SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS

Similar documents
SOLAR COOLING WITH SMALL SIZE CHILLER: STATE OF THE ART

Development of an Innovative 2.5 kw Water- Silica Gel Adsorption Chiller

Solar cooling plants: how to arrange solar collectors, absorption chillers and the load

SorTech package solution description

Modeling and analyzing solar cooling systems in Polysun

Customized Absorption Heat Pumps for Utilization of Low-Grade Heat Sources

APPLICATION OF CUSTOMIZED ABSORPTION HEAT PUMPS WITH HEATING CAPACITIES ABOVE 500 kw PROJECT: ACKERMANNBOGEN, MUNICH

Heat pumps. WP5 Education and Economic Promotion

[N670] Noise Impact of Absorption Machines for Civil Applications. First Author: Franco Cotana. Second Author: Andrea Nicolini ABSTRACT

Report on thermal cooling system implementation and performance

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

Noise Impact of Absorption Machines for Civil Applications

Simulation and Design of Solar Absorption Cooling System. Simulacija i projekt solarnog apsorpcijskog sustava hlađenja

Thermodynamic Simulation of an Advanced Hybrid Solar-Gas Seawater Desalination System

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Experimental analysis of a solar absorption system with interior energy storage

Thermally operated mobile air-conditioning system

Advanced heat driven cooling cycles for low-temperature waste heat recovery

State of the Art of Air-source Heat Pump for Cold Regions

Performance Analysis of a Solar Powered Adsorption Cooling System

Innovative Systems for Solar Air Conditioning of Buildings

Solar Cooling Technologies for Southern Climates - A System Comparison

Analysis of Solar Thermal Cooling System Using TRANSOL

Identified technologies for the InfraSUN pilot plant

Control strategies study of a complete solar assisted air conditioning system in an office building using TRNSYS.

Experimental Research and Performance Analysis of a Solar-Powered. Air-conditioning System in a Green Building

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Reducing running costs, whilst benefiting the environment and the future

Renewable Energy Based Active Cooling System

The 34 th Congress of Euroheat & Power

BUILDINGS & OFFICE SPACES INDUSTRIAL SOLUTIONS. Combined production of Heat and Power. Waste Heat Recovery Bottoming Cycle

A STUDY OF ABSORPTION CHILLER/HEATER APPLICATION IN MARINE ENGINEERING

Comfort Cooling Application Using Fixed Focus Solar Parabolic Dish Concentrator Integrated with Double Effect Vapor Absorption Machine

Product catalogue A25. Absorption Cooling Systems

ADVANCED ABSORPTION CHILLER CONVERTS TURBINE EXHAUST TO AIR CONDITIONING

HIGH EFFICIENCY SHOWERS WASTE WATER HEAT RECOVERY UNIT. Saved power 80kW. Showers waste water 9 C Power consumption 3,1kW. Showers waste water 31 C

Simulation And Optimization of a Solar Absorption Cooling System Using Evacuated Tube Collectors

Héctor Rubio Plana Gas Natural, SDG S.A. 18th. June 2009

Draft proposals for Test methods for close-coupled solar water heating systems - Reliability and safety

i-chiller COMPACT 1 to 4 kw 0 C to 30 C ic03c to ic10c RELIABILITY:

New developed solar thermal systems for heating and cooling Budapest, 16 th April 2009 Tsekouras Panagiotis Mech. Engineer NTUA Centre for Renewable

13/10/2011 Air Solutions International Air Solutions I P/L Solutions to Indoor Air Problems Vapor Absorption Chillers 1

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Free Cooling Technology

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

Solar Air-Conditioning Systems in small - medium scale applications

Design, modelling, performance optimization and experimentation of a reversible HP/ORC prototype.

