Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D.

Similar documents
How much ventilation and how to ventilate in the future? The EU policy by 2020

Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering

Standards for Ventilation and Indoor Air Quality in relation to the EPBD

INTERNATIONAL STANDARDS FOR THE INDOOR ENVIRONMENT Where are we and do they apply Worldwide. Professor Bjarne W. Olesen, PhD Fellow, Treasurer

Articles. Figure 2. Typical set-up of personalized ventilation system.

Professor Bjarne W. Olesen, Ph.D., FASHRAE Society President International Center for Indoor Environment and Energy Technical

Classification of Indoor Climate, Construction, and Finishing Materials

Air distribution and temperature control in classrooms

Standards for Ventilation, IAQ, and Thermal Comfort EVALUATION OF THE INDOOR ENVIRONMENT THERMAL ENVIRONMENT INDOOR ENVIRONMENT.

Trends and drivers in the Finnish ventilation and AC market

Indoor environment for energy performance of buildings a new European draft standard

DISPLACEMENT VENTILATION

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

Air Cleaning Devices: Towards Design of Sustainable Buildings

APPLICATIONS Filtration

ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering

Thermal comfort recent challenges

INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN THE DESIGN OF BUILDING SERVICES SYSTEMS FOR SCHOOL CLASSROOMS

Examples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality.

Chapter 14 Indoor Air Quality

Effect of using low-polluting building materials and increasing ventilation on perceived indoor air quality

Indoor comfort and air quality in spaces equipped with eco-ventilation systems

P U R I F Y I N G T H E A I R Y O U B R E A T H E

TEXAS FACILITIES COMMISSION Edit Date: 4/13/2012 ARCHITECTURAL/ENGINEERING GUIDELINES

ISO INTERNATIONAL STANDARD. Building environment design Indoor air quality Methods of expressing the quality of indoor air for human occupancy

LEED v4 Building Design and Construction Quiz #8 EQ

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Chapter 8: Indoor Environmental Quality

Indoor Air Quality Improvement in a School Building in Delhi

MEP's Letter of Assurance

MEP Engineer's Letter of Assurance

MEP's Letter of Assurance

Human Response to Ductless Personalised Ventilation: Impact of Air Movement, Temperature and Cleanness on Eye Symptoms

Notes on Indoor Air Quality

Human Response to Ductless Personalized Ventilation with Local Air Cleaning: Air Quality and Prevalence of SBS Symptoms

INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS

Indoor Air Quality through Design

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

MEP's Letter of Assurance

Indoor Air Quality (IAQ) Requirements

Saving energy for ventilation by careful selection of building materials Wargocki, Pawel; Knudsen, Henrik N.

INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS

Improve Schools Indoor Environment

The Front Lines of Residential Indoor Air Quality. Dan Ventura

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

LEED And Your Indoor Environment

Indoor environmental input parameters for the design and assessment of energy performance of buildings. BJARNE W. OLESEN

THE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS

PERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES

Measuring Indoor Air Quality presented to AAFAME Members Nov. 14, 2017

ASHRAE s. Indoor Air Quality Procedure. in Ventilation Design

What s in the Air - Truths, Myths & Simple Strategies

Performance of radiant cooling ceiling combined with personalized ventilation in an office room: identification of thermal conditions

ROOM PURIFYING DISINFECTOR HORIZONTAL LAMINAR AIRFLOW

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality

Evaluation methods for indoor environmental quality assessment according to EN15251

Investigation of indoor climate in a naturally ventilated building

VENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS

Human response to individually controlled micro environment generated with localized chilled beam

Indoor air quality and ventilation

Energy and the Built Environment

Indoor Air Quality Assessments during Renovations at Waverly Elementary School Project #J (January 4, 12, 15, 25 and 29, 2018)

Minimum Outdoor Airflow Using the IAQ Procedure

Good indoor air quality (IAQ) management has become paramount in the construction industry as study

ASHRAE Standard INTRODUCTION AND OVERVIEW Plus a few other issues: Outdoor Air Quality and the IAQ Procedure

INDOOR AIR QUALITY PROGRAM

Index of Addenda to ANSI/ASHRAE Standard 62.1

Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness

Indoor Environmental Quality Policy

Mechanical Technical Assignment One ASHRAE Standard Compliance Evaluation

Indoor Air Quality Backgrounder: The Basics

IMPACT OF VENTILATION RATE, OZONE AND LIMONENE ON PERCEIVED AIR QUALITY IN OFFICES

ASHRAE Standard : Ventilation Rate Procedure

IAQ & Energy Impact of Exhaust Air Transfer Ratio

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Indoor Air Quality

Danish Indoor Climate Labelling

Demand Controlled Ventilation. A Detailed Study of Energy Usage by Simulation

Allowance Table for: General:

ISO INTERNATIONAL STANDARD. Building environment design Indoor air quality Methods of expressing the quality of indoor air for human occupancy

Analysis of VOCs & Formaldehyde

Indoor environmental input parameters for the design and assessment of energy performance of buildings

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA

Personal Ventilation: from research to practical use

Indoor Air Quality Tools for Schools

IMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

LEED Best Practices Save $$$

Performance assessment of a ventilated mattress for pollution control of the bed microenvironment in healthcare facilities

BACTERIA MOLD VIRUS POLLEN

Thermal Environment evaluation in commercial kitchens

What Can I Do with IAQ? Seizing the Indoor Air Opportunity Bill Spohn

The European Approach to Decrease Energy Use in Buildings Towards ZEB (Zero Energy Buildings)

Student Performance and Absenteeism Related to IAQ

c Dr. M. Zahurul Haq (BUET) Moist Air & Thermal Comfort ME 415 (2011) 2 / 19

for decreased exposure risk indoors Arsen K. Melikov Workplace and Indoor Aerosols, April , Lund

REHVA EUROPEAN GUIDEBOOKS

Interior surface materials as sources of indoor hygiene defects

DEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA

Transcription:

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Technical University of Denmark

Energy consumption for ventilation Exhaust Ventilation air Up to 30% of the total energy consumption in buildings Energy for conditioning the ventilation air

CRITERIA FOR INDOOR AIR QUALITY ~VENTILATION RATES COMFORT (Perceived Air Quality) HEALTH PRODUCTIVITY ENERGY

INTAKE FOR A PERSON PER DAY 1 kg FOOD 2 kg LIQUID 15 kg AIR

Odds Rstio for "cases" 2 1.5 1 Odds ratio for being a case, i.e. children with at least two symptoms of possible three (wheezing, rhinitis, eczema) as a function of ventilation rates, in single family houses. (Bornehag et al., 2003). 0.5 0 n= 0.17 n= 0.29 n= 0.38 n= 0.62 Mean values for ventilation rates

Figure 1. Adjusted odds ratio of SBS for low outdoor air flow rate in commercial buildings [3]

Standard 62.1 Definition: What is Acceptable Indoor Air Quality? Air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction

STANDARDS EN 15251 Indoor environmental input parameters for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment, lighting and acoustics ASHRAE 62.1 and 62.2-2004 Ventilation and indoor air quality CR 1752 Ventilation of buildings-design criteria for the indoor environment EN 13779 Ventilation for non-residential buildings - performance requirements for ventilation and room-conditioning systems

Indoor pollution sources Human bioeffluents Building materials Furnishing HVAC system Equipment Tobacco smoking Building

European Audit Project to Optimise Indoor Air Quality and Energy consumption in Office Buildings Sensory pollution load- perceived air quality Materials and activities Outdoor air Occupants Ventilation system

TWO PATHWAYS Ventilation Rate Procedure Prescriptively Based Rates by Space Type Rates by occupants level Indoor Air Quality Procedure Performance Based Concentration Targets Occupant Acceptability Air Cleaning Allowed

Analytical procedure Ventilation Rate Health

CEN CR 1752 EN15251 ASHRAE 62.1 Diagram based on studies with Danish subjects (Fanger et.al). Similar results obtained by North-American subjects (Cain et.al.) Similar results obtained with Japanese subjects (Tanabe)

Basic required ventilation rates for diluting emissions (bio effluents) from people for different categories Category Expected Percentage Dissatisfied Airflow per person l/s/pers I 15 1O II 20 7 III 30 4 IV > 30 < 4 Adapted persons 2,5 l/s person (Cat. II )

Indoor pollution sources Human bioeffluents Building materials Furnishing HVAC system Equipment Tobacco smoking Building

Concept for calculation of design ventilation rate People Component Building Component Breathing Zone Outdoor Airflow V bz = R p P z + R s S d + R a A z Minimum l/s/person Number of People Ventilation per Smoker Number of Smokers Building Area Minimum l/s/m²

