SHORT BED ION EXCHANGE TECHNOLOGY PRODUCES ULTRAPURE WATER WITHOUT USING A MIXED BED

Similar documents
KEYWORDS: Ion exchange, compressed short bed, wastewater, filter, secondary water, tertiary water, reverse osmosis (RO), electrodeionization (EDI).

SIX YEARS OF SHORT-BED DEMINERALIZATION AT THE ONTARIO HEALTH SCIENCES CENTRE

Please Contact us for a price on this Refurbished Ion Exchange Softener!

Produced Water Treatment Systems

RECOFLO WATER SOFTENER

Produced Water Treatment Systems

performance of the ultrapure make-up system at Turkey Point Nuclear Power Plant

DOWEX UPCORE Ion Exchange Resins Retrofit of Demineralizer with UPCORE System Cuts Chemical Costs by 50%

IWC TECHNICAL PAPER 176

High Purity Boiler Water Production Using Municipal Waste - water at a Combined Cycle Gas-Fired Generating Station

Lenntech. Dow Liquid Separations. DOWEX Ion Exchange Resins. The Advantages of Uniform Particle Sized Ion Exchange Resins.

using EDI to meet the needs of pure water production

Lenntech. Using EDI to Meet the Needs of Pure Water Production. EDI Process. Summary. Introduction

IWC-10-XX. KEYWORDS: Produced water, ion exchange, nutshell filter

VOLUME 06 ISSUE 07-JULY 2013

The evolution of high purity water production

NEW TECHNOLOGIES & BREAKTHROUGHS TO OLD DEIONIZATION APPLICATIONS

high efficiency ~ simple package ~ proven reliability ChromaPur Chromic Acid Purification Unit

Advanced Produced-Water Treatment & Reuse For Oilfields

ChromaPur. Chromic Acid Purification System

Treatment of Coal Bed Methane Produced Water Using Short Bed Ion Exchange MICHAEL SHEEDY AND PAUL ROBINSON, Eco-Tec Inc., Pickering, Ontario

PRESENTATION OF CONDENSATE TREATMENT

DOWEX Ion Exchange Resins

Bucking the Industry Trend. Simple Change to Water System Saves New Jersey Manufacturer $23,000 Annually

Membrane Technology: From Manufacture to. May Production

DOW Ultrafiltration. Case History. DOW Ultrafiltration Membranes Offer Reliable, Economical Answer to High Solids

Lenntech. Tel Fax

This paper was presented at IEX 96 in Cambridge,UK on July 15 th 1996 and is the copyright of the SCI

Water supplied by Marafiq does not meet the process requirements.

Reducing Energy & Water In Your Boiler House Charles Astbury Commercial Operations GE Water & Process Technologies

POREX Tubular Membrane Filter (TMF ) Applied in a ZLD System as Critical Solid/Liquid Separation Process

0UltraClean. Ion Exchange Resins for Ultra-pure Water in the Electronics and Semiconductor Industry

Operation of Hydranautics New ESNA Membrane at St. Lucie West, FL Softening Plant

IONPURE CONTINUOUS ELECTRODEIONIZATION (CEDI)

Use of Spiral Wound UF in RO Pretreatment

FEDI. Fractional Electrodeionization. The evolution of high purity water production

Producing ultra-pure water. electro-deionization

Reducing Energy & Water In Your Boiler House Charles Astbury Commercial Operations GE Water & Process Technologies

Micro-Media Filtration: An Alternative to Membrane Filtration

Treatment Technologies

Protegra CS RO Series. Meeting All Your Pure Water Demands. Water Technologies

Boiler Water Chemistry: Getting From the Source to the Boiler Colleen M. Layman, PE

technology selection tools for boiler feedwater applications (metric units)

DOW Ultrafiltration. Case History. DOW Ultrafiltration Modules Protect Reverse Osmosis System from High Iron

Presented by: Jeff Freitag, The Water Guy Jon Tiegs, General Manager

REACTION TANKS WATER PURIFICATION THROUGH SERVICE DEIONIZATION

C-100H Strong Acid Cation Exchange Resin in Hydrogen Form (For use in water demineralization)

