After-Fracture Redundancy of Two-Girder Bridge: Testing 1-40 Bridges Over Rio Grande

Similar documents
How Loads Are Distributed

Load capacity rating of an existing curved steel box girder bridge through field test

Nonlinear Redundancy Analysis of Truss Bridges

Appendix D.1. Redundancy Analysis of Composite Spread Box Girder Superstructures under Vertical Loads

Field and Laboratory Performance of FRP Bridge Panels

FATIGUE OF DIAPHRAGM-GIRDER CONNECTIONS

Appendix D.2. Redundancy Analysis of Prestressed Box Girder Superstructures under Vertical Loads

FINAL REPORT EFFECT OF GIRDER SPACING ON BRIDGE DECK RESPONSE. James G. Buckler Graduate Research Assistant

Modjeski and Masters, Inc. Consulting Engineers 04/18/06 St. Croix River Bridge 3D Analysis Report Introduction

Stress-Laminated / Steel T-Beam Bridge System

Potential for high-performance steel in a long span truss bridge

STATE OF NEW HAMPSHIRE DEPARTMENT OF TRANSPORTATION LOAD RATING REPORT GENERAL SULLIVAN BRIDGE - DOVER 200/023 OVER THE LITTLE BAY

AASHTOWare BrR 6.8 Steel Tutorial Steel Plate Girder Using LRFR Engine

AREMA 2008 Annual Conference. LOW PROFILE RAILROAD BRIDGE Steve K. Jacobsen, PE NNW, Inc. Rochester, Minnesota

Investigation of Negative Moment Reinforcing in Bridge Decks

Innovations in Tied Arch Bridges

Direct Redundancy Evaluation of Bridges Designated as Fracture-Critical

Cross Frame Design for Curved and Skewed Bridges

INSPECTION AND REPAIR OF THE DETERIORATED RT.72 MANAHAWKIN BAY BRIDGE

Steve Haines, P.E., Parsons, (303) , James Studer, Kiewit, (926) ,

Purdue e-pubs. Purdue University. Kadir Can Sener Purdue University. Teresa L. Washeleski Michael Baker Jr., Inc,

Deflection Assessment of an FRP-Reinforced Concrete Bridge. By Danielle K. Stone, Andrea Prota, and Antonio Nanni

Inspection of Steel Girder Bridges

103rd Annual T.H.E. Conference February 28 & March 1, 2017 University of Illinois at Urbana-Champaign. Planning and Design. of IL-104 BRIDGE OVER

For Two Steel Bridges

Design and Construction of the SH58 Ramp A Flyover Bridge over IH70. Gregg A. Reese, PE, CE, Summit Engineering Group, Inc.

Toward Development of a Steel Bridge System - Simple for Dead Load and Continuous for Live Load

BENCHMARK PROBLEMS TASK 7 REPORT. Prepared for NCHRP Transportation Research Board of The National Academies. Project No. NCHRP COPY NO.

AASHTOWare BrDR 6.8 Steel Tutorial STL6 Two Span Plate Girder Example

Load Rating of a Steel Composite Girder Bridge

FINAL REPORT COMPOSITE ACTION IN A STEEL GIRDER SPAN WITH PRECAST DECK PANELS: THE I-81 BRIDGE OVER THE NEW RIVER IN RADFORD, VIRGINIA

Dead Loads. Load Resistance ηγ i Q i ΦR n. Design Criteria. EGCE 406 Bridge Design III. Loads on Bridge Summary of Concepts.

