An experimental investigation of a passive chilled beam system in subtropical

Similar documents
IMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS

Individually controlled localized chilled beam in conjunction with chilled ceiling: Part 1 Physical environment

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Human response to individually controlled micro environment generated with localized chilled beam

Ventilation for Changeover-Bypass VAV Systems

On the performance of confluent jets ventilation system in office space

The Pennsylvania State University. The Graduate School. Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

Proceedings of Clima 2007 WellBeing Indoors

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE

DISPLACEMENT VENTILATION

Designing Air-Distribution Systems To Maximize Comfort

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY

Federation of European Heating, Ventilation and Air-conditioning Associations

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Sustainable Chilled Beam Design

Monitoring of Advanced Facades and Environmental Systems

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Taking flexibility into account in designing beam systems

A FIELD STUDY OF A VENTILATED BEAM SYSTEM FEASIBILITY IN THE TROPICAL CLIMATE

Performance of radiant cooling ceiling combined with personalized ventilation in an office room: identification of thermal conditions

ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY

Assessment of thermal comfort near a glazed exterior wall

Experimental investigation on condensation of vapor in the presence of non-condensable gas on a vertical tube

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS

1 Introduction. Trondheim, October 26-28, of the moisture interactions between

Individually controlled localized chilled beam in conjunction with chilled ceiling: Part 2 Human response

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Postprint.

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

Displacement ventilation General layout specifications

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

Information paper 17. Prepared by: David Clark. book:

Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

Air distribution and temperature control in classrooms

For all those with the ability to influence the design, layout or indoor air quality of buildings

Energy and indoor temperature consequences of adaptive thermal comfort standards

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Modelling Approaches for Displacement Ventilation in Offices

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Potential of natural ventilation in shopping centres

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

Introduction to basics of energy efficient building design

Thermal comfort study of a hawker center in Singapore

Performance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional Air System

Evaluation methods for indoor environmental quality assessment according to EN15251

Performance of Wall Confluent Jets Ventilation System in School Environment compared with Displacement Ventilation

ON THE ENERGY CONSUMPTION OF HIGH- AND LOW-LEVEL AIR SUPPLIES

Ultimate Performance of Timber Connection with Normal Screws

What simulation can tell us about building tuning

Halton Chilled beams Janne Summanen Halton Oy

The influence of a capture jet on the efficiency of a ventilated ceiling in a commercial kitchen.

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

CFD in Ventilation, case studies from REHVA CFD guidebook

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment

Potential of Natural Ventilation in Shopping Centres Diederichsen, Alice; Friis, Kristina; Brohus, Henrik; Tranholm, Gitte T.

REHVA EUROPEAN GUIDEBOOKS

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

Indoor comfort and air quality in spaces equipped with eco-ventilation systems

The pros and cons of chilled beams

EXPERIMENTAL STUDY OF DIFFUSE CEILING VENTILATION IN A CLASSROOM

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

A DEVELOPMENT OF A HVAC EXPERIMENTAL CHAMBER AND ITS NUMERICAL MODELâ ÒNUMERICAL HVAC EXPERIMENTAL CHAMBER,Ó ON A COMPUTER

REAL-LIFE OPERATION OF SOLUS SYSTEM: A FOCUS ON THERMAL COMFORT 11 A P R I L D A N VA K D A G E N

Effect of energy renovation on thermal sensation and comfort

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels

Live Transportation Research and Improvement Initiatives

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

FIELD MEASUREMENT OF A RESIDENTIAL FLOOR COOLING SYSTEM AND EVALUATION OF HUMAN THERMAL COMFORT

Modelling of a steam based Paraboloidal Dish concentrator using the computer source code TRNSYS

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

Floor-Supply Displacement Ventilation in a Small Office

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

Experimental investigation on a ceiling capillary radiant heating system

Analysis of Thermal Comfort Conditions and Actual Energy Efficiency for Different Heating Systems in Test Buildings

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

HOW THE NUMBER AND PLACEMENT OF SENSORS CONTROLLING ROOM AIR DISTRIBUTION SYSTEMS AFFECT ENERGY USE AND COMFORT

Performance Investigation of Building Ventilation System by Calculating Comfort Criteria through HVAC Simulation

