HILTI HY 150 REBAR DESIGN GUIDE

Similar documents
Anchor Fastening Technology Manual. HIT-HY 170 mortar with rebar. Hilti HIT-HY 170 mortar with rebar (as post-installed conn.

Post installed rebar connections

Adhesive Anchors SECTION CONTENTS. General Information. Installation Information Design Information Material Information Ordering Information

3. Bond, Anchorage and Shear This chapter will discuss the following topics:

Hilti HIT-RE 10 mortar Economical epoxy mortar for concrete

Post-installed reinforcement bars in structural connections

Hilti HIT-ICE with rebar

New ICC/ACI Design Concept for Post-Installed Reinforcement Bars Kelly Chua, B.Eng (Civil and Structural)

Hilti-HY 110 available in 330ml and 500ml foil packs. Static mixer HIT M1. Rebar BSt 500 S

How to calculate anchorage and lap lengths to Eurocode 2

The nominal cover can be assessed as follows: C nom

HIT-RE 500 V3 INJECTION MORTAR. Technical Datasheet Update: Dec-17

Hilti HIT-RE 500 post-installed rebars

General building approval

Post installed rebar connections

REPORT No MRF /B

HIT HY 200 Implementation Into PROFIS Anchor

Anchor Fastening Technology Manual 09 / 2012

The following excerpt are pages from the Hilti North America Post- Installed Reinforcing Bar Guide.

HLC. Hex head nut with pressed-on washer HLC-H. Bolt version with washer HLC-L. Torx round head HLC-SK. Torx Counter sunk head HLC-EC

English translation prepared by CSTB - Original version in French language. OUTIFIX 82, rue Saint Lazare Paris FRANCE

European Technical Assessment. ETA 15/0226 of General Part TCM400PE, TCM600PE. Trade name of the construction product

1 Basics of post installed rebar connections

Concrete Splitting for Post-Installed Reinforcing Bars According to AS-3600

ANCHORING WITH BONDED FASTENERS

English translation prepared by CSTB - Original version in French language

European Technical Assessment ETA-16/0865 of 08/11/2016

AC100-PRO. AC100-PRO Vinylester 160ML AC100-PRO Vinylester 300ML AC100-PRO Vinylester 360ML AC100-PRO Vinylester 410ML AC100-PRO 160ML AC100-PRO 300ML

Behaviour of Post-Installed GFRP Adhesive Anchors in Concrete

Hilti HIT-CT 1 with HIT-V

Special Reinforced Concrete Structural Walls

Hilti HIT-RE 100 mortar with rebar (as anchor)

CHAPTER 10: GENERAL STRUCTURAL DETAILS

Hilti HVU-TZ foil capsule. HAS-TZ HAS-R-TZ HAS-HCR-TZ rod. Shock

Hilti HIT-HY 200-R 500 ml foil pack (also available as 330 ml foil pack) Static mixer

High Strength Epoxy tested in accordance to ICC-ES AC308

HKD Push-in anchor, Single anchor application

Advancements in Adhesive Anchor Technology

BS EN :2004 EN :2004 (E)

HVU with HAS/HAS-E rod adhesive anchor system

Hilti, Inc South 122 nd East Avenue Tulsa, OK

REPORT No SIMPSON STRONG-TIE AT-HP

Footings GENERAL CONSIDERATIONS 15.2 LOADS AND REACTIONS 15.4 MOMENT IN FOOTINGS

CHAPTER 11 Bar Cutoff

Schöck Isokorb Type CV

HKD Push-in anchor, Single anchor application

1 Input data. Profis Anchor Company: Specifier: Address: Phone I Fax: Page: Project: Sub-Project I Pos. No.

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year.

