By: Boiler Fundamentals and Best Practices

Similar documents
BOILER WATER TREATMENT TECHNOLOGY. DSS HEAD OFFICE - SERPONG May 2008

BOILER FEED WATER AND ITS TREATMENTS

BOILER WATER TREATMENT FOR KILN DRY OPERATIONS Mike Wieland. Technical Presentation

Solus* AP - advanced boiler all-polymer internal treatment technology

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

Boiler Water Chemistry: Getting From the Source to the Boiler Colleen M. Layman, PE

Undesirable impurities in boilers. Maximum permissible Cycles of concentration (NC)

novel polymer technology for boiler deposit control

Optimizing Steam and Cooling Systems for Reliability and Sustainability. Presented By: Kevin Emery

1. Scaling. H.O.: H-5/21, KRISHNA NAGAR, DELHI Tel.: , Fax:

BOILER TREATMENT FACTS AND CONSIDERATIONS

In looking back at the history of boiler

We have softening plant for boiler so water treatment chemicals is not require. We used 90 % condensate water so no need of any chemicals treatment

Western BLRBAC Review/Refresher of Tappi Water Quality Guidelines and Contamination Procedures for mill boilers operating on high purity water

Waterside Cleaning of Recovery Boilers.. Pay Now or Pay Later

NALCO BT-53 Multifunctional Boiler Treatment

Chemical Analysis of Industrial Water TABLE OF CONTENTS

Boiler/Cooling Water Processes and Parameters

Presented by: Jeff Freitag, The Water Guy Jon Tiegs, General Manager

NALCO BT-58 Multifunctional Boiler Treatment

Acid conductivity basics and some experiences

Steamate* technology. superior protection against condensate system corrosion. Water Technologies & Solutions technical bulletin

Evaporative Condenser Passivation. Cameron Klein Strand Associates, Inc.

Characterization of Boiler Water from Various Industries

How A Vertical Tube Falling Film Evaporator Can Be Used to Deliver the Lowest Total Life Cycle Cost for Alberta Produced Water Treatment

EVALUATION OF A CHEMICAL CLEANING FORMULATION FOR THE STEAM GENERATOR OF NUCLEAR POWER PLANTS

Treatment Technologies

ABSTRACT. Key words: high silica, silica polymerization, scale formation, water scarcity, water reuse INTRODUCTION

NALCO BT-31 BOILER INTERNAL TREATMENT

MEASUREMENT OF SODIUM IN WATER/STEAM CIRCUITS

Sulfuric Acid Plant Cooling Tower Improvements

Reducing Energy & Water In Your Boiler House Charles Astbury Commercial Operations GE Water & Process Technologies

the effects of ammonia and organic amines on the water chemistry of gas turbine heat recovery steam generators and associated equipment

on-line cleaning of boilers using a novel polymer technology to avoid acid

Reducing Energy & Water In Your Boiler House Charles Astbury Commercial Operations GE Water & Process Technologies

Steam Cycle Chemistry in Air-Cooled Condensers. NV Energy ACC User s Group * November 12-13, 2009 Andrew Howell * Xcel Energy

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer

View from the Penthouse

CHAPTER 39 BOILER WATER TREATMENT

UNIT-I WATER TECHNOLOGY

Caustic Gouging. PPChem. PPChem 101 BOILER AND HRSG TUBE FAILURES LESSON 5: INTRODUCTION TYPICAL CHARACTERISTICS OF DAMAGE

NALCO BT-28 Condensate Corrosion Inhibitor

By C.F. Chubb Michaud, CWS-VI

ACUMER 2200 High Performance Scale Inhibitor

Chemical Cleaning. Environ. & chemistry dept. Yang Jung Hwan

Copper Turbine Deposits

Zero Liquid Discharge Cooling Tower Treatment at CSI

Filmforming Amines General aspects and application in power plants today

Condensate System Troubleshooting andoptimization

GLIMPSES OF IMPROPER WATER CHEMISTRY IN A SUBCRITICAL PULVERIZED COAL FIRED BOILER AT A THERMAL POWER PLANT

CHLOR-ALKALI INDUSTRY

EBD WATER TREATMENT FOR WATER BOILERS AND COOLING TOWERS

Wastewater Characterization. Tenaska Westmoreland Generating Station

The International Association for the Properties of Water and Steam

Boilers & Fired Systems. Clean Coal Technology Dr. Tanveer Iqbal

Discusser: Melonie Myszczyszyn, CNRL Facilities Engineer, Alberta, Canada

OPTIDOSE 1000 Traceable Polymer A Tool for Maintaining Maximum Heat Transfer

MATERIAL SELECTION AND CORROSION - Vol. II - Power and Desalination Chemistry - H. Moore

