DIVISION 9 FINISHES. This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards

Similar documents
1. Adequate framing details, sizing, spacing and technical information shall be indicated on the documents.

DESIGN AND CONSTRUCTION STANDARDS April 2011

DESIGN AND CONSTRUCTION STANDARDS November 2010

GENERAL PROVISIONS

GENERAL PROVISIONS

C. Wallboard shall not be glued directly to masonry or concrete walls below grade: provide furring.

Produkt Declaration - LEED 2009 New Construction And Major Renovations NC & CS

Note year for Reference as Specified in the LEED V Manual.

SECTION GYPSUM BOARD ASSEMBLIES

DIVISION 9 FINISHES. The Consultant shall consider the use of the space and long-term maintenance requirements in the selection of finishes

1.1 This Section includes surface preparation and the application of base coats, intermediate and topcoats.

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

2. In moist areas, portland cement plaster should be used if a more permanent material is not within budget limits.

In the design development phase, submit finish and material selections to Facilities Management Planning Group for review.

Product Declaration - LEED 2009 New Construction And Major Renovations NC & CS

SECTION RESILIENT BASE AND ACCESSORIES

E. Popcorn or other spray applied textures on ceiling or walls are not acceptable.

SECTION RESILIENT FLOORING

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

Chapter 8: Indoor Environmental Quality

STC MANUFACTURER STEEL DOOR WITH PLYWOOD 3/4

Produkt Declaration - LEED 2009 New Construction And Major Renovations NC & CS

CAMP BLANDING JOINT TRAINING CENTER CONSTRUCTION AND FACILITY MANAGEMENT OFFICE ARCHITECT S PROJECT # CFMO PROJECT #

Interior finishes include wall finishes, floor finishes, wall base finishes, and ceiling finishes.

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

Education Facility Guide Specification

Division 09. Finishes

Division 09 FINISHES TABLE OF CONTENTS

NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

SECTION RESILIENT TILE FLOORING

Interior finishes include wall finishes, floor finishes, wall base finishes, and ceiling finishes.

Division 00 Procurement and Contracting Requirements

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

Gypsum Board Shaft-Wall Assemblies Gypsum board shaft-wall assembly for elevator and mechanical shafts over 2 stories.

DESIGN GUIDELINES AND TECHNICAL STANDARDS

Include a paint or finish schedule on the drawings, listing colors, locations and types of materials.

LARGE STAND ALONE SPECIALTY FLOORING PROJECTS - EXCLUDING CARPET PROJECTS

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS

Low Emitting Materials

Specification and Installation

DESIGN & CONSTRUCTION GUIDELINES

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

SECTION (SECTION 09650) - RESILIENT FLOORING SPECIFIER NOTE:

A. ASTM C635, Standard Specifications for Metal Suspension Systems. B. ASTM C636, Recommended Practice for Installation of Metal Suspension System

UNIVERSITY OF MISSOURI Division 09 - Finishes General Finishes Specification information to be considered by Consultants.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

Carboline Fireproofing Products

TABLE OF CONTENTS Public Safety Building

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

SECTION RESILIENT STAIR TREADS CSI 3-PART SHORT-FORM GUIDE SPECIFICATION USE FOR OUTLINE OR DD SPECIFICATION ISSUES. EDIT TO SUIT PROJECT

Avon Town Hall 10/12/2017 Avon, Colorado Project #: DPA

SECTION ALUMINUM WINDOWS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION ACOUSTICAL CEILINGS

TILE TILE

SAS International GSAS / QSAS compliance

Interior finishes include wall finishes, floor finishes, wall base finishes, and ceiling finishes.

MÉTALEC COMPANY STEEL DOOR WITH HONEYCOMB CORE

SECTION TILING

Vertima record number: FVERT In effect since: August 2013 Last update: December 2014 Technical Data documented and validated by:

F.C.L. INTERIOR FINISHES CHECK LIST 2010 PRODUCT SELECTION - FLOORING GENERAL ITEMS PRODUCT SELECTION GENERAL ITEMS

SECTION SUSTAINABLE DESIGN REQUIREMENTS LEED FOR NEW CONSTRUCTION AND MAJOR RENOVATIONS

(PC-2c) COMMERCIAL PAINTS AND COATINGS - PRODUCT INFORMATION SHEET

EGO Dichtstoffwerke GmbH & Co. Betriebs KG

APPENDIX 01: SAMPLE PRODUCT SUBMITTAL FORM (3 pages) URBAN ARTS ARCHITECTURE Abbott St, Vancouver, BC V6B 2K4 (604)

Mold resistant, paperless gypsum board shall be used in bath, kitchen, and janitor locations.