DESIGNING TWIN TUB GIRDER BRIDGES TO BE NON-FRACTURE CRITICAL. Twin Tub Task Group (T3) Texas Steel Quality Council

Design of Short Span Steel Bridges

Moving Load Analysis for Bridge Structures

Nonlinear Redundancy Analysis of Multi-Cell Pre-stressed Concrete Box-Girder Bridge

Sponsored by the Iowa Department of Transportation and the Iowa Highway Research Board Iowa DOT Project HR-393 JUNE 1998 CTRE

FIELD INSTRUMENTATION AND ANALYSIS OF THE TUTTLE CREEK BRIDGE. Br. No (017)

WRA has been instrumental in improving society's quality of life with cleaner water, improved roads, bridges and railroads, state-of-the-art

BRIDGE CONSTRUCTION USING SELF-PROPELLED MODULAR TRANSPORTERS (SPMT)

CASE STUDY OF LONG SPAN STEEL BRIDGE STABILITY DURING DESIGN AND CONSTRUCTION

Assessment of Load Transfer and Load Distribution in Bridges Utilizing FRP Panels

Clear Creek Road (PM 1.82 & 0.25) Bridge Replacement Projects. Public Meeting, Wednesday, November 20, 2013 Pleasant Valley Middle School

Live Load Test and Finite Element Analysis of a Box Girder Bridge for the Long Term Bridge Performance Program

Analysis of a Severely Skewed Prestressed Concrete Beam Bridge

CHAPTER III DYNAMIC BEHAVIOR OF A LABORATORY SPECIMEN

DISTORTION-INDUCED FATIGUE CRACKING AT WEB-GAP OF WELDED I-BEAMS

Crack Evaluation and Repair of Cantilever Bracket Tie Plates of Edison Bridge

Experimental Investigation and Modelling of Spread Slab Beam Bridges

Title Page: Modeling & Load Rating of Two Bridges Designed with AASHTO and Florida I-Beam Girders

Potential Solutions- Background: Current Designs. Potential Solutions. Goals for Design What are we concerned about?

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Field Instrumentation and Long-Term Monitoring of the FRP Bridge over Dubois Creek in Great Bend, PA

Field study of a steel plate-girder bridge, Final Report, Vol. II of PennDOT Project 86-05, May 1995

Check the strength of each type of member in the one story steel frame building below.

CHALLENGES OF DESIGNING A HIGHLY SKEWED TWO-SPAN CONTINUOUS STEEL GIRDER BRIDGE

Behavior of Open Steel Grid Decks Under Static and Fatigue Loads

Office Building-G. Thesis Proposal. Carl Hubben. Structural Option. Advisor: Dr. Ali Memari

The need to design for robustness in fire. Ian Burgess

Spatial analysis of concrete filled steel tubular tied arch bridge

Comparison of haunched and constant depth steel box bridge girders, International Bridge Conference, Pittsburgh, PA., June 1984 (F.L. Publ.

Uses of Abaqus/Standard in Failure Analysis

ERRATA for G12.1, Guidelines to Design for Constructability, 2016 Edition

Modeling stiffener distortion in orthotropic bridge decks with FEM using superelements

THE NEW AASHTO MANUAL FOR BRIDGE EVALUATION 2008

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Northeast Bridge Preservation Partnership Meeting

Session 2: Basic Load Rating Calculations

How Beams Work, I. Statics and Strength of Materials

Structural Behaviors of Long-Span Cable-Stayed Bridge With A-Shaped Tower Due to Three Wind Speeds

Chapter 1. General Design Information. Section 1.03 Loads and Load Factors. Introduction. Load Modifying Factors

1. Introduction Progress made for the reporting quarter between April 1, 2010 and December 30, 2010 includes the following highlights:

CYCLIC BEHAVIOR OF AN INNOVATIVE STEEL SHEAR WALL SYSTEM

Demonstration Project using Railroad Flatcars for Low-Volume Road Bridges

SHEAR AND BUCKLING STRENGTHENING OF STEEL BRIDGE GIRDER USING SMALL-DIAMETER CFRP STRANDS

Chicago. Crossing. A new Chicago bridge takes over the duties of a former Centurion.

