NRCC Guarded Hot Box Testing (ASTM C ) for Energy Efficiency of a Total Roof Assembly

Similar documents
ROOFING EPDM ELASTOMERIC SHEET ROOFING FULLY ADHERED- CONVENTIONAL

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

SECTION THERMAL INSULATION

TGIK.R Roofing Systems, Uplift Resistance. Roofing Systems, Uplift Resistance

(Project Location) (your firm's name)

JOHNS MANVILLE CONTINUOUS INSULATION WALL SYSTEM MASTER SPECIFICATION June 2014 CSI FORMAT SECTION FOIL-FACED RIGID INSULATION

2001 COMPANY. WIND BLOWN DEBRIS RESISTANT ROOF ASSEMBLIES Hurricane 140 Mph And Tornado 250 Mph Wind Blown Debris

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

Gold Bond BRAND Gypsum Sheathing

SECTION CEMENTITIOUS SHEATHING

EPA Seal and Insulate with ENERGY STAR Insulation Product Certification Report: GAF EnergyGuard Polyiso Insulated Sheathing Board Insulation

TGIK.R Roofing Systems, Uplift Resistance. Roofing Systems, Uplift Resistance

THERMAL AND AIR BARRIER WALL SYSTEM

A. National Roofing Contractors Association (NRCA) Roofing and Waterproofing Manual

1. Clean the existing totally adhered or mechanically attached roof membrane: TPO, EPDM, Hyplon,

2001Co. Compression Board Air Seal Terminations Are a Patented Roof Application Technique

This article will address the test methods used to determine R-values and their relative degree of accuracy.

REPORT HOLDER: STAR R FOAM MANUFACTURING, INC. EVALUATION SUBJECT: STAR R FOAM INSULATION BOARDS

CELCORE CELLULAR INSULATING CONCRETE SPECIFICATION FOR RETROFIT PLACEMENT OVER EXISTING ROOF MEMBRANES

THE EFFECT OF WINDOW-WALL INTERFACE DETAILS ON WINDOW CONDENSATION POTENTIAL

Coal Tar Application and Design Considerations

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

SHEET METAL ROOF TEST REPORT

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

4.2 Materials Membranes: inch, inch or inch thick D General

RECOMMENDED DESIGN SPECIFICATION

Multi-Institutional Academic Health Science & Research Center Evansville, IN

INSTALLATION MANUAL. ZIP System R12 Sheathing. Contents. 07 ZIP System R12 Sheathing Window Installation 08 ZIP System R12 Sheathing Siding Guidelines

Thermal Bridging in Residential Construction

Lamit Industries, Inc. 710 Marion Road Columbus, Ohio P-(614) F-(614)

INSULATION OWENS CORNING INSULATION PRODUCTS IN THIS SECTION:

Construction Standards PAGE

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Existing Roof Assembly Information. 2 nd Roof Assembly

Standard practice for installing cellulose building insulation

Wall Energy Rating Impact of Air Leakage on Energy Performance

PROJECT DIRECTIVE # FOR KALISPELL PUBLIC SCHOOLS

Alply CLASSIC WALL Architectural Insulated Panel Wall System

A Guide to Cold Storage Roof System Design Prepared by GAF Technical Services February, 2019

Mechanical Attachment of Separation Panels Hot Asphalt Attachment of Separation Panels

Contents. ZIP System R-Sheathing

1 of 17. PO Box Bellevue Rd, Newark, DE V F

Why test a system that has already been tested? Typical Manufacturers information for window to wall interface and basis for reported test results.

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

SECTION THERMOPLASTIC MEMBRANE ROOFING. C. Flashings. D. Roofing cant strips, stack boots, roofing expansion joints, and walkway pads.