Product Declaration - LEED 2009 New Construction And Major Renovations NC & CS

MILETTE DOORS BIFOLD PANEL DOORS

***************************************************************************************************************

ADDENDUM 2 - JULY 14, 2015

Product Declaration - LEED 2009 New Construction And Major Renovations NC & CS

Smart Bomb w words. Stella Maris Project Update. IBI Group

CENDREX AHD - GENERAL PURPOSE ACCESS DOOR FOR ALL SURFACE TYPES

A. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars

MILETTE DOORS FRENCH BIFOLD DOORS

LOOSE LAY INSTALLATION GUIDE PAGE 1 of 6

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

MILETTE DOORS FRENCH DOORS

KCDA PURCHASING SPECIALTY FLOORING - LARGE STAND ALONE PROJECTS /sq.ft 0.75 /sq.ft

Visit for REVIT, CSI AND CAD data.

ARCHITECTURAL GUIDE SPECIFICATIONS

RULON WOOD SQUARE SUSPENDED CEILING SYSTEMS ARCHITECTURAL SPECIFICATIONS

RESILIENT FLOORING: Select Step Wood

RULON ACOUSTICAL CEILING SYSTEM ALURATONE 100 ARCHITECTURAL SPECIFICATIONS

Guide Specifications Section Wood Ceiling Coffers

SECTION RESINOUS FLOORING

RESILIENT FLOORING: Hot and Heavy - Secoya

SECTION Indoor Air Quality Management - LEED for Schools CONSTRUCTION MANAGER EDITION

TABLE OF CONTENTS Updated 1/2014 SECTION TITLE DATE

XTREME-BOND INSTALLATION SYSTEM

LEED TECHNICAL DATA SHEET

Napa County Building Officials Coalition

Submittal Transmittal

CONCRETE SCREEDS, INTERIOR FLOORING AND WALL COVERINGS. BME Lepel, Adrienn PhD

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE

Vertima record number: FVERT In effect since: December 2014 Last update: December 2014 Technical Data documented and validated by:

A/E Project No January 27, 2014

ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED.

A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written instructions, whichever are more stringent.

Transcription:

DIVISION 9 FINISHES This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards

1 Table of Contents SECTION 09 05 13 COMMON FINISHES 2 SECTION 09 51 23 ACOUSTICAL TILE CEILINGS 2 SECTION 09 51 33.13 - ACOUSTICAL SNAP-IN METAL PAN CEILINGS 2 SECTION 09 60 00 FLOORING.. 2 SECTION 09 64 00 - WOOD FLOORING 2 SECTION 09 64 66 - WOOD ATHLETIC-FLOORING ASSEMBLIES 3 SECTION 09 65 16 - RESILIENT SHEET VINYL FLOORINGS 3 SECTION 09 65 19 RESILIENT TILE FLOORING 3 Section 09 66 13- PORTLAND CEMENT TERRAZO FLOORING 4 SECTION 09 68 13-TILE CARPETING 4 SECTION 09 69 00-ACCESS FLOORING 4 SECTION 09 72 00-WALL COVERINGS 5 SECTION 09 91 00-PAINTING... 5

SECTION 09 05 13 COMMON FINISHES 50% of the lighting should be able to be controlled by the buildings occupants. Consider motion sensor lighting. Exterior lighting should be at a minimum level for comfort and safety. END OF SECTION 09 05 13 SECTION 09 51 23 ACOUSTICAL TILE CEILINGS Provide 2 x 2 lay-in system for new installations. Match existing ceiling system for repairs and renovations. No tile is to be less than 12" in width or length. Provide a dropped soffit at transition areas to maintain symmetrical layout. Drop soffits a minimum of 1" below ceiling grid. Suspend ceiling system from structural members or floor decking only. Do not attach to roof deck. END OF SECTION 09 51 23 SECTION 09 51 33.13 - ACOUSTICAL SNAP- IN METAL PAN CEILINGS Are only to be used to match existing conditions. END OF SECTION 09 51 33.13 SECTION 09 60 00 - FLOORING Hard flooring must be certified by Floor Score. END OF SECTION - 09 60 00 SECTION 09 64 00 - WOOD FLOORING The University would prefer not to use wood flooring other than for athletic and performing arts facilities. If installed, 50% of the wood used must be Forest Stewardship Council (FSC) certified (Cost based percentage). END OF SECTION 09 64 00 2