FIELD TESTING & LOAD RATING REPORT: MILLARD AVENUE OVER CSX RAILROAD OREGON, OH

Load Test and Rating Report Steel Truss Bridge, Bonham Butler County, Ohio

RECOMMENDED GUIDELINES FOR REDUNDANCY DESIGN AND RATING OF TWO-GIRDER STEEL BRIDGES

SUMMARY BIOGRAPHY LEAN-ON CROSS- FRAME BRACING FOR STEEL GIRDERS WITH SKEWED SUPPORTS

Structural assessment of the integrated steel fly-overs widening the historic multiple-arch concrete viaduct over the Pede valley

Live Load Distribution Factors Suitable For Concrete Bridges Under Ecp 201 And Euro Code 1991 Loading

Fatigue resistance of frankford el line viaduct, 1981

ABSTRACT. Professor Chung C. Fu, P.E. Department of Civil and Environmental Engineering

1. Report No. 2. Government Accession No. 3. Recipient's Catalog No. FHWA/IN/JTRP-2002/26

FIELD TESTING AND LOAD RATING REPORT: BRIDGE OVER RUSH RIVER CASS COUNTY, ND

POST RETROFIT ANALYSIS OF THE TUTTLE CREEK BRIDGE Br. No

Abstract. Many of today s bridge construction projects are erected in stages to limit traffic

ANALYSIS AND DESIGN OF MULTI-STOREY COMPOSITE BUILDING

Simplified Analytical Model for a Queen-Post Covered Timber Bridge

CCTV HEADQUARTERS. ARCH 631 Spring 2018 Daniel Edith Mckenzie Rafael

The Pennsylvania State University. The Graduate School. College of Engineering EVALUATION OF BRACING SYSTEMS IN HORIZONTALLY CURVED STEEL I-

FABRICATED BRIDGE PRODUCTS CATALOG

BrD Superstructure Tutorial

Bijan Khaleghi, Ph, D. P.E., S.E.

December 19, 2012 ADDENDUM NO. 11. To Prospective Bidders and Others on:

Executive Summary Building Description: Introduction... 13

Economical Steel Box Girder Bridges

Analysis of Full Depth Precast Concrete Bridge Deck Panels

Overview. Fracture Critical Inspection History Project Overview Research to Determine Criteria Case Studies Conclusions

Transcription:

After-Fracture Redundancy of Two-Girder Bridge: Testing 1-40 Bridges Over Rio Grande R. L. Idriss, K. R. White, C. B. Woodward, and D. V. Jauregui, Neta Mexico State University The 1-40 bridges over the Rio Grande in Albuquerque, New Mexico, were due to be razed in the fall of 1993 because of geometry and traffic safety considerations, thus providing a unique opportunity for testing them. These medium-span steel bridges represent a common design in the United States and are classified by AASHTO as nonredundant "fracture critical" two-girder steel bridges ("fracture critical" classification means that failure of a primary member would probably cause collapse of the bridge. The subject bridge, built in 1963, is 1,275 ft (390 m) long and consists of three medium-span continuous units with spans of 131, 163, and 131 ft (40, 50, and 40 m) each. The bridge was field tested to determine the impact of a near full-depth girder fracture on the redistribution of loads, the load capacity, and the potential for collapse. Four levels of damage were introduced in the middle span of the north plate girder by making various cuts in the web and the flange of the girder. The final cut resulted in a crack 6 ft (1.8 m) deep in the 10-ft (3.1-m)-deep girder, extending from the bottom flange to the floor beam to girder connection. Data were taken under dead load and under a static live load consisting of an 82,000-lb (365,000-N) truck. The fractured bridge proved to be stable, with minimal deflection and no yielding. The afterfracture response and the load redistribution in the fractured bridge were evaluated. The contribution of the various members to the redundancy of the structure was assessed. ^ I 1 he 1-40 bridges over the Rio Grande in Albu- I querque were due to be razed in mid-1993 be- JL cause of geometry and traffic safety considerations. The bridges represent a common design in the United States and are classified as nonredundant "fracture critical" two-girder steel bridges. AASHTO's Standard Specifications for Highway Bridges (1) defines nonredundant load path structures as "structure types where failure of a single element could cause collapse." The two-girder bridge design, using welded steel plate girders as the primary structural elements was a popular design in the 1950s and 1960s. A large number of these bridges are currently in service around the United States. These bridges have fatigue-sensitive details and are nearing the limit to their practical fatigue life. In a number of instances, cracks developed in the webs, flanges, secondary members, and connections, resulting in uncertainty about the integrity of these bridges and their safety and creating concern for the practicing bridge engineer. Experience shows that two-girder highway bridges typically do not collapse when a fracture occurs in a girder. In many instances, they remain serviceable, and damage sometimes is not even suspected until the fracture is discovered incidentally or during inspection (2,3). Much stiu needs to be learned about the afterfracture behavior of these structures and how the load gets redistributed when fracture occurs. The main ob- 316

