An Intercomparison Between NEL, NRLM, Delft Hydraulics, Alden Research Laboratories, CENAM and NIST Using a 200 mm Twin Orifice Plate Package in Water

Similar documents
An Intercomparison between NEL, CMS/ITRI, SIPAI, KRISS, IPT and CENAM using a 200 mm Twin Orifice Plate Package in Water

Rosemount 405 Compact Orifice Primary Element

Universities of Leeds, Sheffield and York

Flow Test Data Book and Flow Handbook for 405 Compact Orifice Series and 1595 Conditioning Orifice Plate

Flow measurement: some problems to solve and some surprises. Dr Michael Reader-Harris, NEL

COIN. Flow Meters. Segmented Wedge. Your First Choice in Intelligent Flow Management...

Flow Conditioning Why, What, When and Where. Gas Flow Conditioning Why, What, When and Where

World s first LNG research and calibration facility

Flow Meter Calibration

VENTURI FLOWMETERS. Your First Choice in Intelligent Flow Management...

COLORADO ENGINEERING. CERTIFICATE OF CALIBRATION Traceable to the NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY

GUIDANCE NOTE. Performance of Electromagnetic Meters Designed for Use in Part-Filled Pipes.

Long-term Evaluation of Ultrasonic Flowmeters

Pipe Flow Hydraulics

Contour K5 Technical Information

flow measurement Methods

Problems with Pitots. Issues with flow measurement in stacks.

Master Meter Testing at Water Plants and Pump Stations. Jeff Cruickshank, PE

VERIS Accelabar. Superior Flow Measurement Accuracy

ISO INTERNATIONAL STANDARD

VENTURI FLOW METER CALIBRATIONS SERIAL NUMBERS: , , , Prepared for. Imperial Flange and Fitting.

WYATT Orifice flow PrOducTs

MEASUREMENT OF AIRFLOW

Gilflo ILVA flowmeters for steam, liquids and gases

METER SELECTION FOR VARIOUS LOAD REQUIREMENTS. Edgar B. Bowles, Jr. Southwest Research Institute 6220 Culebra Road San Antonio, TX USA

The Unique Accelabar Flow Meter

Mexico Gas Flaring Reduction. EU Flaring Regulatory Measurement Requirements & Best Practice Lynn Hunter

DIVA flowmeter. for saturated steam flow measurement

Venturi Tubes in Wet Gas Improved Models for the Over- Reading and the Pressure-Loss Ratio Method

Gilflo flowmeters. for steam, liquids and gases

Rosemount 405 Compact Primary Element

Pitot Tubes and Industrial DP Transmitters (Optional Exercise)

CUSTODY TRANSFER FLOW MEASUREMENT WITH NEW TECHNOLOGIES. Stephen A. Ifft McCrometer Inc. Hemet, California, USA

K.A.R Water flowmeter specifications. (a) Each water flowmeter required by the chief engineer, or required pursuant to a regulation adopted

Flow Meters Demonstration Unit FMDU

DZR Commissioning Set. Flow Data and Installation Instructions

Erosion Effects in Flowmeters

COOLING TECHNOLOGY INSTITUTE

Euramet project Micro Motion CMF200 Krohne Altometer Optiflux 5000

GTI METERING RESEARCH FACILITY UPDATE Edgar B. Bowles, Jr. and Marybeth G. Nored GTI Metering Research Facility Program, Southwest Research Institute

Effect of Orifice Plate Shape on Performance Characteristics

Laboratory Testing of Safety Relief Valves

Introduction to Water Engineering

ASME PTC Flow Measurement

Averaging PITOT Tube 5RD series

Intercomparison of Multiphase Flow Facilities: Comparison of NEL and Humble, USA (Texaco)

Fluid Flow Conditioning. August 2015

Field Experiences with V Cone Technology. McCrometer Inc. Hemet, CA.