Membrane Technology: From Manufacture to. May Production

Guideline for Technical Regulation Volume 2

The Impact of Thermal Stability on the Performance of Polymeric Dispersants for Boiler Water Systems

Carbohydrazide A Hydrazine Replacement: 10 Years of Utility Experience

GE Polyamine Technology

SRI RAMAKRISHNA INSTITUTE OF TECHNOLOGY COIMBATORE First Year BE/B.TECH ( ) Engineering Chemistry- I

IMPROVING WOOD KILN BOILER RELIABILITY VIA A NEW WATER TREATMENT CONTROL TECHNOLOGY

The Locomotive. A Copper-Plated Thief: The Problem of Copper Deposits in Turbines

Water Treatment Program. Training Manual

PWR Dispersant Review & Update OptiSperse PWR6600 July 1, 2010

OPERATIONAL UPDATE ON INNOVATIVE COOLING TOWER PRETREATMENT TECHNOLOGY

Hydrazine, sodium and dissolved oxygen measurement The power of boiler chemistry

CONSENSUS ON OPERATING PRACTICES FOR THE SAMPLING AND MONITORING OF FEEDWATER AND BOILER WATER CHEMISTRY IN MODERN INDUSTRIAL BOILERS

high cycles cooling tower operation using a revolutionary alkaline treatment program Continuum* AEC (Alkyl Epoxy Carboxylate)

SCRUTINIZE YOUR STEAM SYSTEM

NACE CORROSION 2008 TEG 096X Symposia - Paper 1421

Concentration control of silica in water chemical regime for natural circulation high pressure drum boiler unit of thermal power station

Higher COC and ph Independent Operation of Cooling Water Systems

On-Line Water Chemistry Measurements for Power Plants

IWC ZLD: New Silica Based Inhibitor Chemistry Permits Cost Effective Water Conservation for HVAC and Industrial Cooling Towers

Joel E. Bowdan III, P.E WateReuse California CII Pre-Conference Workshop

Lecture 35. NPK Fertilizers Nitrophosphate Route

Boiler Water No.1 Test Kit Instruction Manual

PAPER MILL DEPOSIT CONTROL

Making feed water for you! Advantage. Protecting any Water Treatment System against. Scaling. a Water Company WAT C H WAT E R

S TUDY. 35 Ton water tube boiler water treatment using BacComber ULF Descaler. Background. Chemical treatment

Modern Treatment Programmes Can Reduce Water Consumption in Cooling Towers

Finding the Root Cause is Critical

Boiler Water Treatment Design: The 5 Biggest Mistakes

Total Water Management in Thermal Power Station By Mr. N. Ramachandran - Associate Vice President (Technology)

BOILERS. Outline. Introduction. Types of Boilers. Assessment of a Boiler. Energy Efficiency Opportunities 2/16/2014

UNIT-I WATER TECHNOLOGY

Boiler Water No.2 Test Kit Instruction Manual

Recovery Boiler Corrosion Chemistry

Taravosh Jam Design & Engineering Co.

Water Treatment Program Manual

Corrosion. in Boiler Tube Bundles

Cooling Tower Treatment Chemicals

Process water quality factors

Feedwater Heaters (FWH)

An Introduction to Water Sampling and Testing of Water Systems

Oxidation And Degradation Products Of Common Oxygen Scavengers

Transcription:

By: Boiler Fundamentals and Best Practices

Boiler - Fundamentals Steam production and steam uses Steam purity and steam quality Types of boilers Basic boiler principles Basic boiler calculations

