Isover Installation Guide

Similar documents
POLTERM MAX PLUS. Non combustible stone wool insulation for ventilated rainscreen cladding and overcladding systems. isover.co.uk


Isover Solutions Guide

PITCHED ROOF SOLUTIONS

HP Partial Fill. Robust, long-lasting protection

TIMBER FRAME HOUSING SOLUTIONS

ISOVER CAVITY WALL INSULATION CWS 36, CWS 34 AND CWS 32 FULL FILL CAVITY WALL SLABS

Fire protection for timber frame & masonry cavity walls

Owens-Corning Building Products (UK) Ltd P O Box 10 St Helens Merseyside WA10 3NS Tel: Fax:

Agrément Certificate 18/5560 website: Products Sheet 1

Why party wall insulation is required

URSA MINERAL WOOL URSA Cavity Batts

Best Prac ce Guide No. 2. (Version 1 April 2015) Design and Installa on guidelines for par al fill cavity wall boards

Separating walls. Countryside Properties, Lock 38, Stoke-on-Trent

Sheathing Board Xtra protection, built in.

K17 Insulated Plasterboard

T-Barrier System. Masonry Applications. Satisfying Fire, Thermal and Acoustic Requirements at the Combined Party Wall and Pitched Roof Junction

Superglass Superwall Cavity Wall Batts Installation Guide - Full-Fill

K8 Cavity Board. Insulation CAVITY WALL INSULATION

T-Barrier System. Timber Frame Applications. Satisfying Fire, Thermal and Acoustic Requirements at the Combined Party Wall and Pitched Roof Junction

Acoustic and thermal insulation solution guide isover.co.uk

June Residential Refurbishment Separating walls

K3 Floorboard. Insulation INSULATION FOR FLOORS

WORK, REST AND PLAY ISOVER MAKES IT POSSIBLE.

K12 Framing Board. Insulation INSULATION FOR USE BEHIND WALL LINING AND FRAMED WALLS

K17 Insulated Plasterboard

K12 Framing Board. Insulation

TCB & PWCB CAVITY BARRIERS Fire Protection for timber/steel frame & masonry cavity walls

K17 Insulated Plasterboard

K15 Rainscreen Board. Insulation INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS

APPROVALS. Jabwall has been approved for this application since 1979, and was the first partial-fill insulation product to gain BBA approval.

SP FIRESTOP SYSTEMS The purpose-made solution for cavity fire stopping

robustdetails E-FC-7 Separating Floor Concrete Separating Floors Concrete E-FC-7

June Non - Residential New Build Partition walls

K3 Floorboard. Insulation INSULATION FOR FLOORS

ROCKWOOL BUILT IN CAVITY WALL INSULATION BATTS ROCKWOOL CAVITY WALL BATT

Cavity closers, fire & acoustic stops Thermo-loc standard cavity closers Thermo-loc plus X and plus C cavity closers Thermo-loc

April Section Party Walls

A Handbook of thermal bridging details incorporating aircrete blocks

SEPTEMBER construction type cavity barriers. SP Firestop Systems. The purpose-made solution for cavity fire stopping

Curved partition and wall lining system

Superior Performance Phenolic Insulation. SR/CW Insulation for Partial Fill Cavity Walls. Walls AS LOW AS 10/4803

robustdetails E-FC-6 Separating Floor Concrete Separating Floors Concrete E-FC-6 SYSTEM INSTALLATION

Insulation for Ventilated Rainscreen Cladding Systems

URSA Cavity Batts URSA GLASSWOOL.