Numerical analysis of eccentric orifice plate using ANSYS Fluent software

Averaging PITOT Tube 5RD series

INTERNATIONAL STANDARD

Flow Conditioning for Irrigation Propeller Meters

IMPROVED WATER RESOURCE MANAGEMENT USING AN ACOUSTIC PULSED DOPPLER SENSOR IN A SHALLOW OPEN CHANNEL

TVA Target Variable Area Flowmeter

FPD170 orifice carrier assemblies Differential pressure primary flow element

Static Mixers. Operation, Installation and Maintenance Instructions. Custom Engineered Solutions. to Meet Your Specific Industry Needs

TOTAL SUSPENDED SOLIDS REMOVAL TEST OF A HIGH DENSITY POLYETHYLENE WATER QUALITY UNIT. By James T. Mailloux Dean K. White

CALDON LEFM Ultrasonic Flowmeters for Gas Applications. Integrating experience, proven technology, and innovation

WHITE PAPER A New Approach to Accurate Water Flow Measurement - The Study of the FPI Mag Accuracy

Insertion Flow Meters. The only hot tap Full Profile Insertion Flow Meter.

Field Experiences with V -Cone Technology. Philip A. Lawrence McCrometer Inc O&G Office Houston TX.

Effects of Pipe Wall Offsets on Differential Pressure Meter Accuracy

Datasheet Rev.4 Jan 2015 Orifice plate - Overview

HYDRAULIC DEMONSTRATION CHANNEL

Foam ratio controller model vrc

The Paradigm Case Method of Flowmeter Selection

An Effect of Fractal Flow Conditioner Thickness on Turbulent Swirling Flow

METROLOGICAL INFRASTRUCTURE FOR OIL FLOW METERS CALIBRATION AND TESTING

IOMaster FPD510 Compact integral orifice flowmeter. Low-cost measurement of small flowrates

HIGH PERFORMANCE FLOW CONDITIONERS Michael P. Saunders Savant Measurement Corporation USA

EMRP 2009 Metrology for Liquefied Natural Gas (LNG) ENG03 LNG. (WP1-Tasks and Final report)

SECTION Inline ULTRASONIC FLOW METERS

Method Implementation Document for BS EN * - Application to manual stack emissions monitoring

SUSPENDED SOLIDS REMOVAL TEST OF A 22 X 44 INCH STORMBASIN MODULAR STORMWATER FILTRATION SYSTEM. By James T. Mailloux

CORIOLIS FLOW METERS - CALIBRATION APPROACH FOR CRYOGENIC APPLICATIONS

Performance Evaluation of High speed Centrifugal pump at Varied Speed Conditions

INSTALLATION EFFECTS AND DIAGNOSTIC INTERPRETATION USING THE CALDON ULTRASONIC METER

VLM10 In-line Vortex Mass Flow Meter

EXPERIMENTAL AERODYNAMICS FLOW TROUGH AN ORIFICE LAB SHEET

PRODUCT INFORMATION DRAFT FLOWSIC600 DRU ULTRASONIC GAS FLOW METER FOR UPSTREAM APPLICATIONS. Gas flow meters

FPI Mag Flow Meter. Next Generation Mag Meter: Solving WTP s Tight Installation Dilemma. McCrometer, Inc. (800)

Comparison of Four Gas Measurement Technologies Orifice/Turbine/Coriolis & Ultrasonic

TVA flowmeter. for saturated steam flow measurement

Introduction To Computational Fluid Dynamics. Presented by Marc Laing CFD Team Manager

STANDARD TECHNICAL SPECIFICATION FOR FLOW ORIFICE ASSEMBLY with ACCESSORIES

Carbon Dioxide as a Test Fluid for Calibration of Turbine Meters

Data Sheet. Measuring System trikon Vortex Flow Meter EDZ 420 in Microprocessor Technology. Vortex meter trikon EDZ 420.