Steam Production and Steam Uses

Steam Production When heat is added to water, its temperature rises at a rate of 0.56 C (1 F) for each heat input of 2.095 kj/kg (1 Btu/lb) If we take water at 0 C (32 F) and we add 419 kj/kg (180 Btu/lb) then we will increase the temperature of the water by 100 C (180 F) This rise in temperature can be detected and is called Sensible Heat (Specific Enthalpy - Water)

Pressure psig Steam Tables Temperature Sensible Heat F Btu/lb Latent Heat Btu/lb Total Heat Btu/lb 0 212 180 971 1151 26.80 15 250 218 946 1164 13.90 31 275 244 929 1173 9.30 51 299 268 912 1180 6.60 100 338 309 882 1190 3.89 150 366 339 858 1997 2.76 200 388 362 838 1200 2.14 Volume Dry Saturated ft 3 /lb Pressure barg Temperature C Water kj/kg Evaporation kj/kg Steam kj/kg 0 100.00 419.04 2257.00 2676.00 1.673 1 120.42 505.60 2201.10 2706.70 0.881 2 133.69 562.20 2163.30 2725.50 0.603 4 151.96 640.70 2108.10 2748.80 0.374 6 165.04 697.50 2066.00 2763.50 0.272 10 184.13 781.60 2000.10 2781.70 0.177 14 198.35 845.10 1947.10 2792.20 0.132 Specific Volume Steam m 3 /kg

Steam Production Steam At normal atmospheric pressure, any further addition of heat to water at 100 C will not increase the temperature but will convert some of the water into steam In order to convert water into steam 2,257 kj/kg (971Btu/lb) of additional heat must be added This cannot be detected as a rise in temperature and is called the Latent Heat of Vaporisation (Specific Enthalpy - Evaporation)

Steam Production Steam Total Heat of Steam = Sensible Heat + Latent Heat of Vaporisation Specific Enthalpy : Steam = Water + Evaporation Thus the Total Heat of Steam (Specific Enthalpy - Steam) is 2,676 kj/kg (1151 Btu/lb) This data is found in Steam Tables

Steam Production Steam From steam tables we can see that the total heat of steam does not vary a great deal as the boiler pressure increase The boiling point (b.p.) increases as the pressure increases Thus the sensible heat increases as the pressure increases, and the latent heat decreases Boiler pressures are expressed in psia, psig, bar, kg/cm 2, kpa

Steam Uses Space heating Drying - paper mill Process heating Sterilisation Humidification Power generation

Steam Purity and Steam Quality

Steam Purity Steam purity is an expression of the quantity of non water components in the steam Components can be dissolved in the steam, dissolved in water droplets entrained in the steam or carried as discrete solid particles in the steam Steam impurities are normally expresses as a quantity in parts per million (ppm) or parts per billion

Steam Quality Steam quality relates to the quantity of moisture present in the steam 100% quality specifying no moisture content 0% quality specifying all liquid Liquid droplets entrained in the steam leaving a boiler contain dissolved solids

Types of Boilers

Types of Boilers Fire Tube Water Tube Waste Heat

Types of Boilers Fire Tube Boilers Water Tube Boilers Waste Heat Boilers Low Pressure Systems Medium to High Pressure Systems Process applications HRSG

Fire Tube Boilers Also referred to as smoke tube boilers, shell boilers, package boilers Multiple gas paths - 2, 3 and 4 pass Internal furnace or fire box as the 1st pass Dry back or wet back design Single fuel or dual fuel design Little or no steam separation equipment

Fire Tube Boilers

Fire Tube Boilers

Fire Tube Boilers Typical designs are O, D and A type boilers Steam separation equipment - drum furniture Cyclone separators Demister pads Baffle plates Have economisers and superheaters Large water tube boilers are field erected and may be unique design

Fire Tube Boilers STEAM DRUM DOWNCOMERS RISERS SUPERHEATER SCREEN TUBES ECONOMISER WATER WALLS AIR HEATER MUD DRUM

Fire Tube Boilers

Waste Heat Boilers Various types and designs Shell and tube exchanger Linked to process Ammonia plant

Waste Heat Boiler Ammonia Plant

Heat Recovery Steam Generators (HRSG) Various types and designs Shell and tube exchanger Water tube boiler Multiple drum system low pressure (LP) medium pressure (MP) high pressure (HP)

