EPR: Steam Generator Tube Rupture analysis in Finland and in France

Similar documents
AP1000 European 15. Accident Analysis Design Control Document

LIMITED COMPARISON OF EVOLUTIONARY POWER REACTOR PROBABILISTIC SAFETY ASSESSMENTS

DISTRIBUTION LIST. Preliminary Safety Report Chapter 12 Design Basis Conditions Analysis UK HPR1000 GDA. GNS Executive.

Simulation of thermal hydraulics accidental transients: evaluation of MAAP5.02 versus CATHAREv2.5

UKEPR Issue 05

Joint ICTP-IAEA Essential Knowledge Workshop on Deterministic Safety Analysis and Engineering Aspects Important to Safety. Trieste,12-23 October 2015

Office for Nuclear Regulation

RELAP5/MOD3.2 INVESTIGATION OF A VVER-440 STEAM GENERATOR HEADER COVER LIFTING

Fatigue Monitoring for Demonstrating

IAEA Training in level 1 PSA and PSA applications. Other PSA s. Low power and shutdown PSA

Westinghouse Small Modular Reactor. Passive Safety System Response to Postulated Events

Station Blackout Analysis for a 3-Loop Westinghouse PWR Reactor Using TRACE

RELAP5 Analysis of Krško Nuclear Power Plant Abnormal Event from 2011

ANTICIPATED ANALYSIS OF FLAMANVILLE 3 EPR OPERATING LICENSE - STATUS AND INSIGHTS FROM LEVEL 1 PSA REVIEW

RELAP 5 ANALYSIS OF PACTEL PRIMARY-TO-SECONDARY LEAKAGE EXPERIMENT PSL-07

NSSS Design (Ex: PWR) Reactor Coolant System (RCS)

AP1000 European 21. Construction Verification Process Design Control Document

NPP Simulators Workshop for Education - Passive PWR NPP & Simulator Overview

Office for Nuclear Regulation

DEVELOPMENT OF ASP METHODOLOGY AND ITS APPLICATION TO THE SIGNIFICANT ACCIDENT PRECURSORS. Sunghyun Park, Seunghyun Jang and Moosung Jae*

Shutdown and Cooldown of SEE-THRU Nuclear Power Plant for Student Performance. MP-SEE-THRU-02 Rev. 004

Ensuring a nuclear power plant s safety functions in provision for failures

Safety Analysis Results of Representative DEC Accidental Transients for the ALFRED Reactor

CANDU Safety #6 - Heat Removal Dr. V.G. Snell Director Safety & Licensing

INVESTIGATION OF CRITICAL SAFETY FUNCTION INTEGRITY IN CASE OF STEAM LINE BREAK ACCIDENT FOR VVER 1000/V320

AP1000 European 9. Auxiliary Systems Design Control Document

UKEPR Issue 04

Research on Safety System Configuration of HPR1000. China Nuclear Power Design Co., ltd: Li Sheng Jie

DISTRIBUTION LIST. Preliminary Safety Report Chapter 11 Steam and Power Conversion System UK HPR1000 GDA. GNS Executive.

Deterministic Safety Analyses for Human Reliability Analysis

IAEA-TECDOC-1361 Assessment and management of ageing of major nuclear power plant components important to safety

Research Article Assessment of Severe Accident Depressurization Valve Activation Strategy for Chinese Improved 1000 MWe PWR

Olkiluoto 3 EPR PSA Main results and conclusions fulfillment of the regulatory requirements for operating license

NOT PROTECTIVELY MARKED. REDACTED PUBLIC VERSION HPC PCSR3 Sub-chapter Normal Operation NNB GENERATION COMPANY (HPC) LTD

Mitigation coverage estimation of passive system s using causal reasoning analysis with Multi-level Flow Model

Licensing of New Build Reactors in the UK Part 2

Introduction to Level 2 PSA

C. heating turbine exhaust steam above its saturation temperature. D. cooling turbine exhaust steam below its saturation temperature.

Analysis of a Loss of Normal Feedwater ATWS with TRACE 5.0

SEVERE ACCIDENT FEATURES OF THE ALTERNATIVE PLANT DESIGNS FOR NEW NUCLEAR POWER PLANTS IN FINLAND

4.2 DEVELOPMENT OF FUEL TEST LOOP IN HANARO

Research Article The Investigation of Nonavailability of Passive Safety Systems Effects on Small Break LOCA Sequence in AP1000 Using RELAP5 MOD 4.