ORIFICE MTERE BASIC SELECTION & DESIGN CONSIDERATIONS. All rights reserved to thepetrostreet.com

FPD190 Differential pressure restriction orifice plates

D & B INJECTION MOULDERS LTD

Model 140MX Flowmeter Functional Overview

FLUID MECHANICS PROF. DR. METİN GÜNER COMPILER

PRODUCT INFORMATION. Model 140MX Flowmeter Functional Overview. PI 14-1 Rev: 1 March 2002

Supersedes: G-16 (rev. 4); CEG The copy of this document located on Measurement Canada s website is considered to be the controlled copy.

It can be reliably stated that experience in South African and international

Final Report. Lisheen Mine Discharge Limit for Phosphorous in Terms of Irish and EU Legislation. November 2007 PROJECT NO.

Streamflow Measurement

BIPM Capacity Building & Knowledge Transfer Programme 2018 BIPM - TÜBİTAK UME Project Placement REPORT

Impact of Pitot tube calibration on the uncertainty of water flow rate measurement

Orifice Plate Diagnostics and

Transcription:

An Intercomparison Between NEL, NRLM, Delft Hydraulics, Alden Research Laboratories, CENAM and NIST Using a 200 mm Twin Orifice Plate Package in Water A Report for NMSPU DTI 151 Buckingham Palace Road London, SW1W 9SS Report No: 302/99 Date: 22 December 1999

This report is issued as part of the contract under which the work has been carried out for the client. NOTES 1 This report may be published in full by the client unless it includes information supplied in confidence by NEL or any third party. Such information, if included within the report, shall be separately designated as confidential by NEL. 2a 2b The prior written consent of NEL shall be obtained by the client before publication by him or any extract from, or abridgement of, this report. The prior written consent of NEL shall be obtained by the client before publication: where such publication is made in connection with any public enquiry, legal proceedings or arbitration where such publication is made in, or in connection with, any company prospectus or similar document where the client has notice that NEL is seeking or intends to seek patent or like protection for any intellectual property produced in the course of rendering the services.

Flow Centre National Engineering Laboratory East Kilbride Glasgow G75 0QU Tel: 01355 220222 Fax: 01355 272999 An Intercomparison Between NEL, NRLM, Delft Hydraulics, Alden Research Laboratories, CENAM and NIST Using a 200 mm Twin Orifice Plate Package in Water A Report for NMSPU DTI 151 Buckingham Palace Road London, SW1W 9SS SUMMARY The new NEL 200 mm twin orifice plate transfer standard assembly, manufactured in stainless steel, was calibrated in water at NEL, NRLM, Delft Hydraulics, Alden Research Laboratories, CENAM, NIST and finally again at NEL. The two orifice plate flowmeters, separated by a perforated plate flow conditioner, were identified as S1 and S2. In all the laboratories the assembly was calibrated with S1 and S2 in the upstream and downstream positions respectively and then with their positions reversed using the flange taps fitted to the flowmeters. This report summarises the results and gives an overview of the laboratories. Comparisons of the calibrations from the different laboratories are presented. Prepared by: Dr M J Reader-Harris Approved by: Mr R Paton Date: 22 December 1999 for Dr F C Kinghorn Director Report No: 302/99 Page 1 of 18

CONTENTS Page 1 INTRODUCTION... 3 2 OBJECTIVES... 3 3 THE LABORATORIES 3.1 NEL... 3 3.2 NRLM... 4 3.3 Delft Hydraulics... 4 3.4 Alden Research Laboratories... 4 3.5 CENAM... 4 3.6 NIST... 4 4 THE TRANSFER STANDARD... 4 5 THE DATA... 5 6 CONCLUSIONS... 5 ACKNOWLEDGEMENTS... 6 LIST OF TABLES... 7 LIST OF FIGURES... 8 Report No: 302/99 Page 2 of 18