IDRISS ET AL. 317 jective of the testing was to investigate the behavior of the fractured bridge and the after-fracture redundancy present in the structure. This paper reports on the redundancy present in a fractured two-girder steel bridge. BRIDGE DESCRIPTION The structure, built in 1963, is a 1,275-ft (390-m) long, noncomposite bridge consisting of three-span continuous units with spans of 131, 163, and 131 ft (40, 50, and 40 m) each. The structural unit is a two-girder design welded with bolted splices with a floor system (Figures 1 through 3). dieted a stable structure, with minimum deflections, and no yielding. The following behavior was observed: 1. Most of the load was observed to be redistributed longitudinally via the north damaged girder to the interior supports, as demonstrated by the large increase in negative moment at the interior supports after fracture (Figure 5), and 2. Some of the load was redistributed in the transverse direction to the intact girder because of the torsional rigidity of the deck, floor beam, and bracing system as shown by the increase in positive moment at midspan of the central span (Figure 6). ANALYTICAL MODEL A preliminary analytical study (4) was needed for (a) safety consideration and {b) gauge placement. A threedimensional finite element computer model of the bridge was developed (4). (Figure 4). A full description of the finite element model appears elsewhere (4). The results of this analytical study (4) were used to (a) evaluate after-fracture behavior and choose defects to implant on the bridge; {b) determine the sensor locations and optimize the quality and quantity of the data acquisition devices; and (c) calculate the load on the jacks during temporary shoring, the clearance needed at the cut, and the positioning of the truck for static loading. The preliminary analysis of the structure with a near full-depth crack at midspan of the central span pre- BRIDGE MONITORING: PLACEMENT OF STRAIN GAUGES On the basis of the preliminary finite element analysis and load path evaluation, the focus of this study was on monitoring the elements that showed the most significant change in load. The following were mainly monitored: 1. The moment in the north (damaged) girder at the interior girder supports; 2. The moment in the south (intact) girder at midspan and at the interior supports; 3. Forces in the bracing at the vicinity of the crack, because the analytical model predicted a large increase in the bracing load at the crack zone; East 3-Span Continuous Unit Expansion Device Contraction Devices in deck 131 ft (40 m) Span 9) 163 ft (50m) (Span 8) 131 ft (40m) (Span 7) Pier a Pier 7 Pier 6 FIGURE 1 Overall plan and elevation of east three-span continuous unit of eastbound 1-40 bridge.

WF 21x02 L 5X5X5/16 6 21.7'(6.62m) B e 20.4' (6.22m) 6 a 21.7- (6.a2m) FIGURE 2 Plan view of steel superstructure below bridge deck. 7" min. (178mm) Concrete Slab W21x62 Stringers W36xl50-182 Floor Beam L 5x5x5/16 Bracing (Z.OSm) (2.29,) (2.2g m) (2.29 m) (2.28 m) FIGURE 3 Cross section of 1-40 bridge at floor beam location. (2.29 m) EXP3 Intact Girder NORTH STR3 Fractured Girder Location o Fracture PIX EXP1 FIGURE 4 Finite element model of 1-40 bridge (below reinforced concrete deck).

