Press-in Piling: Field Testing of Cell Foundations

Similar documents
Performance of high capacity jack-in pile for high-rise building with preboring in weathered sedimentary rock formation

JACK-IN PILE IN MALAYSIA: A MALAYSIAN CONSULTANT S PERSPECTIVE

FIELD MEASUREMENTS OF PIPE PILE BASE RESISTANCE IN MEDIUM DENSE SAND

Post-Grouting of Drilled Shaft Tips on the Sutong Bridge: A Case History

Observed Performance of Long Steel H-Piles Jacked into Sandy Soils

Offshore pile acceptance using dynamic pile monitoring

The effects of pile diameter and sleeve height on incremental filling ratio (IFR)

foundations Dr Trevor Orr Trinity College Dublin Convenor TC250/SC7/EG3 Eurocodes: Background & Applications June 2013, Dublin

Effect of previous cyclic axial loads on pile groups

Repute benchmarks. 4 x 4 pile group in firm to stiff clay. Results from Repute. Comparison with benchmark. Comments. Reference.

Steel screw settlement reduction piles for a raft foundation on soft soil

Skirted Spudcan Sheet Pile Wall Interaction during Jack- Up Rig Installation and Removal in a Harbour Area

Issues on Design of Piled Raft Foundation

Experimental study on axial and lateral bearing capacities of nonwelded composite piles based on pile load test results

NUMERICAL STUDY OF OFFSHORE SKIRTED FOUNDATIONS SUBJECTED TO COMBINED LOADING

INFLUENCE OF BNWF SOIL MODELLING ON DYNAMIC BEHAVIOUR OF PILE FOUNDATION FOR RC FRAME WITH STRUCTURAL WALL

Bearing capacity of closed and open ended pipe piles installed in loose sand with emphasis on soil plug

STATIC AND HIGH STRAIN DYNAMIC TEST CO-RELATION STUDIES ON CAST-IN-SITU CONCRETE BORED PILES

INTERPRETATIONS OF INSTRUMENTED BORED PILES IN KENNY HILL FORMATION

Silent Vibrationless. Technology. teel Sheet Piles. Vinyl Piling. etaining Walls. Piles. tory Piling. oundations. ite Piles. n Free Piling.

Modelling of a pile row in a 2D plane strain FE-analysis

USE OF DIPP PILES FOR A NEW SUP BRIDGE IN WEST MELBOURNE

PILED RAFT DESIGN PROCESS FOR A HIGH-RISE BUILDING ON THE GOLD COAST, AUSTRALIA

Deflection of Helical Piles: A Load Test Database Review

Effect of Particle Size Distribution of Cohesionless Soil and Pile Diameter on the Behavior of Open Ended Pipe Piles

An Experimental Study on Vertically Loaded Driven and Cast- In-Situ Piles

Proceedings of the ASME nd International Conference on Ocean, Offshore and Arctic Engineering OMAE2013 June 9-14, 2013, Nantes, France

The experience in applying of static load and O-cell pile testing geotechnologies in problematical soil conditions of Astana

Advantages / Disadvantages of Piling Methods. Continuous Flight Auger (CFA)

Innovation in Instrumented Test Piles in Malaysia: Application of Global Strain Extensometer (GloStrExt) Method for Bored Piles

Case-history Steel Tubular Pile Cofferdam Foundations in Bangladesh

Bi-Directional Static Load Testing of Drilled Shafts

Bi-Directional Static Load Testing of Drilled Shafts

PILE SETTLEMENT ZONES ABOVE AND AROUND TUNNELLING OPERATIONS

penetrometer test (CPT) soundings were done to supplement the SPT data. Construction recommendations were made for most of the new buildings.