HST3 Metal expansion anchor

Questions with Solution

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Lecture Retaining Wall Week 12

HKD Push-in anchor, Single anchor application

Masonry Reinforcement for Arch Bridges

Technical data No. 17/0001 of 25/04/2017

Anchor HSA Fastening. Technology Manual HSA. Stud anchor. Version /

High Strength Epoxy tested in accordance to ICC-ES AC308

WELCOME TO FISCHER PRESENTATION AMEET PARIKH, TECHNICAL HEAD

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE

Easy to Use A7 Saves You Time and Money

English translation prepared by CSTB - Original version in French language. SPIT EPCON C8 rebars

Hilti HIT-HY 170 mortar with HIT-V rod. Anchor Fastening Technology Manual. Hilti HIT-HY 170 with HIT-V HIS-(R)N 03 / /

Ductile Detailing for Earthquake Resistant R C Structures. Dr. S. K. PRASAD Professor of Civil Engineering S.J. College of Engineering Mysore

Schöck Isokorb type CVB Design

High Strength Epoxy Tested in Accordance with ICC-ES AC308

SUPERPLUS M8-M16. The undercut fixing system that does not require a special setting tool. FUNCTION BENEFITS

HIT-ICE INJECTION MORTAR. Technical Datasheet Update: Jun-18

Schöck Isokorb type CV

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

Hilti HIT-HY 70. Setting depth [mm] M6 M8 M10 M12 M8 M10 M12. Clay common (Dry pressed) f b b) 25 N/mm² L x H x B [mm] 230 x 110 x 76

7.1 Transmission of Prestress (Part I)

> 0. 1 f, they are treated as beam-columns.

DESCRIPTION ADVANTAGES

Hilti HIT-CT 1 post installed rebars

A7+ The Most Versatile Quick Cure Adhesive

High Strength Epoxy Tested in Accordance with ICC-ES AC308

HIT-HY 200-A/R INJECTION MORTAR. Technical Datasheet Update: Oct-18

Schöck Isokorb type K-HV, K-BH, K-WO, K-WU

The ONLY Fast Cure ICC-ES Listed Adhesive for Water-filled Holes and Submerged Concrete

Anchor Fastening Technology Manual. HIT-HY 170 mortar with rebar (as anchor) Hilti HIT-HY 170 mortar with rebar (as anchor) Version

Identifying The Problem

Hilti, Inc South 122 nd East Avenue Tulsa, OK

1 Input data. Profis Anchor Company: Specifier: Address: Phone I Fax: Obeikan Tensile Struct

HST Carbon steel. HST-R Stainless steel HST-HCR High corrosion resistance steel. Fire resistance

Schöck Isokorb Type CM

Anchor Fastening Technology Manual 09 / 2012

SHP-VE / Hammer-in capsule Vinylester capsule resin for use in concrete

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Proposed Revisions to Part 2, Sections 2.13 to Draft DEVELOPMENT AND SPLICES OF REINFORCEMENT SECTION 2.13 DEVELOPMENT REQUIREMENTS

C6+ High Strength Epoxy for All. conditions. One product for most environmental conditions and weather conditions. Curing Times

Ground + 4 floor RCC frame structure in Goa Floor to floor height is 3.0m Plan dimension, 24.0 m x 13.5 m SBC = 20 t/sqm, hard Strata is consider for

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

English translation prepared by CSTB - Original version in French language ITW RED HEAD 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS ILLINOIS USA

Inject-TITE AW All-Weather

English translation prepared by CSTB - Original version in French language

Technical data No. 17/0002 of 22/05/2017

Eurocode 8 Timber and Masonry structures

HIT-HY 200 INJECTION MORTAR. Technical Datasheet Update: Aug-18

Transcription:

HILTI HY 150 REBAR DESIGN GUIDE HILTI HY 150 REBAR DESIGN GUIDE 1

HY150 Rebar Dowelling using Limit States Concrete Design ( A23.3-94) The design method presented here was originally based on Eurocode 2: ENV 1992-1-1 Design of Concrete Structures, Part 1, General rules and rules for buildings. The formulas have been converted to incorporate the load and reduction factors of A23.3-94. Consequently, this method only applies to reinforced concrete. In the case of non-reinforced concrete, - or if the reinforcement is not known - anchor theory must be used. This anchor theory is the basis of the design principles described in the HILTI Engineering Manual i.e. Req d spacing and edge distances. HILTI S internal and external testing including a full scale beam test has shown that the performance characteristics of rebar fastenings with HILTI HIT HY150 correspond to those of cast-in rebars. All construction rules outlined in A23.3-94 apply; in particular, the transmission of the anchoring forces into the connecting building components must be ensured in accordance with the principles of reinforced concrete construction (e.g. transverse reinforcement, concrete cover etc.). In the case of reinforced concrete, the edge distance and spacing are not of primary importance because the tensile force is transmitted by the connection rebars to the cast-in rebars via the concrete bond between them. General Rules: To transfer shear loads the surface of the existing concrete should be roughened. The performance characteristics of HIT HY150 correspond to those of cast-in rebars. All construction rules of A23.3 apply; in particular, the transmission of the anchoring forces into the connecting building components must be ensured in accordance with the principles of reinforced concrete construction (e.g. transverse reinforcement, concrete cover etc.). If the rebar connection is to be loaded before the concrete reaches its 28 day compressive strength, the strength at the time of installation should be used with the given formulae. However, special attention should be given to concrete creep. The formulas used in this guide are based on extensive testing of HILTI HY150 adhesive and can only be used for HY150. Other adhesive or epoxy products will have different bond strengths, ductility and load displacement characteristics which would result in different formulas. HILTI HY 150 REBAR DESIGN GUIDE 2

Definitions: The following definitions are used in this design method: d== Nominal diameter of rebar (mm)= D = Hole diameter (mm) l b = Basic development length (mm) l b, inst = Installed anchorage length (mm) l b, min = Minimum anchorage length (mm) e = Distance between reinforcing bar and nearest connection rebar (mm) a = Distance between reinforcing bar and farthest connection rebar (mm) φ e = Epoxy bond factor = 0.7 (epoxy coated bars) or 1.0 (plain reinforcing) f y = Yield stress of rebar (MPa) φ s = Resistance factor for rebar = 0.85 f c = Concrete compressive strength (MPa) φ c = Resistance factor for adhesive bond to concrete = 0.6 φ b = Resistance factor for adhesive bond to steel = 0.6 γ D = Dead load factor = 1.25 γ L = Live load factor = 1.50 R yd = Design value of rebar strength (N) R bd = Design value of adhesive bond to steel (N) R cd = Design value of adhesive bond to concrete (N) F d = Factored resistance (kn) = MIN{R yd ; R bd ; R cd } Limit to rebar utilization The design tensile force, R yd, at which the rebar steel is fully utilized, results from the product of the cross sectional steel area times the yield strength times the steel factor. R yd = 1/4 x d 2 x π x f y x φ s [N] This value is crucial when the installed length is greater than the basic development length. anchorage HILTI HY 150 REBAR DESIGN GUIDE 3

Limit to adhesive to steel bond utilization The adhesive bond to steel increases linearly with the anchorage length, but only with the square root of the rebar diameter. R bd = 25 x π x l b inst x d 1/2 x φ b x φ e [N] Doubling the diameter only results in a 40% increase of the bond strength. Formula applies to a maximum bar diameter of 25M The factor 25 in the formula is unique to HY150 and was determined after review of comprehensive test data. Limit to adhesive to concrete bond utilization The adhesive bond to concrete increases linearly with anchorage depth, but only with the square root of the concrete strength times the hole diameter. R cd = 4.5 x π x l b inst x (f c x D) 1/2 x φ c [N] The factor 4.5 in the formula is unique to HY150 and was determined after review of comprehensive test data. HILTI HY 150 REBAR DESIGN GUIDE 4

Basic development length If this length is exceeded, the steel is fully utilized. The basic anchorage length is derived by selecting an anchorage length that ensures that the bond strengths are greater than the steel strength. l b = MAX{d 3/2 x f y x φ s /(100 x φ b x φ e );d 2 x f y x φ s /(18 x (f c x D) 1/2 x φ c )} Up to and including 25 MPa concrete it is the bond of the adhesive to the concrete which is crucial, but for concretes greater than 30 MPa it is the bond of the adhesive to the bar that is decisive. Schematic presentation of limits to utilization: HILTI HY 150 REBAR DESIGN GUIDE 5

