Polymer Suspension Insulators 69kV to 765kV

Similar documents
Polymer Station Post Insulators for 69 to 345 kv Applications

Polymer Post Insulators for 46 to 500kV Applications

Transmission Silicone Insulators Line Post 69 kv to 230 kv

INSULATORS NEW. See page J-4 for more information.

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

GROUP A. Polymeric Insulators.

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

Energy Division Insulators

Veri*Lite Deadend, Suspension & Line Post Insulators for 15-69kV Applications

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle.

CS type composite silicone insulators up to 750 kv overhead lines for all pollution of the atmosphere levels

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R

Composite Insulator Components

FOREWORD SCOPE NORMATIVE REFERENCES DEFINITIONS REQUIREMENTS... 4

Polluted Outdoor Insulators Maintenance and Washing

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

Development of Composite Line Spacers for Distribution Lines

8. Hydrophobicity classification guide STRI guide 1.92/1 9. Radio interference characteristics of overhead power lines and high-voltage equipment

United States Department of Agriculture Rural Development Rural Utilities Service. RUS Bulletin 1724E-220

FIJI ELECTRICITY AUTHORITY BIDDING DOCUMENT

General Requirements. Technical Specifications for Insulators of Transmission Lines

GSCH004 Rev /10/2016

Outdoor High Voltage Non-Ceramic Insulators

CHAPTER 2 STRUCTURE AND CRITICAL E-FIELDS

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

SPECIFICATION FOR POLYMER DISC INSULATOR

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Power Systems 2 ELE3015. Lecture 1: Transmission Lines

An Urgent Bulletin from CSA International

COMPOSITE INSULATORS

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

Metal or Plastic Fittings Utilizing an Alternate Material

Specification for Polymer Disc Insulator

Expansion & Deflection Fittings. SOLUTIONS for the Construction Industry

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDERNO. 9/2013 FOR THE SUPPLY OF INSULATORS AND FITTINGS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

Veri*Lite Silicone Rubber Line Post Insulators for 15-72kV Applications

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

IEEE T&D Insulators 101

fire Charcoat Charcoat IC Passive Protection

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

Polymer Cutout Testing Recommendations

33-SDMS-02 SPECIFICATIONS FOR

YARWAY HANCOCK CONTINUOUS BLOWDOWN GLOBE VALVE SERIES 5505

brands you trust. Tufline Lined Ball Valves

Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission overhead lines

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test

PRY-MOULD. High Voltage Accessories for Extruded Cables

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS. Polymer Insulators

Electrical Field Simulation for Different Cases of Polymer Insulators Using FEM

SECTION DETECTABLE GUIDE TACTILES

- Tensile strength of 50,000 psi per ASTM D-638 or 345 Mpa - Notched Izod impact strength of 35 ft-lb/in per ASTM D-256 or 1868 J/M are achieved.

MATERIAL/MANUFACTURER SPECIFICATIONS FOR DISTRIBUTION WATER MAINS AND APPURTENANCES

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SPECIFICATION FOR DISC INSULATORS (Standard Type)

BIDDING DOCUMENT FOR. Supply of Galvanized Steel Tubular Poles, 11KV Polymer Insulators and ACSR Conductors under Saubhagya Scheme

High Strength Epoxy Tested in Accordance with ICC-ES AC308

HARYANA VIDYUT PRASARAN NIGAM LIMITED. TECHNICAL SPECIFICAION FOR POLYMER INSULATOR STRINGS FOR 220KV / 132KV/66KV TRANSMISSION LINES

Table of Contents. Version 1.0. Specifications 2 Technical Specifications 2 Colors and Lumen Count 2. Packaging 6

PART-II. TECHNICAL SPECIFICATIONS FOR 11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator.

ENGINEERING SPECIFICATION EE SPEC

POLYMER HOUSED SURGE ARRESTORS

Soft Seated Butterfly Valves Ductile Iron Wafer Body ANSI/ASME to 6 Sizes

TRANSFORMERS DRY TYPE, OIL FILLED, AMORPHOUS ALLOY CORE. tgood.com. Energy. Fast.