IDRISS ET AL. 319 400 Without crack X -400 crack 100 200 300 400 Distance from East Abutment (ft) 500 u- -400 Intact -1000 100 200 300 400 Distance from East Abutment (ft) 500 FIGURE 5 Top: North girder bottom flange forces; bottom: north girder bottom flange forces under dead load plus two HS-20 truck loadings, no impact (1 kip = 4.45 kn, 1 ft = 0.305 m). 4. Moments in floor beams at midspan and at the connection to the intact girder. It was anticipated that the floor beams at the vicinity of the crack would transfer load to the intact girder through cantilever action and develop a negative moment at their connection to the intact girder as they cantilever toward the crack; and 5. The load increase in the stringers. For this gauges were placed on the bottom flange of the middle stringer and the stringer closest to the north girder fracture (the stringer at the most remote location to the damage was not monitored). The strain gauge locations are shown in Figures 7 through 11. Encapsulated, self-compensated, V4-in. (6.35-mm) metal foil gauges were used (Micro Measurements CEA-06-250UW-305). The deflection was measured at various locations on the north and south girders, particularly at midspan of the west exterior span and at midspan of the central span. BRIDGE TESTING (5) Static Tests A general tractor-trailer with a front-to-back axle spacing of 55.18 ft (16.82 m) and weighing 81,620 lb (363 100 N) was furnished by the New Mexico State Highway and Transportation Department for the static tests. The layout and magnitude of the wheel loads are provided in Figure 12. With this configuration, the truck was found to be 95.5 percent of the maximum New Mexico legal load and roughly equivalent to an HS- 18.35 in the positive moment region of the test bridge. At this location, it gave maximum positive moment at midspan of the central span and almost maximum negative moment at the interior supports. Influence Une studies were used to position the truck. 1. For maximum positive moment at midspan of the central span and almost maximum negative moment at

400 intact -800 100 200 300 400 Distance from East Abutment (ft) 500 Intact -800 100 200 300 400 Distance from East Abutment (ft) 500 FIGURE 6 Top: south girder bottomflangeforces under dead load; bottom: south girder bottomflangeforces under dead load plus two HS-20 truck loadings, no impact (1 kip = 4.45 kn, 1 ft = 0.305 m). Top Flaiife ZST (737iiun) GIZ G44 G18 Em«t G18 Bottom. nange Weit G13 G14 G4S G4e GU «Fixed Brg. e Uidcpan O Ezp. Erf. FIGURE 7 Positioning of strain gauges on north (damaged) girder (view from inside looking out).

IDRISS ET AL. 321 29 (737min) 30" (762inm) Top Flange 29-(7q7min^ East West Bottom Flange G5 G17 9 Fixed Brg. O Midspan O Exp. Brg. FIGURE 8 Positioning of strain gauges on south (intact) girder (view from inside). the interior supports, the third axle of the truck was placed at midspan of the central span 2. For minimum moment at midspan of the central span and large moment at the west interior support, the third axle of the truck was placed 75 ft (22.88 m) from the west end of the three-span unit. Strain gauge zeroing measurements were to be taken with the structure unloaded. Readings were then taken with the third axle of the truck stopped at the abovementioned locations on the north driving lane. This general procedure was repeated for the pristine structure and for the damaged bridge at each stage of the cuts. In addition, strain readings were taken under dead load before and after the flange cuts. Deflection measurements were scheduled to be taken simultaneously with the strain readings. Temporary shoring was positioned below the cut for safety considerations. The support tower was also used for access, as a platform for jacking up the north girder to relieve stress in the bottom flange before the final flange cut and for splicing the flange cut after the testing. Damage Description Four different levels of damage were introduced in the middle span of the north plate girder by making various torch cuts in the web and the flange of the girder. This occurred from September 3-8, 1993. The final cut was to simulate a near full-depth crack in the girder. This type of crack, usually a fatigue crack, develops at South Girder \6V <(}!/ Fixed Bearing -!i - Location of Crack Expansion Bearing -North Girder FIGURE 9 Positioning of strain gauges on lateral bracing system (top view).