Implementation of this Special Provision requires a complete understanding of the following documents:

EFFICIENCY OF MICROPILE FOR SEISMIC RETROFIT OF FOUNDATION SYSTEM

SOIL-STRUCTURE INTERACTION ANALYSIS OF A RAILWAY BRIDGE IN ROTTERDAM

A Design Approach for Piled Raft with Short Friction Piles for Low Rise Buildings on Very Soft Clay

Northport Berth 3 design and construction monitoring

STATIC ALTERNATING CYCLIC HORIZONTAL LOAD TESTS ON DRIVEN

Sabah Shawkat Cabinet of Structural Engineering 2017

MIDAS ELITE SERIES SOIL STRUCTURE INTERACTION ANALYSIS OF SKYSCRAPER IN BRAZIL RICARDO BORN

Some observations on Statnamic pile testing

THEORETICAL AND ACTUAL BEARING CAPACITY OF DRIVEN PILES USING MODEL PILES IN SAND

JACK-IN PILE DESIGN MALAYSIAN EXPERIENCE AND DESIGN APPROACH TO EC7

Challenges of Offshore Geotechnical Engineering

A practical appraisal method for through-wall cracks in tubular structures

Model Tests to Determine the Settlement Characteristics of Steel Hollow Piles under Cyclic Loading Embedded in Silty Sands

Pile foundations Introduction

The Compression Bearing Capacity of Helical Piles in Black Cotton Soil

Effect of Friction Fatigue on Pile Capacity in Dense Sand

SETTLEMENT ANALYSIS OF PILED RAFT BY FINITE ELEMENT ANALYSIS

Bi-Directional Static Load Testing of Driven Piles

Typical set up for Plate Load test assembly

Case Histories in Geotechnical Engineering

University of Bristol - Explore Bristol Research. Peer reviewed version. Link to publication record in Explore Bristol Research PDF-document

EFFECT OF PLUG REMOVAL ON LOAD TRANSFER IN PLUGGED OPEN ENDED PILE BEHAVIOR

A residual is generally a quantity left over at the end of a process. Geol: that remaining after soluble elements have been dissolved and removed

A.Zh.Zhussupbekov Department of Civil Engineering and Engineering Mechanics, Columbia University, New York, USA

Axially Loaded Behavior of Driven PC Piles

Innovative Substructures on Soft Ground

353. Fellenius, B.H., The response of a "plug" in an open-toe pipe pile Geotechnical Engineering Journal of the SEAGS & AGSSEA 46(2)

Foundation Design. Principles. and Practices. Donald P. Coduto. Man-chu Ronald Yeung. William A. Kitch. Third Edition PEARSON

PILE RAFT FOUNDATION BEHAVIOR WITH DIFFERENT PILE DIAMETERS

Sheet Pile Retaining Walls Design and Construction in Brown Fields Environment

Assalamualaikum & Good Morning (May All Of You Gain A Better Understanding)

Environmental vibration resonances of precise bearing platform built on soft soils

NPTEL Course GROUND IMPROVEMENT USING MICROPILES

Pile Design to BS EN :2004 (EC7) and the National Annex

Design and Construction of Drilled Full Displacement Piles using the Penetration Resistance Method

1G Model Study on the behavior of Piled Raft Foundation

Performance of Concrete Filled Steel Tubular Columns

PERFORMANCE OF PILED RAFT WITH VARYING PILE LENGTH ABSTRACT

SECTION DUCTILE IRON PILES

Hybridnamic Rapid Load Tests for Cast-in-situ Piles in Sandy Gravel Soil

Settlement Settlements at working loads must not cause damage, nor adversely affect the serviceability of the structure.

IMPLANT LEVEE. Highly Resilient Disaster Prevention Levee

Ching Guan Kee ABSTRACT

twenty four foundations and retaining walls Foundation Structural vs. Foundation Design Structural vs. Foundation Design

Foundation Innovations Ensure Successful Bridge Replacement

Development of the Combi-Gyro Method, a New Steel Wall Construction Method Combining Steel Sheet Piles and Pipe Piles

Development of New-type Steel-Pipe Methods for Urban Renewal Projects

FURTHER TECHNICAL INFORMATION IN RELATION TO THE OPERATIONS OF OUR GROUP

Centrifuge Model Tests on Settlement Controlling of Piled Raft Foundation in High-Rise Building

