STRENGTHENING OF INFILL MASONRY WALLS USING BONDO GRIDS WITH POLYUREA

Similar documents
IN-PLANE BEHAVIOR OF ALTERNATIVE MASONRY RETROFITTED WITH POLYUREA MEMBRANES

OUT OF PLANE BEHAVIOR OF MASONRY INFILL WALLS RETROFITTED WITH A REINFORCED POLYMER GRID AND POLYUREA SYSTEM

International Journal of ChemTech Research CODEN (USA): IJCRGG ISSN: Vol.7, No.5, pp ,

Determining the Bond-Dependent Coefficient of Glass Fiber- Reinforced Polymer (GFRP) Bars

Cyclic In-Plane Shear of Concrete Masonry Walls Strengthened by FRP Laminates

Influence of Arching Mechanism in Masonry Walls Strengthened with FRP Laminates

INFLUENCE OF ARCHING MECHANISM IN MASONRY WALLS STRENGTHENED WITH FRP LAMINATES. Abstract

STRENGTHENING OF MASONRY WITH NEAR SURFACE MOUNTED FRP BARS. Abstract

SHEAR PERFORMANCE OF RC MEMBERS STRENGTHENED WITH EXTERNALLY BONDED FRP WRAPS

Retrofitting methods

BEHAVIOR OF INFILL MASONRY WALLS STRENGTHENED WITH FRP MATERIALS

FLEXURAL AND SHEAR STRENGTHENING OF REINFORCED CONCRETE STRUCTURES WITH NEAR SURFACE MOUNTED FRP RODS

Experimental Study on the Behaviour of Plastered Confined Masonry Wall under Lateral Cyclic Load

Experimental Study of Reinforced Brick Masonry Structures

Seismic Evaluation and Retrofit of Beam- Column Joints of Mid-America Bridges Part 2: Steel Sheet and Plate Retrofit

An Experimental Study on the Effect of Opening on Confined Masonry Wall under Cyclic Lateral Loading

Experimental investigation of the use of CFRP grid for shear strengthening of RC beams

SEISMIC STRENGTHENING OF INFILLED RC FRAMES BY CFRP


EXPERIMENTAL STUDY OF THE DEFORMATION CAPACITY OF STRUCTURAL MASONRY

SHEAR AND BUCKLING STRENGTHENING OF STEEL BRIDGE GIRDER USING SMALL-DIAMETER CFRP STRANDS

13 TH C ANADIAN M ASONRY S YMPOSIUM H ALIFAX, C ANADA JUNE 4 TH JUNE 7 TH 2017 SEISMIC PERFORMANCE OF REINFORCED MASONRY WALLS STRENGTHENED

FRP Anchorage Systems for Infill Masonry Structures

Experimental Study on Wall-Frame Connection of Confined Masonry Wall

Behaviour of Post-Installed GFRP Adhesive Anchors in Concrete

Retrofitting of Brick Masonry Panels with Glass Fibre Reinforced Polymers

Strengthening of RC Beams subjected to Combined Torsion and Bending with GFRP Composites

Mechanisms of Bond Failure Between Existing Concrete and Sprayed Polymer Cement Mortar with CFRP Grid by Acoustic Emission

Ultimate strength prediction for reinforced concrete slabs externally strengthened by fiber reinforced polymer (FRP)

NUTC R349. Strength of Unbonded Post-Tensioned Walls. August Mohamed Elgawady and Ahmed Gheni

Evaluation of Shear Demand on Columns of of Masonry Infilled Reinforced Concrete Frames

NUTC R Adding Faculty in Transportation Areas - Year 2 & 3: Research Progress on Behavior and Design of Concrete Structures

Behavior and Strength of Bearing Wall Strengthening by CFRP

COMPRESSION BEHAVIOR OF CIRCULAR AND RECTANGULAR RC COLUMNS RETROFITTED BY GFRP LAMINATES: AN EXPERIMENTAL STUDY

STRENGTHENING OF UNBONDED POST-TENSIONED CONCRETE SLABS USING EXTERNAL FRP COMPOSITES

In-plane shear behaviour of unreinforced masonry walls

SEISMIC RETROFITTING OF EXISTING BUILDINGS

Experimental bond behavior in masonry elements externally reinforced with FRP laminates

Strengthening of an Impact-Damaged PC Girder

Upgrading the shear strength of non-ductile reinforced concrete frame connections using FRP overlay systems

Enhancing the Compressive Strength of Square Cross Sectional Column Using FRP Material