Heat rejection systems for solar driven sorption systems

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 7 to 16 KW

RIQUALIFICAZIONE DI EDIFICI ESISTENTI CON ELEVATI STANDARD ENERGETICI: METODI E TECNOLOGIE

DEVELOPMENT OF TRIPLE-EFFECT ABSORPTION CHILLER-HEATER

Renewable Energy. to heat your home. thermia.com

DEVELOPMENT OF A HYBRID AIR-CONDITIONING SYSTEM DRIVEN BY LOW TEMPERATURE WASTE HEAT

Simulation of Solar Thermal Cooling System for an Office Building in Indian Climates using Evacuated Tube Collector

The Present and Future of Refrigeration, Power Generation and Energy Storage. R.Z. Wang Shanghai Jiao Tong University

Dimensioning a small-sized PTC solar field for heating and cooling of a hotel in Almería (Spain)

Product catalogue A25s. Solar Cooling systems

Secondary loop chilled water in super high-rise

PINCH ANALYSIS: For the Efficient Use of Energy, Water & Hydrogen. PULP AND PAPER INDUSTRY Energy Recovery and Effluent Cooling at a TMP Plant

Product catalogue A25s. Solar Cooling systems

BUILDING FOR THE FUTURE

Seasonal performances and compression technology

Air Cooled Chiller (50Hz) Air Cooled Scroll. Air Cooled Screw ACC 05/15

The Path Towards Zero Energy District Cooling Plant in Qatar. Salah Nezar, LEED AP, QSAS GCP, Sustainability Director, QPM

EXPERIMENTATION AND MODELLING OF A SMALL-SCALE ADSORPTION COOLING SYSTEM IN TEMPERATE CLIMATE. July 22, 2013

A CHCP System Constituted by Microturbine and Exhaust Absorption Chiller

Available online at ScienceDirect. Energy Procedia 78 (2015 )

!"#$%&"#'"$( (% +, -

i-chiller 125 to 169 kw ic640 to ic660 ABOUT THE i-chiller RANGE ENERGY & PROCESS EFFICIENCY: RELIABILITY: EASE OF OPERATION & MAINTENANCE:

Gas Natural, SDG S.A. 18th. June 2009

NOVEL CYCLES FOR POWER AND REFRIGERATION

Solar cooling design: a case study

Performance analysis of a new single effect hot water absorption chiller system

Experimentation and simulation of a small-scale adsorption cooling system in temperate climate

Combined Heat and Power

Screw Engine as Expansion Machine Applied in an ORC- Test-Installation - the First Operating Experiences

Eurovent Association Eurovent Certification Activities related to ENERGY EFFICIENCY

Inventaire des installations de climatisation solaires en Europe Inventory of solar cooling installations in Europe

Simulation Studies on Performance of Solar Cooling System in UAE Conditions

Microgeneration Installation Standard : MCS 024 SOLAR DOMESTIC HOT WATER ENERGY CALCULATION. to be used in conjunction with MIS 3001:

ABSORPTION COOLING UNIT DRIVEN BY SOLAR ENERGY

Second Law of Thermodynamics

Gas Turbine Inlet Air Cooling System

ENGINEERING ASSESSMENT OF REACTOR DESIGNS FOR THERMOCHEMICAL STORAGE OF SOLAR HEAT

A New Absorption Machine for Both Cooling and Heating

PINCH ANALYSIS: For the Efficient Use of Energy, Water & Hydrogen. PULP AND PAPER INDUSTRY Energy Recovery and Effluent Cooling at a TMP Plant

Cool Producing Systems Based on Burning and Gasification of Biomass

Development of a small capacity directly air-cooled water/libr absorption chiller

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

Investigations of Intelligent Solar Heating Systems for Single Family House

Solar cooling potential in tourist complexes in the North Aegean

MCW 5-39 kw. Indoor monobloc unit. Water chillers and heat pumps MCW PLUS. Compact single circuit units. 242 galletti.