Method Statement of load Test for Steel Tubular Load Test Trial Piles Rev.3

Single Piles and Pile Groups

The shaft capacity of CFA piles in sand. Gavin, Kenneth; Cadogan, David; Casey, Patrick. American Society of Civil Engineers

THE STUDY OF t-z AND q-z CURVES ON BORED PILE BASED ON THE RESULTS OF INSTRUMENTED PILE LOAD TEST IN MEDIUM AND STIFF CLAYS

Testing of ground anchorages for a deep excavation retaining system in Bucharest

CONFINEMENT CAPACITY OF SQUARE AND CIRCULAR CONCRETE COLUMNS REINFORCED WITH PREFABRICATED CAGE REINFORCEMENT SYSTEM

APPLICATION OF THE HOT SPOT STRESS METHOD TO THE FATIGUE ASSESSMENT OF HOLLOW SECTION SHIPLOADER BOOM CONNECTIONS

Subsoil Bearing Capacity from Load Test Results In Two Locations in Rivers State, Nigeria

Atlaspile. Full soil displacement bored pile, vibration free - low noise economical

UNDERPINNING A CRANE FOUNDATION

SAVINGS FROM TESTING THE DRIVEN-PILE FOUNDATION FOR A HIGH-RISE BUILDING

EFFECT OF DEEP EXCAVATION SUPPORTED BY CONCRETE SOLIDER PILE WITH STEEL SHEET PILE LAGGING WALL ON ADJACENT EXISTING BUILDINGS

Tagus Crossing at Carregado (Portugal): A project respectful of its sensitive environment

Experimental study on axial and lateral bearing capacities of nonwelded composite piles based on pile load test results

Three-dimensional computer simulation of soil nailing support in deep foundation pit

Transcription:

Press-in Piling: Field Testing of Cell Foundations A. G. Yetginer, D. J. White and M. D. Bolton University of Cambridge, Engineering Department Abstract A series of load tests on jacked tubular piles are reported. These tests exa mine the capacity of cell foundations comprising tubular piles installed using the press-in method. Press-in piling machines are capable of installing large tubular piles with up to 4.6 MN of static jacking force, gaining reaction from adjacent piles within the cell. This technique permits the installation of, for example, bridge foundations, with minimal temporary works. By using static jacking force alone, environmental disturbance through noise and vibration is minimized. Since the press-in method provides a measurement of jacking resistance during installation, this value can be used to estimate the long-term capacity of the completed foundation. However, group effects and time effects must be accounted for. This paper discusses possible design approaches and suggests that conventional serviceability design methods may be over-conservative when applied to this novel construction method. Introduction The press-in method is a modern piling technique by which piles are installed using static force alone, with reaction being provided by previously installed piles. Compared to conventional dynamic methods, press-in piling creates minimal noise and vibration (White et al., 2002). Furthermore, the jacking resistance can be measured during installation, and used to estimate long-term capacity. Since press-in piling machines walk along the pile wall under construction, all piles must necessarily be installed at close centres, or indeed touching. This geometry is in contrast to conventional design guidance, which requires a separation of typically two diameters between axially loaded piles, to prevent harmful interaction effects (BS8004, 1986). Research is required to establish the load carrying capacity of pressed-in piled foundations since they lie within this low spacing range. BGA International Conference on Foundations, University of Dundee, Scotland, 2003