TEQUATIC TM PLUS Fine Particle Filter Product Introduction. Trademark of The Dow Chemical Company ("Dow") or an affiliated company of Dow

Lenntech. Ion Exchange Resin Analysis Kit. DOW Ion Exchange Resins DIRECTOR SM Service

INDUSTRIAL SEPARATE BED DEIONIZER. FDI Series. High Purity Industrial Packaged System

Western BLRBAC Review/Refresher of Tappi Water Quality Guidelines and Contamination Procedures for mill boilers operating on high purity water

--... _ 2-- I I J: 3 4 /

DESIGN AND OPERATION OF A HYBRID RO SYSTEM USING ENERGY SAVING MEMBRANES AND ENERGY RECOVERY TO TREAT SOUTHERN CALIFORNIA GROUND WATER.

5.B Generation of pharmaceutical water Author: Michael Gronwald Co-Author: Dr. Ralph Gomez / Up06

Electro Deionization: EDI Systems.

Overview. Commercial High-Purity Water Systems and Applications. Quality Water Is Our Business

A-300, A-300E Strong Base Type II Anion Exchange Resin

ADVANCED SOFTENING MATERIAL. for problem water. SIMPLE SOLUTION FOR 5 PROBLEMS hardness iron manganese natural organic matter ammonium

By C.F. Chubb Michaud, CWS-VI

GENESEE GENERATING STATION UNITS 4 AND 5 WATER CONSUMPTION AND EFFLUENT DISCHARGE CHARACTERIZATION REPORT

MEASUREMENT OF SODIUM IN WATER/STEAM CIRCUITS

Technical Data. Typical Chemical & Physical Characteristics

WTP Design by Computer. David Hayhurst, Purolite International

C-100E Strong Acid Cation Exchange Resin (For use in water softening applications)

Petro-Canada Re-Uses Treated Edmonton Waste Water. Coking.com Safety Seminar Calgary September 2008

CONTROL OF COPPER ELECTROLYTE IMPURITIES USING SHORT BED ION EXCHANGE ABSTRACT

Hetch Hetchy Treatability at the Sunol Valley Water Treatment Plant

Creating SDI Solutions WATER TECHNOLOGIES

Membrane Protection Resins Ion Exchange Resins and Reverse Osmosis in Partnership

Kirill Ukhanov, GE Water & Process Technologies, Russia, describes how advanced membrane technology is helping a Russian refinery to meet stringent

News. Power Generation 11. ph Control Reduces Acid Consumption in Neutralization Process up to 90 % Perspectives in Pure Water Analytics THORNTON

Hydranautics Nitto DESIGN SOFTWARE and SUPPORTING TOOL

Understanding Pretreatment. WesTech Engineering, Inc. Salt Lake City, Utah, USA

REQUEST FOR PROPOSALS DESAL ANTISCALANT/CLEAN-IN-PLACE CHEMICALS BID NO: ADDENDUM 1

Extreme Recovery Membrane Process and Zero Liquid Discharge Low Temperature Crystallization for Treating Scaling Mine Waters

effective deoxygenation by a hybrid process combining gas transfer membranes with catalytic oxygen reduction

PERFORMANCE AND RESIDUAL MANAGEMENT ASSESSMENT OF 5 MGD MEMBRANE WATER PLANT. Presented by: Stephen P. Dorman, P.E.

'HR' SERIES INDUSTRIAL HIGH REJECTION SYSTEMS

POREX Tubular Membrane Filter (TMF) Applied in a Copper Wastewater Reclaim System for a Printed Circuit Board Facility

CONTENTS. reverse osmosis _02. the R.O. plant _04. Micro series _06. LE/HR series _08. series from 500 to 1250 l/h _10

California Dreamin. on such a winter s day. The Mommas and the Papas

WASTEWATER FROM CARBON CAPTURE SPECIAL CONSIDERATIONS FOR WASTEWATER TREATMENT

City of Woodbury. Red Bank Water Treatment Plant - Treatment Alternatives Analysis November 2016