SL175 Panel Technical Data Guide

Firestone Polyiso Boards

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER:

Architectural Roof and Wall Products Guide Specifications

TABLE OF CONTENTS. 1.0 INTRODUCTION 1.1 Greenstone Structural Engineered Panels 1.2 Drawing and Element Numbers

SRP-AirOutshield ROOF Issued:

Pella 250 Series. Wood Frame Construction with Vinyl Siding... V250-ID-888 Wood Frame Construction with Brick Veneer...

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

application instructions

BASIC VENTILATION REQUIREMENTS

SECTION STRUCTURAL INSULATED PANELS

SINGLE PLY MEMBRANE ROOF SYSTEM

A. Source Limitations: Obtain each type of building insulation through one source.

SECTION GYPSUM BOARD

Subject: NRCA MRCA Joint Technical Bulletin. Date: January 2008 NOT COMPROMISE.

ROOFING INSTALLATION GUIDELINES

Trusted Tested Tough Kalaeloa Blvd, Kapolei, Hawaii Phone (808) Fax (808) Neighbor Islands (800)

SECTION CEMENTITIOUS WOOD FIBER DECKS

A. This Section provides information regarding vapor permeable roof underlayment for the exterior roof.

Attachment of Exterior Wall Coverings Through Polyiso to Wood or Steel Wall Framing

Closed-Cell Spray Foam Insulation. Performance in Residential and Commercial Buildings During Adverse Weather

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

Update In Progress. Division 7 Thermal and Moisture Protection Page Section ROOFING AND WATERPROOFING

Technical Data Sheet

ACFoam-II HCFC Free "Green" Polyiso Specification

A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written instructions, whichever are more stringent.

ACFoam -III Specifications Atlas Roofing

TSX Insulation for Exposed Use ROOF WALL SPECIALTY

INSTALLATION GUIDE EPS FOAM

Universal Door Installation Instructions (Good, Better, Best)

Application Specification:

Perm-A-Barrier VPS (Vapor Permeable Sheet)

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MODIFIED BITUMINOUS SHEET ROOFING REPORT HOLDER:

Johns Manville MinWool Water & Fire Block Mineral Wool Insulation

Wood Decks Testing Reveals Best Wood Roof Deck Systems to Resist Wind-Uplift by Fulton Desler, senior engineer, APA The Engineered Wood Association

SECTION LIGHTWEIGHT INSULATING CONCRETE

Light-Metal Roof Edge, Raised

Eclipse Energy Guard. Product Information & Installation Manual General Installation Requirements

The better way to build TM. Installation Manual NAILBASE PANELS

SECTION 1 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

P R O D U C T - S P E C

OREGON CONVENTION CENTER CHILLER PLANT RE-DESIGN CD SET

Tuscaloosa Police Station

Envelope Highlights Mandatory Measures Prescriptive High Performance Walls 150.1

Recommended Fastening Patterns for Rmax Insulation in Low Slope Roofing Applications

GAF EnergyGuard Polyiso Wall Sheathing

GOWANDA, NEW YORK SEPTEMBER 18, 2008 ARCH PROJECT NO

Architectural Wall Products Guide Specifications

Transcription:

Introduction 2001 Company, contracted NRCC/IRC to evaluate and determine both the thermal resistance and air leakage characteristics of five roofing specimens under controlled laboratory conditions. The roofing specimens were tested as thermal resistant barriers as built by 2001 Company & IRC and evaluated in the IRC Guarded Hot Box (Figure 1) under the ASTM C-1363 standard. Objective The objective of this project is to determine, through laboratory measurements and calculations, the thermal resistance and air leakage profiles for five 8 X 8 roof specimens. Test Procedure The principal test method for determining the thermal performance of walls is ASTM Standard C- 1363. Air leakage measurements of the specimens were carried out in the Guarded Box after each thermal evaluation according to ASTM Standard E- 238. This procedure consisted of sheathing the specimen and surround panel with a sheet of polyethylene on the roomside then mating the air leakage apparatus (shown in Figure 1) onto the Guarded Box on the roomside of the specimen. The apparatus was strapped in place and the apparatus-guarded Box interface joints were stuffed with backing rod and sealed with vinyl tape. Figure 1 NRCC_032806_MS 1 Last Rev: 032806