REVIEW ON SHEAR SLIP OF SHEAR KEYS IN BRIDGES

CHAPTER 2 SPECIMEN DETAILS, TEST SETUP AND TESTING PROCEDURE

Technical Notes 39A - Testing for Engineered Brick Masonry - Determination of Allowable Design Stresses [July/Aug. 1981] (Reissued December 1987)

In Plane Behavior of Polypropylene and FRP Retrofitted Brick Masonry Wallets under Diagonal Compression Test

Contents. 1.1 Introduction 1

SEISMIC RETROFITTING OF REINFORCED CONCRETE COLUMNS USING CARBON FIBER REINFORCED POLYMER (CFRP)

COMPARISON OF IN-SITU AND LABORATORY TESTS OF BRICK MASONRY WALLS STRENGTHENED WITH CARBON FIBRE REINFORCED POLYMER FABRIC

Evaluation of the Orientation of 90 and 180 Reinforcing Bar Hooks in Wide Members

RESEARCH ON SEISMIC RETROFIT OF EARTHQUAKE-DAMAGED AND SEISMIC-DEFICIENT STRUCTURES USING FIBRE-REINFORCED POLYMER (FRP) TECHNOLOGY

Debonding Behavior of Skew FRP-Bonded Concrete Joints

Finite Element Analysis of FRP Strengthened Masonry Walls Subject to In-Plane Loading

Seismic Retrofit Of RC Columns With Inadequate Lap-Splice Length By External Post-Tensioned High-Strength Strips

SEISMIC BEHAVIOR OF INFILL FRAMES

SHEAR OF CONCRETE MASONRY WALLS

Strengthening Highway Bridges with CFRP Composites

A SIMPLIFIED METHOD FOR THE ESTIMATION OF THE SEISMIC RESISTANCE OF RC FRAMES WITH WEAK INFILL PANELS

CENTER FOR INFRASTRUCTURE ENGINEERING STUDIES

Retrofitting and Strengthening of Damaged Reinforced Concrete Columns Using Steel Angels Wrapped with Steel Wire Mesh

AFRP retrofitting of RC structures in Japan

Bijapur Karnataka, India) 2. Corresponding Author- Phone , -

RETROFITTING AND REHABILITATION MASONRY STRUCTURES

STRENGTH AND ELASTIC PROPERTIES OF BRICK MASONRY INFILL AT VARIOUS ANGLES INCLINED TO BED JOINT

PRE-CONSTRUCTION INVESTIGATION FOR THE REHABILITATION OF A BRIDGE USING INTERNAL FRP TECHNOLOGIES

Strengthening of infilled RC frames by CFRP

BENDING PERFORMANCE OF MASONRY WALLS STRENGTHENED WITH NEAR-SURFACE MOUNTED FRP BARS. Abstract

SEISMIC REHABILITATION OF REINFORCED CONCRETE BRIDGE COLUMNS IN MODERATE EARTHQUAKE REGIONS USING FRP COMPOSITES

The Use of Sustainable Materials for Quick Repair of Aging Bridges

SEISMIC TEST OF CONCRETE BLOCK INFILLED REINFORCED CONCRETE FRAMES

SEISMIC RETROFIT OF BEAM-COLUMN JOINTS WITH FRP SHEETS

EXPERIMENTAL INVESTIGATION ON THE INTERACTION OF REINFORCED CONCRETE FRAMES WITH PRECAST-PRESTRESSED CONCRETE FLOOR SYSTEMS

Structural Upgrade of Reinforced Concrete Column-Tie Beam Assembly using FRP Composites

AN IMPROVED COMPOSITE ANCHORING SYSTEM

MECHANICAL CHARACTERIZATION OF SANDWICH STRUCTURE COMPRISED OF GLASS FIBER REINFORCED CORE: PART 1

Bond performance of patching materials subjected to environmental effects

SEISMIC STRENGTHENING AND REPAIR OF REINFORCED CONCRETE SHEAR WALLS

Innovative Retrofit of Concrete and Masonry Buildings

OLD KEYS BRIDGE REPAIRS Negative Moment Strengthening of the Rockland Channel Bridge Florida

DURABILITY PERFORMANCE OF EPOXY INJECTED REINFORCED CONCRETE BEAMS WITH AND WITHOUT FRP FABRICS

STRUCTURAL LAB. FACILITY AT IITG IN THE DIRECTION OF TRADITIONAL/LOCAL HOUSING

Effect of prestressed CFRP plate location on behavior of RC beam strengthened with prestressed CFRP plate

CALIBRATION OF A FE MODEL OF MASONRY WALL RETROFIT BY CFRP (CARBON FIBER REINFORCED POLYMER)