1 INTRODUCTION The project was initiated under the DTI National Measurement System Policy Unit 1996-1999 Flow Programme. An intercomparison between six laboratories was carried out in water, using a new 200 mm twin orifice plate assembly consisting of two orifice plate flowmeters separated by a perforated plate flow conditioner. This assembly had been manufactured in stainless steel at NEL. This package was calibrated at NEL in May 1996, at NRLM in Japan in August/September 1996, at Delft Hydraulics in the Netherlands in December 1997, at Alden Research Laboratories in the United States in September/October 1998, at CENAM in Mexico in December 1998, at NIST in the United States in March 1999 and finally again at NEL in March 1999. This report summarises the results and gives an overview of the laboratories and test methods. The salient intercomparison graphs are included. The full list of tables of results and associated figures is included. The tables and figures referenced have not been included in this report but are available in Microsoft EXCEL format in NEL Report No 305/99, entitled Intercomparison work for the 1996-99 Flow Programme. This is available from NEL as a CD ROM. It includes not only this report but also the reports of other intercomparisons carried out within the 1996-1999 Flow Programme. 2 OBJECTIVES The objective of this project is to ensure the continuing accuracy of the participating flow calibration laboratories and thereby to ensure that data from one country are acceptable to other countries. To achieve this objective it is necessary to have fairly regular intercomparison checks between the laboratories, using a flowmetering assembly with repeatable characteristics. These dynamic checks supplement the static traceability chain for an individual laboratory, and identify the systematic differences between laboratories 3 THE LABORATORIES 3.1 NEL The National Engineering Laboratory (NEL) is an industrial research organisation concerned with many areas of mechanical engineering research. Within NEL the Flow Centre is the holder of the UK National Standards for Flow Measurement. Facilities exist for calibration and research involving water, oil, gas and multiphase flow measurement devices. All the facilities are fully traceable to Primary National Standards and most are accredited by the United Kingdom Accreditation Service (UKAS). This package was calibrated in the 10-inch test line of the large water flow facility with an additional 43.5D and 13D of 200 mm NB pipework upstream and downstream of the assembly respectively. Meters are calibrated using a flying start and finish technique against gravimetric standards. Three weigh tanks are available of 1 tonne, 5 tonnes and 50 tonnes. The 5 tonne tank was used for this exercise. Report No: 302/99 Page 3 of 18

The large water test facility is accredited by UKAS with a best measurement capability uncertainty of 0.1 per cent of flowrate. Water/air/mercury manometers were used to measure differential pressure. 3.2 NRLM NRLM is the National Standards Laboratory for Japan. NRLM estimates that the uncertainty of flowrate is about 0.1 per cent of the indicated value and that the uncertainty of the differential pressure is about 0.2 per cent of span. 3.2 Delft Hydraulics Delft Hydraulics is the de facto Dutch national standard for water flowrate measurement at the flowrates for this intercomparison. Delft Hydraulics has a calibration rig uncertainty in flowrate of 0.05 per cent. This is taken to be the uncertainty in flowrate. 3.3 Alden Research Laboratories Alden Research Laboratories in Massachusetts, USA, have two facilities, the Hooper Low Reynolds Number Facility and the Allen High Reynolds Number Facility. Both facilities used a diverter and gravimetric system. In the Hooper facility a 50,000 lb weigh tank was used, whereas in the Allen Facility a 10,000 lb weigh tank was used. In the Hooper facility the water temperature was approximately 12 C, whereas in the Allen Facility it was approximately 40 C. In the Hooper Facility a Mitsubishi type perforated plate flow straightener was installed immediately upstream of the assembly. In the Allen Facility 13D of 8-inch NB pipe was included upstream of the assembly. In the Hooper Facility the uncertainty in discharge coefficient was in the range 0.1 to 0.14 per cent; in the Allen Facility it was in the range 0.12 to 0.32 per cent. 3.4 CENAM The liquid flow facility at the Centro Nacional de Metrología constitutes Mexico s primary standard for liquid flow measurements. The system is based on the static weighing principle with weighbridges of 1.5 tonne and 10 tonne. Their claimed expanded uncertainty for flowrate is in the range 0.008 to 0.06 per cent. As regards differential pressure their expanded uncertainty is 65 Pa and 87 Pa at maximum for S1 and S2 respectively. These maximum values would give rise to a contribution to the uncertainty in the discharge coefficient in the range 0.04 to 0.30 per cent and 0.05 to 0.41 per cent for S1 and S2 respectively. 3.5 NIST The National Institute of Standards and Technology (NIST) is the national standards institute for the United States of America. The NIST Water Flow Measurement Standards use static gravimetric techniques for which the Expanded Uncertainty on the determination of volumetric flow rate is quoted to be ± 0.12%. This Expanded Uncertainty is the result of multiplying a coverage factor of 2 times the Combined Uncertainty which is the root-sum square of the A and B Type Uncertainties for the measurement. This A Type Uncertainty is obtained using statistical techniques, and the B Type is obtained using techniques other than statistical. The gravimetric system used at NIST for these measurements has a capacity to weigh 23,000 kg. This facility included upstream pipework and flow conditioning elements that have produced both mean and turbulent velocity profiles (axial and transverse) that closely approximate the Report No: 302/99 Page 4 of 18