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Data Sheet 110kV TD123II dry type outdoor termination

SECTION FRP GRATING, HANDRAIL, AND SUPPORTS

SECTION 13. A. Extent of Work: The requirements of this section apply to the piping systems specified elsewhere in these specifications.

All definitions are defined according to ANSI/AWWA C

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

Expansion Joint Covers (079513)

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

MECHANICAL TEST FIXTURES

ECONOMIC ANALYSIS OF 400 KV TRANSMISSION TOWERS WITH CROSS ARMS INSULATORS

High Strength Epoxy Tested in Accordance with ICC-ES AC308

ENGINEERING SPECIFICATION PULTRUDED FIBERGLASS GRATING SAFE-T-SPAN HIGH LOAD CAPACITY (47% OPEN AREA) VINYL ESTER. January 24,

ENGINEERING SPECIFICATION. PULTRUDED PEDESTRIAN FIBERGLASS GRATING SAFE-T-SPAN T1210 VINYL ESTER and ISOPHTHALIC. October 25, 2004 Revision 1

Design of MO Surge Arresters with Polymeric Housings

Technical Specification for Outdoor Porcelain Station Post Insulators

Heavy Wall Heat Shrinkable Tubing 5-7. Flame Retardant Heavy Wall Heat Shrinkable Tubing 8. Heat Shrinkable Ends Caps 9

ENGINEERING SPECIFICATION

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

Product Bulletin BPS-102 Revision 2.6 January F l e x B a l l a n d R o t a B a l l J o i n t s

The following document can be provided to an Engineer, Contractor, or Owner to allow them to properly specify MESAN s MXR-KM series Cooling Towers.

TRICON DOUBLE-CON PLUS

C H E M P O S I T E FIBERGLASS REINFORCED

SkyWrap In-line Bypass Ground Wire

Design features - Polymer-housed arresters, PEXLIM

Expansion Joint Covers

Maharashtra State Electricity Distribution Co. Ltd.

D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Valves. MUELLER Tapping Sleeves and Crosses. MUELLER Stainless Steel Tapping Sleeves

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

Applied Materials. The Power of Trust. The Future of Energy.

TECHNICAL SPECIFICATION SECTION- SWITCHYARD ERECTION REVISION -08

CITY OF ODESSA SPECIAL SPECIFICATIONS ITEM 1000 GLASS-FIBER REINFORCED POLYESTER (FRP) REHAB/REPLACEMENT MANHOLE

Mechanical Test Laboratory Price List

Transcription:

CATALOG Polymer Suspension Insulators 69kV to 765kV NGK Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A.

TABLE of CONTENTS Table of Contents... 1 Design Features... 2 Material... 2 Definition of Rating... 2 Standard Material Test... 3 Grading Rings... 4 Adjustments with Grading Rings... 4 Catalog Number System... 5 Configuration of End Fittings... 5 How to select Catalog Number... 6 Shed Profile... 6 25kip SC, SS, SL Shed Series... 7 30kip SC, SS, SL Shed Series... 9 50kip SC, SS, SL Shed Series...11 Extra Long Leakage / 25kip SE Shed Series...13 Extra Long Leakage / 30kip SE Shed Series...14 Extra Long Leakage / 50kip SE Shed Series...15 Standard Leakage / 80kip SN Shed Series...16 Longer Leakage / 80kip SL Shed Series...16 Packing...17 NGK-Locke Polymer Insulators, Inc. is ISO 9001 certified by the British Standards Institutes, BSI. BSI is accredited by NACCA, RAB, and RvC. 1