7 independent studies have measured sensory pollution loads in 120 buildings (olf/m 2 floor) 97 office buildings & assembly halls (previous ETS) 0.23±0.06 6 office buildings (no ETS) 0.11±0.09 10 kindergartens 0.06±0.04 6 schools 0.06±0.06 1 department store 0.15 European standard (EN15251): Very Low-polluting building 0.05 Low-polluting building 0.1 Non-low-polluting building 0.2

Basic Ventilation Airflow for building emissions pollutions (l/s/m²) Category Airflow per person l/s/pers. Very low polluting building Low polluting building Non low polluting building I 1O 0,5 1 2 II 7 0,35 0,7 1,4 III 4 0,2 0,4 0,8

Low Polluting Building The majority of the materials are low polluting. Low polluting materials are natural traditional materials, such as stone and glass, which are known to be safe with respect to emissions, and materials which fulfil the following requirements: The emission of total volatile organic compounds (TVOC) is below 0.2 mg/m²h. The emission of formaldehyde is below 0.05 mg/m²h. The emission of ammonia is below 0.03 mg/m²h. The emission of carcinogenic compounds (IARC) is below 0.005 mg/m²h. The material is not odorous (dissatisfaction with the odour is below 15 %).

Very Low Polluting Building All of the materials are very low polluting and smoking has never occurred and is not allowed. Very low polluting materials are natural traditional materials, such as stone, glass and metals, which are known to be safe with respect to emissions, and materials which fulfil the following requirements The emission of total volatile organic compounds (TVOC) is below 0.1 mg/m²h. The emission of formaldehyde is below 0.02 mg/m²h. The emission of ammonia is below 0.01 mg/m²h. The emission of carcinogenic compounds (IARC) is below 0.002 mg/m²h. The material is not odorous (dissatisfaction with the odour is below 10 %).

Recommended ventilation rates for non-residential buildings for three categories (EN15251) Type of building or space Category Per person l/s,person Per floor area l/s,m 2 Per person l/s,person Per floor area l/s,m 2 Per person l/s,person Per floor area l/s,m 2 Very low polluted building, revision Low polluted building, revision Non-low polluted building, revision Single office I 5,0 1,5 10,0 2,0 20,0 3,0 II 3,0 1,0 7,0 1,4 14,0 2,1 III 2,0 0,6 4,0 0,8 8,0 1,2 Landscaped office Conference room I 7,5 1,5 15,0 1,7 30,0 2,7 II 4,5 1,0 10,5 1,2 21,0 1,9 III 3,0 0,6 6,0 0,7 12,0 1,1 I 1,0 1,5 2,0 6,0 4,0 7,0 II 0,6 1,0 1,4 4,2 2,8 4,9 III 0,4 0,6 0,8 2,4 1,6 2,8

Type of building/ space Single office (cellular office) Occupancy person/m 2 0,1 Category CEN Occupants only l/s person ASH- CEN RAE Rp Additional ventilation for building (add only one) l/s m 2 CEN lowpolluting building CEN Non-lowpolluting building ASH- RAE Ra Total l/s m 2 CEN Low Pol. A 10 1,0 2,0 2 B 2,5 7 0,7 1,4 0,3 1,4 C 4 0,4 0,8 0,8 ASH- RAE 0,55 Landscaped office 0,07 A 10 1,0 2,0 1,7 B 2,5 7 0,7 1,4 0,3 1,2 C 4 0,4 0,8 0,7 0,48 Conference room 0,5 A 10 1,0 2,0 6 B 2,5 7 0,7 1,4 0,3 4,2 C 4 0,4 0,8 2,4 1,55 1 l/s m 2 = 0.2 cfm/ft 2 International Centre for Indoor Environment And Energy

Recommended CO 2 concentrations above outside for non-residential buildings for three categories Compared to 650ppm (1000ppm) VERY LOW POLLUTED LOW POLLUTED NON LOW POLLUTED TYPE OF BUILDING CATEGORY ΔCO2 ΔCO2 ΔCO2 ppm ppm ppm SINGLE OFFICE 1 375 280 190 2 560 400 265 3 930 695 465 LANDSCAPED OFFICE 1 310 220 140 2 465 310 195 3 745 530 340 CONFERENCE ROOM 1 510 465 400 2 735 665 570 3 1265 1160 995 AUDITORIUM 1 480 465 440 2 690 665 625 3 1195 1160 1090 Higher Same Lower

