DESIGN, MONITORING AND EVALUATION OF A LOW ENERGY OFFICE BUILDING WITH PASSIVE COOLING BY NIGHT VENTILATION

Similar documents
INTEGRAL BUILDING AND ENERGY DESIGN OF AN OFFICE BUILDING COMPARISON OF INITIAL DESIGN IDEAS WITH MONITORED RESULTS

ENERKENN: WEB-BASED METHOD TO GENERATE SPECIFIC ENERGY CONSUMPTION DATA FOR EVALUATION AND OPTIMIZATION OF OFFICE BUILDING OPERATION

Limits and potentials of office building climatisation with ambient air

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Potential of natural ventilation in shopping centres

BUILDING INTEGRATED VENTILATION SYSTEMS MODELLING AND DESIGN CHALLENGES

Potential of Natural Ventilation in Shopping Centres Diederichsen, Alice; Friis, Kristina; Brohus, Henrik; Tranholm, Gitte T.

SIMPLIFIED HOURLY METHOD TO CALCULATE SUMMER TEMPERATURES IN DWELLINGS

Work Package 2: Performance of naturally ventilated buildings

Design of passive cooling by night ventilation: evaluation of a parametric model and building simulation with measurements

MONITORING AND EVALUATION OF NIGHT-TIME VENTILATION AND RADIANT COOLING CONCEPTS APPLIED TO LOW ENERGY OFFICE BUILDINGS

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Solar Energy for Hospitals

Energy Efficient Office Buildings with Passive Cooling Results from a Research and Demonstration Programme

BRE Energy Efficient Office of the Future

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

EXPERIENCES WITH LOWEX PCM CHILLED CEILINGS IN DEMONSTRATION BUILDINGS

The Centre for Sustainable Building (ZUB) * A Case Study

Enhancing the Design and Operation of Passive Cooling Concepts

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Optimising Ventilative Cooling and Airtightness for [Nearly] Zero-Energy Buildings, IAQ and Comfort

Work Package 2: Performance of naturally ventilated buildings

EE2E045 A Calculation Method on the Energy Demand of Urban Districts

Potential of ventilative cooling in German residential buildings

ENERGETIC EFFECTS OF DEMAND CONTROLLED VENTILATION RETROFITTING IN A BIOCHEMICAL LABORATORY BUILDING

In general, passive-solar components can be described by the U-value (heat loss coefficient) and

For all those with the ability to influence the design, layout or indoor air quality of buildings

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

Nocturnal natural ventilation for low and zero energy office buildings in Central Chile

CASE STUDIES - CENTRE FOR SUSTAINABLE BUILDING (ZUB) KASSEL, GERMANY

171: An urban office designed for the southern Brazilian climate

Chapter 2 Literature Review

IEA. Retrofit of the Library Building of the University of Bremen

Figure 1: Uncovered and covered PVT collectors

AN APPLICATION OF BUILDING SIMULATION TECHNIQUES TO THE ASSESSMENT OF NATURAL VENTILATION IN OFFICE WITH DOUBLE SKIN FACADE

THE USE OF A SIMULATION TOOL IN ORDER TO OBTAIN THE THERMAL PERFORMANCE OF PASSIVE SOLAR HOUSES IN PORTUGAL

PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING

THE EFFECT OF SUSPENDED CEILINGS ON THERMAL MASS TO REDUCE OVERHEATING

Plus Energy Primary School and Gymnasium, Hohen Neuendorf, Germany

BUILDING SIMULATION AS AN ASSISTING TOOL IN DESIGNING AN ENERGY EFFICIENT BUILDING: A CASE STUDY

Energy Saving Benefits of Daylighting Combined with Horizontal Exterior Overhangs in Hot-and-Humid Regions

BRF Kredit headquarters

Bruck an der Mur. Project summary. Energy concept: Background for the renovation reasons