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

CAN AIR HEATING ALONE BE USED IN PASSIVE HOUSE OFFICE BUILDING IN COLD CLIMATES? REVIEW OF THE OBTAINED RESULTS

Under-Floor Air Distribution System (UFAD): Energy and Thermal Comfort Analysis

Natural Ventilation in Schools and Commercial Buildings (CPD No. 31) Issue 2 May 2017

Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings

Comparison of airflow and contaminant distributions in rooms with traditional displacement ventilation and under-floor air distribution systems

Indoor Airflow Modeling and Data Assimilation. Hengye Yang Ph.D. Student, LISC Dec. 21, 2018

Transcription:

An experimental inestigation of a passie chilled beam system in subtropical conditions Alex Hole 1, Risto Kosonen 2 1 Arup, Sydney - Australia 2 Halton, Kausala - Finland Corresponding email: alex.hole@arup.com.au risto.kosenen@halton.com SUMMARY Chilled beam systems are effectie in proiding good indoor enironmental quality (IEQ) in an energy efficient manner. Howeer, chilled beam systems are not common in sub-tropical climates where the requested cooling capacity is much higher than in temperate climates. This paper reports the findings of physical testing undertaken on a simulated office enironment when the maximum cooling capacity was 122 W/m². Tests were also undertaken for higher theoretical heat gains (up to 164 W/m²). The mock up test enironment included a 3.6m x 3.6m zone, representing a perimeter zone of an office building in a semi sub-tropical southern hemisphere climate. The purpose of the test was to measure the internal temperature distribution and air elocities for different heat gains and also for changes in internal layout. The test results are referenced to recognised standards for occupant comfort, particularly ISO7730. The conducted measures show that the air elocities in the occupied zone were below 0.25 m/s in all tests and the draft rates were below 20 in nearly all measured points. The location of the workplace also did not hae any effect on the air elocities within the space. This shows that passie beam system, including cooled mechanical entilation, is possible to coer the requested cooling capacity in sub-tropical conditions without any draft. BACKGROUND Chilled Beam Application The application of passie chilled beams in HVAC (Heating Ventilation and Air Conditioning) design for office spaces has been reasonably commonplace in Europe with examples of the application spanning oer the last couple of decades. A common design encompasses a combination of entilation air, distributed by mechanical means to a ceiling (or floor) mounted diffuser, and mechanical cooling ia the passie chilled beam element located aboe a perforated ceiling. The passie beam element (battery type) itself is essentially a series of water tubes with fins attached to increase heat transfer to the air. Cooled water circulates through the beam. Airflow across the beam is drien by the natural buoyancy effects from air cooling through the beam element. Other solutions are actie chilled beams where the room entilation air is integrated into the room unit. This study is focussed on passie chilled beam systems. Historically the majority of the application of passie chilled beams has been confined to certain room load densities (typically 50 to 80 w /m²). This is likely to be a symptom of the actual design loads encountered in such European regions. Much research has been

undertaken in relation to the performance of arious combinations and types of chilled beam products for these load scenarios. Zboril et al [1] inestigated the air distribution for actie beams with internal loads ranging from 50 to 80 w/m². A paper by Fredriksson et al [2] inestigates the effect of the location of internal loads on the airflow and finds that the air plume under the beam can be affected by the placement of internal heat sources. It also identifies that air elocities under the beams can fluctuate. The study does not include the presence of mechanical entilation air. Other research, including information published by Reha [3], recommends benchmark limits of capacity for passie chilled beams for optimum heat loads to 80 W/m² (watts per square metre of floor area) with a maximum of 120 W /m². These reports equate this to a specific chilled beam capacity of <150 W/m (Watts per linear metre of beam) when the beam is in an occupied zone, and up to < 250 W/m when installed in a non occupied zone. These limits hae been established on the basis of air elocities and particularly draft within the space. The guide states that these alues should be used as reference alues and special attention should be gien to room air elocities for higher heat loads. It is noted that these limits are based upon tests with no additional influences from room entilation systems. The performance of battery type passie chilled beam systems, in combination with cooled entilation air and higher internal heat gains has limited research. This is of particular interest in semi tropical climates, including parts of Australia, where internal gains are higher than Europe due primarily to higher ambient temperatures and solar intensity. Perimeter office room sensible design gains can often reach 120 W/m² (or higher), een with relatiely high performing double glazed facades. The application of chilled beam HVAC design for office buildings is gaining popularity in Australia due to its potential of reduced energy consumption in comparison with traditional all-air ariable air olume or constant air olume systems. Local regulation and market expectation is also increasing emphasis on energy efficiency in office building designs. Due to the limited application, the performance of chilled beams for higher heat loads (greater than 80 W/m²) is of great interest. Of course the application of passie chilled beam systems for higher heat load spaces is not limited to spaces with higher fabric loads. Spaces with higher internal gains (e.g. call centres, TV studies etc) could make inference from this study. Thermal Comfort An assessment of thermal comfort includes consideration to a number of influences, which can be measured and quantified. These include Dry bulb temperature, humidity (or moisture), radiant temperatures (exposure) and air elocity (or draft). Much study has been undertaken on the interrelation of these items. This study aims to reference standard ISO 7730 standard (1990) which identifies a basic guideline for thermal comfort. This considers the temperature gradient in the room and also the room air elocities as follows (for summer cooling): Draft rating (): < 20 (for category B space. For category C space this is <25) Vertical air temperature difference: <3 C from foot to head when sitting or standing.