Sustainable use of Water and Energy. Produced Water Treatment and Recycling Power Generation from Waste Heat

high efficiency ~ simple package ~ proven reliability AnoPur Acid Purification for Aluminum Anodizing Processes

Producing High-Purity Recycled Water for Industrial Applications with Microfiltration and Reverse Osmosis: Lessons Learned

Eco-Tec Announces RecoPur Super Softening Technology a Produced-Water Treatment Breakthrough

Reclaimed Waste Water for Power Plant Cooling Tower Water & Boiler Feed Make-up. Richard Coniglio, Business Product Manager

Novel Low Fouling Nanofiltration Membranes. Craig Bartels, PhD, Hydranautics, Oceanside, CA Warren Casey, PE, Hydranautics, Houston, TX

Novel Treatment Technologies for Desalination and Selective Ion Removal

Cartwright Consulting Co.

Membrane Desalination Technology

the faculty for factory program (FFF), Jordan

World-leading Amine Purification System for the Removal of Heat Stable Salts from Amine Circuits. Advanced Resource Recovery & Purification Solutions

ACID SEPARATION FOR IMPURITY CONTROL AND ACID RECYCLE USING SHORT BED ION EXCHANGE

Advanced technologies portfolio for Produced Water treatment and reuse proposed by VEOLIA

Saline Water - Considerations for Future Water Supply. Bruce Thomson Water Resources Program UNM

High Purity Water Needs for the PV Industry Part 1: Development of Cost Effective Specification

MPure. Innovative Electrodeionization by MEGA a.s. Czech Republic. MPure ELECTRODEIONIZATION. MPure ELECTRODEIONIZATION

NIPPON PAPER RO SYSTEM + 2 Others

Transcription:

SHORT BED ION EXCHANGE TECHNOLOGY PRODUCES ULTRAPURE WATER WITHOUT USING A MIXED BED Michael Sheedy Eco-Tec Inc., 1145 Squires Beach Road, Pickering, Ontario, Canada, L1W 3T9. Presented at the EPRI 8 th International Conference on Cycle Chemistry in Fossil and Combined Cycle Plants with Heat Recovery Steam Generators, Calgary June 20 23, 2006 Abstract Conventional practice when producing water with a conductivity of less than 0.1umho/cm is to use a mixed bed ion exchange unit. This paper describes a novel short bed ion exchange technology that produces water of this quality using separate columns of cation and anion resin. The principle features of this technology include the use of compressively packed beds only 3 to 6 in depth, fine mesh resins that improve exchange kinetics, counter-current regeneration, and low exchanger loadings. This results in a system that is much smaller and less complex than an installation with a regenerated mixed bed unit. Case studies are presented that describe operation of this technology for the treatment of a surface water source, a municipally treated water source, and RO permeate. Introduction High pressure power boilers typically require make-up water that has the following characteristics: Conductivity <=0.1umho/cm, Silica 5 20 ppb, TOC <=300 ppb, Na, Ca, Mg, Cu, SO 4, Cl 3 20 ppb. The flow sheets most commonly considered when trying to produced this quality of water are the following: 1. Roughing demineralization using two conventional deep bed ion exchange columns followed by a mixed bed polisher, SAC/SBA/MB. 2. Roughing demineralization using reverse osmosis followed by a mixed bed polisher or EDI, RO/MB, RO/EDI. Using Recoflo short bed ion exchange technology it is possible to produce this quality of water without using either a mixed bed polisher or EDI stack. SM/Technical Paper 180 1

