Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

Similar documents
TECHNICAL ANALYSIS #2

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

Standard of Practice - Campus Electrical Distribution System

Engineering Data for Copper and Aluminum Conductor Electrical Cables

DIVISION 26 ELECTRICAL Electrical Power Conductors and Cables

PV Solar Wiring Solutions

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

SECTION INSULATED WIRE AND CABLE

Aluminum vs. Copper Conductors A Serious Alternative?

This section applies to the design and installation relating to wire and cable systems and terminations. 16G Figure 1 16G Figure 2

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

15 kv EPR Insulated, Jacketed, URD Cable

America s Wire Company

26/35kV Copper XLPE Insulation Electric Cable

SECTION GROUNDING


NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

Cables ELE E L CT E C R T R IC I C A A L L

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

PILC Replacement: Getting the Lead Out

REA LISTED. Throughout the catalog you will notice blue highlighted items. These are the most frequently ordered BURNDY Products.

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

BLACK EPR INSULATED MEDIUM VOLTAGE CABLES. Ronald F. Frank, Eng. Consultant

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

1. Section COVER PAGE: remove and replace with new Cover Page, Attached.

*** Supercedes: BECO E and COM , , & ***

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION GROUNDING AND BONDING

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

SECTION WIRES AND CABLES

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

A. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION PART 1 GENERAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

SECTION HEAT TRACING FOR PLUMBING PIPING

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

SECTION GROUNDING AND BONDING

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

SECTION HEAT TRACING FOR PLUMBING PIPING

CONTENTS. B. System Design and Performance Requirements

Increasing the capacity of existing transmission lines by re-conductoring using ACSS HTLS conductors

SECTION GROUNDING AND BONDING

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Kaf-Tech Product Specification

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Permitting and Inspecting PV Systems. PV Codes and Standards 101. Photovoltaic System Basics

Glossary Of Terms M-1

Building Wire CARRYING YOUR ELECTRICITY

Article 300: Wiring Methods And Materials

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables.

RESIDENTIAL QUICK REFERENCE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

Mechanical UNITAP Clear Insulated Multi-Tap UL Listed for Code and Flex Conductor

Technical Specifications

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

TECHNICAL DATA. A REFERENCE FOR The Electrical Power Industry. www. ElectricalPartManuals. com ANDERSON POWER SYSTEMS, INC.

Article 324: Flat Conductor Cable (FCC) 1.! Type FCC (flat conductor cable) cable wiring system is designed for installations under.

DATA SHEET Single Core 2HR Fire Rated Cable

CATALOG. WIRE and CABLE. borderstates.com

Design Standard Conduit for Electrical Systems

(Condensed from National Electric Code)

Procurement Services SVC East Fowler Avenue Tampa, Florida (813)

Please check with your local inspection authority for any additional requirements before installation.

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

MSME Testing Centre, 65/1, G. S. T. Road, Guindy, Chennai, Tamil Nadu. Discipline Electrical Testing Issue Date

SECTION EARTHING AND EARTH FAULT PROTECTION

History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton

SECTION CONDUIT AND FITTINGS

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

SECTION MEDIUM VOLTAGE ELECTRICAL DISTRUBUTION (ABOVE 600 VOLTS)

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

UNDERGROUND SERVICES SECONDARY

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

GROUNDING. Ground-Lok CLAMP SYSTEM SERRATED HEAD - (COMPONENTS)

1. Contractor shall obtain a valid electrical permit from the Town of Perinton.

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS

Transcription:

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

Today s Topics Brief Overview of Southwire In-depth Discussion on Aluminum Characteristics Discussion of Southwire Aluminum 600 volt and MV Products.

Founded in 1950 by Roy Richards Sr. We manufacture all types of wire and cable that deliver power from the generation plant to the residential home.

Southwire Today Employ over 4,000 Worldwide Annual Sales Approx. $5.5 billion 9 distribution centers in North America Leaders in Research & Development First to commercialize a superconductivity circuit that feeds one of our plants Southwire holds more than 240 patents in 40 countries

Monthly Average Copper Price

Why Market Aluminum? COST SAVINGS: 70% of the cable cost is in the metals. With a differential of $2.00 between copper and aluminum there is a potential for 35% - 50% savings Aluminum is code compliant, safe and reliable Honda Indiana Plant 15kv AIA and 600 volt AIA Bloomingburg Ethanol Plant, Bloomingburg, Ohio Met-Life Stadium (GO JETS) Charlotte Bobcat Arena GM 5E Spec Lead time 7 weeks

