CURRENT NORTH LAS VEGAS ADDENDA

Similar documents
City of Middletown WATER & SEWER DEPARTMENT 82 Berlin Street Middletown, CT TEL: (860) FAX: (860)

SECTION PUBLIC WATER SERVICE CONNECTIONS

UNIFORM DESIGN AND CONSTRUCTION STANDARDS FOR EXTENDING WATER DISTRIBUTION SYSTEMS SECTION 2 DESIGN STANDARDS

Underground Piping for Private Hydrants & Sprinkler Supply Line

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.

SECTION 401 WATER PIPE AND FITTINGS 2.2 POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS

TABLE OF CONTENTS PART III MINIMUM DESIGN STANDARDS Section 115 WATER DISTRIBUTION SYSTEM GENERAL SIZING LINES 115.

WASHOE COUNTY DEPARTMENT OF WATER RESOURCES WATER DESIGN STANDARDS

SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

CITY OF LA MARQUE, TEXAS CHAPTER 3 WATER SYSTEM DESIGN CRITERIA

A. Introduction 7 1. Purpose 7 2. Authority 7 3. Contact 8 4. Plan Submittal Process 8 B. Design Standards General 11 a. Future Extensions 11

WATER MAIN EXTENSION DESIGN REQUIREMENTS

APPENDIX B STANDARD CONSTRUCTION DRAWING NOTES

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD

PUBLIC WORKS DEPARTMENT GENERAL NOTES

Rockwood Water People s Utility District Cross Connection Implementation and Regulations

SECTION MEASUREMENT AND PAYMENT

SECTION VI POTABLE WATER, RECYCLED WATER, AND SANITARY SEWER SYSTEM FACILITY CONSTRUCTION

This is only a general checklist; please refer to the CVWD Development Design Manual (DDM) for all requirements and regulations.

120 WATER DISTRIBUTION SYSTEMS

Charlottetown - Water & Sewer Utility Minimum Standard of Acceptability for Water, Sewer & Sprinkler Connections

Town of Cornwall Water & Sewer Utility Corporation

CITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER

SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES

Engineering Design Center. Standard Drawings. 1st Edition -January 2016

ITEM NO. 824 SERVICE SUPPLY LINES (WATER)

WATER RULE 11 WATER SERVICE CONNECTIONS, WATER METERS AND RELATED APPARATUS

Ice Rink Renovation & New Clubhouse

San Antonio Water System Standard Specifications for Construction ITEM NO. 824 SERVICE SUPPLY LINES (WATER)

BACKFLOW PREVENTION ASSEMBLY INSTALLATION STANDARDS

SECTION 41 - WATER DISTRIBUTION SYSTEMS TABLE OF CONTENTS

ROUTE 3 OLD WINTHROP ROAD PROJECT LOCATION I-95 PROJECT LOCATION WESTERN AVENUE NORTH BELFAST AVE.

SECTION 2 Design Manual

NEW WATER SERVICE TAPS AND SPECIFICATIONS FOR REQUIRED METER SETTINGS

SUPPLEMENTAL SPECIFICATIONS AND DRAWINGS TO THE IDAHO STANDARDS FOR PUBLIC WORKS CONSTRUCTION TABLE OF CONTENTS

8 WATER DISTRIBUTION FACILITIES

Addendum No. 1 GORDON WATER MAIN REPLACEMENT PWP Bid No.: WA TMWA Capital Project No.: October 3, 2018

NEW WATER SERVICE TAPS AND SPECIFICATIONS FOR REQUIRED METER SETTINGS

CHAPTER 5 WATER SYSTEM DESIGN STANDARDS

1. Required Minimum Flow:

CHAPTER 8 WATER SUPPLY SYSTEM

YAKIMA COUNTY, WASHINGTON. Special Provisions For Water Main Construction

East Wenatchee Water District Supplemental Provisions to the 2012 WSDOT/APWA Standard Specifications

4A General Information A. Concept... 1 B. Conditions... 1

Public Water Supply District #2 of St. Charles County, Missouri

SECTION DUCTILE IRON FITTINGS. A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller.