2 BGA International Conference on Foundations This paper presents the results of field tests that were carried out in Kochi, Japan, to examine the load carrying capacity of cell foundations installed using the press-in piling technique. The term cell foundation is used to describe a foundation constructed by jacking piles around an enclosed soil block at close centres. Each pile displaces soil, increasing the lateral pressure in the surrounding soil and on the adjacent piles. The load carrying capacity of the cell might thus be expected to exceed the sum of the capacity of the individual piles. However, conventional design approaches do not permit displacement piles to be installed closer than two diameters apart, to avoid possible negative group efficiencies caused by interaction of the piles. This approach may be overly conservative, preventing the use of the press-in method, which requires close pile spacing since the piler uses adjacent piles to provide reaction. This paper firstly examines how the installation load of a single pile relates to subsequent bearing capacity, in order to establish whether installation force provides a useful indicator of long-term behaviour. Secondly, the relationship between installation force of a single pile, and the installation force for piles within a cell is investigated, to establish whether such close pile spacing leads to driveability problems. Finally, the bearing capacity of the completed cell is compared to the capacity of the single pile to establish the efficiency of the cell foundation. Background Previous testing of pressed-in pile foundations is reported by White et al (2003). A series of load tests on rows of 400x400mm steel H-piles was carried out at Shinagawa, Tokyo, to study the design of a foundation system consisting of rings of H-piles forming 20m deep caisson cells. The H-piles were installed in contact with each other, forming closed box sections. These tests demonstrated that: - A positive time effect was observed, i.e. the ultimate capacity of a single pile was found to be greater than the installation load. - A positive group effect was observed, i.e. rows of H-piles when loaded simultaneously showed a greater capacity than the sum of the individual capacities of each pile in the group. The positive group efficiency factor, ζ GROUP, defined by Equation 1, was found to be in the range of 1.6 2.0. n QGROUP ζ GROUP = (1) n Q SINGLE Q SINGLE and Q GROUP are the capacity of a single pile and a group of n piles respectively, where n is the number of the piles in the group. The measured positive group efficiency is in contrast with historic experimental data (e.g. Vesic, 1969), which has lead to design advice requiring a centre-to-centre separation of at least 2D (BS8004, 1986). Subsequent to the

Press-in Piling: Field Testing of Cell Foundations, Yetginer et al. 3 Shinagawa testing, the programme of fieldwork reported in this paper was conducted, with the aim of examining the behaviour of cell foundations constructed from tubular, rather than H-section, piles. Fieldwork Two small-scale cell foundations (Fig.1) were installed and tested at the Takasu Research Centre in Kochi, Japan. Additionally, a single pile, and walls of two and three adjacent piles were installed nearby to the same founding depth. Figure 1: Dimensions of the cell foundations Reaction Piles Test Piles Reaction Piles 150 850 6000 6650 7500 600 600 Figure 2: Reaction pile arrangement in Takasu

4 BGA International Conference on Foundations Each cell foundation consisted of twelve, 6m long, tubular steel piles with an external diameter D of 101.6 mm and a wall thickness t of 5.7 mm. Reaction sheet piles were installed 600 mm (~6D) from the nearest test pile (Fig. 2). The ground conditions in Takasu consist of made ground overlying layers of silt, silty sand and sand (Fig.3) (White et al., 2000). Prior to installation of the piles, the made ground was removed and replaced by sand. Figure 3: Takasu ground conditions

Press-in Piling: Field Testing of Cell Foundations, Yetginer et al. 5 The final installation force for each pile was recorded by fitting a load cell between the jacking chuck of the piler and the head of the pile during the final installation stroke. To examine the relationship between the installation load of a single pile and the bearing capacity of a group of piles a series of maintained load tests was carried out (Table 1). Separate reaction and reference beams were used. Pairs of displacement transducers were used to monitor the settlement of the single and two- and three-pile walls. A steel cap was welded over the cell foundations with the load cell and load test jack mounted centrally on the steel cap. Four displacement transducers, placed at each corner of the steel cap, were used to monitor the settlement of the pile groups. PILE GROUP DATE OF INSTALLATION DATE OF LOAD TEST Single Pile TK02-P1 05-07-02 17-07-02 Two-Pile Group TK02-P2 09-07-02 22-07-02 Three- TK02-P3 05-07-02 18-07-02 Square Twelve- TK02-P12sq 08-07-02 19-07-02 Circular Twelve- TK02-P12ci 09-07-02 23-07-02 Table 1: Schedule of tests at Takasu Test Site The load tests were continued until a settlement of D/4=25mm was reached except in the case of the cell foundations, which were penetrated to a depth of 80 mm. Unload-reload loops were conducted at a settlement of D/5=20mm. The installation and failure loads that were measured during these tests are presented in Table 2, with failure load defined as the load at a settlement of 20 mm.

