Drying of Concrete TDS 183

Similar documents
LATICRETE and Moisture Vapour Emission Rate, Relative Humidity and Moisture Testing of Concrete

Understanding its Effects on Coatings MOISTURE IN CONCRETE. VersaFlex. Copyright 2008 I N C O R P O R A T E D

Subfloor Preparation and Moisture Mitigation

2/13/2015. Abstract. Abstract. Addressing Moisture in Concrete for Roofing and Flooring Applications

CALCIUM CHLORIDE V. IN-SITU RELATIVE HUMIDITY - GEORGE DONNELLY TESTING & INSPECTIONS

SECTION HYDRAULIC CEMENT UNDERLAYMENT

A. Section includes cast-in-place concrete, including reinforcement, concrete materials, mixture design, placement procedures, and finishes.

LATICRETE Family of Adhesives PRODUCT CATEGORY USE MIX WITH SUBSTRATE APPLICATION

Moisture in Concrete: Implications on the Selection of Flooring Systems

10/10/2007. Is it Dark at Night?

SECTION SUBSURFACE PREPARATION FOR FLOOR FINISHES

ARDEX GUIDE SPECIFICATION ARDEX MRF Moisture-Resistant, Rapid-Drying, Skimcoat Patching Underlayment

ARDEX GUIDE SPECIFICATION ARDEX SD-M Designer Floor Finish

KOSTER AMERICAN CORPORATION

SECTION ARDEX TILE AND STONE INSTALLATION MATERIALS AND SYSTEMS

Capillary Rise. Wicking upward from footing / foundation Beware connecting wet soil to moisture sensitive materials via foundations

SECTION MOISTURE RESISTANT/WATER-PROOF FLOORING ADHESIVE FOR CONCRETE SLABS

ARDEX GUIDE SPECIFICATION ARDEX FEATHER FINISH Self-Drying, Cement-Based Finish Underlayment

ARDEX GUIDE SPECIFICATION ARDEX K 22 F High Flow, Fiber Reinforced, Self-Leveling Underlayment

ARDEX GUIDE SPECIFICATION ARDEX GPS GENERAL PATCH & SKIMCOAT Trowelable underlayment

ARDEX A 38 MIX Rapid Set, Premixed Screed

(Fig. 1.1, source: StarLog Volumn VII, Issue 2) (Fig. 1.2, source: StarLog Volume VII, Issue 2)

EXPANKO RESILIENT FLOORING PRE-INSTALLATION GUIDELINES

Preparation of Concrete Substrate: Preparation of Baseplates and Sole Plates: Forming for Grout Placement: General Preparation:

ARDEX GUIDE SPECIFICATION ARDEX K 60 ARDITEX A Rapid Setting Latex Smoothing and Leveling Compound

Uncoupling Membranes for Tile Installations. Technical White Paper UNCOUPLING MEMBRANES

Chapter 2. Basic practices. Topics. 7 Basic practices. Notes. 2.5 Existing flooring and adhesive residue Job site conditions 8

ARDEX A 38TM Rapid Set Screed

ARDEX GUIDE SPECIFICATION ARDEX MRF Moisture-Resistant, Rapid-Drying, Skimcoat Patching Underlayment

DIVISION 3 - CONCRETE Section Concrete Rehabilitation

New SSPC Moisture Testing Guide and Pinhole Standard. Kenneth A. Trimber KTA-Tator, Inc.

STOP CONCRETE COATING FAILURES ONCE AND FOR ALL. THE MOST ADVANCED CONCRETE COLOR SYSTEM EVER.

Thin-Set Troubleshooting Guide for Concrete and Masonry Substrates

Suggested Specification for Tri-Patch Versatile Concrete Patching Compound

A. Description of Work: Work of this section includes self leveling underlayment for interior finish flooring but is not limited to, the following:

NXT SUBSTRATE PREPARATION AND PRIMER GUIDE TDS 230N

How do I choose the right installation solution for my next modular carpet project? NEW CONSTRUCTION

Section SECTION RESINOUS FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Specification and Installation

What you should know about Concrete and Moisture

A Little Too-Much Concrete Moisture Can Make You Sweat a Whole Lot

CONCRETE SUBSTRATE FLATWORK AND MOISTURE MITIGATION

Re-Grouting Floor Joints in Commercial Kitchens and Industrial Applications

DIVISION 3 - CONCRETE Section Concrete Rehabilitation

Planitex SL 35. Engineered Gypsum Self-Leveling Underlayment

ARDEX GUIDE SPECIFICATION ARDEX GS-4 Self-Leveling Repair Underlayment for Distressed Gypsum and Wood Subfloors

MONDO MP 1000 ACRYLIC ADHESIVE DISCLAIMER: Refer to page 5 of this document.

Specification and Installation

4. Floor Substrate Testing Prior to Floor Paint application

Installation of Large Format Tile & Stone

CONCRETE WORK CONCRETE WORK. Underground Electric Distribution Standards I. SCOPE APPLICABLE STANDARDS

A. Section includes cast-in-place concrete, including reinforcement, concrete materials, mixture design, placement procedures, and finishes.

Would You Like Concrete With Little or No Shrinkage, Cracking, and Curling??? We Will Focus on:

Installation of Ceramic Tile in Swimming Pools

American Guild Vinyl Flooring - Steadcrest Collection Installation Instructions

WEIGHT PER PIECE (LBS.)