Aluminum Product Offering Medium voltage single conductor cable 2kv-46kv Multi-conductor non-armored cable CT3-13ET and CT3-09ET Interlocked armor AL-13ET and AL-09ET Single conductor Tray Rated XHHW-2 Multi-conductor Tray Rated XHHW-2/PVC Interlocked armor AL-01XXH Sizes 250kcmil Aluminum and above; 3/0 copper equal ampacity and above

Aluminum Stigma Beverly Hills Supper Club Fire May 28 th 1977, Beverly Hills Supper Club, Southgate KY Catches on fire, 165 fatalities. Aluminum wiring was cited as the most probable cause. It was used on branch circuits; receptacles, switches, cans ext. What Caused the Fire??

Examples of Undesirable Materials Combination in an Electrical Connection RESULT OF DIFFERENCES IN THERMAL EXPANSION AND CREEP OF MATERIALS : Rapid conductor deformation due to creep Loss of mechanical load and connector degradation

Definition of Thermal Expansion and Creep CTE: The coefficient of thermal expansion is defined as the fractional increase in length per unit rise in temperature. Micro inches/inch o F Creep is the measurement of the rate of change of a material s dimension over a period of time when subject to a a force at a particular temperature. Copper and AA8000 series aluminum have similar creep rates unlike EC 1350 which has a much higher creep rate than copper. Micro inches per inch per hour at temperature T and force F.

Conditions for a Reliable Aluminum Electrical Connection The aluminum conductor and connector alloys must have similar creep-properties to avoid loss of contact load and electrical degradation over a long service life

NEC and UL Requirements on Aluminum Conductors NEC 310-14 (1987) Aluminum conductors rated 600 volt used inside buildings shall be made of AA-8000 series. No aluminum grade specification on Medium voltage Cable. Connectors: UL 486B Dual rated lugs for copper or aluminum mechanical or compression.

Aluminum Association AA8000 Series Alloy: Traces of copper gives better thermal stability Traces of iron makes it more flexible Anneal: Aluminum is treated with heat to removes internal stresses in the aluminum. Less brittle Southwire AA8176 six other series are registered with Aluminum Association AA

Conditions for a Reliable Aluminum Electrical Connection Typical example of a UL Dual-Rated connection Al-Cu, Al7-Cu or Al9-Cu.

Creep Loss % or Stress Relaxation kp ALUMAFLEX The creep properties of AA 8176 are comparable to annealed copper.

Connection Preparation For Aluminum Conductors Disrupt surface contaminant films with steel brush Unused aluminum strand surfaces before brushing. Unused aluminum strand surfaces after brushing.

Connection Preparation For Aluminum Conductors Apply a recommended inhibitor to the conductor Torque the bolt or screw to levels recommended by the manufacturer; excessive torque will deform the conductor excessively and may lead to loss of strands (this applies to aluminum and copper conductor)

Copper and Aluminum Comparison COPPER ALUMINUM Heavier 500kcmil strd: 1,544lb/1,000 Better Conductivity per size at 5 & 15kv dc Ohms 500kcmil =.0216 ohms/1,000 Impedance at 75C 60 Hz in Magnetic duct 5 & 15kv ohms/1,000 4/0 : 0.0650 + j 0.0583 ; z = 0.0873 250kcmil: 0.0557 + j 0.0570 ; z = 0.0797 350kcmil: 0.0386 + j 0.0562 ; z = 0.0681 500kcmil: 0.0300 + j 0.0526 ; z = 0.0605 750kcmil: 0.0223 + j 0.0497 ; z = 0.0545 Lighter 54% lighter 750kcmil strd: 704lb/1,000 Aluminum 61% Conductivity of Cu dc Ohms 500kcmil =.0354 ohms/1,000 750kcmil =.0236 ohms/1,000 Impedance at 75C 60 Hz in Magnetic duct 5 & 15kv ohms/1,000 350kcmil: 0.0614 + j 0.0468 ; z = 0.0773 500kcmil: 0.0435 + j 0.0444 ; z = 0.0624 600kcmil: 0.0366 + j 0.0431 ; z = 0.0566 750kcmil: 0.0298 + j 0.0419 ; z = 0.0514 1000kcmil: 0.0233 + j 0.0414 ; z = 0.0475 Source: IEEE 141-1993

Types of Strand Construction Approximate size comparison: 3% 9% 15% Concentric Compressed Compact Solid

Aluminum Cable Construction Aluminum cable is similar to copper with the exception the conductor will be aluminum. Tape shield will remain copper. Tape shield always copper Compressed Cu Compact Al