Work Exercises and Case Studies to Write Safety Evaluation Report

AP1000 European 16. Technical Specifications Design Control Document

SMR/1848-T21b. Course on Natural Circulation Phenomena and Modelling in Water-Cooled Nuclear Reactors June 2007

Example Pressurized Water Reactor Defense-in-Depth Measures For GSI-191, PWR Sump Performance

DEVELOPMENT OF LOW POWER SHUTDOWN LEVEL 1 PSA MODEL FOR WESTINGHOUSE TYPE REACTORS IN KOREA : OVERVIEW, RESULTS AND INSIGHTS

Considerations on the performance and reliability of passive safety systems for nuclear reactors

AP1000 European 15. Accident Analyses Design Control Document

* Science Applications International, Corporation

Status report 78 - The Evolutionary Power Reactor (EPR)

nuclear science and technology

Integrated Safety Assessment of the Steam Generator Tube Rupture Accident in a PWR using Best Estimate Codes

nuclear science and technology

PSA Michael Powell, Roy Linthicum, Richard Haessler, Jeffrey Taylor

MDEP Common Position CP-EPRWG-05

UKEPR Issue 04

Research Article RELAP5/MOD3.3 Best Estimate Analyses for Human Reliability Analysis

CANDU Safety #14 - Loss of Heat Sink Dr. V.G. Snell Director Safety & Licensing

Thermal-Hydraulic Analysis of Single and Multiple Steam Generator Tube Ruptures in a Typical 3-Loop PWR

Nuclear Power Plant Safety Basics. Construction Principles and Safety Features on the Nuclear Power Plant Level

Nuclear Power Plant Safety Basics. Construction Principles and Safety Features on the Nuclear Power Plant Level

6.1 Introduction. Control 6-1

Chapter 4 Safety Principles for France s Pressurised Water Reactors

Elena Dinca CNCAN Daniel Dupleac - UPB Ilie Prisecaru UPB. Politehnica University of Bucharest, Romania (UPB)

I have now made my own analysis of the Fukushima incident and its relevance to the UK's new nuclear build.

Review Article Integral Test Facility PKL: Experimental PWR Accident Investigation

ACR-1000: ENHANCED RESPONSE TO SEVERE ACCIDENTS

Decree No of 10 April 2007

Safety Review on Recent Steam Generator Tube Failure in Korea and Lessons Learned

Joint ICTP-IAEA Course on Natural Circulation Phenomena and Passive Safety Systems in Advanced Water Cooled Reactors

CLASSIFICATION OF SYSTEMS, STRUCTURES AND COMPONENTS OF A NUCLEAR FACILITY

Westinghouse UK AP1000 GENERIC DESIGN ASSESSMENT. Resolution Plan for GI-AP1000-PSA-01. Success Criteria for the Probabilistic Risk Assessment (PSA)

Westinghouse UK AP1000 GENERIC DESIGN ASSESSMENT. Resolution Plan for GI-AP1000-PSA-01. Success Criteria for the Probabilistic Risk Assessment (PSA)

LOCA analysis of high temperature reactor cooled and moderated by supercritical light water

Lecture 7 Heat Removal &

IAEA Generic Review for UK HSE of New Reactor Designs against IAEA Safety Standards EPR

Passive Cooldown Performance of Integral Pressurized Water Reactor

CANDU Safety #12: Large Loss of Coolant Accident F. J. Doria Atomic Energy of Canada Limited

Probabilistic Safety Assessment for Hot Standby and Hot Shutdown

LFW-SG ACCIDENT SEQUENCE IN A PWR 900: CONSIDERATIONS CONCERNING RECENT MELCOR / CALCULATIONS

UKEPR Issue 00

WESTENGHOUSE AP600 ADVANCED NUCLEAR PLANT DESIGN

Source Terms Issues and Implications on the Nuclear Reactor Safety

AP1000 European 7. Instrumentation and Controls Design Control Document

Pressurized Water Reactor Systems

DESIGN AND SAFETY PRINCIPLES LEONTI CHALOYAN DEPUTY CHIEF ENGINEER ON MODERNIZATION

A New Method Taking into Account Physical Phenomena Related to Fuel Behaviour During LOCA