In general terms the differentiation between category B and C relates to the estimated Percentage of People Dissatisfied (PPD), with B targeting less than 10 and C targeting less than 15. For general office type spaces category B is considered the appropriate target. The equation for the determination of draft rating can be found later in this report. In general terms the draft rating takes consideration of both the local air turbulence and dry bulb temperature. METHODS The experiment was conducted at Halton Research Center. A test room (L x W x H = 3.6m x 3.6m x 3.3/2.8m) was used to simulate a real office. In the test room, two passie beams (CPT-105-605-2600/2400) were installed aboe the perforated false ceiling (3195 mm from the floor leel). Three light fittings (each: 2x28 W/T5) and a swirl diffuser (TSR-160) were installed in the false ceiling at the leel of 2800 mm from the floor leel. The gross free area of the ceiling panels was 37 and the perforation holes were 5mm. Close to the window wall, there was arranged an additional opening (300 mm) to improe the buoyancy effect, Fig. 1. Figure 1. Simulated office (workplace layout 1) and the cross-section of the room space. In the basic case of 122 W/m 2, the heat loads are: two computers (260 W), two dummies (150 W), light fittings (168 W), warm window surface (35.0 o C and ~ 600 W) and an electrical foil (400 W) (size of 3.6 m x 1.5 m close to the window) on the floor. The used airflow rate and supply air temperature of the swirl diffuser were 35 L/s (2.7 L/s per m 2 ) and 13 o C. The inlet water temperature of the chilled beams was 15 o C. The requested cooling capacity was arranged by modulating water flow rate of the chilled beams. The room air temperature was in the test cases between 23.5-24.7 o C. Two higher cooling capacity 153 W/m 2 and 164 W/m 2 were also studied. In the case of 153 W/m 2, two extra computers and dummies were installed. The highest cooling capacity (164 W/m 2 ) was arranged from the case of 153 W/m 2 by increasing the heat gain of the dummies. In this study, there was also analyzed the effect of the location of the workplaces on the performance of the passie chilled beam system. One additional case without false ceiling was measured to analyze the effect of the perforated ceiling panels on the air distribution. The studied cooling capacities and office layout cases are shown in Table 1.

Mean air elocity, air temperature and turbulence intensity were measured within the occupied zone at the locations of 0.1m, 0.2m, 0.5m, 1.1m, 1.5m and 1.8m aboe the floor. The measurement grid consists altogether 16 locations (altogether 96 points), Fig. 2. Air flow elocities were measured with elocity sensor type Sensor HT 412 haing accuracy ± 1 of readings. The room air temperature, inlet water temperature, supply and exhaust air temperatures were measured with temperature sensors of type PT100 class A. The water flow rate was measured with Krohne Electromagnetic Flowmeter IFC010 with accuracy less than ± 1 of the readings. The airflow rate was measured with differential pressure transmitter Furness Controls FCO33 with accuracy less than ± 0.5 of the readings. Table 1. Studied heat load and workplace layout cases. Case Room Water flow Heat loads Workplace (WP) layout: air rate (l/s) (W/m 2 ) 1 23.5 0.094 122 1:WP in the middle 2 24.1 0.094 122 2:WP close to the side wall 3 24.0 0.094 122 3:WP close to the window 4 0.094 122 1:WP in the middle (no ceiling 23.4 panels) 5 24.7 0.196 153 1:WP in the middle 6 24.1 0.250 164 1:WP in the middle For measuring of elocity, temperature and turbulence intensity 6-channel low-elocity anemometer HT 400 was used. The used 6 omni-directional elocity probes hae spherical elocity sensor with a diameter of 2 mm, ensuring a fast response. The temperature sensor is shielded against radiation. Instantaneous alues of elocity and temperature are measured simultaneously. Measurements of elocity and temperatures were time aeraged oer 180 s.

