Experimental and numerical comparison of internal insulation systems for building refurbishment

Similar documents
ScienceDirect. Comparison of steady-state and in-situ testing of high thermal resistance walls incorporating vacuum insulation panels

Thermal insulation performance of reflective foils in floor cavities - Hot box measurements and calculations

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

NUMERICAL INVESTIGATION OF THE EFFECT OF INSULATION ON HEAT TRANSFER OF THERMAL BRIDGES WITH DIFFERENT TYPES

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at ScienceDirect. Procedia Engineering 146 (2016 ) 60 68

The influence of thermal bridge calculation method on the building energy need: a case study

Simulation of Solar Air-Conditioning System with Salinity Gradient Solar Pond

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at ScienceDirect. Energy Procedia 96 (2016 )

Impact of Insulated Concrete Curb on Concrete Balcony Slab

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

Available online at ScienceDirect. Energy Procedia 111 (2017 )

Thermal performance of lightweight steel framed wall: The importance of flanking thermal losses

DYNAMIC EFFECT OF THERMAL BRIDGES ON THE ENERGY PERFORMANCE OF RESIDENTIAL BUILDINGS IN BC. Fuad Baba*, Hua Ge

PASSIVE SOLAR WALL INTEGRATED WITH A LATENT STORAGE LAYER

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings

ScienceDirect. Energy and environmental monitoring of a school building deep energy renovation in Italy

ScienceDirect. Thermal performance of a quartz tube solid particle air receiver

A new approach to the design and construction of the nearly-zero-energy building in Sardinia

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Retrofit of an historical building toward NZEB

Validation of a zonal model to capture the detailed indoor thermal environment of a room heated by a stove

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

Towards nzeb buildings: a historical building case study

Available online at ScienceDirect. Energy Procedia 81 (2015 )

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at ScienceDirect. Energy Procedia 85 (2016)

Full scale experimental performance assessment of a prefabricated timber panel for the energy retrofitting of multi-rise buildings

Analysis of the effect of artificial lighting on heating and cooling energy in commercial buildings

Development of a hot water tank simulation program with improved prediction of thermal stratification in the tank

3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies

Optimum sizing of residential cogeneration for prefeasibility estimations. An analytical approach

Model development of a blast furnace stove

INTENT INtegrated Energy walls Test facility

Available online at ScienceDirect. Procedia Technology 23 (2016 )

Available online at ScienceDirect. Energy Procedia 78 (2015 )

ENCLOSURE SOLUTIONS THERMAL BRIDGING GUIDE FIBERGLAS FOAMULAR THERMAFIBER

Available online at ScienceDirect. Energy Procedia 57 (2014 )

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

THERMAL CONDUCTIVITY MEASUREMENT OF POWDER MATERIAL AND ITS OPTIMUM APPLICATION FOR ENERGY EFFICIENT COLD STORAGE

Cost Optimal Retrofitting Of Shopping Malls In Europe

Thermal Performance of Nvelope NV1 Clip System

CEN/TC 89 - Thermal performance of buildings and building components

WILL THE REAL R-VALUE PLEASE STAND UP

The Importance of Slab Edge & Balcony Thermal Bridges

Available online at ScienceDirect. Procedia Engineering 111 (2015 )

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Thermal performance evaluation of an integrated photovoltaic thermal-phase change material system using Taguchi method

Flanking sound transmission in an innovative lightweight clay block building system with an integrated insulation used at multifamily houses

Simulation Analysis of Mass Concrete Temperature Field

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa

Energy study of a non-residential and historic building in transient conditions

Available online at ScienceDirect

Available online at ScienceDirect. Energy Procedia 78 (2015 )

COLD CLIMATE HOUSING RESEARCH CENTER CCHRC. Whole Wall R-Values

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

IR Cameras and Building Insulation Performance

ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY)

Break it, or Lose it: Thermal Bridging in Building Envelopes

An approach for energy conscious renovation of residential buildings in Istanbul by Trombe wall system