Multi Pressure Boiler System with Integral Deaerator

Steam Generators Coil designs, vertical or horizontal Bucket types Steam water separator Boiler water returned to feed tank May include economiser and superheater

Steam Generator - Coil

Basic Boiler Principles

Basic Boiler Principles EXTERNAL TREATMENT MAKE UP WATER AND SOLIDS SATURATED STEAM EVAPORATED WATER HOT WELL DEAERATOR RETURNED CONDENSATE WATER AND HEAT FEEDWATER WATER AND SOLIDS Blowdown - Removes boiler water with a high concentration of solids which is replaced by feedwater containing a low concentration of solids Intermittent blowdown to remove suspended solids in boiler water Continuous blowdown to remove dissolved solids in boiler water

Basic Boiler Principles Water and solids enter the boiler Water leaves the boiler as steam Solids concentrate in the boiler Therefore the boiler water will contain more solids than the feedwater This Concentrating effect is called The Cycles of Concentration or The Cycles

Basic Boiler Principles A boiler can only tolerate a specific number of cycles of concentration This will vary depending on Type and pressure of the boiler Type of external treatment Percentage condensate return

Basic Boiler Principles The chemical factors which limit the boiler water cycles of concentration are Suspended solids (Total Hardness) Dissolved solids Total alkalinity (M Alkalinity) Silica

Basic Boiler Principles How do we determine the chemical control limits that we apply to an operating boiler? British Standard BS2486:1997 ASME Guidelines* 1994 Consensus on operating practices for the control of feedwater and boiler water chemistry in modern industrial boilers

Basic Boiler Calculations

Basic Boiler Calculations Make Up Feedwater Condensate Return

Basic Boiler Calculations Feedwater = Make up + Condensate Return

Basic Boiler Calculations Steam Make (Flow) Feedwater Flow Blowdown

Basic Boiler Calculations Feedwater = Make up + Condensate Return Feedwater Flow (FWF) = Steam Make + Blowdown

Basic Boiler Calculations Feedwater = Make up + Condensate Return Feedwater Flow (FWF) = Steam Make + Blowdown(BD) Feedwater Flow (FWF) = Steam Make + Steam Make Cycles - 1

Basic Boiler Calculations Feedwater = Make up + Condensate Return Feedwater Flow (FWF) = Steam Make + Blowdown(BD) Feedwater Flow (FWF) = Steam Make + Steam Make Cycles -1 Blowdown = Steam make or = FWF Cycles 1 Cycles % Blowdown = 1 as a % of FWF Cycles

Basic Boiler Calculations Condensate Return is also expressed as % of FWF If Condensate Return = 60% Make up = 40% % Condensate + % Make up = 100% = FWF As the boiler water cycles of concentration increase then the feedwater flow and the steam make approach the same number

Basic Boiler Calculations Calculate the feedwater composition (impurities) from make up and condensate analysis below Total Hardness 2 0 M Alkalinity 200 10 TDS 350 15 Silica 6 0 % Condensate 50 Make-Up Condensate Feedwater

Basic Boiler Calculations Calculate the feedwater composition (impurities) from make up and condensate analysis below Make up Condensate Feed water Total Hardness M Alkalinity TDS Silica % Condensate 2 200 350 6 0 10 15 0 50 1 105 182.5 3

Boiler Water Best Practises

Boiler Water Internal Treatment Technology

Why is Effective Internal Boiler Water Treatment Necessary?

Effective Internal Boiler Water Treatment Controls Deposition Corrosion Carryover and

Enhances System Reliability and Efficiency Avoids unscheduled shutdowns Helps ensure uninterrupted production Reduces maintenance costs Reduces operating costs

What Operating Costs are Associated with Boiler Operation?