ARRANGE FOR INSPECTION FORTY-EIGHT HOURS IN ADVANCE

County of Sacramento Standard Construction Specifications January 1, 2008 TECHNICAL PROVISIONS

Town of Huntertown Lima Road * PO Box 95 * Huntertown, IN Phone (260) * * Fax (260)

**RESPONSES TO COMMENTS MUST BE RETURNED WITH REVISED PLANS FOR FINAL PLAN APPROVAL.** Approved as submitted X Needs attention N/A Non-Applicable

WATER SERVICE APPLICATION Not to be used for Fire Service

GUIDE TO WATER SERVICE APPLICATIONS

Chapter 3: Permit Procedures and Requirements

Canyon Lake Water Service Company. Design Guidelines and Specifications

INSPECTION AND ACCEPTANCE FOR MAINTENANCE

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX B WATER AND WASTEWATER SERVICE CONSTRUCTION SPECIFICATIONS

SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION POLYETHYLENE PRESSURE PIPE

SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES

CITY OF TACOMA Department of Public Utilities - Water Division

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

PART 5 WATER SYSTEMS

T a b l e o f C o n t e n t s

SECTION VII WATER. Concrete anchor and thrust blocks shall be provided at all discontinuities in accordance with Standard Details G-7.1 and G-7.2.

Changes for the. TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details

All service lines shall conform to the following requirements:

CONSTRUCTION PROCEDURE

Procedures for Connecting to Central Sewer System

SECTION WATER SERVICE CONNECTIONS

SECTION 8 SEPARATION OF LINES

MAXIMUM TRENCH WIDTH AS REQUIRED SEE MEASUREMENT AND PAYMENT SECTION OF SPECIFICATIONS

SECTION 2100 WATER MAIN

DESIGN AND CONSTRUCTION STANDARDS AND SPECIFICATIONS TABLE OF CONTENTS SECTION 5 WATER DISTRIBUTION SECTION DESCRIPTION PAGE

WATER DISTRIBUTION STANDARD SPECIFICATIONS

PROPOSED CONSTRUCTION BUILDING CODES FOR TURF AND LANDSCAPE IRRIGATION SYSTEMS

ARRANGE FOR INSPECTION FORTY-EIGHT HOURS IN ADVANCE

DESIGN CRITERIA AND STANDARD DRAWINGS FOR WATER AND SEWER FACILITIES

SERVICE LINES, METERS AND APPURTENANCES

CITY OF GAINESVILLE DEPARTMENT OF WATER RESOURCES

SECTION FIRE HYDRANTS

San Antonio Water System Standard Specifications for Construction ITEM NO. 813 WATER SERVICE FOR FIRELINES

CULINARY WATER SYSTEMS

SECTION UNIT PRICES. A. This Section specifies administrative and procedural requirements for the unit prices.

MATERIAL AND INSTALLATION SPECIFICATIONS FOR CONSTRUCTING WATER SERVICES INSPECTIONS

EXCAVATION WORK IN PUBLIC RIGHT-OF-WAY GENERAL NOTES

1. Will have water lines designed by a North Carolina Registered Professional Engineer.

A.1 WATER SYSTEM PLAN SUBMITTAL PROCEDURES AND GENERAL REQUIREMENTS

lates.htm. LIST OF EXHIBITS

Ivins City Standard Specifications for Design and Construction Part 2 Engineering and Design Standards

Copper-Type K soft Drawn 40, 50 HDPE 100 and larger

HUMBOLDT COMMUNITY SERVICES DISTRICT WATER AND SEWER DESIGN AND CONSTRUCTION STANDARDS

SECTION 8 WATER SYSTEMS

Section 5 Design Criteria Domestic Water Facilities

CUYAHOGA COUNTY DEPARTMENT OF PUBLIC WORKS - SANITARY DEPARTMENT DETAIL

KC Water Rules and Regulations For Water Service Lines

SECTION WATER DISTRIBUTION SYSTEM

SKAMANIA COUNTY PUD NO. 1

KC Water Rules and Regulations For Water Service Lines

SECTION NATURAL GAS DISTRIBUTION

SECTION WATER MAINS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA

VALLECITOS WATER DISTRICT SECTION POLYVINYL CHLORIDE (PVC) PRESSURE PIPE

Transcription:

SECTION 1 Section 1.01.73 Fire Service Meter ADD: Type I is not approved for installation in the City of North Las Vegas service area. Section 1.01.107 Pressure Reducing Valve (PRV) or Pressure Regulator ADD: A valve for automatically sustaining or reducing water pressure in a main, lateral, or service line at or to a preset value. The term includes a pressure-reducing valve, a pressuresustaining valve, and a valve that incorporates both features Section 1.01.108 Pressure Regulating Valve ADD: A valve to protect against downstream static pressure damage. Should the downstream flow be stopped, the regulator immediately responds and limits the downstream pressure thus preserving the integrity of the downstream appurtenances Section 1.01.110 Pressure Vacuum Breaker ADD: A vacuum breaker that: A. Contains an independently operating, internally loaded approved check valve, and an independently, loaded air inlet valve located on the discharge side of the approved check valve; and B. Is equipped with properly located, resilient seated test cocks and tightly closing, resilient seated shutoff valves that are attached at each end of the assembly. Section 1.06 Overtime Inspection Fee ADD: Overtime inspection shall apply whenever a contractor is performing work within the proximity of CNLV facilities outside of normal working hours. SECTION 2 Section 2.03.01 Section 2.03.04.B Section 2.10.01 and 2.10.03 Submittal of Hydraulic Analysis for Review and Approval Source HGL and Demand Calculations Steel Casing and Reinforced Concrete Pipe (RCP) Delete and replace with: A. The hydraulic analysis report shall be submitted with the project design for review. However, for larger projects such as a major subdivision, submitting a hydraulic analysis report prior to water plan submission may be required ADD: In the written report of the analysis, account for these types of losses. Do not include these types of appurtenances in the model RCP casings are not approved for installation in the City of North Las Vegas service area. Section 2.11.01 Valves ADD: K. A minimum of two (2) valves shall be located at every mainline tee, or three (3) valves at every mainline cross. Section 2.11.02. Gate Valves ADD: E. The installation of a valve vault is required for all gate valves greater than twelve (12) inches. Section 2.12 Abandonment of Main ADD: The City of North Las Vegas Utilities Department requires removal of main to be abandoned, unless otherwise approved by Engineering Services. If the main is allowed to be abandoned in place, it shall be filled with CLSM material. Section 2.15 Mechanically Restrained Joints ADD: Mechanically restrained joints are required for all mains twelve-inch (12") and larger, and maybe used for smaller diameter mains at the discretion of the City of North Las Vegas. The length of restrained joints shall be clearly identified on drawings, and calculations shall be submitted with the project for City of North Las Vegas' review and approval. Refer to the City of North Las Vegas web address (http://www.cityofnorthlasvegas.com/about/pdfs/mechanicaljointrestraints.pdf) for guidance. Section 2.21.01 Fire Hydrants Location and Spacing ADD: Within 15 feet from back of curb return or driveway in an industrial or commercial area. Section Parallel separations (Mains) 2.22.01.B.2.c.2 and 2.22.01.B.3 ADD: The City of North Las Vegas Utilities Department does not allow cement slurry encasement of water or sewer mains unless no other alternative can be utilized. Final decision is at the discretion of the City of North Las Vegas. Section 2.22.02.B.3.c and 3.d Crossing Separations (Mains) ADD: The City of North Las Vegas Utilities Department does not allow cement slurry encasement of water or sewer mains unless no other alternative can be utilized. Final decision is at the discretion of the City of North Las Vegas. Page 1 of 5