Energy performance analysis of residential buildings in Bari, in the South of Italy

Thermal Performance of Nvelope NV1 Clip System

Comparative Analysis of the Thermal Behavior between Cellular Concrete Blocks and Stabilized Earth Blocks as Wall Materials

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

Available online at ScienceDirect. Energy Procedia 78 (2015 )

SINTEF Building and Infrastructure confirms that. Separating floors with Hunton Silencio 36 / Hunton Silencio Thermo

CEILING TILE. Thermal Mass. Passive Cooling. Thermal Comfort

Quasi-steady state calculation method for energy contribution of sunspaces: a proposal for the European standard improvement

Numerical investigation of the effect of vacuum insulation panels on the thermal bridges of a lightweight drywall envelope

Project Description. Projected build start date 15 Aug 2011 Projected date of occupation 19 Dec Existing external wall construction

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Optimizing the Configuration of a Compact Thermal Facade Module for Solar Renovation Concept in Buildings

Available online at ScienceDirect. Energy Procedia 75 (2015 )

Is Your Envelope Effective? BCBEC Luncheon January 29, 2009

Using phase change materials to reduce overheating issues in UK residential buildings

EXTERNAL WALL PERFORMANCE IN RESIDENTIAL BUILDINGS IN HOT CLIMATE COUNTRIES

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Design, Fabrication and Experimental Study of a Novel Loopheat-pipe based Solar Thermal Facade Water Heating System

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Energy equivalent R-value

Local Temperature Measurements on Full-Size Systems in the Laboratory: Insight into the Extent of Thermal Bridges in Building Envelope Components

Multi-layer Insulation Blanket for Walls

Thermal Analysis of CL-TALON Cladding Support System

Master Level Thesis. Heat transfer tests on EPS material and massive timber wall component. Energy Efficient Built Environment No.

Available online at ScienceDirect. Energy Procedia 78 (2015 )

DYNAMIC ANALYSIS OF ENERGY PERFORMANCE OF DIFFERENT ROOF SYSTEMS DURING THE COOLING SEASON

Energy and Lighting Performance of Buildings in the Neighbourhood Ciudad de los Angeles, Before and After Refurbishing.

COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES

Thermal Bridging and Whole Building Energy Performance

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

FERO RAP TIE AND FAST SYSTEM THERMAL ANALYSIS

ScienceDirect. Experimental study of a single quartz tube solid particle air receiver

Multi-layer Insulation Blanket for Walls

Computational and field test analysis of thermal comfort performance of user-controlled thermal chair in an open plan office

ScienceDirect ENERGY EFFICIENT REFURBISHMENT TOWARDS NEARLY ZERO ENERGY HOUSES, FOR THE MEDITERRANEAN REGION

Transcription:

Available online at www.sciencedirect.com ScienceDirect Energy Procedia 82 (2015 ) 493 498 ATI 2015-70th Conference of the ATI Engineering Association Experimental and numerical comparison of internal insulation systems for building refurbishment Abstract Marco Manzan a *, Ezio Zandegiacomo De Zorzi a,walter Lorenzi b Department of Engineering and Architecture; University of Trieste, via A. Valerio 10,34127 Trieste Italy Edilmaster, via dei Cosulich 10, 34147 Trieste, Italy In order to increase the knowledge of both local builders and designers about the energy efficiency of internal insulation a test chamber has been realized at the Edilmaster site. The test system features two isothermal chambers separated by the specimen under test. The controlled temperatures guarantee a constant temperature difference in order to measure the heat flux with thermofluximeter techniques. In this paper the uninsulated system is a brick wall of about 50 cm thickness which represents a typical solution found in Trieste. Two internal insulation systems, with wooden and metallic studs, have been tested. The measurements highlighted the different thermal behavior between the area covered by the insulation material and the thermal bridges due to studs. The experimental results have been compared with solutions obtained with numerical and analytical methods. 2015 The Authors. Published by Elsevier by Elsevier Ltd. This Ltd. is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Selection and/or peer-review under responsibility of ATI Peer-review under responsibility of the Scientific Committee of ATI 2015 Keywords: wall insulation; energy savings; building refurbishment; thermofluximeter; numerical simulation. 1. Introduction It is well known that buildings in industrialized countries are responsible of a large part of energy consumption and of dangerous emissions in atmosphere; a common figure for Italy is that about the 38% of national energy consumption is absorbed by building climatization [1]. For this reasons European and National regulations impose increasingly tight limits on energy consumption. The respect of these requirements is quite simple in new buildings where the building fabric and system plants can be accordingly designed, exploiting renewable energy resources. The problem is quite more difficult for existing buildings where the interventions can be limited by technical reasons and national regulations. In * Corresponding author. Tel.: +39-040-5583506; fax: +39-040-572033. E-mail address: manzan@units.it. 1876-6102 2015 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the Scientific Committee of ATI 2015 doi:10.1016/j.egypro.2015.11.853