Figure 2. Measurement grid of the conducted experiment when workplaces are in the middle. RESULTS In Fig 3, there is presented the measured air elocity, temperature, turbulence intensity and draft rate profiles for test case 1. The measured elocity profile depicts that the air is well mixed oer the whole occupied zone. Een with a heat gain of 122 W/m 2, the maximum air elocity was only 0.20 m/s. Also, the draft rate alues were acceptable leel. Height (m) 1 2 3 4 5 6 1.80 0.09 22.7 41 7 0.07 22.8 41 4 0.06 23.0 45 3 0.06 23.0 60 3 0.07 22.9 46 4 0.09 22.8 53 7 1.50 0.10 22.6 32 8 0.09 22.7 31 6 0.06 22.8 48 3 0.07 22.8 53 4 0.09 22.8 43 7 0.09 22.7 38 7 1.10 0.12 22.6 28 10 0.12 22.6 28 10 0.09 22.6 37 7 0.09 22.7 48 7 0.10 22.7 35 8 0.12 22.7 35 10 0.50 0.09 22.6 39 7 0.13 22.4 33 11 0.12 22.4 35 10 0.12 22.4 35 10 0.11 22.6 40 9 0.10 22.7 45 8 0.20 0.11 22.8 43 10 0.12 22.7 33 10 0.13 22.6 33 11 0.13 22.6 27 11 0.12 22.8 35 10 0.12 22.8 38 10 0.10 0.16 23.1 29 13 0.15 23.0 28 12 0.15 23.0 26 12 0.16 23.0 22 12 0.18 23.2 23 14 0.17 23.2 26 14 Height (m) 7 8 9 1.80 0.15 22.2 40 15 0.10 22.4 41 8 0.11 22.2 40 10 0.14 22.1 46 15 1.50 0.13 22.2 40 12 0.12 22.3 35 11 0.13 22.1 35 12 0.14 22.1 43 14 1.10 0.10 22.5 46 9 0.14 22.3 34 13 0.14 22.1 38 14 0.15 22.1 38 15 0.50 0.13 22.4 38 12 0.19 22.1 22 16 0.17 22.1 30 16 0.16 22.0 33 16 0.20 0.16 22.1 28 15 0.16 22.1 21 13 0.13 22.2 30 11 0.14 22.1 28 12 0.10 0.20 22.1 22 18 0.18 22.1 22 15 0.15 22.2 31 14 0.15 22.1 29 14 10 Height (m) 11 12 13 14 15 16 1.80 0.14 22.0 43 14 0.09 22.0 49 8 0.09 22.3 44 7 0.10 22.2 44 9 0.17 21.8 47 20 0.19 21.8 38 21 1.50 0.12 22.0 47 12 0.10 22.0 36 8 0.08 22.2 46 6 0.13 22.1 45 13 0.15 21.8 40 16 0.15 21.8 43 16 1.10 0.14 22.0 40 14 0.12 22.0 39 11 0.09 22.1 42 7 0.14 22.0 35 13 0.14 21.9 38 14 0.15 21.8 47 17 0.50 0.13 22.0 39 13 0.13 22.1 38 12 0.12 22.1 34 11 0.13 22.2 37 12 0.14 21.9 34 13 0.12 21.9 40 11 0.20 0.09 22.1 42 7 0.09 22.2 39 7 0.10 22.1 38 8 0.11 22.1 34 9 0.11 22.0 42 10 0.09 22.1 41 7 0.10 0.11 22.1 36 10 0.09 22.2 36 7 0.11 22.2 37 10 0.11 22.1 33 9 0.10 22.0 37 8 0.08 22.1 41 6 Figure 3. Measured air elocity, temperature, turbulence intensity and draft rate in case 1.