Design and retrofitting of a hybrid building in Athens

Lean Buildings: Energy Efficient Commercial Buildings in Germany

The energy benefits of View Dynamic Glass

Investigation of indoor climate in a naturally ventilated office building

User Interactions with Environmental Control Systems in Buildings

PROPOSAL FOR A BUILDING ENERGY EFFICIENCY CERTIFICATE. H.-P. Leimer, Prof. Dr.-Ing.1,*

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

Field Measurements of Thermal Comfort Conditions in Buildings with Radiant Surface Cooling Systems

Effect of passive cooling strategies on overheating in low energy residential buildings for Danish climate

Comparison of the Effects of Various Countermeasures on Energy Consumption in a Residential Building

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

Cold Plane Innovative Method for Humidity Condition Control

Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Press Release. Zero Energy Building for Seoul. Fraunhofer ISE Leads Interdisciplinary Team and Develops Energy Concept

Energy Efficient Buildings in Germany An Introduction

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

COMFORT-PRODUCTIVITY Building costs COMFORT-PERFORMANCE. Radiant Heating and Cooling Systems for Better Comfort and Energy Efficiency INDOOR - OUTDOOR

Two Examples for Corporate Identity by intelligent building design

NATURAL VENTILATION STRATEGIES FOR COMMERCIAL BUILDINGS

CFD ASSESSMENTS WITHIN STRONGLY TRANSIENT DOMAINS. Aizaz Samuel, Jon Hand Energy Systems Research Unit University of Strathclyde, Glasgow, Scotland

Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento

Solar gains in the glazing systems with sun-shading

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran

CLIMATE BASED SIMULATION OF DIFFERENT SHADING DEVICE SYSTEMS FOR COMFORT AND ENERGY DEMAND. 6952, Switzerland Canobbio

Tage Møller Architect office building

The feasibility of natural ventilation in plus energy houses in Germany

Commercial EPC Conventions Issue 1 v2 1 st June 2010

Analysis of different shading strategies on energy demand and operating cost of office building

Responsive Building Elements Actual Development and Trends Within IEA

PASSIVE SOLAR OFFICE BUILDING: FIRST EXPERIENCES AND MEASUREMENTS

THE INSTITUTE OF REFRIGERATION

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD

Denmarks first public CO 2 -neutral building

F. Flourentzou Lefkosia new townhall passive bioclimatic Minergie design. Flourentzos Flourentzou: Innovation park EPFL Lausanne, Switzerland

Intelligent tall building envelope technologies and design alternatives for comfort and energy efficiency in hot, arid climate

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

VALIDATED BUILDING SIMULATION TOOL FOR ACTIVE FAÇADES. Fax ,

DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE

COMFORT AND BUILDING PERFORMANCE ANALYSIS OF TRANSPARENT BUILDING INTEGRATED SILICON PHOTOVOLTAICS

WINDOW AREA IN OFFICE BUILDINGS FROM THE VIEWPOINT OF ENERGY EFFICIENCY

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

Air distribution and temperature control in classrooms

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

SIMALATION AND CONTROL SYSTEM DESIGN OF THERMAL CONDITIONS IN BUILDING USING ACTIVE AND PASSIVE RESOURCES

OFF-GRID PHTOVOLTAIC SUPPLIED COOLING APPLICATIONS FOR REMOTE AREAS

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

OPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU

AN EXPERIMENTAL STUDY AND SIMULATIONS OF PHASE CHANGE MATERIALS IN AN OFFICE THERMAL ENVIRONMENT

Project Description. Projected build start date 01 Mar 2010 Projected date of occupation 01 Aug Energy target.