McGuire Nuclear Station UFSAR Chapter 15

AP1000 European 6. Engineered Safety Features Design Control Document

ELFR The European Lead Fast Reactor DESIGN, SAFETY APPROACH AND SAFETY CHARACTERISTICS. Alessandro Alemberti

Supporting Deterministic T-H Analyses for Level 1 PSA

Technical Challenges Associated with Shutdown Risk when Licensing Advanced Light Water Reactors

AP1000 The PWR Revisited

Research Article Extended Station Blackout Coping Capabilities of APR1400

PSA ANALYSIS FOCUSED ON MOCHOVCE NPP SAFETY MEASURES EVALUATION FROM OPERATIONAL SAFETY POINT OF VIEW

A Brief Overview of the APR1400 Commissioning. KHNP Sep. 13, 2017 Sang Won Lee

An Introduction of Simulator Exercises and Operator Interviews in support of C-2 Human Reliability Analysis

EXPERIMENTS ON THE PERFORMANCE SENSITIVITY OF THE PASSIVE RESIDUAL HEAT REMOVAL SYSTEM OF AN ADVANCED INTEGRAL TYPE REACTOR

ACR Safety Systems Safety Support Systems Safety Assessment

Transcription:

EPR: Steam Generator Tube Rupture analysis in Finland and in France S. ISRAEL Institut de Radioprotection et de Sureté Nucléaire BP 17 92262 Fontenay-aux-Roses Cedex, France Abstract: Different requirements between Finland and France lead EPR designer to define different features (system or action) for management of accidents on Olkiluoto 3 EPR that is under-construction in Finland compared to Flamanville 3 EPR that is foreseen in France. One of these differences concerns the management of Steam Generator Tube Rupture since no primary coolant (liquid and steam) release to the environment is allowed in Finland dislike in France where primary steam releases are not forbidden. This leads to define on Finnish EPR a strategy that anticipates mitigation action compared to French EPR and that only uses the unaffected steam generators. This strategy is intended to reduce the release to the environment. IRSN has analysed an other aspect of the Steam Generator Tube Rupture: the backflow (flow of unborated water from steam generator to the primary circuit). Indeed, if the Reactor Coolant Pumps have been shut down, the creation an unborated water plug because of the backflow could lead to reactivity accident in case of Reactor Coolant Pump restart. IRSN analysis shows that, using the current Olkiluoto 3 SGTR mitigation strategy and very penalizing assumptions, the amount of unborated water transferred to the primary circuit on the Finnish EPR could be higher than on the French EPR in the long term. Discussions are going on between STUK and TVO to finalize the SGTR strategy so that both releases into the environment and risk of backflow can be minimized. 1 INTRODUCTION In France, the Technical Guidelines for the design and construction of the next generation of nuclear power plants with pressurized water reactors specify that the emergency core cooling function can be provided through an optimized concept comprising a cold leg medium head safety injection (MHSI) with an operating pressure below the opening setpoint of the steam generator safety valve. This aims at avoiding the discharge of liquid primary coolant to the environment in case of Steam Generator Tube Rupture (SGTR). The discharge of steam is implicitely permitted allowing for the activity release is largely lower in case of steam release compared to a liquid release. In Finland, the YVL guide 1.0 specifies that pressure management during PWR primary-to secondary leaks shall be so arranged that no coolant discharges to the environment are required. This implicitely forbids liquid and steam discharge to the environment. Because of the different requirements, the management of SGTR accident on EPR reactor that under construction in Finland is different from the EPR reactor that is planned to be built in France. This difference has an impact on the releases to the environment but it can also have an impact on the amount of backflow of unborated water from the affected steam generator (SG) into the primary circuit.