Features of Short Bed Ion Exchange 1. Short bed height and small resin volume The most obvious feature of this type of system is the significantly shorter bed height. Typical bed depths for a demineralizer are 3 to 6. This represents a resin volume that is approximately 10% that of a more conventional deep bed design. Such a dramatic reduction in column size reduces installation cost and footprint. It also allows the equipment to be completely factory pre-assembled and tested prior to shipment, thus reducing commissioning time and cost. 2. Fine mesh resin Short bed systems use resin particles that are about 1/5 the size of conventional resin beads. Reducing the particle size significantly increases the kinetics of the exchange process and allows operation at hydraulic flow rates that are 3 to 5 times higher than in conventional systems. This reduces the diameter of the resin vessels and the required floor space. Finer mesh resins are also stronger and more resistant to cracking due to changes in osmotic pressure 1, 2. 3. Counter current regeneration Counter-current regeneration is the most efficient method for contacting resin and regenerant chemicals. It ensures that the exit end of the resin bed is the most thoroughly regenerated thereby minimizing onstream leakage rates and increasing final water quality. It also minimizes the amount of excess regenerant chemical that must be used to ensure target water quality levels are achieved. 4. Compressed resin bed The resin is packed into the column in a slightly compressed condition. This ensures that no flow channeling and ionic leakage occurs. It also prevents any resin movement within the column ensuring that the benefits of counter-current regeneration are realized. Since no freeboard space exists within the column it is essential that suspended solids be removed from the feed stream. This means that some form of pre-filtration equipment must always be provided with a short bed system. Such equipment typically ranges from cartridge to dual media filters depending on the TSS level. 5. Low resin loading Typically less than 20% of the total exchange capacity of the resin is used in a loading cycle. This is significantly less than is used in a conventional system and ensures that only the most easily accessed and regenerated sites are used. In conjunction with counter-current regeneration this helps to minimize chemical consumption. It also minimizes the volume change associated with each loading and regeneration sequence, which helps to reduce resin bead physical stress and cracking. SM/Technical Paper 180 2

6. Short cycle times The low resin loading and high flow rates combine to produce short cycle times. For example, a system treating a feed stream with 170 mg/l TDS and producing 3 Meghom.cm quality product water has a total cycle time including regeneration of only 17 minutes. Such short regeneration times can reduce the need for redundant equipment through the use of surge tanks that would otherwise be impractically large for the multi-hour regeneration sequences that are common for conventional systems. Theory and Performance of Short Bed Ion Exchange Within an ion exchange column there is a relatively shallow layer of resin where the exchange process is actually taking place. Upstream of this layer the resin has already been exhausted while downstream the resin has yet to receive any significant loading. Short bed ion exchange technology is based on the manipulation and control of this shallow layer or "mass transfer zone, MTZ". In effect the depth of a short bed column is reduced to just slightly greater than the MTZ. Under some conditions the depth of the MTZ can be estimated using the following equation derived by Glueckauf 3 or by the NTU HTU approach outlined by Treybal 4. Z B = (H p +H o )/2 x { 1/(a-1) x ln(1/x B ) a/(a-1) x ln(1/(1-x B )) + 1} + (H f +H o )/2 x { a/(a-1) x ln(1/x B ) 1/(a-1) x ln(1/(1-x B )) - 1} Where Z B = H p = H f = H o = Half the height of the MTZ for ionic species B Plate height contribution due to particle diffusion and is directly proportional to resin particle (diameter) 2 and fluid velocity Plate height contribution due to film diffusion and is directly proportional to resin particle diameter Plate height contribution from finite particle size a = Resin separation factor for a given ion pair (ie Ca and Na) x B = Ionic fraction of B This equation shows that the depth of the MTZ and the kinetics of the exchange process are very dependant on the diameter of the resin bead. A smaller particle helps to reduce the depth of the MTZ while permitting operation at higher flow rates. In fact, due to the relatively low concentrations being treated during the loading step the kinetics of the exchange process are primarily limited by diffusion across the mass transfer film surrounding the resin bead. Under these conditions the exchange rate is inversely proportional to the bead diameter. SM/Technical Paper 180 3