Boiler Operating Costs Fuel - Gas, Oil, Coal Water - Influent and Effluent Regenerants - Salt, Acid, Caustic Water Treatment

Boiler Operating Costs Fuel - Gas, Oil, Coal Water - Influent and Effluent Regenerants - Salt, Acid, Caustic Water Treatment

Boiler Operating Costs Need to minimise all operating costs Reducing boiler water blowdown gives water, energy and chemical savings Need to maximise efficiency Maintain clean heat transfer surfaces Heat recovery systems

Effective Internal Boiler Water Treatment Controls Deposition

Boiler Water Deposit Control Hardness salts Calcium Magnesium Metal oxides Iron Copper

Comparison of Heat Transfer Surfaces With and Without Deposits Metal Metal Scale Fireside Waterside Fireside Waterside 600 F 800 F and above 500 F 500 F Without deposits With deposits

Energy Loss from Scale Deposits (from Energy Conservation Programme Guide for Industry & Commerce) Energy Loss % 8 7 6 5 4 3 2 Iron & Silica Scale High Iron Content Scale "Normal" Calcium Carbonate Scale 1 0 1 1 3 1 5 3 64 32 64 16 64 32 0.4 mm 0.8 mm 1.2 mm 1.6 mm 2.0 mm 2.4 mm Scale Thickness, inches or mm

Long Term Overheating

Boiler Water Deposit Control Removal of impurities Pretreatment plant Chemical treatment Controlled blowdown

Effective Internal Boiler Water Treatment Controls Deposition Corrosion

Boiler Water Corrosion Control Oxygen pitting Caustic corrosion Embrittlement or gouging Acidic attack

Oxygen Corrosion - Pitting

Caustic Gouging

Acid Corrosion Acid Corrosion

Effective Internal Boiler Water Treatment Controls Deposition Corrosion Carryover

Control of Boiler Water Carryover Effective mechanical steam separation Proper control of boiler water chemistry Antifoam, as needed Avoid major contaminant ingress Proper boiler operating practices

What Types of Internal Boiler Water Treatments are Available?

Internal Treatment Programmes General Classifications Precipitating Solubilising Combination

Internal Treatment Programmes Phosphate/Polymer Phosphonate/Polymer Chelant/Polymer Phosphate/Chelant/Polymer All Polymer Coordinated ph/phosphate/polymer All Volatile Treatment (AVT)

Boiler Water Polymers are Crucial to the Success of any Internal Treatment Programme

How do Boiler Water Polymers Function?

Boiler Water Polymers The mechanisms by which boiler water polymers function are Complexation / Solubilisation Crystal modification Dispersion

Calcium phosphate, magnesium silicate crystals formed in boiler water without dispersant

Calcium phosphate, magnesium silicate crystals formed in boiler water in the presence of a sulphonated polymer

Variables Affecting Polymer Performance Functional group carboxylated (SCP/SCCP) sulfonated (SSP) phosphorylated (HTP) Polymer backbone Molecular weight

Typical Polymer Structures CH CH 2 CH 2 CH CH 2 CH C = O C = O C = O O - Polyacrylate X OH NH 2 X Acrylate-Acrylamide Copolymer CH 3 CH 2 CH CH CH C CH 2 C=O O - Polymethacrylate X SO 3 - X Sulfonated Styrene-Maleic Anhydride Copolymer O = C O C = O Y

Typical Polymer Structures O - CH 2 CH CH 2 CH R P = O C = O CH 2 O - O - H + O [CH 2 CH 2 O] m H n Phosphonate Polyethylene glycol allyl ether (PEGAE) - O O = P CH 3 C O = P O - CH 2 CH 3 C - O OH O - O = P OH HEDP O - Poly (isopropenyl phosphonic acid) PIPPA X

Polymer Performance vs Molecular Weight Deposition Polymer Molecular Weight

Programme Selection Considerations Boiler pressure, design Pre-treatment plant type Feedwater quality Hot well, deaerator type Steam turbine Control capabilities

Chemical Factors Total Dissolved Solids (TDS) Alkalinity Silica Suspended Solids

ASME Boiler Feedwater Quality Guidelines for Modern Industrial Drum Pressure (kg/cm²) Water-Tube Boilers Iron Copper (ppm Fe) (ppm Cu) Hardness (ppm CaCO 3 ) 0-21 22-31 32-42 43-52 53-63 64-70 71-105 0.10 0.05 0.03 0.025 0.02 0.02 0.01 0.05 0.025 0.02 0.02 0.015 0.015 0.01 0.30 0.30 0.20 0.20 0.10 0.05 0.0