Evaluation methods for indoor environmental quality assessment according to EN15251

Appraising the effects of window opening behaviour in an office building in different climates

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

IMPACT OF OCCUPANT BEHAVIOUR ON LIGHTING ENERGY USE Heverlee, Belgium Corresponding address:

Transcription:

DESIGN, MONITORING AND EVALUATION OF A LOW ENERGY OFFICE BUILDING WITH PASSIVE COOLING BY NIGHT VENTILATION Sebastian Herkel 1, Jens Pfafferott 1 and Matthias Wambsganß 2 1 Fraunhofer Institute for Solar Energy Systems, Heidenhofstr. 2, D-79110 Freiburg, Germany, herkel@ise.fhg.de 2 Universität Karlsruhe (T.H.), fbta, Englerstr. D-76100 Karlsruhe, Germany ABSTRACT In moderate climates, one promising feature to reduce the energy demand of office buildings for air conditioning without reducing comfort is passive cooling by night ventilation. An office building has been designed, realised and monitored for a long time period in the framework of the German research programme solar optimised buildings. The night cooling of the office building has been realised by natural ventilation. The unique possibility of stepwise realisation from design through the maintenance and the monitoring up to the optimisation is used to evaluate the contribution of simulation tools on the design of the buildings. KEYWORDS Night Ventilation, Monitoring, Passive Cooling, Simulation BACKGROUND Former research indicates clearly, that the primary energy demand of new office buildings is dominated by the electricity demand for lighting, ventilation and air conditioning. [Weber 1999]. From a study made by Nilson on Swedish office buildings some recent trends can be derived [Nilson 1997]: Office buildings have experienced a continuous decrease in heating demand following the development of stricter building codes. This increased efficiency of the thermal envelop has been accompanied by higher electricity demands. These data can be transfered to the Central Europe building stock. To reduce the electricity demand without reducing comfort passive cooling by night ventilation is used in the office building of DB Netz AG in Hamm, Germany. Figure 1: View and Floor Plan. The building has an U-shaped floor plan with offices oriented to the ambient and to an atrium, which is defined as an preconditioned outer space. This building has been designed, realised and monitored for a long time period in the framework of the German research programme solar optimised buildings SolarBau, for more information about the building and the programme see www.solarbau.de. The absence of investment subsidies ensured that all design solutions (total primary energy use below 100 kwh/(m_a) with excellent visual and thermal comfort) were realised under representative economical conditions. Concerning the temperature performance in summer, the focus usually lies on the avoidance of not wanted solar gains in the moderate German climate. The remaining internal loads can often be counterbalanced by controlled ventilation, additional night ventilation or by earth-to-air-heat exchangers [Voss 2000].

BUILDING DESCRIPTION AND MONITORING OF NIGHT VENTILATION Within the design process thermal and daylight simulation were used to optimise the energy performance of the building [Wambsganß 1998]. Artificial lights are dimmed and the building is sun-protected by external venetian blinds. The ventilation strategy during the operation hours uses both natural (from ambient and atrium) and mechanical ventilation in the offices, the multifunctional floor areas are mechanically ventilated with air intakes and exhausts. Night ventilation is used to activate the thermal capacity of the bare concrete ceiling. Cooling capacity of an earth-to-air-heat exchanger adds on night ventilation. Fresh air flows through opened flaps due to the stack effect caused by the atrium. In summer, it is automatically activated by the BMS from 2am 8am. Fig.2 gives an overview on the building, its ventilation and the location of the monitored offices. The ventilation strategy depends on ambient temperature (night ventilation), operation time (mechanical ventilation), and user behaviour (natural ventilation). floor atrium exhaust air office monitoring 16 N 26 flap (night) window (day) outlet (night) door (day) 3A024 atrium 16 43 16 19 mixing box earth-to-airheat exchanger bypass supply air T air T room T ceiling Figure 2: Floor Plan, Cross Section and Detail of the monitored office building. Typical ventilation scheme (dotted line: natural night ventilation; drawn line: hybrid day ventilation) and position of the monitored sensors. The buildings energy performance was monitored over 2 years with a high time resolution. Within the monitoring campaign energy demand for heating and ventilation, the internal loads caused by equipment, operative and intra-fabric temperatures, flow volumes by mechanical ventilation as well as climatic site conditions were measured. Occupancy correlates strongly to the working hours. These measurements were completed by short term measurements of air leakage rates using tracer gas technique with the concentration decay method in order to get a more detailed information on the flow paths in different operation status. Tab.1 gives the key information on the building. Information concerning energy consumption, climate and internal loads results from measurements. TABLE 1 Building key information on geometry and energy performance (01/01/2001 31/12/2001). gross volume [m_] net. floor area [m_] operation hours elect.demand f. service tec. [kwh/m_a] heat demand (design) [kwh/m_a] mean daily internal load [W/m_] T ambient (mean) [ C] I - glob,hor (mean) [kwh/m_d] 25,705 5,974 8am 6pm 22.3 65 6.4 11.2 2.56 OPERATIVE TEMPERATURE The results from a one year monitoring on an hourly base have been analysed regarding the operative temperature. A detail study (short-term measurement) showed that the monitored