distributions for fully developed, equilibrated pipe flow. These distributions were measured at the location of the inlet to the 200mm tandem orifice meter assembly with laser Doppler velocimetry (LDV) along horizontal and vertical diameters. These measurements were done in advance of the orifice testing, but during the orifice testing, these LDV distributions were monitored in real-time using a non-intrusive, 8-path, in-line ultrasonic meter that also has the diagnostic capabilities to quantify and assure that profile skew and swirl remained at the negligible levels indicated by the LDV results. 4 THE TRANSFER STANDARD In each laboratory the 200 mm assembly was installed as shown in Figure 1 (first installation), with additional 200 mm NB pipework upstream and downstream of the assembly respectively, and the flowmeters calibrated simultaneously. The flowmeters were then interchanged as shown in the second installation of Figure 1 and again calibrated simultaneously. In all cases, the orifice plates remained attached to their respective adjacent pipes so that the results would not be affected by separating and reconnecting flanges close to them. The tappings on the orifice plates were connected via triple-tee piezometer rings. Dimensions of the orifice plates: Orifice Plate S1 S2 Throat diameter (d) mm 102.72 102.71 Pipe diameter (D) mm 205.94 206.25 A mean value of 206.09 mm for the pipe diameter was used in the calculations for both orifice plates. Both orifice plates were fitted with corner, flange, and D and D/2 tappings. Only the flange tappings (4 tappings in each tapping plane) were used in the present tests. 5 THE DATA All the sets of data from the calibrations and the associated figures are listed in this report. All the tables of data and figures are available in NEL Report No 305/99 issued as a CD-ROM. Only the graphs pertinent to the conclusions are included here. All the data from the different laboratories are given in Tables 1 19 of Report No 305/99. Each set of data has been fitted using an equation of the form 0.5 6 10 C = A + B. Re D Each set of data together with a fitted line has been plotted in Figures 2 25 of Report No. 305/99. So that the data can be compared the line fits of all the data are plotted in Figures 26 29. Because of the range of line temperature of the data, the data have also been corrected to 20ºC on the basis that d act = d ref [1 + 0.0000167(T act - 20)], Report No: 302/99 Page 5 of 18