322 FOURTH INTERNATIONAL BRIDGE ENGINEERING CONFERENCE G40 036 North G41 G30 South North North North (a) Floor Beam FBQ G38 034 037 035 (b) Floor Beam FBIO 026 G28 G2S 027 (c) Floor Beam FBll (d) 032 030 G33 Floor Beam FB12 G31 FIGURE 10 Positioning of strain gauges on floor beams. South South South fatigue-sensitive details in the bridge, often at the girderto-floor beam connection because of out-of-plane bending of the web. The cut in the girder was done in four stages. Damage was to be inflicted on the bridge by a series of cuts, near midspan of the central span of the north girder 2.5 ft (0.762 m) west of the center of the bridge, midway between two vertical stiffeners. The first-stage cut was a cut in the web 2 ft (0.61 m) deep, originating at the floor beam connection level. Next the cut was continued to the bottom of the web. During this cut of the web, the web bent out of plane approximately 1 in. (25.4 mm). The third stage was to cut the flange halfway in from each side, directly below the web cut. Finally, in the fourth stage, the flange was severed completely, leaving the upper 4 ft of the web and the top flange to carry load at that location. For the final cut, the north girder was blocked up and jacked upwardv2 in. (12.7 mm) to relieve dead load stress in the flange. Computer predictions required the girder to be jacked up 4 in. (19.1 mm) to relieve the bottom flange stress; however, the wooden blocks beneath the jacks began to crack at about V2 in. (12.7 mm). It was decided thatv2 in. (12.7 mm) was enough to alleviate the force in the bottom flange and to allow a safe final cut. The bottom flange was then severed entirely and the girder was slowly lowered until no contact existed between the jacks and the flange. The final cut resulted in a crack 6 ft (1.83 m) in the 10-ft (3.1-m)-deep girder, extending from the bottom flange to the floor beam to girder connection. Using the support tower as a reference level, the distance to the bottom flange was measured before and after the final flange cut. The difference of the two measurements represented the added deflection of the South Girder Stringers G43 / 042 / Fixed Bearing -Location of Crack Expansion Bearing North Girder FIGURE 11 Positioning of strain gauges on stringers (top view).

IDRISS ET AL. 323 8.58'(2.01 m) 8.17' (i.aa m) \ S, S 1 (4.80 m) \ In 4.26' (1.30 m) 9 f J \ s N N e O N \ r "1 2 e 5.56 kipa (24.74 KN) 4 e 7.85 kips (34.9 KN) 4.12' (1.2( m] 4.13' 1.28in 1 4 1 1 ( \ \ i > 4 8 8.52 kipi (29.0 KN) (2.29m) HGURE 12 AppUcation of HS-18.35 truck to bridge deck. north girder caused by the mid-depth fracture under dead load. Utilizing this approach, the bottom flange of the girder at the cut deflected by only "At in. (17.5 mm), and the crack opened Vs in. (9.52 mm). When the truck was positioned above the cut, the crack opened to V4 in. (19.1 mm) and the girder deflected by an additionalv2 in. (12.7 mm), for a total deflection under dead and live load of IVu in. (30.2 mm). There were no signs of yielding. On Thursday, Sept. 9, equipment was removed from the bridge site, and the cut flange was spliced for security during the razing of the bridge. Strain Gauge Data There was no significant change in strains experienced by the gauged members during the various stages of damage, as shown in Tables 1 through 5 until the bottom flange was completely severed. This shows that load redistribution did not occur until the bottom flange was completely cut. The only noticeable change throughout the various phases was localized and occurred after the second web cut. During this cut, gauges G13 and G14 located on the bottom flange of the damaged girder, closest to the fracture, experienced a surge in tension (Table 1). This shows that the web plus half flange fracture did not alter the bridge stiffness enough to initiate load transfer. It is not until the flange is totally severed that the load redistribution occurs. Load Redistribution Korth {Damaged Girder) The after-fracture strain readings show that the north girder is the dominant redundant load path. Continuity at the interior supports allowed the girder to redistribute the load longitudinally through cantilever action to the interior supports. This is shown by the significant increase in negative moment at the interior supports as shown by the surge in compression force in the bottom flange of the north girder at the interior supports. This is evident by the large negative changes in strain recorded for the gauges positioned at the fixed support (G2) and at the expansion bearing (Gil) as shown in Table 1. The largest strain measured in the structure was measured at the interior supports of the damaged girder. The live load stresses measured at G2 and Gil were 1.32 ksi and 1.50 ksi, respectively. The predicted live load stress at these locations by the finite element model was at 2.0 ksi, which proved to be conservative. The predicted dead load stress (finite element model) was 13 ksi. The total dead and live load stress was 15