SECTION 09 64 66 - WOOD ATHLETIC- FLOORING ASSEMBLIES The University prefers to use maple, strip flooring on fixed, wood sleepers and sub-floor. Sealer, stain or finish used must meet South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004. END OF SECTION 09 64 66 SECTION 09 65 16 - RESILIENT SHEET VINYL FLOORINGS The University prefers to install Mannington sheet vinyl floor covering. END OF SECTION 09 65 16 SECTION 09 65 19 RESILIENT TILE FLOORING The University prefers to use vinyl composition tile (RTF). "Fritztile" or similar, is not allowed. Vinyl base to be standard colors of black, gray or brown from continuous rolls with preformed corners. Tile setting adhesives and grout must meet South Coast Air Quality Management District (SCAQMD) Rule 1168. VOC limits correspond to an effective date of July 1, 2005 and rule amendment date of January 7, 2005. Carpet must comply with the Carpet and Rug Institute Green Label Plus Program. Carpet cushion must conform to the Carpet and Rug Institute Green Label Program Carpet adhesive must comply with Sealants section. END OF SECTION 09 65 19 3

SECTION 09 66 13- PORTLAND CEMENT TERRAZO FLOORING Use control joints at all columns. Precast terrazzo is preferred for large areas. Bonded acrylic epoxy terrazzo is preferred. Terrazzo is the preferred flooring in toilet rooms. During renovation the color and style is to match existing terrazzo finishes. Concrete base control joints to align with terrazzo pattern. Samples to be submitted within 30 days of Notice to Proceed. Sealer, stain and finish used must meet South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004. END OF SECTION 09 66 13 SECTION 09 68 13- TILE CARPETING All carpet laid in the building must conform to the Carpet and Rug Institute Green Label Plus Program. Carpet Cushioning installed must conform to the Carpet and Rug Institute Green Label Program. Carpet tile is preferred. END OF SECTION 09 68 13 SECTION 09 69 00- ACCESS FLOORING Access flooring shall be coordinated with Americans with Disabilities Act (ADA) to include ramps, steps, rails and doors. END OF SECTION 08 70 00 4

SECTION 09 72 00- WALL COVERINGS There is no University preference for this Section. END OF SECTION 09 72 00 SECTION 09 91 00- PAINTING Mechanical and Electrical Equipment: 1. Flexible connections between ventilating fans and ducts shall not be painted. Valve stems and other close fitting mechanical and moving parts shall not be painted. Nameplates on motors and other mechanical equipment shall not be painted. 2. All fire alarm system raceway, conduits, junction boxes, and terminal boxes shall be of red color or shall be painted red. Painting and Finishing Schedule: 1. The choice of all finishing material shall be based on durability in wear and cleaning. 2. Concrete Masonry Units: Brush or roller painting is preferred with block filler applied first. Lightweight concrete block may be spray painted, provided coverage is the same as brushing. 3. Wood Doors: Natural or light colored finishes should not be used on wood doors or wood base because such finishes are easily discolored or damaged from foot traffic and floor cleaning operations. 4. Equipment Rooms: Painting may be omitted on walls and ceilings in mechanical equipment rooms. 5. Telecom Rooms must be painted or sealed. 6. The University prefers an eggshell to semi-gloss finish. A flat finish is not acceptable. Protection: 1. Provide adequate ventilation particularly when painting on buildings which remain user-occupied 5

The University prefers to use low VOC paints. VOC limits must stay within the parameters laid out in the Green Seal Standard GS-11, Paints, First Edition, May 20, 1993. Interior anti-corrosive paint used on ferrous metal substances should comply with the Green Seal Standard GC-03, Anti-Corrosive Paints, Second Edition, January 7, 1997. Clear wood finishes, floor coatings, stains, and shellacs applied to interior elements: Do not exceed the VOC content limits established in South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004. Sealants: 1. Adhesives, sealants and sealant primers must comply with the South Coast Air Quality Management District (SCAQMD) Rule #1168. Aerosol adhesives must comply to the Green Seal Standard for Commercial Adhesives GS-36 2. Sealer, stain and finish used on concrete, wood, bamboo or cork flooring must meet the requirements of the South Coast Air Quality Management District (SCAQMD) Rule #110, Architectural Coatings, 1 January 2004. END OF SECTION 09 91 00 This section of the Building Standards establishes minimum requirements only. It should not be used as a complete specification 6