Robust details. Section 5 robust details. Robust Details Limited Davy Avenue Knowlhill Milton Keynes MK5 8NB

Multi-layer Insulation Blanket for Walls

RW SEMI-RIGID AND RIGID SLABS (RWA45, RW3, RW4, RW5 & RW6)

FERMACELL Powerpanel H 2 O for Wet & Moisture affected areas

August 2008: Issue 1. Non - Residential New Build Built - up Metal Walls

Cavity fire barriers. Cavity fire barriers. Fire separation within concealed spaces. C06 Floors and ceilings

Concrete Soffit Direct Fix

Multi-layer Insulation Blanket for

Double Brick Cavity Walls

April Section Cladded Walls

Multi-layer Insulation Blanket for Walls

PIR Insulation XT/CW (T&G) Insulation for Partial Fill Cavity Walls. Walls 08/ /0183

Superior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803

Superior Performance Phenolic Insulation. SR/FB Insulation for Steel and Timber Frame. Walls AS LOW AS 10/4803

Superior Performance PIR Insulation. XO/FB Insulaton for Steel & Timber Frame. Walls 12/4956

Part E robustdetails. robustdetails. January 2018 Update Pack

Superior Performance PIR Insulation XO/FB. Insulaton for Steel & Timber Frame. Walls 12/4956

Soffit Board. Insulation

Multi-layer Insulation Blanket for Walls

Eco-Versal. insulation. Polyisocyanurate (PIR) foam core with aluminium foil composite to both sides BASELINE TOPLINE SLIMLINE

EARTHWOOL RAINSCREEN SLAB INSTALLATION GUIDE

Insulation - Products

Manual for Insulating Using the Seamless Thermal Insulation System

Product. Regulations. Rockwool Ltd Pencoed Bridgend CF35 6NY Tel: Fax: Agrément Certificate No 93/2884 Second issue*

HOW TO: INSULATE YOUR HOME AND UNDERSTAND U-VALUES GTEC THERMAL BOARD WITH PLASTERBOARD

ROCKWOOL BUILT IN CAVITY WALL INSULATION BATTS ROCKWOOL CAVITY WALL BATT

GypLyner. GypLyner. Metal framed wall lining system. All our systems are covered by SpecSure when using genuine Gyproc and Isover products.


A Handbook of thermal bridging details incorporating aircrete blocks

Product Information Sheet

GUARANTEED ASPHALT LIMITED

ROCKSILK DRITHERM CAVITY SLAB Isolation de murs à double paroi Kerndämmung. Regulations B3(4) C2(a)(b) L1(a)(i) L2(a)

Construction Standards PAGE

Phenolic foam thermal insulation products for buildings and building services end use applications

TECHNICAL. Cavity Wall Partial - Fill Insulation. Stylite.

Gypwall systems. incorporating Gyproc Habito


June Residential New Build Timber Frame Walls

Acoustray perimeter cavity stops

1. Section 04300: Concrete Masonry Units

Contents P/ 3. Ensuring Optimal Results P/ 4. Roof Insulation SF40 P/ 5. Roof Insulation Over Rafter Application P/ 6

MINERAL WOOL INSTALLATION GUIDANCE: ENSURE A PERFECT FIT

SIDERISE SC cavity barriers & fire stops for suspended ceilings

GypLyner (walls) Metal framed wall lining system. GypLyner.

EcoHome-Insulation.com. Aluminium Foil Bubble Insulation. General Purpose Insulation. Dry Lining. Cavity Wall. Insulation System.

URSA TF Roll URSA GLASSWOOL.

SAINT-GOBAIN ISOVER CAVITY WALL INSULATION WALLTHERM(2) CAVITY WALL INSULATION

Why External Wall Insulation?

Part E robustdetails. robustdetails. September 2015 Update Pack. Dear Colleague,

Polypipe TDI. A comprehensive range of products designed to provide complete and economical solutions to cold bridging and other insulation problems.