Adapted or Un-adapted? Bioeffluents (body odor) Adapted need only one third of outside air (~7 l/s to 2.5 L/s) Tobacco smoke (ETS) Only limited adaptation (odor, irritation) Building materials and HVAC systems No adaptation International Centre for Indoor Environment And Energy

Adapted or Un-adapted? Conference rooms. Adapted? Classrooms. Adapted? Restaurants. Un-adapted? Department stores. Un-adapted International Centre for Indoor Environment And Energy

v Required ventilation rate The total required system ventilation rate is calculated by taking into acount the ventilation effectiveness: Total system ventilation rate = V/ε v

Ventilation effectiveness

Inhaled Air Quality V eff 1 V eff 1.4 (6)

Ventilation effectiveness

Air Distribution Configuration Ceiling supply of cool air 1.0 Ceiling supply of warm air and floor return 1.0 Ceiling supply of warm air 15 F (8 C) or more above space temperature and ceiling return. Ceiling supply of warm air less than 15 F (8 C) above space temperature and ceiling return provided that the 150 fpm (0.8 m/s) supply air jet reaches to within 4.5 ft (1.4 m) of floor level. Note: For lower velocity supply air, Ez= 0.8. Floor supply of cool air and ceiling return provided that the 150 fpm (0.8 m/s) supply jet reaches 4.5 ft (1.4 m) or more above the floor. Note: Most underfloor air distribution systems comply with this proviso. Floor supply of cool air and ceiling return, provided low- velocity displacement ventilation achieves unidirectional flow and thermal stratification Floor supply of warm air and floor return 1.0 Floor supply of warm air and ceiling return 0.7 Makeup supply drawn in on the opposite side of the room from the exhaust and/or return Makeup supply drawn in near to the exhaust and/or return location 0.5 5. As an alternative to using the above values, Ez may be regarded as equal to air change effectiveness determined in accordance with ASHRAE Standard 129 16 for all air distribution configurations except unidirectional flow. Ez 0.8 1.0 1.0 1.2 0.8

Energy Efficient Technologies Indoor air quality Reduce loads (pollution sources) Natural ventilation Heat recovery Air distribution (contaminant removal) effectiveness» Personal ventilation Air cleaning Thermal comfort Reduce loads (building shell, solar screen, internal loads) Low Temperature Heating- and High Temperature Cooling Systems Use of building mass (Thermo-Active-Building-Systems (TABS)) Drifting temperatures

Only 0.1 % is inhaled International Centre for Indoor Environment And Energy

International Centre for Indoor Environment And Energy

Round Movable Panel Headset International Centre for Indoor Environment And

Smoke visualization How it works... International Centre for Indoor Environment And Ene

Full-scale measurements Exposed Polluting International Centre for Indoor Environment And Energy

First results... outstanding performance! Ventilation Effectiveness V C C CEN Report CR 1752 (1998) E I C C S S Concentrations: C E exhaust air C S C I supply air breathing zone Mixing ventilation Mixing ventilation Displacement ventilation Personalized ventilation T supply - Vent. effect. T supply - Vent. effect. T supply - Vent. effect. T supply - Vent. effect. T inhal T inhal T inhal T room C - C - C - C - < 0 0,9-1,0 < -5 0,9 <0 1,2-1,4-6 1,2-2,2 0-2 0,9-5 - 0 0,9-1,0 0-2 0,7-0,9-3 1,3-2,3 2-5 0,8 > 0 1 >2 0,2-0,7 0 1,6-3,5 > 5 0,4-0,7 International Centre for Indoor Environment And Ene

AIR CLEANING Filters Photocatalytic Oxidation (PCO) Electrostatic Dessicant air cleaners Others International Centre for Indoor Environment And Energy

Clean and dirty filters

Why do filters pollute? Particle concentration Percentage Dissatisfied International Centre for Indoor Environment And Energy

Hypotheses SVOCs sorbed on particles SVOCs in gas phase Oxidized SVOCs Unreacted SVOCs

Gas phase air purification technologies Photo-catalytic oxidation (PCO) Ozone oxidation Thermal catalytic oxidation (TCO) Plasma oxidation Botanic filtration Sorption filtration

Number of Published Articles 450 400 350 300 250 Catalytic Oxidation Filtration Ozone Plasma Sorption UVGI 200 150 100 50 0 1992 1994 1996 1998 2000 2002 2004 2006 2008 2010 Published Year

Photo catalytic Oxidation (PCO) Catalyst:TiO 2 UV H 2 O CO 2 Adsorption of contaminants Photocatalytical reaction Desorption of final products