where d act and d ref are the orifice diameters at the actual line temperature, T act, and 20 C respectively. The corrected data are shown in Figures 30-33. The Alden data had already been corrected for temperature and so no further correction has been made. 6 CONCLUSIONS With S1 upstream (Figure 30) the total spread of the data is 0.37 to 0.49 per cent. With S2 downstream (Figure 31) the total spread of the data is 0.26 to 0.33 per cent. With S2 upstream (Figure 32) there appears to be an error in the Allen data; excluding them the total spread is 0.28 to 0.29 per cent. With S1 downstream (Figure 33) the total spread of the data is 0.33 to 0.40 per cent. Generally the laboratories agree within approximately ± 0.2 per cent. The spread of the downstream data is generally slightly smaller than the spread of the upstream data. The spread obtained with S2 is smaller than that obtained with S1. The two orifice meters were inspected on their return and no defects in either were seen. The pipework has been discoloured between leaving NEL and its return here. To inspect the meters thoroughly would require them to be dismantled, and this dismantling has not been done for the reasons given in Section 2. Comparison of the upstream and the downstream data shows that the effect of the Spearman flow conditioner 15.7D upstream of an orifice plate of diameter ratio 0.5 is a shift in discharge coefficient of approximately -0.15 per cent. When the upstream data are compared with the Reader-Harris/Gallagher Equation in ISO 5167-1:1991/Amd. 1:1998 the Equation lies above the mean of the data by 0.04 to 0.00 per cent for S1 and by 0.15 to 0.12 per cent for S2. This is well within the expected uncertainty of the Equation. ACKNOWLEDGEMENTS The participation of NRLM, Delft Hydraulics, Alden Research Laboratories, CENAM and NIST and the hard work of their staff are gratefully acknowledged. Report No: 302/99 Page 6 of 18

LIST OF TABLES PROVIDED IN NEL REPORT No 305/99, ENTITLED INTERCOMPARISON WORK FOR 1996-99 FLOW PROGRAMME NEW NEL 200 mm TWIN ORIFICE PLATE TRANSFER STANDARD ASSEMBLY Flowmeters Table Lab / Date Test Upstream Downstream No Facility No 1 NEL May-96 3075 S1 S2 2 NEL May-96 3076 S2 S1 3 NEL Mar-99 3269 S1 S2 4 NEL Mar-99 3270 S2 S1 5 CENAM Dec-98 1 S1 S2 6 CENAM Dec-98 2 S2 S1 7 CENAM Dec-98 3 S1 S2 8 DELFT Dec-97 1 S1 S2 9 DELFT Dec-97 2 S1 S2 10 DELFT Dec-97 3 S2 S1 11 DELFT Dec-97 4 S2 S1 12 NIST Mar-99 1 S1 S2 13 NIST Mar-99 2 S2 S1 14 ALDEN Oct-98 1 S2 S1 (Hooper Low ReD) 15 ALDEN Oct-98 2 S1 S2 (Hooper Low ReD) 16 ALDEN Sep-98 1 S1 S2 (Allen High ReD) 17 ALDEN Sep-98 2 S2 S1 (Allen High ReD) 18 NRLM Aug-96 1 S2 S1 19 NRLM Sep-96 2 S1 S2 Report No: 302/99 Page 7 of 18

LIST OF FIGURES PROVIDED IN NEL REPORT No 305/99, ENTITLED INTERCOMPARISON WORK FOR 1996-99 FLOW PROGRAMME NEW NEL 200 mm TWIN ORIFICE PLATE TRANSFER STANDARD ASSEMBLY Figure Lab / Date Test No Facility No Flowmeter Position 2 NEL May-96 3075 S1 Upstream Mar-99 3269 3 NEL May-96 3075 S2 Downstream Mar-99 3269 4 NEL May-96 3076 S2 Upstream Mar-99 3270 5 NEL May-96 3076 S1 Downstream Mar-99 3270 6 CENAM Dec-98 1 S1 Upstream 3 7 CENAM Dec-98 1 S2 Downstream 3 8 CENAM Dec-98 2 S2 Upstream 9 CENAM Dec-98 2 S1 Downstream 10 DELFT Dec-97 1 S1 Upstream 2 11 DELFT Dec-97 1 S2 Downstream 2 12 DELFT Dec-97 3 S2 Upstream 4 13 DELFT Dec-97 3 S1 Downstream 4 14 NIST Mar-99 1 S1 Upstream 15 NIST Mar-99 1 S2 Downstream 16 NIST Mar-99 2 S2 Upstream 17 NIST Mar-99 2 S1 Downstream 18 ALDEN S1 Upstream (Hooper Low ReD) Oct-98 1 (Allen High ReD) Sep-98 1 19 ALDEN S2 Downstream (Hooper Low ReD) Oct-98 1 (Allen High ReD) Sep-98 1 Report No: 302/99 Page 8 of 18

