SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

Similar documents
BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

PRIMARY UNIT SUBSTATIONS SECONDARY 1000 V AND ABOVE SECTION SECTION

SECTION SECONDARY UNIT SUBSTATIONS SECONDARY LESS THAN 1000 V

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

SECTION AUTOMATIC TRANSFER SWITCH

LOW-VOLTAGE SERVICE ENTRANCE SWITCHBOARDS SECTION D

SECTION SECONDARY UNIT SUBSTATIONS

SECTION BUSWAYS

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

A. Section includes busway and fittings including plug-in units.

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard

ADDENDUM NO. 1 BID AND CONTRACT DOCUMENTS FOR. BID No. 2019PW299

SECTION MOTOR CONTROL CENTER

SECTION ENCLOSED BUS ASSEMBLIES

SECTION LOW-VOLTAGE TRANSFORMERS

FIELD TEST AND OPERATIONAL CHECK SECTION A. Refer to Section 16010, Electrical General Requirements.

Point Eight Power, Inc. Switchgear Specification Low Voltage UL 1558 Metal-Enclosed Switchgear

UNIFIED FACILITIES GUIDE SPECIFICATIONS. Use for Southeast projects only **************************************************************************

SECTION CONVECTORS

SECTION ENCLOSED BUS ASSEMBLIES

SECTION HEAT TRACING FOR PLUMBING PIPING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Capital Projects Group Transfer Switch Specification

SECTION SECONDARY UNIT SUBSTATIONS

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

SECTION LOW-VOLTAGE SWITCHGEAR

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

SECTION PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

SECTION INTEGRATED POWER ASSEMBLY (IPA)

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

1 29SEP03 ALL General update with miscellaneous changes in entire document.

SECTION FUEL-FIRED UNIT HEATERS

SECTION BASIC ELECTRICAL REQUIREMENTS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS

SECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED

WESTERN MUNICIPAL WATER DISTRICT ADDENDUM NO. 2

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION EXTERIOR ATHLETIC LIGHTING

SECTION AIR COILS

Equipment Specifications Low Voltage. Active Harmonic Filter

SMALL GENERATOR INTERCONNECTION REQUEST (Application Form)

SECTION GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification.

ARCHITECTURAL DESIGN ASSOCIATES, P.C O STREET, SUITE 105 LINCOLN, NE

METAL ENCLOSED BUS SOLUTIONS

Capital Projects Group Air Terminal Units Specification

Certificate of Compliance

L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System

A&E Standards Electrical Substations & Transformers Division 26 Electrical

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

This section applies to the requirements for electrical Inspection, calibration, and testing.

Section 70 Airport Transformer Vault and Vault Equipment (FAA L-109)

2. Water Pressure Booster Systems. 3. Duplex Pedestal Type Sump Pumps.

SPECIFICATION FOR SIMPLEX SWITCHBOARDS

Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Standard of Practice - Campus Electrical Distribution System

ELECTRICAL INSPECTION BULLETIN (Effective )

TENOCHCA HALL - FAN COIL UNITS, RESTROOM AND FINISH RENOVATION PROJECT NO

LTH3700, HOLLOW METAL SLIDING FIRE DOOR

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Installation guidelines for users of Magnum DS Low-Voltage Front-Access Switchgear Assemblies for seismic applications

Addendum #2 T Lake Major Water Supply Plant New Standby Power System

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 11/10/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

SECTION 16080P - ELECTRICAL TESTING

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

OVERHEAD SERVICES - SECONDARY

SECTION MEDIUM VOLTAGE TRANSFORMERS

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Unit Substation Transformer Construction Checklist (under 500 kva)

CITY & COUNTY OF DENVER COMMUNITY PLANNING & DEVELOPMENT BUILDING PERMIT POLICY

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

DISTRIBUTION TRANSFORMER SPECIFICATION #

SECTION PATIENT BED SERVICE WALLS

INSULATION GUARD MEG (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.