Perceived air quality (decipol) Results: Bldg mat, PCs, filters 20 15 P<0.017 Purifier Off Purifier On 10 5 P<0.03 0 low (35 L/s) intermediate (59 L/s) Outdoor air supply rate

Perceived air quality (decipol) Results: Human bio effluents 30 25 20 P<<0.001 Purifier Off Purifier On P<<0.001 15 10 5 0 low (12 L/s) intermediate (25 L/s) Outdoor air supply rate

PD % PAQ in PD% with and without desiccant rotor 100 80 P<0.0007 P<0.0108 P<0.0219 without desiccant rotoer with desiccant rotor 60 40 20 Conditions: Room volume: 40m 3 Outdoor airflow: 13L/s Outdoor air exchange Rate: 1.17 1/h Room relative humidity: 40% Room temperature: 23ºC Recirculated airflow: 54L/s 0 Carpet Linoleum Human

Effect of air cleaning on perceived Air Quality Sources: Peoplebuilding materialsused filters

STANDARDS Test methods for assessing the performance of gas-phase air cleaning media and devices for general ventilation - Part 2: Gas phase air cleaning devices (GPACD) (ISO/DIS 10121-2:2011) ISO/TC 142, Cleaning equipment for air and other gases CEN/TC 195 Air filters for general air cleaning

Chemical Air Cleaning Efficiency

Perceived Air Quality Air Cleaning Efficiency

Clean Air Delivery Rate

Reduction of Ventilation Rate Testing with gas concentrations The building component can be reduced according to the air cleaning efficiency Testing of Perceived Air Quality (PAQ) The total ventilation rate can be reduced according to the PAQ air cleaning efficiency.

Destilled water

Natural mineral water

Performance Ventilation vs performance % 100 98 96 94 92 90 (R 2 =0.777; P=0.009) 0 1 2 3 4 5 6 7 Ventilation rate (L/s per olf)

Performance Performance of schoolwork as a function of classroom ventilation 1,4 1,2 1 0,8 0,6 R 2 = 0.59 0 2 4 6 8 10 12 Ventilation (L/sp) Doubling ventilation rate ~14.5% higher performance

Summertime classroom T in C (NB: Different classes with natural/mechanical ventilation) 30 25 20 No AC AC 15 Off Low High Mechanical ventilation

Hours/week with windows open (NB: Different classes with natural/mechanical ventilation) 15 10 5 No AC AC 0 Off Low High Mechanical ventilation

Hours/week with windows open (NB: different classes in winter & summer) 10 8 6 4 Summer Winter 2 0 Low High Ventilation (with no cooling)

Analytical calculation of required ventilation Comparable to analytical calculation of cooling loads. No table with cooling loads (W/m 2 ) depending on room type.

Ventilation rate Cooling load Parameter Ventilation rate Cooling load Comfort requirement % dissatisfied-odor(paq) % dissatisfied Health- TLV Max. t o, 26 o C Analytical Mass balance Heat balance Outside environment Particles, odors, gases Temperature, solar load, humidity Air cleaning Heat recovery Building materials Emissions/adsorption Heat resistance/heat capacity People Bioeffluents Heat emission Evaporation Internal sources Emissions Heat emission Computers Odors, gases Watts HVAC system Outside air, emissions from components Outside air, Cooled air, heat exchange

CONCLUSIONS Air Cleaning as substitute for ventilation must be introduced in standards for required ventilation rates in buildings Test standards for gas phase air cleaners must also include measurements of perceived air quality A certification scheme must be introduced

CONCLUSIONS There is no standard which directly specifies requirements for the indoor air quality. Instead it is indirectly achieved by specifying a required minimum ventilation rate There is a general agreement between ASHRAE and EN standards that both contributions from people and contributions from buildings (materials, furnishing, HVAC systems) must be taken into account when specifying the required ventilation rate. The standards for specifying ventilation rates should distinguish between buildings with low-emitting materials and buildings with high-emitting materials. This should increase the interest in establishing better test methods and better labelling of building materials.

CONCLUSIONS Whether the required ventilation rate should be based on adapted or un-adapted persons should be evaluated on a case-by-case basis between rooms and the activities they serve; but at the same time, the health must be taken into account. For better evaluation of the health risk there is a need for threshold limit values that safeguard health in non-industrial environments In the future the goal must be a full analytical calculation of the minimum required ventilation rate (taking into account material emissions, air cleaning, etc)