Minimum anchorage length Nothing is gained by setting the rebar deeper than the basic development length but it is often useful to work with a larger diameter rebar, but a shallower hole. The design value of the connection force F d is the minimum of R yd, R bd & R cd. To ensure that the force acting on the connection rebar is transmitted to the cast-in rebar the principles of reinforced concrete must be checked and the following minimum lengths must be followed. Minimum anchorage lengths vary from A23.3-94 since the rebars are post-installed not cast-in. For anchorages in tension: l b,min = MAX(0.3 x l b ; 10 x d; 100 mm) For anchorages in compression: l b,min = MAX(0.6 x l b ; 10 x d; 100 mm) When rebars in tension or compression are lapped the minimum overlap is: l b,min = MAX (0.6 x l b ;15 x d; 200 mm) Table 1 Summary Table of Minimum Embedments and Overlaps Rebar Size Rebars in tension in 20 MPa concrete (mm) Rebars in tension in concrete > 30 MPa (mm) Rebars in compression in 20 MPa concrete (mm) Rebars in compression in concrete > 30 MPa (mm) Overlaps in 20 MPa concrete (mm) Overlaps in concrete > 30 MPa (mm) 10M 115 115 145 130 200 200 15M 160 160 240 220 240 240 20M 195 195 325 300 320 300 25M 255 255 510 435 510 435 HILTI HY 150 REBAR DESIGN GUIDE 6

Distance between cast-in rebars and new rebars If the clear space between the connection rebars and the nearest cast-in rebar is... e > 4 x d the overlap must be increased by an amount e - 4 x d Table 2 Overlap Increase Required (mm) Rebar Size Spacing between existing bars = 150 mm Spacing between existing bars = 200 mm Spacing between existing bars = 300 mm Spacing between existing bars = 400 mm 10M 30 55 105 155 15M 15 35 85 135 20M 0 25 75 125 25M 0 0 50 100 The minimum distance between cast-in rebars and farthest away connection rebars should be: a > MAX(2 x d; 20 mm) HILTI HY 150 REBAR DESIGN GUIDE 7

Transmissible forces According to the given formulae and good bond conditions, the following values result depending on the load level and the installed anchorage length. Factored Resistance Tables Factored Resistance must be greater than Factored Load Table 3 Factored Resistance for Dowels in 20 MPa Concrete Bar Hole Diameter (mm) Bar Size Diameter (mm) Factored Resistance of Connection Force Fd (kn) for 20 MPa Concrete Anchorage Length (mm) 115 160 200 255 300 400 500 600 700 800 900 Development Length (mm) 11.3 10M 14 16.3 22.7 28.3 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0 240 16 15M 20 27.1 33.8 43.2 50.8 68.0 68.0 68.0 68.0 68.0 68.0 400 19.5 20M 25 37.8 48.2 56.8 75.7 94.6 102.0 102.0 102.0 102.0 540 25.2 25M 28 51.1 60.1 80.1 100.1 120.1 140.2 160.2 170.0 850 Notes: 1. Rebar: f y = 400 MPa; If epoxy coated bars are used embedment must be increased by 30% 2. Holes must be drilled with Hilti rotary hammer drills or if core drilled they must be conditioned with Hilti conditioning bits 3. For bars in compression or overlap bars the minimum embedments are shown in Table 1. To fully develop a lap splice use the development length plus the overlap increase shown in Table 2. Table 4 Factored Resistance for Dowels in Concrete > 30 MPa Bar Hole Diameter (mm) Bar Size Diameter (mm) Factored Resistance of Connection Force Fd (kn) for Concrete > 30 MPa Anchorage Length (mm) 115 160 200 255 300 400 500 600 700 800 Development Length (mm) 11.3 10M 14 18.2 25.3 31.6 34.0 34.0 34.0 34.0 34.0 34.0 34.0 215 16 15M 20 30.1 37.6 47.9 56.4 68.0 68.0 68.0 68.0 68.0 365 19.5 20M 25 41.5 52.9 62.3 83.0 102.0 102.0 102.0 102.0 495 25.2 25M 28 60.2 70.8 94.4 118.0 141.6 165.2 170.0 720 Notes: 1. Rebar: f y = 400 MPa; If epoxy coated bars are used embedment must be increased by 30% 2. Holes must be drilled with Hilti rotary hammer drills or if core drilled they must be conditioned with Hilti conditioning bits 3. For bars in compression or overlap bars the minimum embedments are shown in Table 1. To fully develop a lap splice use the development length plus the overlap increase shown in Table 2. HILTI HY 150 REBAR DESIGN GUIDE 8