temperature (Pt 100 mounted at the wall) is not the air temperature but almost identical to the operative temperature. The criterion used is the annual temperature distribution within the office hours (Monday to Friday from 8am to 6pm), the percentage with operative temperatures above 25 C should be lower than 10%. Fig.3 shows the cumulative annual air temperature distribution for three office rooms which represent an outside room (), the multifunctional zone (3A024) and an inside room (). The results shows acceptable indoor climate conditions, though they do not match strictly the comfort criteria. The dots represents the operative temperature in, but sorted by the ambient dry bulb temperature. It shows, that only with ambient temperatures above 26 C there is a strong relationship between the indoor operative temperature and the ambient, while below that temperature other effects like internal and external loads dominate. operative temperature [ C] 30 29 28 27 26 25 24 23 22 T_amb (sorted) (unsorted) (sorted) 3A024 (sorted) (sorted) 0 100 200 300 400 500 600 operation hours [h] ; cutting out 600 h/a of 2,600 h/a Figure 3: Results of monitoring of the DB Hamm building: cumulative operative temperature distribution for typical office rooms within the working hours 8am-6pm (Apr 2000 Mar 2001). The temperature exceeds 25 C in in 280h and in in 400h of 2600h office hours. The effect of night ventilation (efficiency evaluated by the operative temperature) in the office located at the facade () is higher then in the office located at the atrium (). 30 27 24 21 18 15 operative temperature [ C] night ventilation office and atrium night ventilation l i T_amb 3A024 4896 4920 4944 hour of the year, 25th of July 2001 to 26th of July 2001 Figure 4: Operative temperatures from outside to inside:, 3A024 and. The outside room benefits from the cool ambient air. If the outside flaps are closed, room will benefit from the natural ventilated atrium and night ventilation will stop in room (almost no air change). The first experiment is during day: The hybrid ventilation is evaluated by measurement with / without mechanical ventilation and with / without natural ventilation (flaps). Mechanical and natural ventilation intensify each other (in room ). The second experiment is for night ventilation: The flaps both in all rooms and at the bottom and the top of the atrium are opened. The doors between office and multifunctional zone are partly open, partly closed. The measured air change rates in rooms in the second (2B023), third ( and ) and forth floor (4B012) are given in Tab.2. Due to the reduction of the hydraulic resistance, the air