DEVELOPMENT OF A HIGH EFFICIENCY ABSORPTION CHILLER-HEATER AND A COMPACT ABSORPTION CHILLER-HEATER

SIMPLICITY OR INTELLIGENCE? Heat pumps and water-cooled chillers Cooling capacity kw Heating capacity kw 30WG / 61WG / 30WGA

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Providing free cooling from low temperature waste heat

Green Star Design & As Built Submission Template

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

Deployment of a New Series of Eco Turbo ETI Chillers

Transcription:

SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS F. Asdrubali, G. Baldinelli, A. Presciutti, M. Caporali University of Perugia - Industrial Engineering Department, Via G. Duranti 67 - Perugia SUMMARY In last years the international market of air conditioning pointed out a growing interest for solar cooling. This kind of interest was encouraged by the introduction of small size absorption chillers suitable for residential applications. The aim of this work consists of a comparative evaluation of these systems to assess their respective potentialities. Such comparison allows to point out qualities and limits of each system, giving some indications to anyone who would like to enter the solar cooling market. Finally, even though recent publications presented some of these combined systems (absorption chiller solar panels) as already operating, the paper underlines how important technical aspects are yet unsolved. Therefore at the Industrial Engineering Department laboratories a research project was developed, aimed to investigate the behaviour of a solar field absorption machine. INTRODUCTION In last years the consumption of energy for air conditioning knew a dramatic increase, due to higher comfort condition requirements. Besides the wide use of compression machines fed by electric energy increases the demand peaks of electric power in summer (figure 1). Greenhouse gases emissions raising with energy consumption and refrigerant fluid losses, make worse the vicious circle linked to the climatic change. winter summer Fig.1 Historical evolution of summer and winter demand peaks of the Italian net In this context the possibility of using solar energy for residential cooling finds its better applications, taking into account of the maximum contemporaneity between availability of solar radiation and cooling demand. Nowadays, absorption chiller result, in fact,one of the more promising technologies for the energy saving in the refrigeration field. However the need of using small volume technical spaces and, at the same time, limited solar collector surfaces, imply more research efforts to improve the technical and economical feasibility of these kind of systems. This article, by giving a recognition on the state of the art of the sector and reporting some data and results about a system realized at the laboratories of the Industrial Engineering Department of the University of the Study of Perugia, underlines how the research is now in the precompetitive development phase near to its commercial evolution. STATE OF THE ART OF ABSORPTION CHILLERS Thanks to the interesting applicative aspects highlighted, the industry has began to insert, in the international market, little size absorption chillers (6 17 kw of chilling power), designed to be fed by solar energy. Through an in-depth market research, a group of absorption chillers have been individuated, satisfying the above stated requirements and so able to enter soon the market. Low power absorption chillers are not very common and there are no data available about their real perfomances in long periods applications. Therefore, only systems in precompetitive development were chosen because they are ready to be commercialized. Group I This chiller (figure 2), produced in Sweden, has an operating process that is based on a cycle of charge and discharge of two similar barrels, each one constituted by two heat exchangers (reactor condenser, evaporator absorber) which, alternating, are able to give or store energy. The working fluid is a solution of H 2 O-LiCl. In the charge phase the water evaporates in the reactor and condenses in the upper heat exchanger that now is working as condenser. During the discharge phase the water evaporates in the upper heat exchanger, that now is working as evaporator, and condenses in the reactor, that now is working as absorber. This chiller can also operate with the inverse cycle, in this way it can be utilized during winter to produce heat. However, this kind of configuration introduces