DESIGN FEATURES Polymer suspension insulators of NGK-Locke Polymer Insulators, Inc. (NLPI) are products on the housing (sheath) or at the weathershed interfaces. Housing is directly vulcanized to the core during compression molding process, providing superior bonding performance. Also, pressure controlled uniform crimping providing superior long-term mechanical performance. HOUSING TO CORE -- Housing and core are and the interface strength between housing and core is higher than the tearing strength of housing itself. SHED PROFILE -- On the basis of contamination level, we can propose best-fit shed profile. (See page 6). Shed profile complies with IEC Pub. 60815 Guide for the selection of insulators in respect of polluted conditions. END FITTING TO CORE -- Crimping process is for each step, minimizing stress concentration. ACOUSTIC EMISSION (AE) DETECTION -- During crimping of end fittings on the core, all the products are checked for possible damage of core by AE detection. HOUSING AND END FITTING INTERFACE (SEALING) -- integral to the housing provides positive contact with the end fittings and RTV (Room Temperature Vulcanized) prevents the ingress of moisture MATERIAL WEATHERSHEDS (SHED) & HOUSING (SHEATH) -- Weathersheds and housing are the same material (100% silicone rubber) before adding fillers. The best mixture of base polymer, fillers, and additive agents achieves excellent contamination, weatherability, anti-tracking, and anti-erosion performance. CORE -- High quality pultruded FRP (Fiberglass Reinforced Plastic) rod is used. The rod is made with good alignment and distribution of fibers within Epoxy resin. END FITTINGS -- High grade forged steel or ductile iron is used. And all ferrous parts, other than stainless steel, are galvanized in accordance with ASTM A153. Cotter key is made from stainless steel. GRADING RINGS -- High grade aluminum alloy is used. DEFINITION OF RATING SPECIFIED MECHANICAL LOAD (SML) -- The SML is a load specified by the manufacturer that has to be verified during a mechanical load test. It forms the basis for selection of an insulator. ROUTINE TEST LOAD (RTL) -- The RTL is a rating equal to 50% of the SML. 2

STANDARD MATERIAL TEST Polymer suspension insulators of NGK-Locke Polymer Insulators, Inc., pass all the requirements of prototype test and design test specified in ANSI C29.11 and ANSI C29.12 and also comply with the following tests. ULTRA-VIOLET TEST -- Samples 4.3 x3.0 x0.08 are subjected to ASTM G53 Standard Practice for Operation Light- and Water- Exposure Apparatus (Fluorescent UV-Condensation Type) for Exposure of Nonmetallic Materials. After checking appearance, including SEM observation, weight loss, receding contact angle, we confirm that the sample passed this test (12,000 hrs) without cracks and blisters. TRACKING AND EROSION (AGING) -- Our polymer insulators pass tracking and erosion test (5,000 hours) specified in IEC Pub. 61109 Annex C. Annex C is cyclic test to simulate natural climate such as rain, fog, ultra-violet, and voltage. Also our polymer insulators pass tracking and wheel test (30,000 cycles) specified in CEA LWIWG-01 and CSA C411.4. NON FLAMMABILITY -- Samples 5 x0.5 x0.12 are subjected to IEC Pub. 60707 flammability test. The samples meet the criteria FV0. Also this test is specified in IEC Pub. 61109. POWER ARC -- Polymer insulators withstand 150kA cycles power arc under applied tension load of 3000 lbs without failure. (Complies with clause 8.2.5 of IEEE 1024) HIGH PRESSURE WASHING -- Polymer insulators are designed to withstand high pressure water washing at 550psi nozzle pressure, nozzle diameter 1/4, and the distance of 10 from the nozzle to polymer insulators. Tracking Wheel Test Aging test under UV conditions 3