Internal Treatment Programmes Phosphate/Polymer

Phosphate/Polymer Treatment Reactions: Ca + PO 4 + OH Ca(OH)PO 4 Calcium Phosphate Hydroxide Hydroxyapatite Mg + SiO 3 + OH Mg(OH)SiO 3 Magnesium Silica Hydroxide Serpentine

Phosphate/Polymer Treatment Characteristics Hardness controlled by precipitation Polymers used to control hardness sludge and metal oxides Phosphate residual used for programme control Hydroxide alkalinity required (ph : 10.5-12)

Phosphate/Polymer Treatment Boiler Control Parameters Phosphate residual as PO 4 depending on hardness in the feedwater usually associated with boiler pressure and environmental legislation M alkalinity of 700 ppm as CaCO 3 (25 % of TDS) Polymer : min 360 ppm as SP8100 Still the most used method for treating low pressure boilers

Phosphate/Polymer Treatment Advantages Tolerates a wide range of feedwater hardness Non corrosive treatment Suitable for low to medium pressure systems Disadvantages Is a precipitation programme (some deposition is normal) Higher blowdown rates may be required Easy operator control

Internal Treatment Programmes Phosphate/Polymer Phosphonate/Polymer

Phosphonate/Polymer Characteristics Organic phosphor donors combined with three synergistic polymers Complexes hardness, iron and copper ions in BFW Disperses/solubilises contaminants in boiler minimising sludge formation

Phosphonate/Polymer a) Solubilising Boiler Control Parameters 200-300 ppm in blowdown (BFW hardness + tot Fe) max 1 ppm for 300 ppm in boiler filtered tot. PO 4 min 6 ppm in BD Other : conductivity SiO 2 M-alk

Phosphonate/Polymer b) Precipitating Boiler Control Parameters Phosphate residual as PO 4 depending on hardness in the feedwater M alkalinity of 700 ppm as CaCO 3 (25 % of TDS)

Internal Treatment Programmes Phosphate/Polymer Phosphonate/Polymer Chelant/Polymer

Chelant/Polymer Treatment Common Chelating Agents EDTA NTA

Chemical Structure of EDTA H H - OOC - CH 2 N -C -C-N - OOC - CH 2 H H CH 2 - COO - CH 2 - COO -

EDTA/Calcium Complex CO O CO CH 2 CH 2 O O Ca N N CH 2 CH 2 CO CH 2 O CH 2 CO

Chelant/Polymer Treatment Characteristics Are solubilising treatments Chelant complexes hardness and soluble iron / copper Polymers used to enhance metal oxide control Must be fed to the feedwater line

Chelant/Polymer Treatment Advantages Solubilising treatment Effective on hardness and soluble iron Allow reduced blowdown Disadvantages Requires intensive operator control Potentially corrosive if misapplied Increased reliability and efficiency Suitable for low to medium pressure systems

Internal Treatment Programmes Phosphate/Polymer Phosphonate/Polymer Chelant/Polymer Phosphate/Chelant/Polymer

Chelant/Phosphate/Polymer Treatment Characteristics Utilises EDTA chelant (partial chelation) Primarily a solubilising programme Phosphate provides back-up upset protection Residual phosphate test used as programme control Polymers used to control metal oxides and other precipitates

Advantages Chelant/Phosphate/Polymer Primarily a solubilising treatment Effective on hardness and iron May allow reduced blowdown Increased reliability and efficiency Easy and accurate control test Tolerates a wide range of feedwater hardness Suitable for low to medium pressure systems Treatment Disadvantages Some precipitation is possible Potentially corrosive if misapplied

Internal Treatment Programmes Phosphate/Polymer Chelant/Polymer Phosphate/Chelant/Polymer All Polymer

All Polymer Treatment Characteristics Certain polymers can be effective complexing agents Principle mechanism is complexation of soluble impurities Secondary mechanism is dispersion of particulates Fed to the boiler feedwater

Limitations of Polyacrylate Based All Polymer Programmes Low tolerance to feedwater quality upsets Potential for calcium polyacrylate deposition Releases ammonia Economiser iron pick-up Precise testing for polymers is difficult

Internal Treatment Programmes Phosphate/Polymer Phosphonate/Polymer Chelant/Polymer Phosphate/Chelant/Polymer All Polymer/OptiSperse AP