494 Marco Manzan et al. / Energy Procedia 82 ( 2015 ) 493 498 this case, the correct approach is to reduce the building losses by increasing building fabric insulation while assuring internal healthy conditions. The refurbishment of opaque facades in existing building can be done at the internal or external side; the two solutions are compared in [2] where it is highlighted that for identical insulated wall area internal insulation requires less investment cost than the external one. However the internal insulation can be the only solution for historical buildings, this the typical Italian situation especially in historical city centers. A common mistake about the thermal losses computation in refurbished buildings with internal insulation is to evaluate the envelope thermal resistance omitting the effect of structural studs used to build the internal insulation structure, as described in [3] and [4] for light steel frame structures. In order to increase the knowledge of both local builders and designers about the internal insulation, an agreement has been signed between the Università degli Studi di Trieste (Department of Engineering and Architecture, DIA) and Edilmaster of Trieste, a local construction school. The scope of this agreement is to test insulation methodologies applied to common structures used in Trieste. Nomenclature B thickness [m] C thermal conductance [W/(m 2 K)] c specific heat [J/(kg K)] H height [m] L width [m] Ra Rayleigh number Greek thermal conductivity [W/(m K)] density [kg/m 3 ] temperature [ C] Subscripts ctr center std stud c cold h hot w wall eff apparent in stud channel 2. Test chambers For testing the insulation systems, a calibrated hot and cold chamber has been realized at Edilmaster facility. In the first phase, wall conductance has been measured using a thermoflux system [5]. In a second phase, the system will be updated in order to perform measures using a calibrated hot box method so in the design of the two chambers, we have followed the requirements of UNI EN ISO 8990:1999. The system is composed by two insulated chambers with a length of 4.70 m, width 2.24 m and height 2.20 m, the two chambers are separated by the test wall with dimensions of 1.90 x 1.93 m and area equal to 3.67 m 2. Table 1 reports the composition of chamber walls:

Marco Manzan et al. / Energy Procedia 82 ( 2015 ) 493 498 495 Table 1. Chamber structures material walls ceiling floor Thickness [mm] material Thickness [mm] Material Thickness [mm] plasterboard 12.5 Plasterboard 12.5 EPS 200 EPS 75 EPS 100 Wood board 25 Plasterboard 12.5 Mineral wool 50 EPS 100 The temperature in the cold chamber is kept constant by an air-conditioning unit; whereas, the hot chamber is kept at a higher temperature by means of two 100 W electrical resistances with a fan for air distribution. A thermostat maintains the hot chamber temperature at about a constant value of 26 C by switching on or off one of the two resistances. The cold chamber is maintained at a temperature of nearly 5 o C, value selected after some trials in order to increase the time between de-frosting cycles. The values have been selected in order to maintain a constant and sufficiently elevated temperature difference among rooms. The measurement system, product by LSI, is composed by: Data acquisition system BABUC A Heat Flux Plate BSR240 4 RTD BST240 for the measure of the wall superficial temperature 2 RTD EST0338#s for the measure of chambers air temperature The uniformity of the wall temperature in the zone of the measure is checked with an infrared camera FLIR E 60 bx. 3. Measured Walls A typical wall traditionally used in historical buildings located in Trieste has been selected for the measurements. It is a supporting wall assembled with solid bricks of size 55x25x12 cm. Considering internal and external 1.25 cm thick plaster the overall thickness of the wall is 0.51 m. Before applying the insulation layers the thermal conductance of the base wall has been measured using the thermofluximeter equipment obtaining C w=1.64 W/(m 2 K). Two intervention on the base wall have been considered by applying 3 cm EPS boards at the hot side of the wall separated by studs at a distance of 500 mm then covered by a 12.5 mm thick plasterboard as presented in Figure 1 a). The difference between the two systems is the type of vertical studs having the same size 60x30 mm; wooden studs in the former and C- shape metallic studs in the latter. Figure 1 b) presents a picture of the test wall with metallic studs without the plasterboard cover layer. The same picture shows the bended metal ribbons used to fix the metal studs to the wall. It is worth noting that this disposition creates a thermal bridge between the cold wall and the internal warm plasterboard. 4. Results Four measures have been carried for characterizing the insulation performance on the tested wall: the specific heat flux on the center of insulation panel and on the wooden and metal studs. Table 2 reports the measured values: cold and hot temperatures, averaged on the two thermoresistances positioned on the hot and cold sides of the specimen, and the resulting one dimensional thermal conductance. We can observe that, as expected, the values of conductance measured at the centre of the EPS board coincide, while the conductance on the wood stud is equal to 64% of the one measured on the metallic stud.

496 Marco Manzan et al. / Energy Procedia 82 ( 2015 ) 493 498 The low performance of metal studs can be shown also In Figure 3 b) in which the effect of metallic studs is clearly visible. Table 2 highlights the requirement to evaluate a real conductance and hence transmittance of the insulated wall taking into account the effect of the supporting studs too. In the following two techniques are presented in order to obtain the overall thermal performance of the wall. Studs Wall c Eps B st a) b) Plasterboard L is L st Figure 1: internal insulation system with metallic studs a), picture of the internal assembly b) Table 2. Experimental Results 4.1 Wall conductance Wooden Metal center stud center stud c 6.2-1.1 6.1 6.2 h 24.7 23.2 24.3 22.9 11.3 22.0 11.1 23.5 C 0.61 0.90 0.61 1.41 Based on the results presented in Table 2 the overall conductance of the insulated wall has been obtained. For this the methods of UNI EN ISO 6946:2008 has been used. The thermal characteristics of the non uniform layer composed by metal and wooden studs and insulation board, presented in Figure 1 a), has been obtained using the measured fluxes reported in Table 2 and a conductivity of 0.21 W/(m K) for the plasterboard layer. Table 3 reports the wall conductance along with the error between the adiabatic and isothermal approach of UNI EN ISO 6946:2008. It is worth comparing the results of Table 3 with the ones reported in Table 2. Considering also the studs the conductance is 6.6 % higher for wooden studs and 32.8% higher for metal studs respect the one obtained using EPS board center values only. Table 3: Conductance of whole wall C w error Wooden suds 0.65 0.7 % Steel Studs 0.81 16.1 %