Sections through of Chapter 5 of the Victoria City Code are amended to read as follows: ARTICLE IX. NATIONAL ELECTRICAL CODE

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

TRI-COUNTY RURAL ELECTRIC COOPERATIVE, INC. Policy Bulletin No Appendix A SAFETY & INTERCONNECTION REQUIREMENTS FOR ALTERNATE ENERGY PRODUCTION

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR

Interconnection Application

1.0 In addition to the requirements previously presented herein, each specification shall contain the following general information:

1. The plan needs to show compliance with the 2013 CEC, 2013 CBC and 2013 CRC. [ CBC] RESPONSE:

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS

33-SDMS-02 SPECIFICATIONS FOR

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR BRIDGE NAVIGATION LIGHTING

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

Transcription:

MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and Non-Automatic Transfer Switches (NATS) having the ratings, features/accessories and enclosures as specified herein and as shown on the contract drawings. RELATED SECTIONS C. D. Section 16671A Transient Voltage Surge Suppression Section 16475 Circuit Breakers and Fusible Switches Low Voltage Section 16901 Microprocessor-Based Metering Equipment Section 16904 Microprocessor Trip Units for Low-Voltage Circuit Breakers REFERENCES The transfer switches and all components shall be designed, manufactured and tested in accordance with the latest applicable standards of UL and NEMA as follows: 5. 6. 7. 8. 9. 10. UL 1008 Transfer Switches UL 991 NFPA 70 National Electrical Code NFPA 99 Essential Electrical Systems of Health Care Facilities NFPA 110 Emergency and Standby Power Systems NEMA ICS 10 AC Transfer Switch Equipment IEEE 446 Recommended Practice for Emergency and Standby Power Systems IEC 801-2, 3, 4, and 5 CISPR 11 Compliant with FCC Part 15, Subpart B, Class SUBMITTALS FOR REVIEW/APPROVAL The following information shall be submitted to the Engineer: Master drawing index Front view and plan view of the assembly Schematic diagram Nameplate schedule 16496A-1 03/04/14

5. Component list 6. Conduit space locations within the assembly. 7. Assembly ratings including: a. Short-circuit rating b. Voltage c. Continuous current rating. 8. Major component ratings including: a. Voltage b. Continuous current rating c. Interrupting ratings. 9. Cable terminal sizes 10. Product Data Sheets. Where applicable, the following additional information shall be submitted to the Engineer: Busway connection Connection details between close-coupled assemblies Composite front view and plan view of close-coupled assemblies Key interlock schematic drawing and sequence of operations 5. Mimic bus. 05 06 SUBMITTALS FOR CONSTRUCTION The following information shall be submitted for record purposes: 5. Final as-built drawings and information for items listed in section 04 Wiring diagrams Certified production test reports Installation information Seismic certification as specified The final (as-built) drawings shall include the same drawings as the construction drawings and shall incorporate all changes made during the manufacturing process. QUALIFICATIONS The manufacturer of the assembly shall be the manufacturer of the major components within the assembly. For the equipment specified herein, the manufacturer shall be ISO 9001 or 9002 certified. C. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of five (5) years. When requested by the Engineer, an acceptable list of installations with similar equipment shall be provided demonstrating compliance with this requirement. D. *Provide Seismic tested equipment as follows: * Note to Spec. Writer Optional 16496A-2 03/04/14