TABLE 1 North (Damaged) Girder: Strain Readings Under Truck Loading at Central Span in Microinches per Inch No Damage 1st Web Cut 2nd Web Cut 1st Flange Cut Final Cut Gage G2 (S) Fixed Bearing -30.9-30.8-31.1-31.5-46.2 Gage Gil ( ^ Expansion Bearing -35.4-35 -35-35.9-51.6 Gage G13 cut 89.5 89.3 110 122 0 Gage G14 ( W cut 87.4 87.8 133 135 0 TABLE 2 per Inch Stringers: Strain Readings Under Truck Loading at Central Span in Microinches No Damage 1st Web Cut 2nd Web Cut 1st Flange Cut Final Cut STRl G42-5.5-5.0-5.8-6.5 2.9 STR2 G43-0.3 1.8 1.8 1.4 14.9 TABLE 3 South Intact Girder: Strain Readings Under Truck Loading at Central Span in Microinches per Inch No Damage 1st Web Cut 2nd Web Cut 1st Flange Cut Final Cut G5 (Fixed Bearing) -3.7-3 -3.3-3.2-2.6 G8 (Expansion Bearing) -5.5-4.4-4.8-4.9-5 G17 (Midspan) 19 18.3 17.6 17.4 23.4 TABLE 4 per Inch Floor Beams: Strain Readings Under Truck Loading at Central Span in Microinches No Damage 1st Web Cut 2nd Web Cut 1st Flange Cut Final Cut FB9 Gage G39-1.0-1.1-1.1-0.9 1.7 FBIO Gage G35-3.9-4 -4.5-4.5-6.9 FBll Gage G27-7.1-7.6-7.9-7.9-23.6 FBI2 Gage G31-3.8-3.9-3.7-3.2-3.3 TABLE 5 Inch Bracing: Strain Readings Under Truck Loading at Central Span in Microinches per No Damage 1st Web Cut 2nd Web Cut Ist Flange Cut Final Cut Panel East of Crack G21.8-1.6-2.0-2.1-24.9 G24 28.4 26.2 28.6 30 68.0 Panel Crack G20 8.5 8.1 9.6 10.5 15.5 G23 20.8 19.2 21.2 21.5 57.0 Panel West of Crack G22-16.5-19.3-19.8-19.7-58.1 G25 36.2 37.2 37.5 38.3 68.5