The present study presents the different strategies and their impact on the secondary-toprimary backflow. 2 SGTR MANAGEMENT 2.1 SGTR management in France Short term phase The SGTR leads to a loss of primary coolant which is transferred to the Steam Generator (SG) affected by the rupture. The break induces a decrease of the Reactor Coolant System (RCS) pressure and a contamination of the secondary side due to SGTR direct flow rate. The reactor trip occurs either on "Pressurizer pressure < MIN2" or on "SG level > MAX1" in affected SG. The reactor trip signal automatically trips the turbine and with assumption of unavailability of the Main Steam Bypass (MSB) because of its non F1-classification or because of the loss of offsite power (LOOP) which is superposed at turbine trip, the SG pressure rapidly increases resulting in steam discharge to the atmosphere through the main steam relief trains (MSRT). Continuous loss of RCS coolant inventory and primary coolant contraction after reactor trip in case of an initial full power state lead to depressurize the primary side. Either on Safety Injection (SI) signal or on "SG level > MAX2" in the affected SG (if not already actuated in SI signal), a partial cooldown is performed by MSRT of all SGs (included the faulted one) from a 95.5 bar secondary pressure down to 60 bar at a cooldown rate of -100K/h. At end of partial cooldown, RCS pressure is given by the Medium Head Safety Injection (MHSI) shut off pressure (between 85 bar and 97 bar) and a contaminated SGTR direct flow still enters the affected SG, leading to its level increase. At this stage, a controlled state (Sl and SGTR mass flow balance) is already reached. On "SG level > MAX2" and after the end of partial cooldown, the affected SG is identified and automatically isolated on its steam side (closure of its Main Steam Isolation Valve (MSIV), the MSIV of the 3 unaffected SG remaining open, lifting-up of its MSRT pressure setpoint above the MHSI delivery pressure and below the Main Steam Safety Valves MSSV pressure setpoint). The short term management of the SG is presented on the figure 1. 2

Figure 1: short term - French strategy Then, the pressure balance between primary side and affected SG is reached and the leak is finally cancelled. This is the end of the short term phase. The sequence describes above does not credit non-f1a classified systems. As a response of the activity signal (F1B classified), specific SGTR conter-measures can be actuated by the operator such as reactor and turbine trip, pressuriser spray to decrease primary pressure down to secondary pressure, cut off of pressuriser heaters, start up of both CVCS pump and reduction of the letdown flow to makeup SGTR flow. Long term phase The safe shutdown state is defined as a state where the Low Head Safety Injection (LHSI) is connected in Residual Heat Removal mode and the affected SG is isolated. The sequence of actions to be performed by the operator to reach the safe shutdown state can be divided into 2 successive phases. Boration and Cooldown The boration is performed via the Emergency Boration System (EBS). In order to compensate the EBS injection (avoidance of primary pressure increase by high pressure EBS pumps) the plant is cooled down simultaneously by the unaffected SGs. The EBS is sized to balance the volume contraction and the reactivity insertion of a 50 k/h cooldown with both pumps in operation. If, as a single failure, one pump fails, the operator reduces the cooldown gradient to 25 k/h. As additional measure not to perturb the pressure balance between primary side and the affected SG, the MHSI is kept under operation (this maintains primary pressure). Depressurization of RCS and Affected SG The primary side and faulted SG depressurizations are performed, after completion of the boration and cooldown phase, by opening the MSRT of the affected SG, after isolation of MHSI and accumulators and EBS. If the MSRT fails for any reason, the depressurization can also be done via the bypass valve of the MS isolation valve (classified F1B) without any risk of back flow. 3

If the water level in the affected SG is too high (risk of water entrainment when the SG restarts to boil) some inventory reduction can be performed by opening the SG blowdown line between the affected SG and an unaffected one (blowdown line F1B classified) before depressurization. 2.2 SGTR management in Finland With respect to the French management, the first difference is that the response of the activity signal is credited to anticipate mitigation actions. The second difference is that on activity signal, all main steam isolation valves are closed, the setpoint of the MSRT on the affected SG is increased to about 100 bar (above MHSI delivery pressure and below MSSV pressure setpoint) and the setpoint of the MSRT on the other SG is steply decreased down to 60 bar (see figure 2). This fast cooldown aims at reducing the duration of steam releases to the atmosphere. Figure 2: short term - Finnish strategy Other differences are: - restarting of reactor coolant pumps before cooldown, if they have been stopped because of a loss of offsite power (LOOP); - EBS pumps run until cooldown completion. 3 SGTR ANALYSES 3.1 SGTR analyses in French and Finnish Safety Analysis Reports The goal of SGTR analyses presented in the Safety Analyses Reports is to: - check that there is no overfilling of the affected steam generator, - evaluate the releases to the environment. Two analyses are presented in both French and Finnish Safety Analysis Reports: - 1 tube SGTR without CVCS in French PCC3 and Finnish DBC3, - 2 tubes SGTR without CVCS in French PCC4 and Finnish DBC4. 4

