DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

Similar documents
DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

CITY OF LOS ANGELES CALIFORNIA

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588

To: Firm: Project: Product Specified: Specified Location:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW BUILDEX 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 100 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

ESR ICC Evaluation Service, Inc. Issued March 1, 2006 This report is subject to re-examination in one year.

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Trusted ICC ES CONCRETE SECTION: SECTION: 05 HILTI, INC. Look. Conformity! ICC-ES Evaluation

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

*Corrected October 2005

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code.

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

CALIFORNIA ERIC GARCETTI MAYOR

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT:

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INTALLED CONCRETE ANCHORS

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year.

Trusted ICC ES HILTI, INC. SYSTEM E ANCHOR. Conformity! Look. Evaluation. ICC-ES Evaluation

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

ICC-ES Evaluation Report Reissued March 2014 This report is subject to renewal May 1, 2015

Trusted ICC ES HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: MITEK USA, INC.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036

ICC-ES Evaluation Report. ESR-3342 Reissued July 1, 2013 This report is subject to renewal August 1, 2015.

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

LEGACY REPORT ER-5608* Reissued February 1, Legacy report on the 1997 Uniform Building Code

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC SOUTH 122 ND EAST AVENUE TULSA, OKLAHOMA 74146

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: LNA SOLUTIONS A KEE SAFETY LOGISTIC LTD

The following excerpt are pages from the North American Anchor Fastening Technical Guide, 2011.

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc. Reissued September 1, 2008 This report is subject to re-examination in one year.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW RED HEAD 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

ESR-2202 Issued May 1, 2009 This report is subject to re-examination in one year.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS DIVISION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: SAS STRESSTEEL INC. 100 NEW DUTCH LANE FAIRFIELD, NEW JERSEY 07004

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC.

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: AKRON PRODUCTS COMPANY

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: LINDAPTER

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD.

Hilti, Inc South 122 nd East Avenue Tulsa, OK

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

ICC-ES Evaluation Report. ESR-1917 Reissued May 2015 This report is subject to renewal May * * *Deleted by the City of Los Angeles

CITY OF LOS ANGELES CALIFORNIA

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: DEXTRA MANUFACTURING CO., LTD.

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: SUZHOU HONGLY HARDWARE CO., LTD.

DIVISION: CONCRETE SECTION: POST-TENSIONED CONCRETE REPORT HOLDER: PRECISION-HAYES INTERNATIONAL

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: BOSTITCH FASTENING SYSTEMS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

LEGACY REPORT DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

where: P s = Applied service tension load, pounds (kg). P t V s V t

ICC-ES Evaluation Report Reissued January 1, 2012 This report is subject to renewal in one year.

Transcription:

0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 687 (6) 699 0 www.icc es.org ESR 8 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 MASONRY SECTION: 0 0 9.6 MASONRY ANCHORS REPORT HOLDER: HILTI, INC. 70 DALLAS PARKWAY, SUITE 000 PLANO, TEXAS 70 EVALUATION SUBJECT: KWIK BOLT MASONRY ANCHORS Look for the trusted marks of Conformity! 0 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 08 ICC Evaluation Service, LLC. All rights reserved.