IDRISS ET AL. 325 ksi, less than the inventory stress level recommended by AASHTO (0.55 times the yield stress) of 20 ksi. Stringer-Deck System After fracture, load is shed to the stringer-deck system. The after-fracture strains (Table 2) recorded for gauges G42 and G43 showed the stringers to be carrying more load. In addition, the longitudinal gauge positioned on the bridge deck showed a large surge in compression following the crack. South Girder The intact girder has an increase in positive moment at midspan as indicated by the positive change in strain recorded at that location by Gauge G17 (Table 3). A 20 percent increase in tension in the bottom flange at midspan was measured under live load. Floor Beams As predicted, the floor beams at the vicinity of the crack redistributed the load to the intact girder. The most drastic change occurred in floor beam FBll located at the crack. It acted essentially as a cantilever beam because of the lack of support from the damaged girder. This cantilever action is demonstrated by the increase in negative moment at the connection with the intact girder as indicated by the strain measurements at that location (Table 4). Floor beam FBIO, located directly west of the crack, also experienced an increase of negative moment at its south end, but not as much as floor beam FBll. The other two floor beams located in the crack zone but further away from the crack, FB9 and FB12, do not show a significant change in behavior. Lateral Bracing System Strain readings show a large increase in the load carried by the diagonals (Table 5). There also was a change in load patterns for the lateral bracing. The two diagonals in the bay at the crack were both in tension and experienced a drastic increase in their tensile force (strain measured after fracture was two to three times the strain measured before fracture). Because of twisting in the structure, in the panel east of the crack, one of the diagonals increased in tension while the other went from tension to compression. Role of the Deck Longitudinal as well as transverse load redistribution is provided by the deck. After-fracture strains recorded under dead load with the deck rosette are provided in Table 6. The table gives the results gathered during the last two stages of girder cuts. The longitudinal gauge, which was positioned on the bridge deck above the middle stringer, recorded a large surge of compression on completion of the final flange cut. The transverse gauge placed at the same location as the longitudinal gauge indicated an increase in tension in the deck. Before the crack, the deck acts as a continuous beam over the stringers in the transverse direction. When the crack is imposed, the north portion of the bridge near the crack sags downward. Like the floor beams at that location, the deck cantilevers out from the higher supported areas on the south end. This is indicated by an increased tension experienced by the deck in the transverse direction. CONCLUSIONS When a mid-depth fracture was imposed on the north girder of the three-span unit, it changed the bridge into a new but still stable structure. Deflection at the crack was minimal at Vlu in (30.2 mm) under dead plus live loading, and there was no yielding. The load redistribution was provided in the three-dimensional structure by both primary and secondary members via the deck, stringers, floor beams, and bottom lateral bracing. Most of the load was redistributed longitudinally through the damaged girder and stringer deck system to the interior supports. The main load path proved to be the fractured girder itself as it redistributed the load longitudinally to the interior supports through cantilever action. The floor beams, lateral bracing system, and deck transferred the load to the intact girder, through torsional stiffness of the system. This load transfer in the transverse direction occurred mainly at the vicinity of the crack. TABLE 6 After-Fracture Strains in Deck Under Dead Load in Microinches per Inch Gage First Flange Cut Final Flange Cut Longitudinal -5.5-138 Transverse 2.6 17.2 @ 45 degrees -5.4-47.4

326 FOURTH INTERNATIONAL BRIDGE ENGINEERING CONFERENCE FURTHER RESEARCH The following recommendations are suggested to extend the reported research: 1. Investigate the after-fracture behavior of the bridge with a crack at midspan of an exterior span. This fracture scenario could prove to be more critical than the fracture at midspan of an interior span because the cantilever action provided by the interior supports will not be available at the abutment. 2. Investigate the possible loss of composite action between the girder and the deck with increasing loading. 3. Develop nondestructive monitoring systems for this family of bridges. On the basis of the bridge testing results, this monitoring system can be effective and can focus on the critical zones. ACKNOWLEDGMENT This study is part of the overall testing of the 1-40 Bridge, in Albuquerque, New Mexico. It was funded by a grant from the National Science Foundation, the New Mexico State Highway and Transportation Department, FHWA, and the New Mexico Alliance for Transportation. REFERENCES 1. Standard Specifications for Highway Bridges, 13th ed. AASHTO, Washington, D.C., 1983. 2. Daniels, J. H., W. Kim, and J. L. Wilson. NCHRP Report 319: Recommended Guidelines for Redundancy Design and Rating of Two Girder Steel Bridges. TRB, National Research Council, Washington, D.C., 1989. 3. Schwendeman, L. R, and A. W. Hedgren. Bolted Repair of Fractured 1-79 Girder. Journal of the Structural Division ASCE, Vol. 104, No. STIO, Oct. 1978, pp. 1567-1669. 4. Idriss, R. L., and D. V. Jauregui. Load Path Evaluation of the 1-40 Bridge. Report 94-01 to the National Science Foundation. Department of Civil Engineering, New Mexico State University, April 1994. 5. White, K. R., and J. Minor. Testing of the 1-40 Bridge. Phase 1 Final Report. FFTWA, U.S. Department of Transportation, 1994.