SECTION THERMAL INSULATION

ULTIMATE Tech Wired Mats High performance for high temperatures

Independent twin frame high performance acoustic separating wall system

August 2008: Issue 1. Non - Residential New Build Built-up Metal Roofs

How glass or rock mineral wool works in a wall or floor cavity

Transcription:

Isover Installation Guide Installing Separating Masonry Cavity Wall Insulation

At Saint-Gobain Isover we develop sustainable insulation solutions to protect both your built environment and the natural environment. To maintain our focus we have placed environmental responsibility at the heart of our business strategy. The importance of correct installation The purpose of this guide is to provide technical guidance for installing Isover insulation into separating masonry cavity walls. Quality and accuracy of installation is vitally important if a separating structure is going to meet the acoustic and thermal performance detailed at the design stage. Mortar build-up at the bottom of the cavity, mortar snots on wall ties and insulation without tightly butted joints can all lead to substandard acoustic and thermal performance and can lead to expensive additional sound testing and corrective work. Our vision to lead the UK mineral wool market in energy efficiency and acoustic insulation solutions will be achieved with products that meet the highest thermal, acoustic and fire safety performance levels. We will meet changing regulations first and surpass current regulations for those that wish to excel. Our products will provide best value solutions for the residential, commercial, RMI and technical building environments, be safe to use and help to protect the environment. Isover Technical Advice Our dedicated technical support team can provide guidance with regulation compliance, product installation and product performance. Tel: 0115 945 114 E-mail: isover.enquiries@saint-gobain.com 2 www.isover.co.uk Isover Technical Advice Tel: 0115 945 114

Insulating separating masonry cavity walls Before you start Storage and packaging Palletised packs of Isover separating wall insulation can be stored outdoors on a flat, welldrained, hard standing surface. Loose packs must be stored under cover and off the ground until required for use. For safety reasons it is not recommended that pallets are stacked. Free pallet repatriation service To further support our Point Plan for environmental sustainability, we are pleased to advise that a new pallet repatriation service is now available to allow removal of Isover pallets from your branch or site location, in an environmentally responsible way. European Logisitics Management Ltd (ELM) will be providing a free collection of Isover pallets (minimum quantity applies per collection) from your preferred stockist or site location your stockist or contractor simply has to call 0800 282 488 to arrange a collection. Wall Ties The level of sound insulation between buildings using masonry separating walls is highly dependent on the separation provided by the cavity between the wall leaves. Wall Ties separating The following text gives generic guidance for the installation of cavity wall ties. For a detailed installation procedure and guidance, advice should be sought from the wall tie manufacturer. Wall ties are vital for securing the structural integrity of a wall. Installing them incorrectly can lead to acoustic weak spots, cracking or even the collapse of walls. Spacing For walls where both leaves are thicker than 90mm, position wall ties at a maximum of 900mm horizontal x 450mm vertical centres (2.5 per m²). Ties should be evenly distributed over the wall area and should preferably be staggered.* Around openings, position wall ties with a minimum vertical spacing of 00mm (usually 225mm to suit one block course) and no more than 225mm from the edge of the opening. Additional Guidance Wall ties are a primary source of acoustic transmission. For this reason it is important to prevent mortar build up around the wall ties and at the foot of the cavity. Bridging effects can lead to significant sound transmission between the attached properties, by-passing any useful isolation effect that the cavity provides and may result in significant reduction in acoustic isolation performance. It is important to prevent mortar build up at the base of the cavity in order to prevent it bridging the wall leaves at and above ground floor structure. Bridging effects can lead to significant sound transmission between attached properties, by-passing any useful isolation effect that the cavity provides and may result in a significant reduction in acoustic isolation performance. * This is guidance only Isover Technical Advice: isover.enquiries@saint-gobain.com www.isover.co.uk

Procedure Installation procedure Step 1 Build the first section of leading leaf to a height of three block courses along the full length of the wall with the first row of wall ties two courses up. Step 2 Before installing the insulation, clean off any mortar snot protruding into the cavity and from any wall ties or cavity trays. Step Remove the insulation from its packaging. Ensure that the product remains in roll form but expose approximately 750mm of length. Step 4 Position the top edge of the insulation in contact with the wall tie and the back edge in contact with the block face. The insulation should then be carefully unrolled along the full length of the wall, positioned and held in place by the wall ties. Step 5 For effective edge sealing in a full-fill external cavity, ensure the insulation is tightly butted to the external wall insulation. For effective edge sealing in a partial filled cavity, an Isover flexible cavity barrier is required. 4 www.isover.co.uk Isover Technical Advice Tel: 0115 945 114

