapest, 16 th April 2009 Tsekouras Panagiotis Mech. Engineer NTUA Centre for Renewable

New Technologies and Opportunities for Solar Thermal Applications

Solares Kühlen Technische und wirtschaftliche Grundlagen Absorptionskälte und Adsorptionskälte

Solar thermal heating systems in European Union

Solar Thermal Application in Industry

Potential of Solar Process Heat

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Control strategies study of a complete solar assisted air conditioning system in an office building using TRNSYS.

Status and perspective of solar cooling in Europe

Solar Combisystem European Overview of installed Systems Altener Contract Number: /C/00-002/2000

Development of a technology roadmap for solar thermal cooling in Austria

Contribution of Solar Heating and Cooling to a 100% Renewable Energy System

Modeling and analyzing solar cooling systems in Polysun

Research Priorities in Solar Cooling and Refrigeration Systems

State of the art for solar thermal or PV cooling and refrigeration

The Sun from SOLution Solartechnik GmbH Solar domestic hot water, heating, cooling and electricity DERBI International Conference 11th-13th of June

OPERATIONAL EXPERIENCES OF A TDHP SYSTEM FOR SOLAR COOLING AND HEATING OF A CANTEEN

The Solar Thermal Potential in Europe

Solar Roadmaps and Implementation Plans The global perspective

1. Solar-thermal systems: current state of the sector and anticipated developments

The Sun from SOLution Solartechnik GmbH Solar domestic hot water, heating, cooling and electricity DERBI International Conference 11th-13th of June

Daniel MUGNIER Madrid, 11/04/2016

Investigations of thermal self-sufficient Residential Buildings with Solar Energy Systems

Heat Pumps Applications and the Potential for Lebanon

ST-ESCOs Project. ST-ESCOs. Energy in Upper Austria NEWSLETTER. Demand for speedy legislation on renewable energy for heating and cooling

Potential of Solar Thermal in Europe. Werner Weiss, AEE Institute for Sustainable Technologies Peter Biermayr, Vienna University of Technology

SOLAR ENERGY USED FOR HEATING AND COOLING SYSTEMS

The IEA Solar Heating and Cooling Technology Collaboration Program

Passive Houses Worlswide: International Developments

Australian Solar Cooling Interest Group (ausscig) Conference DHW/COOLING HYBRID STRATEGY FOR SOLAR COOLING:

Residential buildings retrofit: the role of solar technologies

Experimentation and simulation of a small-scale adsorption cooling system in temperate climate

Solar Heat in Industrial Processes It s applicability in South Africa Solar thermal power seminar

MESSIB Multi-source Energy Storage System Integrated in Buildings

SolarKeymark-II. Large open EU market for solar thermal products. Deliverable D 18

Part of Thermally driven heat pumps for heating and cooling. Ed.: Annett Kühn Berlin: Universitätsverlag der TU Berlin, 2013 ISBN

Clean Cooling. Cooling in the EU Challenges and Policies April 2018 Dubai - UAE. the new Frontier Market for UAE & the GCC region

Solares Heizen und Kühlen IEA SHC Task 38 Ergebnisse

Solar Thermal Systems Status Technologies - Perspectives. Dr. Bernd Eikmeier Bremer Energie Institut

Available online at ScienceDirect. Energy Procedia 48 (2014 )

Commercialising of thermal powered refrigeration

Analysis of applicability of PLPE method for the test of a Solar Cooling system.

Available online at ScienceDirect. Energy Procedia 101 (2016 )

PV for Cooling & Heating. Daniel MUGNIER Hamburg, 14/09/2015

Making a difference to your environment. Suncool conference LIFE11 ENV/SE/ SUNCOOL

Heat pump market development and their contribution potential towards energy savings and climate protection

Simulation And Optimization of a Solar Absorption Cooling System Using Evacuated Tube Collectors

Simposio Internacional Oportunidades de Eficiencia Energética en el Sector Agro-Alimentario. 7 de Octubre Centro Español San Fernando

Trane Engineering News Multi-pipe unit for heating and cooling buildings

Solar systems for heating and cooling of buildings

Advanced Solar Thermal (AST) SOLID Energy, Inc.