change in rooms with open door is conspicuously higher than in rooms with closed doors. Due to the stack effect the air change rate decreases with the position of the room. : daytime TABLE 2 Air change rates measured by SF6 tracer gas concentration decay method on August 2000 and July 2001, wind velocities remain below 20 km/h during experiment. No ventilation, flaps closed Ventilation, flaps closed No ventilation, flaps open Ventilation, flaps open air change per hour 0.3 1.2 2.0 4.1 different rooms: night ventilation 2B023 door open 4B012 door closed door open door closed air change per hour 6.5 2.5 3.7 2.7 DATA EVALUATION BY SIMULATION In order to quantify the cooling capacity by night ventilation and to better understand the thermodynamic phenomena an adapted simulation is performed. Reasons are to derive hints on the uncertain input parameter of simulations in the design phase, on the optimisation potential of passive cooling and on the necessary complexity of simulation tools. The methodology to use simulation for data analysis can shortly be described in three steps. Set-up of the model, parameter identification based on short term measurements, and analysis of the accuracy of the simulation with long term measurements. We do not aim primarily at an accurate result for every time step but at the excellent modelling of user behaviour and long term building characteristic based on monitoring of a building in service. For a deeper analysis a 4 week summer period from 16 th of July 2001 to 12 th of August 2001 is chosen which represents different climatic conditions concerning ambient temperatures, wind and irradiation. A detailed simulation of a cross section of the building is performed using ESP-r [Clarke 2001]. The measured internal loads and the climatic conditions are used as boundaries. Air flow is modelled by an flow network. (Discharge factors of the flaps are adapted by an parameter variation.) Due to the absence of status information of doors and windows, the user behaviour concerning free ventilation is derived from a Fourier analysis on measured temperatures to identify dates of temperature gradients (opening or closing of flaps etc.). A sufficient correlation between measurements and model is shown in Fig.5. operative temperature 29[ C] 28 27 26 25 24 23 22 :meas :meas :sim :sim 21 4704 4872 5040 5208 5376 hours of the year, 16th of July 2001 to 12th of August 2001 Figure 5: Measured and simulated operative temperatures in office rooms and. Despite of some uncertainties in simulation and measurement the operative temperatures during operation hours are a good match. The period with increasing ambient temperature and solar radiation fit very well in both long term and short term characteristics. The measured operative and surface temperatures of the ceiling are used to quantify the differences between measurements and simulation. The simulation model is checked in two ways. First a Monte Carlo variation on the three main characteristics according to [Keller 1997] was performed (deviation within 2 σ-boundaries): Building capacity C (25%), heat loss

coefficient K (20%), and heat gain coefficient Ψ (20%). From the results given in Tab.3, two lessons can be learned: The mean value of the outer office () fits better while the deviation in the room attached to the atrium is lower. Room A3009 is less sensitive on uncertain model parameters than on ambient conditions and user behaviour. TABLE 3 Results of a Monte-Carlo simulation of the four main characteristics of the simulation model. Deviation δ of the difference T simulation - T measurement within 2 σ-boundaries. T - operative T ceiling T - operative T - ceiling mean bias [K] 0,06 0,06 0,16 0,16 deviation [K_ / 672] 0,050 0,016 0,012 0,024 Secondly a Fourier analysis is performed on both measured and simulated temperatures in order to quantify the buildings dynamic. The operative temperature is characterised by two elements of the Fourier row (4 weeks and 1 day), to characterise the ceiling temperatures an additional period of a week is needed. The results given in Tab.4 show a good correlation of measurements and simulation of both the operative and ceiling temperatures for the long term period. The short time dynamic agrees less for the operative temperature (2h phase shift), since the night ventilation leads to a supplementary, not uniformly distributed harmonic oscillation. TABLE 4 Results of a Fourier Analysis of the measured and simulated operative and ceiling temperatures in room. Operative temperature Ceiling temperature Measurement Simulation Measurement Simulation Mean value 25.0 C 25.1 C 25.5 C 25.1 C Amplitude (672 h) 1.7 K 1.9 K 1.3 K 1.6 K Phase shift 132 h 139 h 90 h 110 h Amplitude (168 h) - - 0.1 K 0.1 K Phase shift - - 40 h 4 h Amplitude (24 h) 0.6 K 0.6 K 0.06 K 0.08 K Phase shift 2.3 h 0.3 h 0.2 h 0.9 h The simulation does not match the measurements at every time step (see Fig.5) but describes the building characteristics incl. user behaviour well (Tab.4), with small deviation (Tab.3). OPTIMISATION OF NIGHT VENTILATION Two strategies will lower the level of operative temperature. Night ventilation (optimised) is to control the flaps at the top of the atrium by the operative temperature in the multifunctional zone 3A024 (set point: 20 C, 10pm 7am) and the flaps at the bottom of the atrium by the air temperature in the atrium (set point: 18 C, 4am 8 am). Additionally, the windows are closed automatically when ambient temperature exceeds 26 C. No change in the shading control, and no mechanical ventilation occurs. This will halve hours with T > 25 C even without mechanical ventilation because the heat gains are reduced and the building is cooled down stepwise and effectively. Mechanical ventilation (additional) is to control the night ventilation time based (base case) without manual engagement (i.e. no illogical user behaviour) and to use mechanical ventilation (earth-to-air-heat exchanger) at operative temperature in the multifunctional zone 3A024 above 24 C. The rooms related to the atrium () can significantly reduce the maximum temperature (direct cooling effect), while the mean temperature in all rooms remain higher (less effect by night ventilation). Additional, natural ventilation effect is partly disturbed (cp. Tab.2) by the mechanical ventilation during day time.