significant complication in the plan layout and raies maintenance costs. Nominal chilling capacities kw 8,8 10 Temperature C 12-6 18-15 (in-out) chilled Flow m 3 /s 3,61*10-4 8,05*10-4 water Pressure drop mbar 350 Hot water cooling water Temperature (in-out) C 85-75 72-62 Flow m 3 /s 3,33*10-4 3,33*10-4 Pressure drop mbar 200 Temperature (in-out) C 35-27 35-27 Flow m 3 /s 7,22*10-4 7,22*10-4 Pressure drop mbar 320 electric need electric net V 230 V ~ 1 ph 50 Hz Pump of the absorber W 70 Pump of the refrigerant W 50 Tab.2 Ratings of the absorption group realized at the Technische Universität of Berlin Fig.2 Picture of the Swedish chiller. As shown in figure 3, the charge power increases if the temperature of the hot source increases and if the temperature of cooling water diminishes. charging power (kw) hot water temperature ( C) Fig.3 Charging power vs hot feeding fluid temperature and of the cooling water temperature (T hs ). Ratings of this chiller are showed in the table 1. Ths cooling water inlet temperature This chiller, actually, seems to be the most promising one for the simplicity of the hydraulic system and the possibility of solar energy feeding. From the economic point of view, a preliminary analysis, showed a high ratio between initial investment and kw produced. However, if this chiller is fed by solar energy it needs of a control system of the working fluid solution concentration because the LiBr mix may cause encrustations which can compromise the inner parts of the machine. Group III The German producer, is going to put in the international market a 15 kw absorption chiller. It is a system with tested performances but it requires a feeding solar power of 21 kw unsuitable with the residential applications. It is made up of two separate where evaporatorabsorber and generator-condenser are positioned. This chiller realizes the classic absorption cycle and utilizes H 2 O-LiBr as working pair. Ratings of this model are presented in table 3. Typology Capacity Maximum COP power Summer 56 kwh 10/20 kw 68% Winter 76 kwh 12,5/25 kw 85% Tab.1 Ratings of the Swedish chiller. Group II The second system, investigated at the Technische University of Berlin [1] and nowadays in the production phase, is a classic absorption chiller that uses H 2 O-LiBr as working fluid. Ratings of this chiller are showed in the table 2.

Chilling power (kw) 15 COP 0,71 T in ( C) 17,5 Chilled water Hot water Cooling water Dimensions T out ( C) 11 Flow (m 3 /h) 1,9 Pressure drop (mbar) 350 Nominal pressure. (bar) 6 Power in (kw) 21 T in ( C) 90 T out ( C) 80 Flow (m 3 /h) 2,0 Pressure drop (mbar) 250 Nominal Pressure bar 6 Cooling power (kw) 35 T in ( C) 30 T out ( C) 36 Flow (m 3 /h) 5 Pressure drop (mbar) 900 Nominal pressure. (bar) 6 Length (mm ca.) 1500 Width (mm ca.) 7500 height (mm ca.) 1600 Tab.3 Ratings of the German chiller. Group IV An absorption chiller, working with the H 2 O-LiBr pair, with a nominal refrigerant power smaller than the others (table 4), is already in the production phase by a Spanish company. This model is very compact and it is available also with an incorporated cooling system that removes the heat from the machine. Water circuit Hot circuit Chilling Cooling Tin 11 C 42 C Tout 9 C 47 C Flow (m3/s) 3,33*10-4 5,55*10-4 Pressure drop 0,3 bar 0,4 bar Heat to the generator (90 C) Tin ( C) 90 6,7 kw Flow (m3/s) 3,33*10-4 Pressure drop Average courrent absorbed (A) 0,2 bar 1,2 Average electric power (W) 286 Tab.4 Ratings of the Spanish chiller. poles belt engine Fig. 4 Spanish machine, connection motor - chiller. The particularity of this machine consists of the rotating generator. An electric motor is coupled with the generator and during the cycle it rotates with a constant speed equal to 260 rpm (figure 4). The effect that this rotation induces is an improvement of the mass and heat transfer process. In this way, increasing the efficiency of the system, weight and bulk decrease. Group V This is a Japanese model whose ratings of which are presented in table 5. The peculiarity of this system is the absence of the internal circulation pump and so the total independence of the refrigerant process from any electric feeding; this compromises, however, the power output of the system CHILLING POWER 17,4 [kw] CHILLED WATER Tout 9 [ C] Tin 14 [ C] Flow 0,83 [l/s] Max Pressure at the Evaporator 98 [kpa] HOT WATER Tout 82 [ C] Tin 88 [ C] Flow 1,157 [l/s] Max Pressure at the generator 295 [kpa] Thermic need 29,1 [kw] COOLING WATER Tout 34,5 [ C] Tin 29,5 [ C] Flow 2,22 [l/s] Max circuit pressure 295 [Pa] COP 0,6 Tab. 5 Ratings of the Japanese chiller. The independence from the electric feeding, makes interesting a in depth analysis of the internal processes of this system where the coefficient of performance (COP) depends only by the ratio (freezing power produced thermic feeding power). Therefore, this absorption chiller was the object of the study at the laboratories of Industrial Engineering Department of the University of Perugia, through a proper experimental plant fed by solar energy and monitored by a real time acquisition system.