GRADING RINGS Grading discs and/or rings are applied to NLPI polymer insulators for higher operating voltages to reduce electrical stress concentration on and within the insulator and to reduce radio and/or television interference. General recommendations of grading ring application are as follows. System Voltage 138 kv and below 161 kv 230 kv 345 kv 500 kv NLPI Top Grading (tower side) None None None ø4 disc ø8 Ring* Rings (Discs) Bottom Application (line side) None ø4 disc ø8 Ring* ø11 Ring ø15 Ring NLPI Insulator Cat# Suffix -- -04-08 -41-85 Grading discs are factory-installed. Field installation is required for grading rings. The clamp part of the NLPI grading ring is designed to ensure correct position mounting only. * : In case of SL and SE sheds, need larger diameter of grading ring such as ø9.5 or ø11. For other combinations of corona ring application please check with factory. ADJUSTMENTS WITH GRADING RING The electrical and physical values shown in the following pages are for the insulators without grading rings or discs. The following table is required if grading rings or discs are used for system voltages of 161 kv and above. System Voltage 161 kv 230 kv 345 kv 500 kv Arcing Distance, inch (mm) -0.8-2.0-2.8-5.5 Adjustment of (-20) (-50) (-70) (-140) tabular values Low Frequency F/O Dry, kv -5-15 -25-50 for 25k, 30k, Low Frequency F/O Wet, kv -5-15 -20-45 50k and 80k Critical Impulse F/O pos., kv -10-30 -45-85 SML insulators Critical Impulse F/O neg., kv -15-30 -45-90 Net Weight, lb (kg) +1 +3.1 +5.4 +14.3 (+0.45) (+1.4) (+2.5) (+6.5) The above adjusted electrical values are just for guidance because of non-linearity of electrical characteristics. 4

CATALOG NUMBER SYSTEM CONFIGURATION OF END FITTINGS 5

HOW TO SELECT CATALOG NUMBER Our catalog number is self-explanatory. Please follow the following general guidance to determine a catalog number. No. Procedures Example (equivalent to ANSI 52-5, 7 bells) 1 To select mechanical rating, SML If rating is 25kip, 251 251-S_- 0- - (refer to page 5) 2 To select Shed Profile on the basis If medium contamination area, 251-SS 0- - of leakage distance. See the shed profile is SS following Shed profile for details. (refer to shed profile in this page) 3 To select Number of Sheds on the If section length is 40 1 /4 (=5 3 /4 251-SS250- - basis of section length x7), number of sheds is 25 (refer to page 7~16) 4 To select configuration of End If socket & ball, -SJ 251-SS250-SJ- Fitting (refer to page 5) 5 To select Grading Ring application If system voltage is 230kV, ring 251-SS250-SJ-08 on the basis of system voltage application is 08 (refer to page 4) SHED PROFILE 6

NGK-Locke Polymer Insulators, Inc. 1609 Diamond Springs Road, Virginia Beach, Virginia 23455, U.S.A. Tel: +1(757) 460-3649 Fax: +1(757) 460-3550 Website: www.ngk-polymer.com Email: info@ngk-polymer.com NGK INSULATORS, LTD. U.S.A. NGK-Locke, Inc. Atlanta Office 1880 West Oak Parkway, Suite 104 Marietta, Georgia 30062, U.S.A. Tel: +1(404) 659-3153 Fax: +1(404) 524-6185 Baltimore Office 2525 Insulator Drive Baltimore, Maryland 21230, U.S.A. Tel: +1(410) 347-1700 Fax: +1(410) 347-1724 Los Angeles Office 21250 Hawthorne Blvd., Suite 500 Torrance, California 90503, U.S.A. Tel: +1(310) 316-3323 Fax: +1(310) 316-3944 Canada NGK Insulators Canada, Ltd. Toronto Office 2700 Matheson Blvd. East, Suite 700 East Tower, Mississauga L4W 4V9, Ontario, Canada Tel: +1(905) 602-1266 Fax: +1(905) 238-8247 Montreal Office 1501, Avenue McGill College Bureau 515 Montreal (Quebec) H3A 3M8, Canada Tel: +1(514) 281-8488 Fax: +1(514) 281-8596 All Other Countries NGK Insulators, LTD Add: 2-56, Suda-cho, Mizuho, Nagoya, 467-8530, Japan Tel: +81-52-875-7511 Fax: +81-52-872-7530 Web: http://www.ngk.co.jp/english/index.html pr-office@ngk.co.jp