Figure 2 shows the freezer building side of the test chamber. The Freezer building side Is maintained 0 degrees F during the test process. Fig. 2 Freezer Building Side The insulated wall 10 ft x10 ft painted green (lower right) with an 8 ft x 8 ft center space for a roof assembly. Test sample will be exposed to zero degrees F for 78 hours in the freezer building An 8 ft x 8 ft roof assembly test sample comprised of a roof waterproofing mem brane, cover board-separator sheet, insulation, fire barrier, vapor-air barrier, structural roof deck, fasteners, adhesives, and any other components is installed in the insulated wall. The insulated wall in green with a metal deck roof sample, abuts the freezer building side of the guarded hot box test chamber. The roof waterproofing membrane is exposed to the freezer building to be maintained at zero degrees F for 78 hours. Notice in Fig. 3, how the metal roof deck carrying the roof assembly is sealed with urethane foam into the center of the insulated wall. Tim O'Connor of NRCC positions the hot box into the roof assembly test sample Fig. 3 Roof Assembly is Sealed with Urethane Foam NRCC_032806_MS 2 Last Rev: 032806

Once the 8 ft x 8 ft roof assembly test sample is sealed into the insulated center wall, a Guarded Hot Box is sealed to the interior building side of the roof assembly, as shown in the Figure 4. In figure 5 there is an electric heater at the bottom of the guarded hot box that will maintain this two-foot wide 8x8 hotbox at plus 68 degrees F through the test duration. There are many thermocouples inside the test chamber to monitor the air and heat flow during the test cycles. Figure 4 If you look closely at the lower picture (Figure 5) you can see the thermocouples through the interior of the guarded hot box. Also note the electric heater at the bottom. Figure 5 NRCC_032806_MS 3 Last Rev: 032806

The test chamber has four sections. 1. Left side 12x12 freezer building to maintain exterior roof waterproofing membrane at zero degrees F. 2. Center insulated wall that the roof assembly is mounted into 3. The Hot Box, a two-foot wide 8 ft x8 ft electric heated space, maintained at plus 68 degrees F to measure BTU s of electric to maintain temperature in the hot box 4. Right side Guarded Building. Once the hot box is installed on the roof sample, it is guarded from laboratory atmospheric conditions by a 12 ft x12 ft insulated building in which the interior heat of plus 68 degrees F and 50% relative humidity is maintained. This guard building will keep the hot box itself from loosing heat during the test cycle to changing laboratory atmospheric conditions. Figure 6 Notice in Figure 6 how the guarded building will be sealed over the hot box to the roof sample wall, that is sealed to the freezer building. Figure 7 NRCC_032806_MS 4 Last Rev: 032806

Test samples are carefully constructed, and every detail is recorded, to document the total roof assembly as installed with accuracy. Tim O Connor assists in installing the two-layer 1.5-inch ISO that is staggered two-feet in length and width over the bottom insulation layer. Figure 8 Test Sample 1A fully adhered EPDM membrane to mechanically fastened ISO (1 per 4 Sq.Ft) Test Sample 1B Mechanically attached EPDM over fastened ISO Insulation joints were formed with less than 1/16-inch gap between boards. A roofing nail could not fall through the joints. Figure 9 Note the manufacturing injection wrinkles (figure 10) in the ISO insulation board surface, which is very common. The following 5 points of foam injection during the manufacturing process create thermal deficiencies in the ISO board. Figure 10 NRCC_032806_MS 5 Last Rev: 032806

Sample 2 2001 Co. patented air barrier ( shown in Figure 11) with loose laid insulation weighted in place with half-inch gypsum. Figure 11 As shown in Figure 12, there are no screws or fasteners used with 2001 Company roof assembly. Figure 12 Figure 13 The roof membrane is totally adhered to the gypsum and extended down the perimeters and penetrations to the air barrier, to stop lateral air infiltration into the roof assembly. NRCC_032806_MS 6 Last Rev: 032806