SOLAR COOLING PLANT OF THE UNIOVERSITY OF PERUGIA The absorption system fed by solar energy realized at the laboratories of Industrial Engineering Department of the University of Perugia [2][3], allowed the performance evaluation of the absorption chiller with different climatic conditions as incident solar energy and the average temperature of the external air. The solar energy collectors system is made up of 15 evacuated tubes panels with an effective surface of 30 m 2. The collectors are orientated towards the south direction with a tilt angle of 20, they are disposed on three strings each one composed by 5 modules. This kind of disposition has been chosen because it is characterized by best performances and minimum pressure losses of the circuit. The circulation of water in the solar circuit is given by a pair of twin pumps that are positioned in the laboratory immediately after the heat exchanger. The plant of the solar circuit is presented in figure 5. to the tank heat exchanger recovery solar pumps Fig. 5 Solar absorption system of the University of Perugia; plant of the solar circuit. The mixture of water and glycol of the solar circuit cannot be directly used to feed the absorption chiller; for this reason there is an heat exchanger that allows the thermal energy transfer from the circuit solar mixture to the water that is sent to the users. As illustrated in figure 6, the heat transferred by the exchanger is stored in a 600 l first tank (S). This tank is connected, by another independent circuit, with a second tank (boiler B) of major capacity (1500 litres) that contains a group of three electric resistances (30 kw) for thermal auxiliary energy. The storage system described can work in three different ways: 1 storing in the tank and mixing with the boiler; 2 chiller direct feeding without storage 3 fan-coils feeding for winter operating. The three operating cases are described as follow: pumps S-B collectors Fig.7 Solar absorption system of the University of Perugia: picture of the tank. Case 1. Storing in the tank and mixing with the boiler In this case the solar energy is given to the tank by the heat exchanger. The twin pumps (group 1, SC-S in figure 6) allow the water circulation between the tank and the heat exchanger. Another couple of twin pumps (group 2 S-B, in figure 6) allows the mixing between the tank and the boiler. the switch of these two groups is automatically regulated by an electronic control when the tank temperature reaches the limit manually imposed. If the temperature in the tank falls down under the limit imposed on the thermostat the two twin pumps groups switch off automatically. The water in the boiler, finally, is sent to the chiller by the third pump (group 3). Case 2. Chiller direct feeding without storage The plant runs this operating case if the temperature inside the collectors reaches a limit established and fixed on the electronic control; when this happens a system of electric valves is activated, allowing the circulation of the fluid directly to the chiller (figure 8). SC = exchanger S = tank B = boiler MF = chiller pumps S-B pumps S-C Fig. 8 Solar absorption system of the University of Perugia; operating way scheme in case 2. SC = exchanger S = tank B = boiler MF = chiller pumps S-C Fig. 6 Solar absorption system of the University of Perugia; plant of the system.