6 BGA International Conference on Foundations Installation Load (kn) Failure Load (Load per Pile) (kn) Single Pile 49.9 50.0 Two P1 46.3 P2 56.6 Three Square Twelve Circular Twelve P1 56.3 P2 74.7 P3 70.9 P1 57.4 P2 73.2 P3 72.9 P4 60.4 P5 99.8 P6 118.7 P7 83.3 P8 87.7 P9 101.8 P10 89.4 P11 108.2 P12 98.5 P1 49.2 P2 71.5 P3 83.7 P4 79.3 P5 90.1 P6 89.6 P7 88.7 P8 115.6 P9 105.8 P10 109.5 P11 116.7 P12 128.5 Table 2: Results of load tests at Takasu Test Site 116 (58) 174 (58) 700 (58) 600 (50)

Press-in Piling: Field Testing of Cell Foundations, Yetginer et al. 7 Single Pile Bearing Capacity The load-settlement curve for the single pile is presented in Fig.4. A stiff linear response is followed by plunging failure at a load of 50 kn after a settlement of D/50=2mm. The load during this test was increased in steps of 10kN and was kept at each load level until the creep rate was below 1mm/h. This value of ultimate capacity is comparable to three design predictions following well-known design methods derived for use with conventional (dynamically) installed piles (Table 3). This good agreement suggests that installation method has only a minor influence on ultimate capacity, and indicates that conventional design methods for ultimate capacity may be applied to pressed-in piles. Meigh, 1987 API Method, 1993 Jardine & Chow, 1996 Shaft friction (kn) Base resistance (kn) Total capacity (kn) 20.0 34.5 54.5 22.2 19.5 41.7 30.5 24.8 55.3 Table 3: Bearing capacity (Predictions using conventional methods) The high initial stiffness, with ultimate capacity reached within a settlement of D/50=2mm is notable, since the design of urban deep foundations is usually DISPLACEMENT (mm) 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 LOAD (kn) 0 10 20 30 40 50 60 Figure 4: Load test of the single pile

8 BGA International Conference on Foundations governed by serviceability rather than ultimate limit state considerations (Randolph, 1994; Tomlinson, 2001). Conventionally installed driven piles typically require a settlement of at least D/10 to mobilize full capacity with bored piles being even more compliant. This high measured stiffness indicates that the large safety factors applied to ultimate capacity to satisfy serviceability requirements of conventional piles may be reduced when applied to pressed-in piles, with a consequent improvement in design efficiency. The installation and failure load of the single pile were identical, at 50 kn, indicating that for pressed-in piles in sand, tested within a few days of installation, the jacking force offers a reliable indication of the ultimate capacity (Table 2). Group Efficiency The capacities of the circular and square cell foundations, defined by the load at a settlement of D/5=20mm, were 600 kn and 700 kn respectively (Table 2), indicating a group efficiency, ζ GROUP, of 1.02, when Q SINGLE is taken as the installation load of the weakest pile in the group. These values of unity indicate that any positive or negative interaction effects balance each other. In both cases the pile with the lowest installation load, i.e. the weakest pile, was the first pile to be installed in the group. Hence, to estimate the capacity of an entire cell foundation, it may be sufficient to install one pile, recording the jacking resistance. The load-settlement curves of the cells were comparable to the single pile test, with an initially stiff response leading to mobilization of the full capacity at a settlement of D/10=10mm (Fig.5). LOAD (kn) 0 100 200 300 400 500 600 700 800 0 1 DISPLACEMENT (mm) 2 3 4 5 6 7 8 9 Circular Cell Square Cell 10 Figure 5: Load test of the square and the circular cells