Examples: Example 1) Wall connection A vertically compressed new wall is dimensioned as follows: f c = 20 MPa f y = 400 MPa New wall thickness = 180 mm Vertical bars in new wall - 10M @ 200 mm Horizontal bars in new wall - 10M @ 250 mm 10M @ 250 180 mm 10M @ 200 mm (Existing Floor) A) Floor connection: Req d load = 34.0 kn @ 200 mm both sides Therefore use 10M @ 200 mm both sides with hole depth = l b = 240 mm & D = 14 mm (from Table 3) Alternate 1: Try 15M @ 200 mm both sides; F d,req d = R yd (10M) = 34.0 kn Interpolating from Table 3: @ l b,inst = 205 mm F d = 34.6 kn > 34.0 kn but from Table 1 l b,min = 240 mm (Rebars in compression in 20 Mpa concrete) Since l b,min = 240 mm there is no reduction in embedment realized by using a larger bar. B) Side wall connection: F d, req d = 34.0 kn @ 250 mm both sides Therefore use 10M @ 250 mm both sides with hole depth = l b = 240 mm, D = 14 mm (from Table 3) Alternate 1: Try 15M @ 250 mm both sides; F d, req d = 34.0 kn Interpolating from Table 3 @ l b,inst = 205 mm F d = 34.6 kn > 34.0 kn From Table 1: Check l b,min = 160 mm < l b,inst O.K. (Rebars in tension in 20 MPa concrete It is simple to vary the hole depth by using the load table. HILTI HY 150 REBAR DESIGN GUIDE 9

Example 2) Wall extension The existing wall is reinforced by 10M bars at 250 mm both sides and shall be extended by a new wall with the following characteristics: f c = 20 MPa f y = 400 MPa Wall thickness = 200 mm 10M @ 250 mm Lap connection: 10M @ 250 mm both sides Hole depth = l b = 240 mm (Table 3) D = 14 mm Nothing is gained by rebars of larger diameter because the force acting on the connection must be transmitted to the cast-in reinforcement via the overlap. If the position of the existing rebar is not known it is advisable to assume the worst case regarding the proximity of the nearest cast-in rebar. Since e > 4 x d, the overlap must be increased by e - 4 x d. Therefore l b,inst = 240 + (250/2-4 x 11.3) = 320 mm If this is a large installation it is recommended that the existing rebar be located with a Hilti Ferroscan and the overlap of 240 mm can be used. Example 3) Installation of an intermediate floor Details: Slab thickness = h = 160 mm f c = 20 MPa f y = 400 MPa Rebar in new slab - 10M @ 150 mm 10M @ 150mm The anchorage to the walls is done using connection rebars having the same diameter and spacing as those in the slab. Only the minimum anchorage depth is required for rebars at supports. Connection: 10M @ 150 mm From Table 1 l b,min = 115 mm Therefore, embedment = l b,min = 115 mm & D = 14 mm The connection surfaces must be roughened to take up the shear force. HILTI HY 150 REBAR DESIGN GUIDE 10

Example 4) Connection of a balcony Details: Slab thickness = h = 150 mm f c = 20 MPa f y = 400 MPa Rebar in existing slab = 10M @ 200 mm both ways Rebar in new slab = 10M @ 200 mm both ways 10M @ 200 mm 10M @ 200 The bars in the top of new slab should be embedded into the existing slab at least equal to the basic development length for a 10M bar, l b = 240 mm. D = 14 mm If the existing rebar locations are not determined using the Hilti Ferroscan the embedment must be increased by 200/2-4 x 11.3 = 55 mm to a total length of 295 mm. The connection surfaces must be roughened to take up the shear force. In the bottom layer, 10M bars @ 200 mm should also be installed to the minimum embedment for a 10M of 115 mm for reasons of good detailing. HILTI HY 150 REBAR DESIGN GUIDE 11