Analytical prediction of tension force on stirrups in concrete beams longitudinally reinforced with CFRP bars

Hybrid Simulation Based on Finite Element Analysis of a Continuous Gird Bridge with Fiber Reinforced Polymer composition

Use of FRP to Strengthen and Repair Marine Structures

SEISMIC REHABILITATION OF UNREINFORCED MASONRY SHEAR WALLS. Omer O. Erbay 1 and Daniel P. Abrams 2

Investigation on Behaviour of Reinforced Concrete Beam Column Joints Retrofitted with FRP Wrapping

In-plane testing of precast concrete wall panels with grouted sleeve

Comparisons to Tests on Reinforced Concrete Members

Masonry Structures Confinement with Glass Fiber Reinforcement Polymers

AN INVESTIGATION OF SEISMIC RETROFIT OF COLUMNS IN BUILDINGS USING CONCRETE JACKET

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING

Strengthening of RCC Column Using Glass Fibre Reinforced Polymer (GFRP)

HISTORICAL REVIEW OF MASONRY STANDARDS IN NEW ZEALAND

PERFORMANCE OF LAP SPLICES IN CONCRETE MASONRY SHEAR WALLS UNDER IN-PLANE LOADING

Basic types of bridge decks

BEHAVIOR OF FULL-SCALE SHEAR DEFICIENT CORNER RC BEAM-COLUMN CONNECTIONS RETROFITTED WITH CFRP SHEETS

Chapter 2 Notation and Terminology

Masonry infills with window openings and influence on reinforced concrete frame constructions

4/12/2011. Outline. Introduction. Introduction. Introduction. Introduction

Transcription:

I.1 June 2005 STRENGTHENING OF INFILL MASONRY WALLS USING BONDO GRIDS WITH POLYUREA SUMMARY Glass fiber reinforced polymer (GFRP) grids reinforced polyurea was used to strengthen unreinforced concrete masonry and clay brick (URM) walls. The URM walls were loaded to ultimate condition under an in-plane diagonal compressive force (see Figure 1). Different variables including amounts and directions of the polyurea were investigated. It was observed that the failure modes of the URM walls changed due to the strengthening schemes. Test results indicate that application of GFRP grid reinforced polyurea is an effective retrofit scheme for the walls, because the in-plane capacity of the strengthened walls increased significantly. A failure theory was modified to predict the shear capacity of the tested URM walls and the numerical results matched with the experimental results within a reasonable degree of accuracy. Two Hydraulic Jacks to Load Walls During Testing Instrumentation Steel Shoe a. Concrete Block Walls b. Clay Brick Walls Figure 1. Test Setup

BACKGROUND It is well documented that unreinforced masonry walls have demonstrated poor performance during earthquakes, and effective retrofitting schemes are needed to upgrade existing masonry structures. Traditional strengthening methods include: (a) filling of cracks and voids with injected grout; (b) stitching of cracks with metallic or other materials; (c) external jacketing; (d) external or internal post-tensioning with tendons; (e) externally bonding of fiber reinforced polymer (FRP) sheets; and (f) installation of glass FRP (GFRP) bars. Seismic loads induce severe in-plane and out-of-plane force demands on infill masonry walls. For masonry infill frames, different failure modes can occur based on the interaction mechanism as well as the relative stiffness relationship between the infill walls and the surrounding frame. These failure modes include shear friction, diagonal tension, shear sliding failure, and compression failure. When subjected to an in-plane load, the infill walls and the surrounding structural frame act in a composite action. The two components separate under loading except in the vicinity of the corners. As a result, compression forces are transmitted through one diagonal compression strut of the infill walls. This condition was simulated in the testing of the walls for the experimental program. In recent years the application of fiber reinforced polymer (FRP) to strengthen masonry walls has been investigated. Increase of out-of-plane and in-plane capacity of the strengthened unreinforced masonry (URM) walls has been reported. Strengthening of unreinforced masonry (URM) walls with polyurea was studied in this program. Polyurea is a unique class of polymer defined as the reaction of an isocyanate prepolymer and a blend of primary and secondary amine terminated polols. A polyurea coating combines extreme application properties, such as rapid cure and insensitivity to humidity, with great physical properties, including high hardness and flexibility. The polyurea spray coating technique has been applied in various areas, including corrosion protection and containment. However, due to the relatively low stiffness and tensile strength, the polyurea is potentially limited in retrofit applications that require increases in strength. Therefore, in this program polyurea was reinforced with GFRP grids to strengthen the URM walls. OBJECTIVE To evaluate the effectiveness of in-plane strengthening of URM walls by using polyurea spray system, and to study the behavior of the URM walls subjected to an in-plane diagonal compression load. In addition, one of the primary objectives of this research program was to develop analytical models that are effective in predicting the shear capcapoty of walls retroffited with GFRP girds reinforced polyurea. SPECIMENS Five unreinforced concrete block walls and five clay brick walls were tested under a diagonal compressive load test setup. With the exception of one concrete and one clay wall without strengthening, the other four concrete masonry walls and four clay brick walls were strengthened with GFRP grid reinforced polyurea. Page 2