ICC-ES Evaluation Report www.icc-es.org (800) -687 (6) 699-0 ESR-8 Reissued February 08 This report is subject to renewal February 09. A Subsidiary of the International Code Council DIVISION: 0 00 00 MASONRY Section: 0 0 9.6 Masonry Anchors REPORT HOLDER: HILTI, INC. 70 DALLAS PARKWAY, SUITE 000 PLANO, TEXAS 70 (800) 879-8000 www.us.hilti.com HiltiTechEng@us.hilti.com EVALUATION SUBJECT: KWIK BOLT MASONRY ANCHORS.0 EVALUATION SCOPE Compliance with the following codes: 0, 0, 009 and 006 International Building Code (IBC) 0, 0, 009 and 006 International Residential Code (IRC) 0 Abu Dhabi International Building Code (ADIBC) The ADIBC is based on the 009 IBC. 009 IBC code sections referenced in this report are the same sections in the ADIBC. Property evaluated: Structural.0 USES The Kwik Bolt (KB) Masonry Anchor is used to resist static, wind, and earthquake tension and shear loads in uncracked, fully grouted concrete masonry unit (CMU) construction. The anchor system is an alternative to cast-in-place anchors described in Section 8.. (0 edition), or Section.. (0, 008, 00 edition) of TMS 0/ ACI 0/ ASCE, as applicable, as referenced in Section 07 of the IBC. The anchor systems may also be used where an engineered design is submitted in accordance with Section R0.. of the IRC..0 DESCRIPTION. Kwik Bolt : The Kwik Bolt expansion anchors consist of a stud, wedge, nut, and washer. The stud is manufactured from carbon material. The carbon steel Kwik Bolt anchors have a μm (0.000 inch) zinc plating. The anchor is illustrated in Figure of this report. The wedges for the carbon steel anchors are made from carbon steel, except for all / -inch (6. mm) lengths, which have AISI 6 stainless steel wedges. All carbon steel components are zinc-plated. The stud consists of a highstrength rod threaded at one end. The standard Kwik Bolt has a thread length equal to or less than three bolt diameters, while the Long Thread Kwik Bolt has a thread length greater than three bolt diameters. The tapered mandrel has an increasing diameter toward the anchor base, and is enclosed by a three-section wedge that freely moves around the mandrel. In the vertical direction, the wedge movement is restrained by the mandrel taper at the bottom and by a collar at the top of the mandrel. When the anchor nut is tightened, the wedge is forced against the wall of the predrilled hole to provide anchorage.. Fully Grouted CMU Masonry: Fully grouted CMU masonry must comply with Chapter of the IBC. The compressive strength of masonry must be at least,00 psi (0. MPa) at the time of anchor installation. The concrete masonry must be fully grouted, and constructed from the following materials:.. Concrete Masonry Units (CMUs): Fully grouted concrete masonry walls must be constructed from minimum Type I, Grade N, lightweight, medium-weight or normal-weight concrete masonry units (CMUs) conforming to ASTM C90 (IBC). The minimum allowable nominal size of the CMU is 8 inches (0 mm) wide by 8 inches (0 mm) high by 6 inches (06 mm) long... Grout: The masonry units must be fully grouted with grout complying with Section 0. of the 0 IBC, Section 0. of the 0 IBC, Section 0. of the 009 and 006 IBC, or Section R606.. of the 0 IRC, or R609.. of the 0, 009 and 006 IRC, as applicable. Alternatively, the grout must have a minimum compressive strength, when tested in accordance with ASTM C09, equal to its specified strength, but not less than,000 psi (.8 MPa)... Mortar: Mortar must be Type N, S or M, prepared in accordance with Section 0 of the IBC, or Section R606..7 of the 0 IRC, or R607. of the 0, 009 and 006 IRC, as applicable..0 DESIGN AND INSTALLATION. Design: Minimum embedment depth, edge distance, and spacing requirements are set forth in Table. Allowable stress design tension and shear loads are as noted in Tables and. Allowable loads for Kwik Bolt anchors subjected to ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 08 ICC Evaluation Service, LLC. All rights reserved. Page of