SUMMARY OF FIGURES (Contd) Figure Lab / Date Test No Facility No Flowmeter Position 20 ALDEN S2 Upstream (Hooper Low ReD) Oct-98 2 (Allen High ReD) Sep-98 2 21 ALDEN S1 Downstream (Hooper Low ReD) Oct-98 2 (Allen High ReD) Sep-98 2 22 NRLM Sep-96 2 S1 Upstream 23 NRLM Sep-96 2 S2 Downstream 24 NRLM Aug-96 1 S2 Upstream 25 NRLM Aug-96 1 S1 Downstream 26 Comparison of Cals. S1 Upstream 27 Comparison of Cals. S2 Downstream 28 Comparison of Cals. S2 Upstream 29 Comparison of Cals. S1 Downstream 30 Comparison of Cals. (Corr.) S1 Upstream 31 Comparison of Cals. (Corr.) S2 Downstream 32 Comparison of Cals. (Corr.) S2 Upstream 33 Comparison of Cals. (Corr.) S1 Downstream Report No: 302/99 Page 9 of 18

Report No: 302/99 Page 10 of 18

0.610 0.605 0.600 NEL Test No.3075 (May 1996) NEL Test No. 3269 (March 1999) CENAM Test No.1 (9 Dec 1998) CENAM Test No.3 (15 Dec 1998) DELFT Test No.1 (16 Dec 1997) DELFT Test No.2 (17 Dec 1997) NIST (March 1999) Hooper Low ReD Facility (22 Oct 1998) Allen High ReD Facility (16 Sept 1998) NRLM (2 Sept 1996) NRLM DELFT Test No.1 DELFT Test No2 NIST Hooper 0.5 per cent Allen 1.0 D 1.5 2.0 2.5 3.0 3.5 4.0 (Re /10 6 ) -0.5 Figure 26 - Comparison of Calibrations with S1 Upstream Report No: 302/99 Page 11 of 18

0.610 0.605 0.600 NEL Test No. 3075 (May 1996) NEL Test No. 3269 (March1999) CENAM Test No.1 (9 Dec 1998) CENAM Test No.3 (15 Dec 1998) DELFT Test No.1 (16 Dec 1997) DELFT Test No.2 (17 Dec 1997) NIST (March 1999) Hooper Low ReD Facility (22 Oct 1998) Allen High ReD Facility (16 Sept 1998) NRLM (2 Sept 1996) DELFT Test No.2 NRLM DELFT Test No.1 NIST Hooper 0.5 per cent Allen 1.0 D 1.5 2.0 2.5 3.0 3.5 4.0 (Re /10 6 ) -0.5 Figure 27 - Comparison of Calibrations with S2 Downstream Report No: 302/99 Page 12 of 18

0.610 0.605 0.600 NEL Test No.3076 (May 1996) NEL Test No. 3270 (March 1999) CENAM (Dec 1998) DELFT Test No.3 (19 Dec 1997) DELFT Test No.4 (22 Dec 1997) NIST (March 1999) Hooper Low ReD Facility (21 Oct 1998) DELFT Test No.4 Allen High ReD Facility (28 Sept 1998) NRLM (26 Aug 1996) DELFT Test No.3 NRLM NIST Hooper 0.5 per cent Allen 1.0 1.5 2.0 2.5 3.0 3.5 4.0 (ReD/10 6 ) -0.5 Figure 28 - Comparison of Calibrations with S2 Upstream Report No: 302/99 Page 13 of 18