The investigated variables include amounts and directions of the reinforced polyurea, as well as the numbers of surfaces of the walls being strengthened. It was found that the shear capacity of the strengthened walls increased significantly. A failure theory was modified to predict the shear capacity of the strengthened walls in this program. Analysis indicated that this modified theory predicted the shear capacity of the tested walls within a reasonable degree of accuracy. The five concrete block walls were built following a running bond pattern, and had the nominal dimensions of 64 x 64 x 6 in. With the exception of the control (wall A), four walls were strengthened with the grid reinforced polyurea system. Each grid strip was 4 in. wide and 64 in. long. These walls were labeled M-A to M-E, as indicated in Table 1. The five clay brick walls were built following a running bond pattern, and had a nominal dimensions of 48 x 48 x 3 ½ in. The walls were fully grouted. As before, to the exception of the concrete brick wall the remaining walls were strengthened with the grid reinforced polyurea system. Each grid strip was 4 in. wide and 48 in. long. These walls were labeled B-A to B-E, as also indicated in Table 1. Before application of the polyurea, epoxy paste was used to level the rough surface of the walls, where the polyurea was to be sprayed. Next, the surrounding areas of the walls were covered by thick plastic sheets. In all strengthened walls, the polyurea was first sprayed to the assigned places, followed by attaching one ply glass grid to the polyurea immediately. Next additional polyurea was sprayed to the grid until it was completely covered. The surrounding areas of the walls were covered by thick plastic sheets before spraying, as shown in Figure 2 and 3. This process was identical for the concrete masonry and the clay brick walls. Figure 2. Before spraying Figure 3. During spraying The polyurea cured within minutes after application. After the application was finished, each grid reinforced polyurea strip was approximately ¼ in. thick and 5 in. wide. Two walls (B and C) were strengthened with a horizontal polyurea system, and the other two walls (D and E) with a vertical system. The strengthening schemes for the concrete masonry and clay brick walls were exactly the same and are summarized in Table 1. Page 3

Wall Table 1. Strengthening Scheme Strengthening scheme Numbers of polyurea strips Single/ double sides M-A None -- -- M-B Horizontal strips 4 Single M-C Horizontal strips 8 Double M-D Vertical strips 4 Single M-E Vertical strips 8 Double B-A None -- -- B-B Horizontal strips 4 Single B-C Horizontal strips 8 Double B-D Vertical strips 4 Single B-E Vertical strips 8 Double MATERIAL PROPERTIES The glass grid was made with longitudinal cords, which were connected to each other by transverse cords of a much smaller size. The tested tensile strength was 85.2 ksi, with an elastic modulus of 5306 ksi. The polyurea demonstrated elastic behavior up to approximately 70% of its ultimate strength, with an elastic modulus of 26 ksi and a tensile strength of 1.0 ksi. In the test, the volume percentage of the glass grid in the entire cross-section of the grid reinforced polyurea is approximately 5%. For this content, the reinforced polyurea was elastic to failure. The material properties of the polyurea system are shown in Table 2. Table 2. Material Properties Tensile Elastic strength modulus (ksi) (ksi) Ultimate strain (%) Grid 85.2 5306 1.8 Polyurea 1.0 26 43.7 Grid reinforced polyurea 5.6 272 2.3 Mortar The mortar used to build the walls was available in bags in a dry premixed composition of cement and sand. It was classified as Type N according to ASTM standard. The average compressive strength was 823 psi, with a standard deviation of 177 psi. Concrete Masonry The concrete blocks had a nominal dimension of 16 x 8 x 6 in. The average compressive strength of the blocks was 2,400psi. Clay Bricks The clay bricks had the nominal dimensions of 2 ¼ x 3 5 8 x 7 ¾ in. The average compressive strength of the bricks was 2,330psi. TEST SETUP The specimens were tested in a closed loop fashion. Two hydraulic jacks, with a capacity of 67.4 kips each, were connected in parallel and positioned at one end to apply the desired load (see Figure 1). The diagonal forces were applied by one steel shoe placed at the top corner and transmitted to another identical shoe at the bottom corner of the walls through two high strength steel rods positioned on both sides. INSTRUMENTATION The diagonal load was recorded through two load cells positioned at the corner of the walls. RESULTS AND DISCUSSIONS Concrete Masonry Wall M-A failed with a shear-friction mode along the diagonal in the direction of external load, with an ultimate load of 31.2kips. For wall M-B, diagonal shear-frictional crack caused the overall failure. Local cracks were also observed on the blocks Page 4