Comparison of Copper and Aluminum Conduit Fill, 600 Volt Cu Size Amps Al Size Amps EMT Size #4 85 #2 90 1 1/4 #2 115 1/0 120 1 1/2 1/0 150 3/0 155 2 2/0 175 4/0 180 2 3/0 200 250 kcmil 205 2 1/2 4/0 230 300 kcmil 230 2 1/2 250 kcmil 255 350 kcmil 250 2 1/2 350 kcmil 310 500 kcmil 310 3 400 kcmil 335 600 kcmil 340 3 500 kcmil 380 750 kcmil 385 4 600 kcmil 420 900 kcmil 430 4 Conduit Fill - Table C.1; C.1A, 2005 NEC Annex C, 4 wire plus ground Ampacity Table 310.16 @75C; 30C ambient.

Comparison of Copper and Aluminum Conduit Fill, 5kv Cu Size Cu OD Amps Rigid Size Al Size Al OD Amps Rigid Size #2 0.76 130 3 1/0 0.84 140 3 1/0 0.87 180 3 4/0 0.98 215 3 2/0 0.91 205 3 4/0 0.98 215 3 4/0 1.02 280 3 350kcmil 1.13 305 3 250kcmil 1.07 315 3 500kcmil 1.26 380 4 350kcmil 1.18 385 4 600kcmil 1.35 385 4 500kcmil 1.30 475 4 750kcmil 1.45 490 4 750kcmil 1.49 600 5 1000kcmil 1.60 580 5 Conduit fill is based on 3 phase with equipment ground size per NEC. All Conduit Sizes are Rigid Metal Ampacity based on Table 310.73 and 310.74 conduit in air. 1000kcmil Al DOES NOT meet the ampacity of 750kcmil Cu.

Comparison of Copper and Aluminum Conduit Fill, 15kv Cu Size Cu OD Amps Rigid Size Al Size Al OD Amps Rigid Size #2.99 150 3 1/0 1.04 150 3 1/0 1.08 195 3 4/0 1.19 230 3 2/0 1.12 225 3 4/0 1.19 230 3 4/0 1.22 295 4 350kcmil 1.35 310 4 250kcmil 1.28 330 4 500kcmil 1.47 385 4 350kcmil 1.38 395 4 600kcmil 1.56 395 5 500kcmil 1.50 480 5 750kcmil 1.66 485 5 750kcmil 1.76 585 5 1000kcmil 1.89 565 6 Conduit fill is based on 3 phase with equipment ground size per NEC. All Conduit Sizes are Metal Rigid Ampacity based on Table 310.73 and 310.74 conduit in air. 1000kcmil Al DOES NOT meet the ampacity of 750kcmil Cu.

Flexibility Alloying and annealing processes make AA-8176 as flexible for equivalent Ampacity copper conductors. NEC 312.6(B) requires the same bending space in enclosures at terminals for equal ampacity copper and AA-8176 conductors.

Pulling Tensions and Minimum Bending Radius AA 8176 aluminum has higher tensile strength to weight ratio than equivalent copper ampacity. Max allowable tensile for copper is 0.008 lbs/cmil and for AA 8176 is 0.006 lbs/cmil. Minimum bending radius for both aluminum and copper shielded cable is 12 times the OD and 8 times the OD for non-shielded cable.

Pulling Tensions (Cont.) Conductor Size Max Allowable Tension lbs Weight lbs/1,000 Max Pull Length (ft) 0.3 coef fric 500kcmil Cu 4000 lbs 1544 8,639 750kcmil Al 4500 lbs 704 21,307

New Products New No Lead EPR Polymer New Sim pull Jacket for MV cable Instrumentation Cable (600V)

Ingredients of our Current EPR Insulation ERI-3728-5 Base Filler (EPDM) Silane Paraffin Wax Red Lead Clay Filler Zinc oxide Polyethylene Peroxide Southwire buys its EPR from Electric Cable Compounds, Inc located in Seymour Connecticut. The present EPR compound we use is Superohm ERI-3728-5.

Ingredients of our New EPR Insulation ERI-3748 Base Filler (EPDM) Silane Paraffin Wax Red Lead Clay Filler Zinc oxide Polyethylene Peroxide Eco Friendly Cable EFC Dovetails with green environments, Hospitals, schools, institutional.

Features of our New EPR Insulation ERI-3748 No Lead Creamy in color Lead is what gives EPR its reddish color UL listed AEIC qualified Has wet rating just like leaded EPR EXACT SAME Characteristics

Questions? We want to earn your business!!!