While not used for process design purposes these approaches help to explain the significance of the relevant process parameters such as particle diameter, solution flow rate, and resin selectivity and provide a theoretical basis for the use of short ion exchange beds. Figure 1 shows experimental data for the measured MTZ in a cation resin column treating a 170 mg/l TDS water source. Under these conditions the product water quality produced after subsequent treatment through a short bed anion column ranged between 3 5Megohm.cm. The two curves show the location of the MTZ before and after loading at steady-state. To produce each curve the resin was extruded from a column and separated into 6 equal portions. Each section was then titrated with NaOH. The curves clearly show the following: Consistent with counter-current regeneration, the resin at the top (inlet) of the column and to the left of the curves is predominantly in the salt form, while the resin at the bottom (outlet) of the column and to the right of the curves, is primarily in the acid form. The area between the curves represents the actual loading that takes place each operating cycle and is less than 20% of the total bed capacity, which is represented by the area below the max. capacity line. The actual depth of the mass transfer zone in this case is only about 3. Since these data were produced from a column at steady-state the MTZ cycles back and forth between these boundaries each operating cycle. Mass Transfer Zone Acid Form Resin (meq/g-wet resin) 2.5 Max. Capacity 2 1.5 1 0.5 0 0 1 2 3 4 5 6 Top Bed Depth (inches) Af t er Loading Bef ore Loading Botto Figure 1 SM/Technical Paper 180 4

A similar curve could be produced for the anion column. Since the exchange on the anion resin is followed by neutralization of the hydroxyl ion it may be expected that this more favourable equilibrium condition would result in an even shorter mass transfer zone. In practice, the author has found that when trying to produce high purity water the lower capacity of the anion resin and its much lower selectivity for silica prevents operation with an anion bed shorter than the cation bed, unless use of a degassifier is considered. For a dual short bed system such as the unit shown in the figure 2, typical performance is described in table 1. Figure 2 This Recoflo short bed demineralizer can produce up to 600 gpm (136 m3/hr) of high purity water Table 1 Typical Short Bed Performance Feedwater Conductivity (µs/cm) Product Water Resistivity (Mohm-cm) 340 1-5 200 10-12.5 20 16-18 4 17.5 18.1 The less favourable equilibrium condition in the cation bed does explain why there is more sodium leakage from the cation bed relative to chloride leakage from the anion bed. The result being that under most conditions the primary contribution to ionic leakage from a dual short bed (SAC/SBA) demineralizer is sodium hydroxide. The other obvious source of caustic is of course incompletely rinsed regenerant solution. In a short bed system the problem of residual regenerant is addressed by using a relatively small volume of rinse water, typically about 1 bed volume, followed by a brief period of internal recirculation through both beds before the unit is returned to service. SM/Technical Paper 180 5

To further improve performance, the problem of onstream sodium leakage from the cation bed is addressed by adding a small polishing bed of SAC resin to the skid and locating it immediately after the primary anion bed. This Triflo configuration, shown in figure 5 extends the range of feed water conductivity that may be treated to 1,000µS/cm, while still allowing the production of better than 10 Megohm.cm product water. The TDS fed to this polishing bed is minimal which means that the regeneration frequency is very low and the additional regenerant consumption is insignificant. For the same reason it is possible to operate this bed at almost double the hydraulic flow rate and with a bed depth of only 3, which is half the depth of the primary units. Furthermore, it is possible to reduce the primary cation bed regenerant dosage since the resulting incremental leakage will be captured by the polishing bed. In this way the overall regenerant consumption can be reduced. Short Bed Triflo Case Study This Triflo system was commissioned in the fall of 2002 and produces 500 gpm of high purity water with a conductivity of less than 0.1 micromho/cm and less than 4 ppb SiO 2 without using a mixed bed polisher. The water is used to feed a 2,000psig coal fired boiler. The primary water sources are either raw water drawn from one of the Great Lakes or the local municipal supply both with a Total Dissolved Solids (TDS) of about 160 mg/l as CaCO 3, conductivity of about 310µs/cm and the following water analysis. Calcium 95 mg/l Bicarbonate 111.5 mg/l Magnesium 50 mg/l Sulfate 21.9 mg/l Sodium 13 mg/l Chloride 14.1 mg/l Other cations 2.2 mg/l Silica 1.5 mg/l Other anions 0.8 mg/l Total cations 160.2 mg/l Total anions 149.8 mg/l Turbidity up to 100 NTU TSS up to 100 mg/l TOC normally <2 mg/l, spikes to 7 mg/l ph 7.5 8.5 Temperature 35 80F This new system has now been in service for almost 4 years and has consistently produced less than 0.1 micromho/cm water. 6