The equipment and major components shall be suitable for and certified by actual seismic testing to meet all applicable seismic requirements of the [latest International Building Code (IBC)] [latest California Building Code (CBC) with OSHPD Amendments]. [The equipment shall have OSHPD Special Seismic Certification (OSP) Pre-Approval.] The Project Structural Engineer will provide site specific ground motion criteria for use by the manufacturer to establish SDS values required. The IP rating of the equipment shall be 5 The Structural Engineer for the Site will evaluate the SDS values published on the [Manufacturer s] [OSHPD] website to ascertain that they are "equal to" or "greater than" those required for the Project Site. 5. The following minimum mounting and installation guidelines shall be met, unless specifically modified by the above referenced standards. a. b. c. The Contractor shall provide equipment anchorage details, coordinated with the equipment mounting provision, prepared and stamped by a licensed civil engineer in the state. Mounting recommendations shall be provided by the manufacturer based upon the above criteria to verify the seismic design of the equipment. The equipment manufacturer shall certify that the equipment can withstand, that is, function following the seismic event, including both vertical and lateral required response spectra as specified in above codes. The equipment manufacturer shall document the requirements necessary for proper seismic mounting of the equipment. Seismic qualification shall be considered achieved when the capability of the equipment, meets or exceeds the specified response spectra. 07 08 09 10 REGULATORY REQUIREMENTS Provide a certificate of compliance with UL 1008 for the transfer switches furnished under this section. DELIVERY, STORAGE AND HANDLING Equipment shall be handled and stored in accordance with manufacturer s instructions. One (1) copy of these instructions shall be included with the equipment at time of shipment. FIELD MEASUREMENTS OPERATION AND MAINTENANCE MANUALS Equipment operation and maintenance manuals shall be provided with each assembly shipped, and shall include instruction leaflets and instruction bulletins for the complete assembly and each major component. PART 2 PRODUCTS 01 MANUFACTURERS Eaton * 16496A-3 03/04/14

C. * MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features and functions. Manufacturers listed above are not relieved from meeting these specifications in their entirety. Products in compliance with the specification and manufactured by others not named will be considered only if pre-approved by the engineer ten (10) days prior to bid date. Note to Spec Writer: Select from the table below to fill in the data required for 02A 02 RATINGS TABLE 16496A-1 Transfer Switch Rating When Used With Rating When Used With Upstream Fuses Ampere Rating Upstream Circuit Breaker Suggested Breaker Rating 240V 480V 600V Maximum Fuse Rating Fuse Type 480V 100 100 100 65 25 200 J, T 200 150 150 100 65 25 400 J, T 200 225 225 100 65 25 400 J, T 200 300 300 100 65 25 400 J, T 200 400 400 65 35 25 600 J, T 200 600 600 65 50 25 800/1200 J, T 100/200 800 800 65 50 25 1200/1600 L 100/200 1000 1000 65 50 25 1600 L 200 C. D. The transfer switch shall have equal 3-second withstand; closing and interrupting ratings of * amperes at * volts. The transfer switch shall be 100% equipment rated for continuous duty. The transfer switch shall be 100% equipment rated for continuous duty as shown on the drawings and shall conform to the applicable requirements of UL 1008 for emergency system total load. The manual transfer switches shall be fully rated for all types of loads, inductive and resistive, without over-sizing, either open or enclosed. 03 CONSTRUCTION Manual Transfer Switch (MTS) shall be manually operated by a permanently attached manual operator. -- *OR -- * Note to Spec. Writer Insert data in blanks * Note to Spec. Writer Select one 16496A-4 03/04/14

E. F. G. H. I. Non-Automatic Transfer Switch (NATS) shall be electrically operated by integrally mounted pushbuttons. The transfer switch shall consist of completely enclosed contact assemblies. Control power for electrical operation shall be derived from a control power transformer connected to the line side of the source to which the load is being transferred. Transfer switch shall have pilot lights that indicate the following: NORMAL Source connected {12C} EMERGENCY Source connected {12D} NORMAL Source available {12G} EMERGENCY Source available {12H} Main contacts shall be designed to withstand multiple fault currents and shall meet UL 489 and/or UL 1087 requirements. The transfer switch shall be mechanically interlocked to prevent cross connection of sources when operated. Transfer switches shall be capable of being operated manually under full rated load conditions. Removable manual operating handles are not acceptable. Manual operators requiring source or load disconnection prior to manual operation are not acceptable. On transfer switches requiring a fourth pole for switching the neutral, the neutral shall be fully rated with equal withstand, closing and interrupting ratings to the power poles. Switched neutral poles which are add-on or overlap, or that are not capable of breaking full rated load current are not acceptable. 04 05 06 07 WIRING/TERMINATIONS Terminal blocks shall conform to NEMA ICS Terminal facilities shall be arranged for entrance of external conductors from the top or bottom of the enclosure. The main transfer switch terminals shall be suitable for the termination of conductors shown on the plans. ENCLOSURE Each transfer switch shall be provided in a *[NEMA 1] [NEMA 12] [NEMA 3R] [NEMA 4] [NEMA 4X] enclosure suitable for use in environments indicated in the drawings. FINISH NEMA 1, 12 or 3R enclosures shall be painted with the manufacturer s standard light gray ANSI 61 paint. NEMA 4 or 4X shall be stainless steel, non-painted. ACCESSORIES The following accessories shall be provided: *Main contact assemblies for *[NORMAL] [and] [EMERGENCY] source(s) shall be equipped with thermal magnetic or electronic trip units and AB DE-ION arc extinguishers. Trip units shall have adjustable instantaneous trip values for each pole. Tripping mechanisms shall be designed trip-free so that the contacts cannot be held closed against an abnormal circuit condition {16N/E/B/S}. [Insert data or references from Sections 16475 and 16904 as required] * Note to Spec. Writer Optional 16496A-5 03/04/14

MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) *Service entrance rating {37} *Ground fault protection on *[NORMAL] [and] [EMERGENCY] source(s) {37A or B} *NORMAL Source Tripped pilot lights {12L} 5. *EMERGENCY Source Tripped pilot lights {12M} 6. *Transient voltage surge suppression with a rating per phase of *[50] [80] [100] ka {51} [See Section 16671A for more information] 7. *Generator start circuit protection rated for *[12] [24] DC {51} 8. *Space heater rated for *[100] [400] watts {41A or C} 9. *Lockable stainless steel cover for controller {38} 10. *Customer metering on the *[NORMAL] [and] [EMERGENCY] source(s) {18} [Insert data or references from Section 16901] PART 3 EXECUTION 01 02 03 FACTORY TESTING The following standard factory tests shall be performed on the equipment provided under this section. All tests shall be in accordance with the latest version of UL and NEMA standards. Insulation check to ensure the integrity of insulation and continuity of the entire system Visual inspection to ensure that the switch matches the specification requirements and to verify that the fit and finish meet quality standards Mechanical tests to verify that the switch s power sections are free of mechanical hindrances Electrical tests to verify the complete electrical operation of the switch and to set up time delays and voltage sensing settings of the logic. The manufacturer shall provide three (3) certified copies of factory test reports. INSTALLATION The Contractors shall install all equipment per the manufacturer s recommendations and the contract drawings. FIELD QUALITY CONTROL Provide the services of a qualified factory-trained manufacturer s representative to assist the contractor in installation and start-up of the equipment specified under this section for a period of * working days. The manufacturer s representative shall provide technical direction and assistance to the contractor in general assembly of the equipment, connections and adjustments, and testing of the assembly and components contained therein. * Note to Spec. Writer Optional * Note to Spec. Writer Select one * Note to Spec. Writer Insert data in blanks 16496A-6 03/04/14

The contractor shall provide three (3) copies of the manufacturer s field start-up. 04 05 06 07 MANUFACTURER S CERTIFICATION A qualified factory-trained manufacturer s representative shall certify in writing that the equipment has been installed, adjusted and tested in accordance with the manufacturer s recommendations. The Contractor shall provide three (3) copies of the manufacturer s representative s certification. TRAINING ** The contractor shall provide a training session for up to five (5) owner s representatives for * normal workdays at a jobsite location determined by the owner. The training session shall be conducted by a manufacturer s qualified representative. The training program shall consist of the instruction on the operation of the assembly, circuit breakers and major components within the assembly. INSTALLATION C. The contractor shall install all equipment per the manufacturer s recommendations and the contract drawings. All necessary hardware to secure the assembly in place shall be provided by the contractor. The equipment shall be installed and checked in accordance with the manufacturer s recommendations. FIELD SERVICE The manufacturer of the ATS shall also have a national service organization that is available throughout the contiguous United States and is available on call 24 hours a day, 365 days a year. * Note to Spec. Writer Insert data in blanks 16496A-7 03/04/14