Innovative Systems for Solar Air Conditioning of Buildings

Executive Summary. Final July Introduction

5 th GENERATION DHC NETWORKS

Demonstration of the TESSe2b system in residential houses in Austria, Cyprus and Spain and their energy analysis

Heating and cooling Europe with solar

Identified technologies for the InfraSUN pilot plant

Daniel MUGNIER Karsltad, 09/10/2014

EXPERIMENTATION AND MODELLING OF A SMALL-SCALE ADSORPTION COOLING SYSTEM IN TEMPERATE CLIMATE. July 22, 2013

Solar Energy Overview

Solar Air-Conditioning Systems in small - medium scale applications

Solar Heat Worldwide

Solar air-conditioning

Solar Cooling Technologies for Southern Climates - A System Comparison

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Challenges for Price Reduction of Solar Thermal Systems

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

Smart energy grid using local energy resources

Zafer URE.

Potential areas of industrial interest relevant for cross-cutting KETs in the Energy domain

TASK 53. New generation solar cooling & heating systems (PV or solar thermally driven systems) Task description and Work plan November 2013

BSRIA Air Conditioning Worldwide Market Intelligence

Performance analysis of a new single effect hot water absorption chiller system

NSX ANNOUNCEMENT. Public Letter to Shareholder

State of the art of new generation commercially available products

Heat rejection control strategy for stationary tests of discontinuous thermally driven chillers

IEA SOLAR HEATING & COOLING PROGRAMME

Solar Thermal Market & support schemes in Germany. German Solar Industry Association (BSW-Solar)

Buildings and Environment Energy Systems

Solar Heat Worldwide

ScienceDirect. Application of a novel, vacuum-insulated solar collector for heating and cooling

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

Transcription:

EVALUATION OF STANDARD SOLAR COMBI PLUS SYSTEMS FOR SMALL SCALE APPLICATIONS R. Fedrizzi 1, G. Franchini 2, D. Mugnier 3, P. N. Melograno 1, M. Theofilidi 4, A. Thuer 5, B. Nienborg 6, L. Koch 6, R. Fernandez 7, A. Troi 1, W. Sparber 1 1: EURAC Research, Viale Druso 1, 39100 Bolzano, Italy, email: roberto.fedrizzi@eurac.edu 2: Università degli Studi di Bergamo, Viale Marconi 5, 24044 Dalmine (BG), Italy 3: Tecsol, 105 rue Alfred Kastler, 66004 Perpignan, France 4: CRES, 19th km Marathonos Ave.,190 09 Pikermi, Greece 5: AEE INTEC, Feldgasse 19, 8200 Gleisdorf, Austria 6: Fraunhofer ISE, Heidenhofstr. 2, 79110 Freiburg, Germany 7: Ikerlan Technological Research Centre, Juan de la Cierva 1, 01510 Miñano, Spain ABSTRACT Small sorption chillers are available on the market for the installation in solar assisted domestic hot water and space heating plants. Their use in office and residential buildings could potentially lead to a significant mitigation of the primary energy consumption and therefore of the CO 2 production for air conditioning. However, the economical sustainability of this technology shows significant hurdles due to the costs of the investment and of the plant s design. The latter could be reduced if standard system configurations were considered for installation, as it actually happens in the case of ordinary domestic hot water plants. The presented work concerns with the analysis of the methods and the results elaborated within the IEE programme SolarCombi+ project. The aim of this project is to take small scale sorption chillers and identify and promote standardised systems for combined solar water, space heating and cooling production up to cooling loads of 20kW. Accelerating and smoothing the market entry of those systems, the project contributes to achieving energy policy goals of the EU and supports the diffusion of a technology where a group of European enterprises has a favourable starting point for international leadership. INTRODUCTION The air conditioning market both for heating and cooling is expanding rapidly in Europe as a result of increasing comfort expectations; almost 49% of the total energy consumption in Europe is employed for buildings heating and cooling [1]. About 90TWh of electrical energy are used for summer air conditioning in EU15, the biggest markets being Spain (33TWh), Italy (27TWh) and France (10TWh) [2]. For this reason much effort in the EU energy policy [3] is devoted to the implementation of renewable energies for the management of the buildings thermal loads [4]. Already today, solar thermal energy for domestic hot water (DHW) preparation and for space heating is a developed technology with a high penetration rate in some countries, as Germany and Austria. Solar driven sorption chillers were up to now only manufactured in the high power range (>100 kw cold ). Today, machines with rated power between 5 and Figure 1 Solar combi+ system explanatory scheme.