ESR-8 Most Widely Accepted and Trusted Page of combined shear and tension forces are determined by the following equation: where: P s = (P s /P t ) / + (V s /V t ) / Applied service tension load (lbf or N). P t = Allowable service tension load (lbf or N). V s = Applied service shear load (lbf or N). V t = Allowable service shear load (lbf or N).. Installation Requirements: Kwik Bolt must be installed in holes drilled into the base material using carbide-tipped masonry drill bits complying with ANSI B.-99. The nominal drill bit diameter must be equal to that of the anchor. The drilled hole must exceed the depth of anchor embedment by at least one anchor diameter to permit over-driving of anchors and to provide a dust collection area. The anchor must be hammered into the predrilled hole until at least six threads are below the fixture surface. The nut must be tightened against the washer until the torque values specified in Table are attained.. Special Inspection: Special inspection under the IBC and IRC must be provided in accordance with Sections 70 and 70 of the IBC. Under the IBC, additional requirements as set forth in Sections 70 and 706 must be observed, where applicable. The code official must receive a report, from an approved special inspector, that includes the following details:. Anchor description, including the anchor product name, nominal anchor and bolt diameters, and anchor length.. Hole description, including verification of drill bit compliance with ANSI B.-99.. Installation description, including verification of masonry compressive strength and verification of anchor installation and location (spacing and edge distance) in accordance with Hilti s published installation instructions and this report..0 CONDITIONS OF USE The Kwik Bolt Masonry Anchors described in this report are suitable alternatives to what is specified in, those codes listed in Section.0 of this report, subject to the following conditions:. Anchor sizes, dimensions, and installation must comply with this report and Hilti s published installation instructions.. Allowable tension and shear loads must be as noted in Tables and of this report.. Calculations and details demonstrating compliance with this report must be submitted to the code official for approval.. The use of anchors must be limited to installation in uncracked fully grouted CMU masonry. Cracking occurs when ft > fr due to service loads or deformations.. Design of Kwik Bolt Masonry Anchors installed in fully grouted CMU masonry to resist dead, live, wind and earthquake load applications must be in accordance with Section...6 When using the basic load combinations in accordance with IBC Section 60.., allowable loads are not permitted to be increased for wind or earthquake loading. When using the alternative basic load combinations in 009 and 006 IBC Section 60.. that include wind or seismic loads, the allowable shear and tension loads for anchors are permitted to be increased by / percent. Alternatively, the basic load combinations may be reduced by a factor of 0.7 when using 009 and 006 IBC Section 60... For the 0 and 0 IBC, the allowable loads or load combinations may not be adjusted..7 Where not otherwise prohibited in the applicable code, anchors are permitted for use with fireresistance-rated construction provided that at least one of the following conditions is fulfilled: Anchors are used to resist wind or seismic forces only. Anchors that support fire-resistance-rated construction or gravity load bearing structural elements are within a fire-resistance-rated envelope or a fire-resistance-rated membrane, are protected by approved fire-resistance-rated materials, or have been evaluated for resistance to fire exposure in accordance with recognized standards. Anchors are used to support nonstructural elements..8 Use of carbon steel Kwik Bolt anchors must be limited to dry, interior locations..9 Special inspection must be provided in accordance with Section. of this report..0 Anchors are manufactured by Hilti, Inc., Feldkircherstrasse 00, Schaan, Liechtenstein; and Hilti Operaciones de Mexico S.A., Matamoros, Tamaulipas, Mexico, under a quality control program with inspections conducted by ICC-ES. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Expansion Anchors in Masonry Elements (AC0), approved November 0, including seismic tests, reduced spacing tests and reduced edge distance tests. 7.0 IDENTIFICATION The anchors must be identified in the field by dimensional characteristics and packaging. The packaging label indicates the manufacturer s name (Hilti, Inc.) and address, the size and type of anchor, and the ICC-ES report number (ESR-8). A length identification code letter is stamped on the threaded end of the bolt. The length identification system is described in Table.