Insulating separating masonry cavity walls Procedure Step 6 Build up the second block leaf to the top of the insulation. Step 7 Successive sections of wall may proceed as described in points 1 to 7. Excess mortar must be removed from the cavity face and a cavity board used to prevent mortar droppings on the top edge of the insulation. When installing Isover insulation care should be taken to ensure butt joints are tightly butted and vertical joints staggered from course to course. Step 8 It is recommended that at corners, the insulation should be closely butted to avoid cold bridges. Ideally, the uncut edge of the insulation should be used for this purpose or an edge straight cut with a sharp knife. Folding the insulation around corners is not recommended. Step 9 At the roof junction, compression fit Isover Cavity barriers between the wall and roof covering. The Barrier should cover the full width of the wall. Isover Technical Advice: isover.enquiries@saint-gobain.com www.isover.co.uk 5

Best practice tips Do not pierce the insulation with wall ties to prevent tearing the insulation and creating a thermal bridge. Do cut the insulation using a sharp knife and straight edge. Do fit small pieces of insulation with the fibres running horizontally to the wall to ensure fully-fitted. Do not push insulation down into the cavity as a tightly butted horizontal joint cannot be ensured. Do keep the top edges of the insulation clean of mortar by using a cavity board. Do protect all exposed areas of insulation with a weatherproof material or board when work is suspended or during rain. Do not bend insulation around corners as this creates air gaps within the cavity. Do stagger vertical joints and ensure they are tightly butted. 6 www.isover.co.uk Isover Technical Advice Tel: 0115 945 114

Insulating separating masonry cavity walls Isover RD Party Wall Roll A glass mineral wool roll designed for use in E-WM-17, E-WM-20 and E-WM-24 Robust Details wall constructions to exceed acoustic performance requirements set out in Building Regulations Approved Document E (England and Wales). The product also conforms to the Robust Details generic full-fill mineral wool specification for all other masonry cavity separating details. Product Thickness (mm) Width (mm) Length (mm) Pack area (m²) Isover RD Party Wall Roll 75 2 x 455 8500 7.74 Isover RD Party Wall Roll 100 2 x 455 6000 5.46 Isover RD Party Wall Roll 125 2 x 455 5000 4.55 Isover RD Party Wall Roll 150 2 x 455 4000.64 Thermal bypass solution Meets the full-fill requirement to help deliver a zero U-value for party walls as defined in Building Regulations (Approved Document L1A, Table ). Robust Details approved solution Proprietary component of E-WM-17, E-WM-20 and E-WM-24 Robust Details wall constructions and also conforms to the Robust Details generic full-fill mineral wool specification for all other masonry cavity separating details. Proven practical site solutions No requirements for PCT (Pre-Completion Testing). Roll format ensures minimal or no vertical butt joints. Removes the need for additional wet trade No requirement for a wet plaster or parge coating resulting in significant time and cost savings (E-WM-17, E-WM-20 and E-WM-24 only). Euroclass A1 fire rating Totally non-combustible and fire safe. Isover Technical Advice: isover.enquiries@saint-gobain.com www.isover.co.uk 7

www.pointplan.co.uk www.isover.co.uk Isover Order Placement or Order Enquiries: Tel: 0800 02 2555 Fax: 0800 917 9188 Published Date: July 2014 Isover Document Reference: I-SMW-IG-1401 Technical Advice Line Buildings Insulation: Tel: 0115 945 114 Email: isover.enquiries@saint-gobain.com Saint-Gobain Isover Gotham Road East Leake Loughborough Leicestershire LE12 6HX Tel: 0115 969 8010 Email: isover@saint-gobain.com Isover reserves the right to revise product specifications without notice. The information in this document was correct to the best of our knowledge at the time of publication. It is the users responsibility to ensure that it remains current prior to use. The information in this document is for guidance only and should not be read in isolation. Users should read and familiarise themselves with all the information contained in this document and ensure that they are fully conversant with the products and systems being used, before subsequent specification or installation. For a comprehensive and up to date library of information visit the Isover website.