along the diagonal. The failure load was 53.4kips. For wall M-C, although stepped shear friction cracks were observed, the wall failed due to shear slide at the bed joints, with an ultimate load of 43.0kips. For wall M-D, the typical shear friction failure was observed on both sides of the wall, with an ultimate load of 34.8kips. For wall M-E two major diagonal cracks were observed before the wall reached the ultimate condition. The ultimate load was 50.6kips. The test results are compared in Table 3. Table 3. Test Results Concrete Masonry Wall Failure mode Load F (kips) M-A Shear friction 31.2 M-B Shear friction 53.4 M-C Shear slide 43.0 M-D Shear friction 34.8 M-E Shear friction 50.6 Clay Bricks Wall B-A failed due to a shear-friction crack along the diagonal in the direction of external load, with an ultimate load of 18.2 kips. For wall B-B, the horizontal strengthening constrained the development of the stepped crack, and failure was confined between the top two polyurea strips on the strengthened side. On the other side the diagonal crack was observed at the upper part of the wall. The wall failed due to a shear friction crack with an ultimate load of 29.8 kips. For wall B-C, horizontal cracks at the bed joints between the grid reinforced polyurea and the mortars were observed. The failure was strictly confined within the top two horizontal strips, where slight local failure of the bricks was observed. The wall failed with a combination of shear slide and shear friction at 33.3 kips. For wall B-D, on the strengthened side, scattered diagonal cracks were observed outside of the vertical grid reinforced polyurea. On the other side, diagonal cracks passed along the bricks for the entire height of the wall. No significant cracks along the bed or head joints were observed. The ultimate load was 36.4 kips. For wall B-E, no clear cracks were observed at the bed or head joints, and the failure was caused by a local compression failure of the bricks at the upper portion of the wall. The tension cracks of the bricks were observed as well. The results of the in-plane diagonal load F are shown in Table 4. Table 4. Test Results Clay Bricks Wall Failure mode Load F (kips) A Shear friction 18.2 B Shear friction 29.8 C Combination of shear slide and friction failure 33.3 D Diagonal tension 36.4 E Combination of diagonal tension and local failure 33.5 ANALYTICAL MODELS Mann and Müller developed one failure theory to explain the behavior of masonry walls subjected to shear and compressive stresses based on the Coulomb equation and other equilibrium conditions. It was assumed that compressive stress in the direction of the bed joints was negligible, and no shear stress was transferred through the head joints. Based on a more realistic distribution of normal stress on the bed joints, Crisafulli et al. modified this principle. According to Page 5

this modified theory the horizontal shear stress τ m acting on the masonry units along the bed joint creates a torque and needs to be balanced by a vertical couple. These two models were used in predicting the shear capacity of the walls. Further details are presented in the report. CONCLUSIONS The following conclusions can be drawn from the current research: Strengthening of URM walls with grid reinforced polyurea is an effective scheme. After strengthening, the in-plane capacity was increased significantly. The failure mode of the strengthened walls changed after strengthening, and depends on the strengthening schemes.. Desired failure modes may be achieved by implementing appropriate strengthening schemes. The theoretical model gave a reasonable prediction of the capacity of the URM walls subjected to in-plane diagonal loads. WANT MORE INFORMATION? Details on this test program and additional data can be found in the final report. CONTACT Piyong Yu Graduate Research Assistant University of Missouri-Rolla Tel: (573) 341-6629 Fax: (573) 341-6215 Email: py4x9@umr.edu Pedro Franco Silva, Ph.D., P.E. Assistant Professor of Civil Engineering University of Missouri-Rolla Tel: (573) 341-6280 Fax: (573) 341-6215 Email: silvap@umr.edu Notice and Disclaimer: The contents presented herein reflect the views of the author(s), who are responsible for the facts and the accuracy of the information presented herein. This document is disseminated under the sponsorship of the Center for Repair of Bridges and Buildings (RB2C), located at the University of Missouri -Rolla, in the interest of information exchange. RB2C assumes no liability for the contents or use thereof. Page 6