Figure 3 Triflo Process Flowsheet As the analysis indicates this water will at times contain significant amounts of TSS. To prolong filter run length the initial process design allowed switching to a city water source when turbidity levels exceeded 100 NTU. Feed turbidity is monitored by an online turbidity meter. To remove TSS three dual-media Spectrum Filters 5 were provided with each capable of delivering 50% of the required net product flow. A photograph of one of the filters is shown in figure 4. Each filter is 66 inches in diameter and is operated at a maximum hydraulic flowrate of 428 gpm (18 gpm/ft 2 ). The bulk of the suspended solids are removed in the upper filtration layer, which consists of coarse anthracite with an effective size of 0.6 0.8mm. The lower layer acts as a polishing filter to remove the residual solids not retained by the anthracite. A unique high-density micro-media is used with an effective size less than 0.1mm. SM/Technical Paper 180 7

Figure 4 66 diameter Spectrum filter that can process up to 428gpm while producing a filtrate with less than 0.1NTU This filtrate stream is pumped to two short bed Triflo ion exchange trains. Each train was designed to provide a net product flow rate of about 290 gpm. As previously described a Triflo unit consists of three short depth compressively packed ion exchange beds. The primary SAC/SBA columns are 60 inches in diameter and 6 inches in depth and operate at 30 gpm/ft 2. The final polishing cation resin bed is only 48 inches in diameter and 3 inches in depth and runs at 50 gpm/ft 2. A photograph of one of the Triflo units is shown in figure 5. Figure 5 60 diameter Triflo short bed demineralizer producing 290gpm product water with a conductivity <0.1umho/cm SM/Technical Paper 180 8

Counter-current regeneration of the primary SAC and SBA resin beds is automatically initiated after processing a fixed volume of solution. The normal onstream loading time for the primary beds is about 10 minutes. The primary regeneration sequence is fully automated and takes about 11 minutes. The conc. Chemicals are injected inline via gear pumps into regenerant DI water. To ensure adequate removal of silica during anion regeneration the regenerant DI water is heated to 140F in an electrically heated warm water supply tank. Upon completion of the primary regeneration sequence water is recirculated through the primary cation and anion beds to remove any residual unwashed regenerant chemicals. As a result of the small TDS load on the cation polisher bed it is only regenerated after 100 loading cycles of the primary beds have been completed. This is also automatically initiated. Product water conductivity and silica performance data collected from a log sheet monitoring program are shown in the figure below. The data clearly show that product water conductivity was consistently below 0.1 micromho/cm and that silica levels were generally less than 4 ppb. The long-term trend indicates a decline in the silica concentration and more stable readings. Silica levels subsequent to this monitoring period were typically in the 2-4 ppb range. This is attributed to minor program and sampling modifications and the performance of in-situ anion bed cleaning when silica levels start to increase. WE PPPP Triflo Performance Conductivity (micromho/cm) 0.5 0.45 0.4 0.35 0.3 0.25 0.2 0.15 0.1 0.05 0 24- May-02 Product Conductivity 01- Sep-02 10- Dec-02 20- Mar-03 28- Jun-03 06- Oct-03 14- Jan-04 Product Silica 23- Apr-04 7 6 5 4 3 2 1 0 01- Aug-04 Silica (ppb) Date Figure 6 Triflo product water quality SM/Technical Paper 180 9