Press-in Piling: Field Testing of Cell Foundations, Yetginer et al. 9 Enclosure Effects: Driveability Enclosure effects are defined as the changes in the installation load of individual piles, as the construction of the cell foundations advances. Examining the data from the tests in Takasu it can be seen that increased jacking resistance is encountered as construction progresses (Table 2). This is a well-known effect, which can lead to problems of driveability in close-centred pile groups. 140 INSTALLATION LOAD (kn) 120 100 80 60 40 20 Pile 2 Pile 1 Pile 3 Pile 4 Pile 6 Pile 5 Pile 8 Pile 7 Pile 9 Pile 10 Pile 11 Pile 12 0 0 2 4 6 8 10 12 14 PILE NUMBER Figure 6: Installation of the square cell foundation 180 INSTALLATION LOAD (kn) 160 140 120 100 80 60 40 20 Pile 2 Pile 1 Pile 4 Pile 3 Pile 5 Pile 6 Pile 8 Pile 7 Pile 9 Pile 10 Pile 11 Pile 12 0 0 2 4 6 8 10 12 14 PILE NUMBER Figure 7: Installation of the circular cell foundation

BGA International Conference on Foundations 10 The progressive increase in jacking force can be attributed to the increase in lateral pressures in and around the soil block that is enclosed as the construction of the cell foundation advances. Fig. 6 and 7 show the increase in installation force as each cell foundation is completed. This recorded increase in resistance has implications for the deployment of press-in piling machines for the construction of cell foundations. It is not sufficient to mobilize a machine with jack capacity greater than the strength of a single pile. Instead, a jack capacity of approximately twice the capacity of a single pile is required to install the final pile in each cell. Conclusions The press-in method allows measurement of jacking resistance during the installation of piles. The field tests described in this paper show that this measurement is a useful indicator of the long-term capacity of pressed-in piles in sand. Piles installed using the press-in method show very high initial stiffness during maintained load tests and the full pile capacity is mobilised at a very small settlement. Consequently, the large safety factors that are normally applied to ultimate capacity to meet serviceability limits can be reduced significantly when using the press-in method and more efficient use can be made of the potential capacity of a piled foundation. The field tests described in this paper also show that the bearing capacity of a complete cell foundation can be estimated from the installation load of a single pile. No negative group effects on ultimate capacity due to the proximity of the other piles in the group were evident. However, an increase in the installation force of the individual piles was measured as the cell foundation advanced. This observation has implications for machine selection to avoid driveability problems. Acknowledgements The field testing was carried out with the support of Giken Seisakusho Co. Ltd. The authors acknowledge the technical assistance provided by Mr. T.Nagayama, Mr. D.J. Rockhill and Mr. A.J.Deeks. References American Petroleum Institute (API) 1993 RP2A. Recommended practice of planning, designing and constructing fixed offshore platforms Working stress design, 20 th edition, Washington, 59-61. BS 8004 1986. Code of practice for foundations. Jardine R.J. & Chow F.C. 1996. New design methods for offshore piles, Marine Technology Directorate (MTD) Publication, 96/103, London.

Press-in Piling: Field Testing of Cell Foundations, Yetginer et al. 11 Meigh A.C. 1987. Cone penetration testing Methods and Interpretation, Construction Industry Research and Information Association (CIRIA), Ground Engineering Report, pp147. Randolph M.F. 1994. Design methods for pile groups and piled rafts, Proceedings of the 13 th International Conference on Soil Mechanics and Foundation Engineering, Delhi, India (5): 61-82. Tomlinson M.J. 2001. Foundation design and construction, 7 th edition, Prentice Hall, Harlow, England. Vesic A.S. 1969. Experiments with instrumented pile groups in sand, ASTM STP 444, 177-222. White D.J., Sidhu H.K., Finlay T.C.R., Bolton M.D. & Nagayama T. 2000. Press-in piling: The influence of plugging on driveability, Proceedings of the 8 th International Conference of the Deep Foundations Institute, New York, 299-310. White D.J., Finlay T.C.R., Bolton M.D. & Bearss G. 2002. Press - in piling: Ground vibration and noise during pile installation, Proceedings of the International Deep Foundations Congress, Orlando, USA, ASCE Special Publication 116 pp 363-371. White D.J. 2003. A novel urban foundation system using pressed-in H-piles, XIII th European Conference on Soil Mechanics & Geotechnical Engineering.