Changes in office layout did not hae any effect of the performance of the air distribution. This is seen in case 2 &3. The maximum air elocity was 0.20 m/s when the workplaces were located in the middle of the room, close to the side wall or close to the window. Also when the false ceiling was remoed, the air elocities did not increased. In fact, the maximum elocity slightly reduced. When the cooling capacity was increased from 122 W/m 2 to 153-164 W/m 2, the maximum air elocity was increased to alue of 0.23 m/s. Also, the draft rate alues were acceptable leel: only in the couple of points - index was higher than 15. It should be noted that the typical limit of air elocity is set to 0.25 m/s during cooling season. Thus, the studied chilled beam concept fulfills this international standard threshold for the air elocity een when the cooling capacity was ery high 150-160 W/m 2. Table 2. Measured air elocities and draft rate () in the test cases. Case 1 2 3 4 5 6 Heat gain (W/m 2 ) 122 122 122 122 153 164 Workplace location Middle Side Window Middle Middle Middle max 0.20 0.20 0.20 0.17 0.23 0.23 ag 0.12 0.10 0.09 0.12 0.13 0.13 Line number of the max. elocity 7 2 7 9 10 7 max 21 19 20 19 20 20 ag 11 8 8 11 11 11 Number of point > 15 8 2 7 6 16 15 Number of lines > 15 5 1 3 4 7 6 DISCUSSION AND CONCLUSIONS Seeral tests were performed in order to establish the draft and heat gain performance of a mock up passie chilled beam installation under a number of scenarios. In summary these scenarios included: Adjustment of internal heat gains from 120 W/m² through to 164 W/m² (all cases); Adjustment to the internal layout of equipment, desks and people (case 2&3); Adjustment to the water flow rates deliered to the passie chilled beams in order test for increased capacity; Remoal of perforated ceiling (case 4); The results identify that within the range of these tests the draft rate () could be maintained below 20 (with one reading at 21 for case 1) which would indicate compliance with ISO7730 For a category B building. More specifically the following was obsered. The remoal of the perforated ceiling produced minimal difference to the draft and temperature performance for the internal heat gain loads at 120 W/m². Similarly, increasing the internal gains to 164 W/m² (case 6) resulted in broadly equialent performance in terms of draft. At first glance this appears to be in contradiction to established limits of performance for battery type passie beam products. Howeer further reiew indicates that the influence of the mechanically introduced air supply ia swirl outlet diffusers has a profound effect on

the air flow within the space. This can be illustrated by the smoke test demonstrations where it is apparent that the air moement is drien from these diffusers. Similarly, adjustments to the internal layout of equipment produced little effect on the air moement. This could be attributed to the relatiely small load as a percentage of the simulated fabric and lighting gains, which were fixed. In all cases, the whole olume is fully-mixed as demonstrated by the measured elocities and from smoke tests. There is not any location in the occupied zone that exhibited excessiely high elocities. Also the maximum elocity is approximately 2-times higher that aerage elocity in all cases. Temperature distribution across the height of the room in all cases is significantly less than the 3 C target. Again the fully mixed enironment is reason for this. In conclusion it is apparent that the total performance is a combination of the influence of the cooling elements, air diffusion and thermal plumes of heat gains (although in this instance the affect of thermal plume was limited to changes in internal layout, which resulted in negligible affect). Focusing on the performance of a chilled beam element in empty space will not gie the total iew. All elements should be analysed concurrently. In cases where heat gains are high (> 80 W/m²), this is required. Analysis could be undertaken using full-scale mock-up or with CFD simulation. Howeer special attention should be made to the boundary conditions and modelling of heat gains to achiee an accurate result. These tests found that under certain conditions a combination of cooled air supply through swirl outlet diffusers, and battery type passie chilled beams can proide room sensible cooling capacities of 120 W/m² and potentially up to 164 W/m² without exceeding the requirements of ISO7730 for occupant comfort for category B office buildings. It is belieed that the mechanically introduced air supply plays a significant role in the resultant air elocities within the space. The extent of influence of this is likely to be dependant upon the diffuser selection and airflow rate and this should be gien due consideration. The tests presented did not compare different diffuser types so quantifying the effect of this may be the subject of further study. REFERENCES 1. Zhoril, V., Meliko, A., Kosonen, R. (2006). Air flow distribution in rooms with chilled beams. 17th Air-Conditioning and Ventilation Conference. 17 19 May 2006 in Prague. 2. Frediksson J, Sandberg M, Moshfegh B. Experimental inestigation of the elocity field and airflow pattern generated by cooling ceiling beams. Building and Enironment 36 (2001) pp. 891-899 3. Reha. Guidebook no.5. Chilled Beam Cooling. Federation of European Heating and Airconditioning Associations.