Case 3. Fan-coils direct feeding for winter heating This configuration (figure 9) is used for winter heating utilizing three fan-coils: a 9 kw one and a couple of 3,5 kw each. SC = exchanger S = tank B = boiler MF = chiller pumps S-B pumps S-C fan-coils Fig. 9 Solar absorption system of the University of Perugia; operating way scheme in case 3. minutes when this temperature is lower than 88 C. The same period is requested if the period of inactivity is longer than 3 4 days. The tests effectuated allowed to verify the functionality of the installation and the acquisition system. The different operating way for the system are continuously analyzed to identify the best operative configuration and, therefore, to obtain the maximum use of the solar source with a minimum use of electric resistances and a major COP of the absorption chiller. Next tests, therefore, will be done with some different temperatures fixed in the electrical controls, in the thermostats and in the refrigerant water but above all trying to maintain, the same weather and operating conditions at the aim of obtaining comparable results. However, preliminary tests gave a daily value of COP between 0,35 and 0,46 (table 6). Values lower than the nominal 0,6 but, in any case appreciable, considering that they are obtained with a feeding solar system that cannot supply constant thermal power. ANALYSIS OF SYSTEM PERFORMANCES In table 6 the results of some days of tests are reported with different climatic conditions and for different operating configurations of the system. In each measurement the switch on time of the chiller is changed: in relation with the temperature of feeding. In fact, it needs a starting period higher than 30 Typology Mod. I One room tank boiler Mod. I Tank and boiler thermally separated Mod. II Direct solar Time rad T min T max min C C W/mq rad med W/mq rad max W/mq Resistance kwh Solar kwh kwh tot. really give to the system Total solar fraction % 11.00-17.00 28 35 444 870 1109 40.2 58.9 85.2 69.2 0,45 11.00-17.00 27 37 232 910 1118 80.0 67.6 142.4 47.5 0,43 11.00-17.00 25 37 357 864 1126 38.0 68.9 106.9 64.5 0,43 15.00-18.00 27 38 289 640 837 nc 27.6 0,42 13.00-17.00 25 36 456 557 1073-14.3 14.3 100.0 0,41 11.00-17.00 25 33 289 965 1150 93.8 78.8 145.4 47.4 0,42 11.00-17.00 25 32 208 915 1269 43.1 64.5 107.6 59.9 0.40 11.00-17.00 28 30 464 906 1135 66.7 73.0 122.0 55.2 0,41 11.00-17.00 21 35 411 875 1186 79.4 65.2 144.6 45.1 0,42 11.45-17.00-73.4 73.4 100.0 0,38 11.50-14.30 27 35 167 695 1135-33.8 33.8 100.0 0,37 Tab. 6 Energy and climatic data of each measurement. COP

Solar System thermic production years 2005-2006 Solar energy used need of the chiller SFI % kwh 6000 5000 4000 3000 2000 1000 0 % 100 90 80 70 60 50 40 30 20 10 0 August September October November December January February March Fig. 10 Solar absorption system of the University of Perugia; efficiency of the system expressed by Solar Fraction Index SFI (%). April May June July August September October November In figure 10 the efficiency of the solar plant is reported, expressed in percent values of the covered requirements (SFI) of the chiller. The graph highlights, particularly, how the group worked principally in the months of June and July, when the request of cooling of the laboratories were higher ( in August the laboratories are almost not operative) and in these periods of maximum operating it is possible to see the highest values of solar fraction covering (higher than 35%). It is underlined that the greater potentiality of this technological solution has the best performances when more freezing power is required. Therefore, it appears that the system can be fed only by solar energy exclusively during the hottest hour of the day (from 12:00 to 16:00). In these conditions it receives a power of about 15 18 kw at a temperature of about 70 C and it presents a COP of 0,35. At nominal working conditions of the chiller (in terms of exchanged powers), collectors can give average values equal or upper than those evaluated in the design phase, achieving solar fraction even greater than 60 %. high level of electric consumption due to the summer air cooling and to contextual problems of reducing greenhouse gases emissions. References [1] F. Asdrubali, F. Ziegler, J. Albers, G. Baldinelli, A. Presciutti, S. Petersen; Comparison with two similar solar driven absorption chillers for different values of solar radiations 61 Congresso ATI, Solar Cooling, Perugia 15 September 2006. [2] Albers J., Ziegler F., Asdrubali F., Investigation into the influence of the cooling water temperature on the operating conditions of the thermosyphon generators; Proc. of International Sorption Heat Pump Conference, Denver, USA, 20-22 June 2005. [3] Asdrubali F., An experimental plant to evaluate the performances of an absorption refrigerator, Proc. of International Congress on Refrigeration, Washington, D.C, 17-22 August 2003. Conclusions In the present work the research state of the art on absorption chillers systems of small size fed by solar energy for the residential sector was conducted. It is underlined that the introduction of this kind of systems in the market of the cooling air is yet in a phase of precompetitive development. However, this phase is next to an end as the analysis done on these systems, by the University of Perugia, showed that the solar cooling technology is mature to become an answer to the