Section 2.24.01.A Taps 4 inches and larger ADD: The City of North Las Vegas Utilities Department requires stainless steel tapping sleeves when tapping an existing Asbestos Cement Pipe. Section 2.24.01.B Taps 4 inches and larger ADD: Size on size taps are not allowed in the City of North Las Vegas service area Section 2.26.02.B & C Section 2.27.02 Size Water Plan Drawing Submittal Requirements ADD: The City of North Las Vegas Utilities Department requires easements in accordance with these Standards. ADD: All water system plans submitted to the City of North Las Vegas shall contain the most recent set of "Standard" Notes" required by the City of North Las VegasEngineering Services Division. Section 2.27.02.13 Water Plan Drawing Submittal Requirements ADD: Profiles will be provided for all mains greater than or equal to 8 inches in diameter. Section 2.27.05.A Approval Requirements ADD: The City of North Las Vegas Utilities Department does not provide preliminary plan technical approval. Section 2.28 Nevada Department of Transportation (NDOT) Permits SECTION 3 ADD: Refer to submittal application for NDOT Encroahment permit at http://www.cityofnorthlasvegas.com/about/pdfs/submittalappforndotencroachmentpermit.pd f for requirements. Section 3.01 Standard Specifications ADD: The City of North Las Vegas Municipal Water Service District Rules and Regulations, latest edition, takes precedence. Section 3.09 Record Drawings ADD: Record Drawings as required under this section shall include at a minimum: 1. "As-Built" Format: A. 24"x36" Mylar (min. 4 mil. thickness). B. The word "As-Built" in large letters. C. Streets and easements identified. D. All "proposed" information removed, leaving only "As-Built" information. E. Digital Submittal (CD) per the City of North Las Vegas Utilities Department requirements. 2. Water "As-Builts" must include: A. Plan showing size, material and offset of main deflections (if any), location of service laterals at property lines (also stationing at main, if not perpendicular to the main), stationing of all fittings and appurtenances (fire hydrants, air vacs and blowoffs), stationing for all valves and offsets for valves on laterals and intersecting mains. B. Finished grade and top of pipe elevations every 600 feet, at intersecting mains and at grade changes for all mains 14" and larger or any mains installed in streets with right-of-way 80 feet or greater. C. Finished grade and top of gate valve operating "nut" elevations for all gate valves on mains. Make and model of gate valves to be given. D. Stationing and alignment of any existing utilities the main crosses at the time of installation. Section 3.10.01.G Excavation ADD: The City of North Las Vegas Utilities Department does not allow CLSM to be placed in the pipe zone. Section 3.10.04 Pipe Zone Backfill ADD: The City of North Las Vegas Utilities Department does not allow CLSM to be placed in the pipe zone. Section 3.10.05 Trench backfill ADD: The City of North Las Vegas Trench Backfill Policy shall take precedence Section 3.12 Installation of pipe casing ADD: RCP Casings are not approved for installation in the City of North las Vegas service area. Section 3.14.02 Connection to existing facilities ADD: Size on size taps are not allowed in the City of North Las Vegas service area. Page 2 of 5

Section 3.17.01 Cementatious Materials DELETE: "II or" in the first sentence. Section 3.19.05.B Section 3.19.05.C Tapping Sleeves (other then steel pipe) Tapping Sleeves (other then steel pipe) ADD: Stainless Steel tapping sleeves shall be used on Asbestos Cement Pipe in the City of North Las Vegas service area. ADD: Note 3: Size on size taps are not allowed in the City of North Las Vegas service area. Section 3.19.10 Polyethylene (PE) Tubing ADD: Polyethylene (PE) tubing is not approved for water service installations Section 3.19.14 Fire Hydrants ADD: Private fire hydrants shall be painted red. Public fire hydrants shall be painted yellow. Section 3.24.02.E Lateral Installation ADD: Coupling location to be determined by the City of North Las Vegas Utilities inspector. Section 3.27.02 Disinfection B. ADD. Required disinfection concentration levels may be attained utilizing tablets as outlined in ANSI/AWWA Standard C651-86. STANDARD PLATES PLATE 1 New Service Installation Legend 3, ADD: Per Section 3.19.11. Legend 6, ADD: The City of North Las Vegas installs all meters 2" and smaller PLATE 2 New Service Installation Plate 2 is not approved for installation in the City of North Las Vegas service area. PLATE 3 New Service Installation Legend 3, ADD: Per Section 3.19.11. Legend 6, ADD: The City of North Las Vegas installs all meters 2" and smaller. PLATE 4 New Service Installation Plate 4 is not approved for installation in the City of North Las Vegas service area. PLATE 6 PLATE 7 PLATE 8 PLATE 9 Dual Residential Service Installation Dual Residential Service Installation Backflow Prevention Dual Backflow Prevention Plate 6 is not approved for installation in the City of North Las Vegas service area. Legend 3, ADD: Per Section 3.19.11. Legend 6, ADD: The City of North Las Vegas installs all meters 2" and smaller The City of North Las Vegas allows 3/4" backflow assemblies. Plate 8 is for the installation of 3/4" - 2" Backflow prevention assemblies. ADD: Note No. 5: When installing a Reduced Pressure Principle Backflow, the relief valve must be installed 12" to 14" above the concrete pad ADD: Note No 6: Provide and install a backflow preventer security system. Sentry model SG75-200 or Legend 3, ADD: Brass Pipe to be used as risers on the upstream and downstream sides of the backflow assembly only. Type "K" copper to be used from the meter cock to the first 90 (Legend Item No. 2). Type "K" copper to also be used from the downstream 90 (Legend Item No. 2) to 12" past the concrete slab. Legend 5, ADD: Brass Unions do not need to be installed when installing a flanged backflow assembly. The City of North Las Vegas allows 3/4" backflow assemblies. Plate 8 is for the installation of 3/4" - 2" Dual Backflow prevention assemblies. ADD: Note No. 5: When installing a Reduced Pressure Principle Backflow, the relief valve must be installed 12" to 14" above the concrete pad ADD: Note No. 6: Provide and install a backflow preventer security system. Sentry model SG75-200 or Page 3 of 5