What is OptiSperse AP? A new, revolutionary programme using patented co-polymer technology A stand-alone all polymer / all organic boiler internal treatment programme which provides superior control over hardness and iron deposition

OptiSPerse AP Treatment vs. Traditional All Polymer Programme Traditional All Polymer OptiSperse AP Programme Generates ammonia Forms calcium-polymer deposits with BFW hardness excursions or underfeed Overfeed may cause foaming Corrosive to economiser surfaces Must be fed downstream of copper alloys No ammonia generated No treatment related deposition No steam purity problems Not corrosive to preboiler circuit May be fed ahead of copper alloys in BFW

Research Boiler Studies Under Fouling Conditions Test Conditions 900 psig (63 kg/cm 2 ) All-polymer Programme Ca/Mg/Fe present DWD TRADITIONAL ALL-POLYMER OPTISPERSE AP 0 1 2 3 4 5 POLYMER/HARDNESS RATIO

Research Boiler Studies Under Potential Fouling Conditions (Equal Polymer Actives) Deposit Weight Density 300 psig (21 kg/cm 2 ) 600 psig (42 kg/cm 2 ) 900 psig (63 kg/cm 2 ) OPTISPERSE AP Traditional All-Polymer

Internal Treatment Programmes Phosphate/Polymer Phosphonate/Polymer Chelant/Polymer Phosphate/Chelant/Polymer All Polymer Coordinated ph/phosphate/polymer

Coordinated ph/phosphate Polymer Treatment Characteristics Primarily for high purity/high pressure systems Mainly a corrosion control programme Phosphate used to control ph and neutralise excess caustic Polymers used to control deposition

Corrosion of Mild Steel vs. ph Relative Corrosive Attack 8.5 ph 12.7 ph Safe Range 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Caustic Concentration Mechanism Magnetite NaOH Steam Out NaOH NaOH NaOH NaOH Boiler Water in Fe 3 O 4 Porous Deposit NaOH

Prevention magnetite steam escapes porous deposit HPO 4 2 - Na + HPO 4 2 - Na + Na + HPO 4 2 - Na + HPO 4 2 - Na + HPO 4 2 - Boiler water in

Minimising Caustic Concentration and Corrosion using Phosphate NaOH + Na 2 HPO 4 Na 3 PO 4 + H 2 O Caustic Disodium Trisodium Water Soda Phosphate Phosphate

Co-ordinated Congruent Phosphate/pH Control Chart Maximum Boundary 3.0:1 Na/PO 4 Molar Ratio 2.6:1 Na/PO4 10.8 10.6 10.4 10.2 10.0 9.8 9.6 9.4 9.2 9.0 8.8 8.6 8.4 8.2 "Free" Caustic Region 2.7:1 Na/PO4 Control Boundary 2.2:1 Na/PO 4 Molar Ratio 2.8:1 Na/PO4 "Captive" Alkalinity Region Tri-Sodium Phosphate Vector Control Diagram Di-Sodium Phosphate 1 2 3 4 5 6 7 8 10 15 20 30 40 50 60 Ortho-phosphate, as PO 4 mg/l ph Caustic Blowdown Mono-Sodium Phosphate

Internal Treatment Programmes Phosphate/Polymer Phosphonate/Polymer Chelant/Polymer Phosphate/Chelant/Polymer All Polymer Coordinated ph/phosphate/polymer OptiSperse HTP

Characteristics of HTP-2 A unique new phosphorylated boiler polymer Particularly effective on iron Demonstrated clean-up ability Designed for high purity/high cycles systems Suitable for use up to 125 kg/cm²

HTP-2 Polymer Structure CH 3 CH 2 C O = P OH O - Poly (isopropenyl phosphonic acid)... PIPPA X

Internal Treatment Programmes Phosphate/Polymer - OptiSperse PO, OptiGuard MCP Phosphonate/Polymer - OptiSperse PQ Chelant/Polymer - OptiSperse CL Phosphate/Chelant/Polymer - OptiSperse CP All Polymer - OptiSperse AP, OptiGuard MCA Coordinated ph/phosphate/polymer - OptiSperse HTP All Volatile Treatment (AVT)