Table 2 shows a comparison of regenerant consumption for the Triflo system and the previous SAC/degassifier/SBA conventional system. The Triflo unit has provided a dramatic improvement in product water quality and a substantial reduction in regenerant acid consumption, however the reduction in caustic consumption is more modest, due to the fact that the Triflo system does not use a degassifier as the did the previous system. Table 2 Triflo System Performance Old System Triflo Consumption Performance Consumption Performance Acid 0.38 gal/kgal Conductivity 2-3 umho/cm Sodium 40-80 ppb Caustic 0.34 gal/kgal TOC 500 ppb Silica 5 ppb Chloride 5-10 ppb Sulfate <4 ppb 0.17 gal/kgal Conductivity <0.1 umho/cm Sodium ~1 ppb 0.29 gal/kgal TOC 200 ppb Silica 2-4 ppb Chloride 1-2 ppb Sulfate <1 ppb Short Bed Polisher Case Study In 2001 a high purity water treatment system was installed as a replacement system at a nuclear power station 6. The system has a capacity of 1050 gpm (239 m 3 /hr). It treats Great Lakes surface water through direct filtration, reverse osmosis (single pass) followed by a double pass through short bed demineralizers, each one consisting of a separate bed of cation and anion resin (see Figure 7 below). Table 3 Performance data from a double pass two bed system after single pass reverse osmosis Feed Water Product Water Spec Actual Performance 300-340µS/cm > 16.7 MΩ-cm 18-18.3MΩ-cm Silica 0.6-1.3ppm <2.0ppb 0.36ppb Sodium 10-13 ppm <0.2ppb <0.05ppb TOC 1.5-3.0ppm <10ppb 5.1ppb Chloride 20-25 ppm <0.8ppb <0.3ppb Sulfate 24-27 ppm <1.8ppb <0.5ppb SM/Technical Paper 180 10

Figure 7 1050 gpm (239m3/hr) capacity high purity system with Recoflo short bed ion exchange polishers in foreground. Large vessels are micro-media filters for surface water direct pre-filtration. Reverse osmosis units are in background. This system has been operating for 4 years and consistently produces water of the quality indicated in Table 3. The RO permeate quality which feeds the ion exchange polishers is typically in the range of 10-20µS/cm, with 2-3 ppm TDS and 60 ppm CO2. The final quality indicates the purity that can be achieved using this process, without the use of mixed resin beds. Pilot testing prior to the selection of the system indicated that a single cation/anion short bed polisher could achieve the specified quality. However, since this was the first commercial installation of Recoflo short bed technology at this capacity and product water purity, and since the client was a nuclear power station that needed a reliable, continuous supply of demineralized water, it was decided to install the system in a twostage configuration. The first stage demineralizers have a total cycle time of 39 minutes, which includes the 7 minute regeneration sequence. Chemical consumption is 0.33 lb-sulfuric acid and 0.67 lb-caustic soda per 1000 gallons of water produced. The final polisher is in service for 29 hours and is then regeneration in 11 minutes before returning to service. In both cases the regeneration sequence is fully automated. Chemical consumption of the final polisher is 0.067lbs of sulfuric acid and 0.05lbs of caustic soda per 1000gallons of water produced. For a system producing 500 gpm continuously, this would correspond to a 200 gal (760 l) tote of 93% sulfuric acid lasting for 580 days and a 200 gal tote of caustic lasting 350 days. The waste volume from each of the two final polishers which treat 525 gpm (120 m 3 /hr) is 418 gal (1653 l) per regeneration. SM/Technical Paper 180 11

Summary The case studies presented in this paper clearly demonstrate that Recoflo short bed ion exchange technology can be used to produce high purity water for boiler feed make-up without using a mixed bed polisher or EDI cell. References 1. Dowex Fine Mesh Spherical Ion Exchange Resins For Pharmaceutical and Fine Chemical Column Separations, Form 177-01509-702XQRP, Dow Liquid Separations, http://www.dow.com/liquidseps/pc/special/biotech.htm. 2. Diaion Manual of Ion Exchange Resins and Synthetic Adsorbent I, Mitsubishi Chemical Corporation, Japan, 1995 p62. 3. E. Glueckauf, Ion Exchange edited by Friederich Helfferich, McGraw-Hill Book Company, Inc., New York, 1962 p 463. 4. R.E. Treybal, Mass Transfer Operations 2 nd Edition, McGraw-Hill Book Company, Inc., New York, 1968 p 556. 5. C. Brown, Micro-Media Filtration: An Alternative to Membrane Filtration, Presented at the Southwest Chemistry Conference, Park City Utah 2002, http://www.eco-tec.com/techpapers/tp%20160%20micro%20filtration.pdf 6. Hourigan, Russell; Nicolaides, Gabriel; Dejak, Michael - Outsourced Water Treatment Plant for Boiler Water Make-Up: A Case Study. Technical Paper presented at the International Water Conference 2005. 12 SM/Technical Paper 180