ESR-8 Most Widely Accepted and Trusted Page of TABLE INSTALLATION SPECIFICATIONS SETTING DETAILS ANCHOR SIZE / inch / 8 inch / inch / 8 inch / inch Drill bit size = anchor diameter Wedge clearance hole / / 6 Anchor length (min./max.) / / / 8 7 / 7 / 0 6 Thread length std./long thread length Installation: Torque guide values Carbon steel: Min. Embedment (ft-lb) in Carbon steel: Std. Embedment concrete masonry Min. base material thickness For SI: inch =. mm, ft-lbf =.6 N-m. / / 8 7 / 6 / 9 / 6 / 8 / 6 / / 6 7 / 8 / 8 / / / 7 / 6 6 6 inches or. embedment depth, whichever is greater Installation torques are applicable for all anchors installations unless noted otherwise in this report. 0 0 TABLE ALLOWABLE TENSION AND SHEAR VALUES FOR HILTI KWIK BOLT CARBON STEEL ANCHORS INSTALLED IN THE FACE SHELLS OF FULLY GROUTED CMU MASONRY WALLS (in pounds),,, ANCHOR DIAMETER (inch) / / 8 / / 8 / For SI: inch =. mm, lb =. N. EMBEDMENT DEPTH / 8 / 8 / / / / / / 8 MINIMUM DISTANCE FROM EDGE OF WALL 6 TENSION IBC/IRC SHEAR IBC/IRC 0 0 7 89 7 7 66 76 66,0 0 66,7 7 80 7,8 6 70 69,7 99 7,0, 89 67 89,08,6 67,68,67 Values valid for anchors installed in face shells of Type, Grade N, lightweight, medium-weight, or normal-weight concrete masonry units conforming to ASTM C90. The masonry units must be fully grouted with coarse grout conforming to 0. of the 0 IBC, or 0 IBC Section 0., or 009 and 006 IBC Section 0., as applicable. Mortar must comply with Section 0 of the IBC. Masonry compressive strength must be at least,00 psi at the time of anchor installation. Anchors must be installed a minimum of / 8 inches from any vertical mortar joint in accordance with Figure. Anchor locations are limited to one per masonry cell with a minimum spacing of 8 inches on center. Allowable loads or applied loads may be modified in accordance with Section.6 of this report for the 009 and 006 IBC, due to short-term wind or seismic loads. Embedment depth must be measured from the outside face of the concrete masonry unit. 6 For intermediate edge distances, allowable loads may be determined by linearly interpolating between the allowable loads at the two tabulated edge distances.

ESR-8 Most Widely Accepted and Trusted Page of ANCHOR DIAMETER (inch) TABLE ALLOWABLE TENSION AND SHEAR VALUES FOR HILTI KWIK BOLT CARBON STEEL ANCHORS INSTALLED IN TOP OF FULLY GROUTED CMU MASONRY WALLS (in pounds),,, EMBEDMENT DEPTH TENSION Perpendicular to Wall SHEAR Parallel to Wall IBC/IRC IBC/IRC IBC/IRC / 7 9 9 / 8 / 68 9 9 For SI: inch =. mm, lb =. N. Values valid for anchors installed into top cells of Type, Grade N, lightweight, medium-weight, or normal-weight concrete masonry units conforming to ASTM C90. The masonry units must be fully grouted with coarse grout conforming to 0. of the 0 IBC, or 0 IBC Section 0., or 009 and 006 IBC Section 0., as applicable. Mortar must comply with Section 0 of the IBC. Masonry compressive strength must be at least,00 psi at the time of anchor installation. Anchors must be installed a minimum of / inches from edge of the block. Anchor locations must be limited to one per masonry cell with a minimum spacing of 8 inches on center. Allowable loads or applied loads may be modified in accordance with Section.6 of this report for the 009 and 006 IBC, due to short-term wind or seismic loads. Embedment depth is measured from the top edge of the concrete masonry unit. TABLE LENGTH IDENTIFICATION CODES STAMP ON ANCHOR A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Length of Anchor From / / / / / 6 6 / 7 7 / 8 8 / 9 9 / 0 6 7 8 Up to but not including For SI: inch =. mm. / / / / 6 6 / 7 7 / 8 8 / 9 9 / 0 6 7 8 8