Legend 3, ADD: Brass Pipe to be used as risers on the upstream and downstream sides of the backflow assembly only. Type "K" copper to be used from the meter cock to the first 90 (Legend Item No. 2). Type "K" copper to also be used from the downstream 90 (Legend Item No. 2) to 12" past the concrete slab. PLATE 19 Trench Section Backfill Specification Notes Legend 5, ADD: Brass Unions do not need to be installed when installing a flanged backflow assembly. ADD Note No. 10: Refer to the City of North Las Vegas Trench Backfill Policy. PLATE 23 Casing Installation Note No. 5 ADD: Casing to be filled with sand. ADD Note No. 7: The maximum distance from edge of spacer to inside of casing is one inch (1") PLATE 30 Anchor Block Details Note No. 1, ADD: Refer to Clark County Interagency Quality Assurance Committee (IQAC) for concrete mix design. PLATE 31 Thrust Block Installation Note No. 4, ADD: Refer to Clark County Interagency Quality Assurance Committee (IQAC) for concrete mix design. Note No. 7, ADD: Refer to section 2.15 of these standards. PLATE 34 Excavation for Wet Taps Size on size tap is not allowed in the City of North Las Vegas service area. PLATE 36 PLATE 37 2" Manual Blowoff 6" Manual Blowoff ADD: Note No. 5: Carsonite Marker required in unimproved areas. ADD: Note No. 5: Carsonite Marker required in unimproved areas. PLATE 38 Combination Air Valve PLATE 39 Valve Box Installation and Adjustment PLATE 40 Fire Hydrant Installation Note No. 2, ADD: No fire hydrant shall be installed within fifteen (15) feet from back of a curb return or driveway within a commercial or industrial area PLATE 51 Compound Meter with Bypass and Double Check Valve Plate 51 is not approved for installation in the City of North Las Vegas service area. PLATE 53 Type I Fire Service Meter Plate 53 is not approved for installation in the City of North Las Vegas service area. PLATE 55 Type III Fire Service Meter Plate 55 is not approved for installation in the City of North Las Vegas service area. PLATE 56 Compact Backflow Prevention Legend 6, ADD: The pad size is to meet full opening requirements of the enclosure. Refer to PLATE 57 Dual Compact Backflow Prevention ADD: Note 8: For RPDA and DCDA, install a meter security system, Abloy Defender or Legend 6, ADD: The pad size is to meet full opening requirements of the enclosure. Refer to ADD: Note 8: For RPDA and DCDA, install a meter security system, Abloy Defender or Page 4 of 5

PLATE 58 Dual Conventional Backflow Prevention Legend 5, ADD: The pad size is to meet full opening requirements of the enclosure. Refer to PLATE 59 Inline Backflow Prevention ADD: Note 7: For RPDA and DCDA, install a meter security system, Abloy Defender or Legend 3, ADD: The pad size is to meet full opening requirements of the enclosure. Refer to Legend 2, ADD: In conformance with ASSE 1060, Category 2 ADD: Note 5: For RPDA and DCDA, install a meter security system, Abloy Defender or Page 5 of 5