30kW cold are available to be included in solar combi+ systems (see Figure 1) for small applications, which make up for the major part of heating and a constantly growing part of cooling demand. Costs of the investment and lack of experience of designers and installers are the most important barriers for a broad diffusion of solar combi+ applications. The assessment of standard system configurations might reduce considerably the design effort for single applications and is the basis for the development of package solutions possibly manufactured at a large scale level. The presented paper concerns with the analysis of the methods and the results elaborated, within the IEE programme SolarCombi+ project, in the process of evaluation of standard solar combi+ configurations. Aim of the process is the definition of a reduced number of system configurations, which can be promoted and applied similarly to the standardized systems for domestic hot water production, which work reasonably well in common applications and are independent of the specific products considered. METHOD The study started from an extensive campaign of numerical simulations carried out in TRNSYS on a basic plant configuration detected through market and technical analysis. Each industrial partner of the consortium opted for one of the two plant layouts represented in Figure 2, which suites best the working features of its chiller. Figure 2 Solar combi+ layouts selected by the industrial partners. Within the basic systems, a number of parameters were varied; so called fixed, semi-fixed and free parameters were identified and a range of values was selected for each one. As fixed parameters of the analysis were taken: Geographical location of the solar combi+ plant Building in which the solar combi+ plant is installed Chiller brand. Three locations were chosen, representative of different climatic areas between the south and mid Europe, with fairly different needs in terms of heating and cooling demands [5, 6]; in particular the climatic conditions in Naples (south Italy), Toulouse (south France) and Strasbourg were considered. Three small scale applications with different specific heating and cooling requirements were also selected: one office and two residential buildings (see Table 1). The size of the building was adapted to the Reference Power of the specific chiller Power (power delivered at the rated generator temperature and condenser/evaporator temperatures given by the heat rejection/distribution technologies) to allow a fair comparison of the chillers performance.

Simulations were performed for each of the five commercial chillers studied. The three parameters above were named fixed since they cannot be settled by the manufacturer/designer. On the contrary technology related figures might be negotiated to some extent. Within this category were considered: Collectors (flat plate and evacuated tube collectors) Heat rejection system s (wet cooling tower, dry air cooler and hybrid cooler) Chilled/Warm water distribution system (fan coils and chilled ceiling). Fan coils were simulated with regard to all the applications, while chilled ceilings were only considered in case of residential building. Office Avg. consumption residential Low consumption residential Heating Cooling Heating Cooling Heating Cooling Strasbourg 69 34 Toulouse 34 50 46 6 25 6 Naples 9 81 21 18 9 18 Table 1 Thermal loads relative to office application, average and low energy consumption residential buildings. Thermal loads for given application change as a function of the climatic conditions Finally, collectors area and warm water storage volume were considered as free parameters of the analysis. Even in this case however, constraints were decided related to economical and technical performance of the solar combi+ system: Collectors area between 2 and 5 m²/kw Ref. Pow. cold Warm water storage volume between 25 and 75 l/m 2 collectors area The collectors area was scaled with regard to the Reference of the single chiller. A large number of performance, environmental and economical figures were evaluated for about 2500 simulations. Among those, four were evaluated as the most interesting for the assessment of the standard system configurations: Total solar fraction Total electrical efficiency Primary energy saved per year Primary energy saved per year and per collectors area The first two are technical parameters. The total solar fraction accounts for the fraction of the total DHW, heating and cooling needs covered through the solar energy utilization. The total electric efficiency is the average ratio of the total thermal loads (for heating, cooling and domestic hot water) and the electrical consumption of the system (comprising chiller and solar circuits pumps, heat rejection system fans, etc). The primary energy saved is an environmental figure comparing energy needs of the conventional and the renewable solution, while the last two join techno-economical aspects to environmental ones. The primary energy saved per collectors area accounts for the expense, in terms of system size, of the environmental benefit. Each of the four parameters mentioned above was used to detect a best system layout: for each set of fixed parameters, the system configurations that maximize/minimize the given figure were determined in terms of semi-fixed and free parameters. A set of good solutions