0.610 0.605 0.600 NEL Test No. 3076 (May 1996) NEL Test No. 3270 (March 1999) CENAM Test No.2 (13 Dec 1998) DELFT Test No.3 (19 Dec 1997) DELFT Test No.4(22 Dec 1997) NIST (March 1999) Hooper Low ReD Facility (21 Oct 1998) Allen High ReD Facility (28 Sept 1998) NRLM (26 Aug 1996) DELFT Test No.3 NRLM DELFT Test No.4 NIST Allen 0.5 per cent Hooper 1.0 D 1.5 2.0 2.5 3.0 3.5 4.0 (Re /10 6 ) -0.5 Figure 29 - Comparison of Calibrations with S1 Downstream Report No: 302/99 Page 14 of 18

0.610 NEL Test No. 3075 (May 1996) NEL: Test No. 3269 (March 1999) CENAM Test No.1 (9 Dec 1998) CENAM Test No.3 (15 Dec 1998) DELFT Test No.1 (16 Dec 1997) DELFT Test No.2 (17 Dec 1997) Hooper Low ReD Facility (22 Oct 1988) Allen High ReD Facility (16 Sept 1998) NRLM (2 Sept 1996) NIST (March 1999) DELFT Test No.1 DELFT Test No2 0.605 NRLM Hooper NIST 0.5 per cent Allen 0.600 1.0 1.5 2.0 2.5 3.0 3.5 4.0 (ReD/10 6 ) -0.5 Figure 30 - Comparison of Calibrations withs1 Upstream (Corrected) Report No: 302/99 Page 15 of 18

0.610 0.605 0.600 NEL Test No.3075 (May 1996) NEL Test No.3269 (March 1999) CENAM Test No.1 (9 Dec 1998) CENAM Test No.3 (15 Dec 1998) DELFT (Test No.1 (16 Dec 1997) DELFT Test No.2 (17 Dec 1997) Hooper Low ReD Facility (22 Oct 1998) Allen High ReD Facility (16 Sept 1998) NRLM (2 Sept 1996) NIST (March 1999) DELFT Test No.2 NRLM DELFT Test No.1 NIST 0.5 per cent Hooper Allen 1.0 1.5 2.0 2.5 3.0 3.5 4.0 (Re D /10 6 ) -0.5 Figure 31 - Comparison of Caliibrations with S2 Downstream (Corrected) Report No: 302/99 Page 16 of 18

0.610 0.605 0.600 NEL Test No.3076 (May 1996) NEL Test No. 3270 (March 1999) DELFT Test No.3 (19 Dec 1997) DELFT Test No.4 (22 Dec 1997) Hooper Low ReD Facility (21 Oct 1998) Allen High ReD Facility (28 Sept 1998) NRLM (26 Aug 1996) CENAM (Dec 1998) NIST (March 1999) NRLM DELFT Test No.4 DELFT Test No.3 Hooper NIST 0.5 per cent Allen 1.0 D 1.5 2.0 2.5 3.0 3.5 4.0 (Re /10 6 ) -0.5 Figure 32 - Comparison of Calibrations with S2 Upstream (Corrected) Report No: 302/99 Page 17 of 18

0.610 0.605 0.600 NEL Test No. 3076 (May 1996) NEL Test No. 3270 (March 1999) CENAM Test No.2 (13 Dec 1998) DELFT Test No.3 (19 Dec 1997) DELFT Test No.4(22 Dec 1997) NIST (March 1999) Hooper Low ReD Facility (21 Oct 1998) Allen High ReD Facility (28 Sept 1998) NRLM (26 Aug 1996) DELFT Test No.3 NRLM DELFT Test No.4 NIST NIST Hooper Allen 0.5 per cent 1.0 D 1.5 2.0 2.5 3.0 3.5 4.0 (Re /10 6 ) -0.5 Figure 33 - Comparison of Calibrations with S1 Downstream (Corrected) Report No: 302/99 Page 18 of 18