Both are analysed with LOOP (maximization of the releases to the environment) and without LOOP (maximization of SG filling) assumed at the turbine trip depending on the goal of the studied cases. An additional analysis is presented in the Finnish Safety Analysis Report: the 1 tube SGTR with CVCS. 3.2 SGTR and maximisation of the backflow 3.2.1 Studied SGTR The goal of the present study is to maximize the secondary-to-primary backflow. Thus, a 2 tubes SGTR has been studied because it speeds up the primary depressurisation and allows a larger flow through the broken tube. The thermal-hydraulic code CATHARE has been used to simulate the transient. Both French and Finnish strategies have been simulated. 3.2.2 Assumptions The goal of the present IRSN analysis is to maximize the secondary-to-primary flow. This lead to some differences on the assumptions. In the French and Finnish Safety Analysis Reports, the following assumptions are assumed to maximize primary-to-secondary flow and release to the environment: - CVCS charging flow is credited, - maximum MHSI flow rate (97 bar shutoff pressure), - minimum MSRT setpoints in the affected steam generator (94 bar before partial cooldown, 58.5 bar at the end of partial cooldown, 100 bar after setpoint lift-up), - maximum MSRT setpoints in the safe steam generator (97 bar before partial cooldown, 61.5 bar at the end of partial cooldown). In order to penalise the secondary-to-primary flow, assumptions that maximized secondary/primary flow are assumed in the present study: - CVCS charging flow is not credited, - minimum MHSI flow rate (85 bar shutoff pressure), - maximum MSRT setpoints in the affected steam generator (97 bar before partial cooldown, 61.5 bar at the end of partial cooldown (only on French EPR), 100 bar after setpoint lift-up), - maximum MSRT setpoints in the safe steam generator (97 bar before partial cooldown, 61.5 bar at the end of cooldown). LOOP is assumed in the present study since unborated water injection in the primary circuit is problematic when the RCP have been stopped. 3.2.3 Objectives In order to avoid the risk of return to criticality in case of heterogeneous dilution, the volume of the unborated water plug that is send to the core inlet in case of RCP restart shall be lower 5

than about 3 m 3. This volume is the volume of backflow above which RCP restart shall not be allowed. 3.2.4 Results In French EPR, the partial cooldown is performed by all SGs. At the end of the short term phase, the balance between RCS and SGa pressure is reached at the MHSI delivery pressure (see figure 3). Figure 3: French case - primary and secondary pressures So, the risk of SGTR backflow is prevented by the MHSI operation. Just before RCS depressurisation, 2 tons of unborated water have flowed from secondary to primary circuit (see figure 4). Figure 4: French case RCS inlet and outlet flowrates 6

If the EBS is stopped once the cold shutdown is reached, as is done in French EPR, the SGTR backflow is no more limited. More than 30 tons of unborated water is transfered from secondary to primary circuit (see figure7). Figure 7: Finnish case RCS inlet and outlet flowrates with early EBS cut-off 4 CONCLUSIONS IRSN has analysed the impact of both French and Finnish strategies on the risk of backflow (secondary-to-primary flow) following a Steam Generator Tube Rupture. Indeed, if the Reactor Coolant Pumps have been stopped (fr example because of LOOP), the creation an unborated water plug higher than about 3 tons because of the backflow could lead to reactivity accident in case of RCP restart. IRSN analysis shows that, using the current Olkiluoto 3 SGTR mitigation strategy and very penalizing assumptions, the amount of unborated water transferred form the secondary circuit to the primary circuit on the Finnish EPR is ten times more than on the French EPR in the long term. The conclusions of this analysis have been discussed with the STUK. Based on their own analysis and supported by these discussions, STUK has asked AREVA NP and TVO to study this phenomenon and if necessary to propose a way to manage it. 8