Energy efficiency test chamber. The freezer roof membrane side is monitored with thermocouples for consistency of zero degrees F air flow across the roof membrane surface. Figure 14 Figure 15 In order to get the 2 ft x 8 ft wood frame out of the hot box test chamber, the specimen was picture framed around the 22- gauge metal deck with U channels, and the metal deck panels were cross braced together with pipes. Figure 16 NRCC_032806_MS 7 Last Rev: 032806

Sample 3 2001 Co. patented air seal perimeter application technique uses slow rise adhesive foam to stop horizontal air infiltration under nailers and at through roof penetrations. Figure 17 Metal deck joints and weld holes are air sealed. Insulation boards are adhered to the deck and themselves with slow rise adhesive foam. Note overspray on insulation butt joints to stop convection air currents in the roof assembly. Figure 18 Figure 19 TEMPORARY ROOF is accomplished with a nominal half inch spray foam cover which can be installed as soon as the deck is in place. After the building is constructed and other tradesmen have left the roof, the finish waterproofing membrane is installed. Note the temporary roof can last for over one year. NRCC_032806_MS 8 Last Rev: 032806

Samples 4 and 5 2001 Co. patented air seal perimeter application technique uses slow rise adhesive foam to stop horizontal air infiltration under nailers and at through roof penetrations. Sample 4 (Fig. 21) used two layers of 2 ISO adhered with adhesive foam. Figure 20 Metal deck joints and weld holes are air sealed. Insulation boards are adhered to the deck and themselves with slow rise adhesive foam. Note overspray on insulation butt joints to stop convection air currents in the roof assembly. Figure 21 Figure 22 Sample 5 (Fig. 22) used one layer of 4 ISO adhered to the metal deck with slow rise adhesive foam. Both samples were covered with a loose laid EPDM wind vented membrane. NRCC_032806_MS 9 Last Rev: 032806

Summary of NRCC Test Results Page 10 NRCC_032806_MS 10 Last Rev: 032806

The problem in commercial roofing systems is that the common method of determining the total R value, that is the real ability of a roof assembly and waterproofing membrane system to resist the transmission of heat or cold, is not evaluated correctly on the actual roof assembly as installed. The individual sum of the R values of each specific component of a roof assembly are simply added up to ass-error-taint the Total R value. Factors Causing Roof Assembly Energy Deficiencies 1. Convective air currents inside the building, egress up through the roof deck 2. Lateral air infiltration, through perimeter and penetrations in the flutes of a metal deck 3. Metal thermal bridging of mechanical fasteners 4. Insulation joint line heat escape 5. Mechanically attached membrane ballooning 6. Sustained extreme cold and hot temperatures for three days effect on the specific gas entrapment of the different insulation formulas 7. Insulation manufacturing deformities, voids in the board, improper chemical reaction etc. 8. Through roof deck penetrations and attachments All these deficiencies create different thermal energy deficiencies that lower the total R value. In roof assembly testing for wind uplift or for fire safety at Underwriters Laboratories (UL) or at Factory Mutual Insurance (FM), the total roof assembly, including a roof deck, is tested as installed on the roof, to get a rating. The roofing industry needs to adopt a total roof assembly concept in rating energy efficiency or R value of roof assembly. The guarded hot box method ASTM C1363-97 is the best test method available today as mandated by Federal Regulations, according to FTC code 16-CFR 460, on insulation testing of any building assembly. NRCC_032806_MS 11 Last Rev: 032806

Figure 23 below shows a 2001 Company roof where snow melt occurred over insulation joints from convection air currents and thermal transmission from mechanical fasteners on a totally adhered EPDM over a single layer of 3 ISO with six fasteners per board. Figure 23 NRCC_032806_MS 12 Last Rev: 032806