Marco Manzan et al. / Energy Procedia 82 ( 2015 ) 493 498 497 5. Numerical results The results reported in Tables 2 and 3 clearly show that it is a mistake to disregard the effect of studs in for computing the conductance and therefore transmittance of a refurbished wall. Along with the experimental approach, two calculation methods are also presented. 5.1 Analytical calculus The methods of UNI EN ISO 6946-2008 are used with material properties obtained in UNI EN ISO 10456:2008, with reference to Figure 1 a) the problem is easy for the wooden studs, while the thermal resistance of metallic studs must be evaluated because of the convective flow inside the hollow narrow channel between studs and wall. To evaluate the thermal resistance of a metallic stud the following correlation is applied: (1) Where H st is the camber height. The metallic stud value conductance is C st = 1.38 W/(m 2 K), and takes into account using Eq. (1) the convective resistance only, while neglecting stud thin metal wall conductivity and radiation effects inside the narrow cavity. Table 4 reports the computed values and the percentage difference of the wall conductance with the experimental values of Table 3. Table 4. results of analytical calculus 5.2 Numerical simulation C is C st C w Wood stud 0.66 1.09 0.78 +20% Metallic stud 0.66 1.38 0.84 +3.8% The simplified analytical method does not take into account the multidimensional heat transfer problem, furthermore the heat transfer through steel studs has to take into account also the effect of radiation inside the hollow chamber between the stud and the wall, furthermore, conduction in the metal studs cannot be neglected. In order to complete the analysis a three-dimensional simulation of the insulation system has been carried using the software Ansys Fluent 14.5. The structured grid features about 150 000 hexahedral cells, with 2 nd order upwind discretization for flow and heat transfer inside stud and S2S model for radiative heat transfer computation. Table 5 reports the numerical results using the values for the whole wall, while Figure 2 presents the comparison of plasterboard surface temperature obtained with the numerical simulation and a thermographic picture. The inspection of Figure 2 shows how the metallic stud influences the surface temperature, for instance the effect of metallic brackets, which connect the stud to the wall, is clearly visible in both the numerical simulation and infrared picture. 6. Conclusions An experimental and numerical approach has been performed in order to obtain the thermal performance of two internal insulation systems. The effect of wooden and metallic studs has been highlighted. The results show that the use of conductance values neglecting the studs effect leads to an overestimation of the insulation performance of refurbished walls. Overall conductance values have been obtained using experimental results and two computational methods. The numerical results give insulated wall conductance values that fall within a 10 % difference with the experimental results. However, the results

498 Marco Manzan et al. / Energy Procedia 82 ( 2015 ) 493 498 show that for a real comparison between local heat flux values and the overall heat transfer through the insulated wall a hot box apparatus should be used, therefore such equipment will be implemented in the already existent test facility. a) b) Figure 2: Comparison between simulated temperatures a) and thermographic picture b) Table 5. Results of numerical computation C ctr C std C w Wooden stud 0.65 0.97 0.70 +7.1% Metallic stud 0.65 1.21 0.73-10.0 % Acknowledgements This work was supported by Università degli Studi di Trieste with FRA 2013 grant. References [1] CTI Comitato Termotecnico Italiano Energia e Ambiente. Attuazione della certificazione energetica degli edifici in Italia Rapporto 2014.. [2] Kolaitis, Malliotakis E, Kontogeorgos DA, Mandilaras I, Katsourinis DI, Founti MA. Comparative assessment of internal and external thermal insulationsystems for energy efficient retrofitting of residential buildings. Energy and Buildings 2013, 64: 123 131 [3] Kosny J, Yarbrough D, Childs P, Mohiuddin SA. How the Same Wall Can Have Several Different R-Values: Relations Between Amount of Framing and Overall Thermal Performance in Wood and Steel-Framed Walls, in Thermal Performance of the Exterior Envelopes of Buildings X, proceedings of ASHRAE THERM X, Clearwater, FL, 2007. [4] de Angelis E, Serra E. Light steel-frame walls: thermal insulation performances and thermal bridges, Energy Procedia 2014; 45, p 362 371. [5] Buratti C, Moretti E. misura della resistenza termica di un campione in muratura, 63 Congresso Nazionale ATI - Energie per lo sviluppo sostenibile - Palermo 23-26 settembre 2008 Biography Marco Manzan is Associate professor of Thermodynamics and Heat Transfer at the University of Trieste. Main research effort has been committed to the numerical analysis of heat transfer problems working on finite element solution of thermal problems, stability of numerical methods in convection problems and energy buildings performance simulation.