that allow for system environmental-technical performance close to the best was also established: the two solutions closest to the best for each set of fixed parameters were taken. This was done since the best environmental-technical solution might not be the most effective from the point of view of marketing-cost aspects. RESULTS Table 2 shows results of the simulations run with regard to a low energy consumption residential building placed in Naples and setup with chilled ceilings. Naples was selected for the discussion as the most severe environment in terms of cooling needs, due to its high summer temperatures and latent loads induced by the proximity of the sea. The table allows comparing the system performance if semi-fixed parameters are exchanged: flat plate (FP) and evacuated tubes (ET) collectors, wet cooling tower (WCT) and hybrid cooler (HC, dry air cooler + sprinkled water) are taken into consideration. Representative average values for the chillers investigated are presented. More data than the ones relative to the standard configurations selected (the three performing best) are reported to show the potential improvements achievable through well-designed systems. Coll. H.R. Coll. area [m2/kw] Storage Vol. [l/m2] TOT. Solar Fraction Electrical Efficiency [ ] Relative PE Saved Specific PE Saved [(kwh/year)/m2] Specific CO 2 Saved [(kg/year)/m2] ET WCT 4.27 50 70 20.3 38 168 65 ET WCT 4.27 75 73 20.2 45 196 72 1 ET WCT 5.00 25 67 20.7 34 136 51 ET WCT 5.00 50 76 20.4 49 184 65 ET WCT 5.00 75 80 20.3 56 209 71 FP WCT 4.27 50 64 20.1 29 128 46 FP WCT 4.27 75 68 20.0 36 157 46 2 FP WCT 5.00 25 61 20.3 23 86 54 FP WCT 5.00 50 70 20.0 39 146 54 FP WCT 5.00 75 75 20.1 47 175 54 ET HC 4.27 50 68 20.2 35 153 38 ET HC 4.27 75 71 20.0 39 175 36 3 ET HC 5.00 25 68 20.6 35 127 41 ET HC 5.00 50 71 20.4 38 147 41 ET HC 5.00 75 77 20.3 50 192 43 Table 2 Solar combi+ systems performance related to a low energy consumption residential building placed in Naples. Chilled ceilings used. Once the collectors area and the heat rejection system are set, the effect of changing collectors, from ET to FP (dataset 1 and 2), is a slight decrease of the solar energy utilization ability of the system (solar fraction decreases of around 5-10%). A much larger cut is noticed in terms of primary energy saved; reductions between 15 and 30% are obtained, depending on the warm water storage size. This is mostly due to the lower water temperatures that might be reached with the flat plates technology and that affect both summer (chilling) and winter system performance. Moreover, the storage size becomes more and more important as far as the collectors return temperature drops. Comparing the heat rejection systems (datasets 1 and 3), the effect of using a technology that is less effective than the wet cooling tower is a decrease of the performance of the entire plant. The drop of primary energy saved (6-8%) is not so significant as in the case of the solar