TABLE 5 Classification of temperatures: hours (operation and not-operation time) > 25 C for different night ventilation strategies (16/07/2001 12/08/2001; 672 h). hrs. > 24 C hrs. > 25 C hrs. > 26 C Room 3A024 3A024 3A024 night ventilation (base case) 471 630 654 324 447 495 231 301 313 night ventilation (optimised) 259 382 475 156 224 296 54 101 175 mechanical ventilation (additional) 345 575 571 231 275 332 78 44 144 T ambient 122 111 85 CONCLUSIONS AND FURTHER WORK The building is designed to achieve moderate summer indoor climate conditions. The percentage with operative temperatures above 25 C is around 10%. Passive cooling by free night ventilation improves the thermal comfort without increasing the electricity demand. The presented methodology on data evaluation using simulation allows a deeper insight in the efficiency of night ventilation (air flow paths, user behaviour, building characteristics, heat transfer) and give the possibility to improve ventilation strategies. Hybrid ventilation strategies have to be implemented carefully in order to avoid disturbance of the natural ventilation by additional mechanical driven air flows. We will apply this methodology on other buildings and different ventilation strategies in order to model night ventilation efficiency more precisely. We prepared further experiments to ascertain the coefficient of performance COP for different passive cooling strategies - based on simulation and measurements of air flow and air, operative and surface temperatures: Mechanical (easy to control) and natural (no electricity demand) night ventilation in comparison with concrete slab cooling (not air driven). Further work is to be done to evaluate the influence of user behaviour and changes in the design phase on the efficiency of night ventilation. Acknowledgements The research has been funded by the German Ministry of Economy and Technology under the reference O350006R. References L. Weber, I. Keller. (1999). Stromverbrauch in Bürogebäuden: Gespart ohne zu wollen, ENET Bulletin SVE/VSE Vol. 18/99, pp. 19-23, Switzerland. Nilson, Uppström, Hjalmarsson, (1997). Energy Efficiency in Office Buildings lessons from Swedish Projects, Swedish Council for Building Research. ISBN 91-540-5787-6 Wambsganß M., Fichter E. (1998). Integrales Energie- und Gebäudekonzept für ein Verwaltungsgebäude, 8. Symposium Thermische Solarenergie, OTTI, Germany. Voss, K. et al (2000). Toward Lean Buildings Examples and Experience from a German Demonstration Program for Energy Efficiency and Solar Energy Use in Commercial Buildings, Conf. Proceed. of EUROSUN 2000, Copenhagen, Denmark. Baker N., (1999). Environmental Comfort - Optimization or Opportunity, Conf. Proceed. of Low Energy Building Conference 99, September 17 th to 18 th in Hamburg, Germany. Clarke J A (2001). Energy Simulation in Building Design (2nd Ed.), Butterworth-Heinemann. ISBN: 0-750650-82-6 Keller B. (1997). Klimagerechtes Bauen. Teubner Stuttgart. ISBN: 3-519-05080-3