collectors change; the trend is due on one side to the lower chillers overall performance when coupled with this kind of heat exchanger and on the other side to an higher electrical energy consumption for driving its fans. Table 3 reports the results for the same chiller and application (Naples, low energy consuming residential building); in this case, the building is setup with fan coils as a distribution system for the chilled and heating water. Again a reduction of performance with regard to the first set of data shown in Table 2 is noticed (compare dataset 1 and 4), with a large effect mostly on the primary energy saved: decreases between 40-50% are reported on average. In general chilled ceilings are better suited since higher distribution temperatures (13-18 C) are employed and higher thermal inertia is obtained with respect to fan coil systems. On the other side, in some cases (e.g. refurbished buildings) fan coils are the only useful way for distributing heating and cooling. Coll. H.R. Coll. area [m2/kw] Storage Vol. [l/m2] TOT. Solar Fraction Electrical Efficiency Relative PE Saved Specific PE Saved [(kwh/year)/m2] ET WCT 4.27 50 63 14.6 13 37 ET WCT 4.27 75 68 14.9 22 37 4 ET WCT 5.00 25 65 15.1 18 42 ET WCT 5.00 50 69 15.0 22 44 ET WCT 5.00 75 75 15.0 35 44 Table 3 - Solar combi+ systems performance related to a low energy consumption residential building placed in Naples. Fan coils used. The last column of Table 2 and Table 3 represents the saved CO 2 per collectors area: CO2 savings between 36 and 72 kg/year/m 2. In absolute terms, the CO 2 emissions avoided range between 2 and 4 tons/year in all studied cases. If one bears in mind that the residential building considered could be used by a 4 people family (0.5 to 1 tons CO 2 spared each), and that in a typical European city every inhabitant is responsible for around 8 to 10 tons of CO 2 emitted per year (transport and economical activities are considered in this figure), it can be noticed that the large scale diffusion of solar combi+ systems would lead to a significant reduction of the CO 2 emissions and therefore of the primary energy used. If only heating, cooling and DHW needs are regarded, primary energy savings between about 30 and 60% are reported in case of well-designed solar combi+ systems. The comparison of the four datasets shows that the chilled ceiling, wet cooling tower and evacuated tubes collectors configuration allows the solar combi+ system to perform best from a purely technical and environmental point of view. This outcome is applicable to all chillers investigated, leading to a best standard system configuration, chiller independent. The simulations for the office application show the same result even when fan coils are considered for the distribution (wet cooling tower and evacuated tubes should be preferred). Moreover, the best solutions are obtained when the biggest collectors area and storage volume are used. A change of the trend would be obtained for bigger system size (collectors area larger than 7m 2 /kw); nevertheless, the highest collectors areas were not investigated since they are not suitable for small applications. When the solutions close to the best are regarded (i.e. the good ones), the effect of both exchanging technologies and varying components size is not clearly chiller and application independent. This aspect and cost issues raw investment costs are considered together with cost of primary energy saved when planning a system - leave a certain freedom to the

manufacturers when designing a standard system configuration. For example, in the case reported, the best technical solution is also the best economical one, if only the cost per saved primary energy is regarded. However, solutions that provide somewhat lower overall effectiveness (e.g. systems setup with a dry cooler or flat plats) might result also in significantly lower system costs. CONCLUSIONS The above discussion shows that standard configurations for solar combi+ systems might be determined, mostly chiller independent, which can be promoted and applied similarly to the standard systems for DHW with reasonably good results in typical/average cases. The technologies and sizes of the components to be selected are clearly stated from a environmental-technical point of view. However, considerations about investment and costs per primary energy saved might lead to standard configurations that differ to some extent from the ones showed before. Although well designed solar driven solar combi+ systems allow major reductions of primary energy usage and CO2 emissions, their cost is still significantly higher than the one of traditional air conditioning systems. The gap could be easily bridged through national funding schemes for the duration of the market startup phase and consequently to economy of scale. ACKNOWLEDGEMENTS Acknowledgements go to the EACI that funded the Solar Combi+ project under IEE program (contract N : EIE/07/158/SI2.466793). REFERENCES 1. European Solar Thermal Technology Platform Federation (ESTTP): Solar Heating and Cooling for a Sustainable Energy Future in Europe. 2. J. Adnot et al.: Energy Efficiency and Certification of Central Air Conditioners (EECCAC), Final Report Vol. 1. Armines, Paris, 2003. 3. Final report on the Green Paper "Towards a European strategy for the security of energy supply", COM(2002) 321 final, Brussels, 26.6.2002. 4. Energy for the Future: Renewable Sources of Energy - White Paper for a Community Strategy and Action Plan COM(97)599 final (26/11/1997). 5. ECOHEATCOOL WP1: The European Heat Market. 6. ECOHEATCOOL WP2: The European Cold Market.