SECTION A. Schönox AP- Synthetic Gypsum Self Leveling Underlayment. B. Schönox VD-Primer for porous substrates

Installation Guide LVP Glue Down

StrataWorx Tile. Installation Guidelines 1. CONDITION YOUR SITE AND TEST 2. PREPARE THE FLOOR

SECTION HYDRAULIC CEMENT UNDERLAYMENT

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 03 - CONCRETE

MARATHON & MARATHON PLUS RUBBER TILE

Smart Vapor Retarders

SECTION CAST IN PLACE CONCRETE FOR FLOOR SLABS ON GRADE THAT WILL RECEIVE SEMI-PERMEABLE OR IMPERMEABLE FLOOR FINISHES

Novoplan 2. Professional Self-Leveling Underlayment. where to use. limitations

SECTION SHEET MEMBRANE SOUND REDUCTION, CRACK ISOLATION / JOINT BRIDGING, AND WATERPROOFING

LVP GLUE DOWN INSTALLATION GUIDE PAGE 1 of 6

Krystol Internal Membrane (KIM ) Guidelines and Procedures - NZ

Cutting Edge Solutions Using Advanced Self Leveling Materials. ICRI National Convention April 14, 2010

May 2, 2018, Bethany, Conn. -- LATICRETE, a leading manufacturer of globally proven construction solutions for

FLOOR SCREEDS & ADDITIVES SOLUTIONS FOR INDUSTRIAL, RETAIL, RESIDENTIAL & PUBLIC BUILDINGS UZIN. THE FLOOR BELONGS TO YOU.

TK Products MCC April 12, 2018

This section applies to the design and installation of cast-in-place concrete, shotcrete, precast concrete, and post-tensioned concrete.

PREPARATION IS THE KEY TO SUCCESSFUL FLOOR COATINGS By Bob Cusumano

FLOORING INSTALLATION SYSTEMS. Product Catalog

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

1. Rapid Set Cement. 2. Methods of preparation. 3. How to stage a job site. 4. Installation Mix, place, finish. 5. Coloring the TRU.

XTREME-BOND INSTALLATION SYSTEM

SECTION HYDRAULIC CEMENT UNDERLAYMENT

A. Drawings and general provisions of the contract, including General and Supplementary Conditions, apply to this section.

System Specification CEM-DYE 25 SYSTEM Division 9 Finishes Section Staining and Transparent Finish

RESILIENT FLOORING: Select Step Wood

EARLY AGE SHRINKAGE AND MOISTURE LOSS OF CONCRETE

Copyright. What is Lightweight Concrete? magazine

SECTION RESILIENT TILE FLOORING

MOISTURE CONTROLLED.

Underfloor Heating. BS8425 Code of Practice for Installation of Laminate Floorcoverings and the Code of Practice issued by the

Features. Specifications. VersaShield MBX slashes up to half the total cost with a quick and effective concrete moisture mitigation up to 99.5% RH.

Text applicable to Parterre luxury vinyl tile, plank and resilient sheet flooring unless otherwise evident.

Dusit Roongsang, P.E. Presented at. PNWS AWWA Conference Bellevue, WA May 1, 2015

Dryshake CSI Format Section 07160

Moisture barrier for protection of flooring assemblies up to 99.5% relative humidity

SECTION 434 HIGH PERFORMANCE CONCRETE (HPC)

ALETTE GLUE DOWN INSTALLATION INSTRUCTIONS

Fast drying and setting cement for floor screeds (24 hours) hydraulic binder for shrinkage - compensated screeds

Learn how to reduce the amount of moisture in concrete floors.

ARDEX GUIDE SPECIFICATION ARDEX TRM Transportation Repair Mortar Fast-Setting Concrete Repair Mortar

SECTION SHEET MEMBRANE SOUND REDUCTION, CRACK ISOLATION / JOINT BRIDGING, AND WATERPROOFING

SECTION ARDEX WOOD FLOORING INSTALLATION MATERIALS AND SYSTEMS

Resilient and Wood Floor Covering Flatness Requires High Performance, Cementitious Self-Leveling Underlayment

Transcription:

Drying of Concrete TDS 183 As the occurrence of fast track construction continues to rise, the need to install a finished floor on a wet concrete slab is typically far too soon for the floor covering. Vinyl (tile or sheet), epoxy coatings, paint, rubber floors, vinyl backed carpet, and flooring over a waterproofing membrane will all be negatively affected by high moisture content, high moisture vapor emission rate and/or high relative humidity (RH) within the concrete. Concrete scheduled to receive flooring must be dry enough to permit an adhesive to bond properly and prevent damage to the flooring. For epoxy based materials, the concrete must be dry enough to develop adequate bond and allow the epoxy to properly cure. Ceramic tile and stone, installed without a membrane, are much less sensitive to moisture and high moisture levels. It is very important to note that the only way to properly control moisture in, and moving through, a concrete slab-on-grade is to have a properly specified, placed and correctly installed vapor barrier under the slab. If a vapor barrier is not present then it will be impossible to guarantee that the moisture content, relative humidity and moisture vapor emission rate of the concrete will ever achieve or maintain necessary levels during the life of the slab. In practice, the RH in sub-grade soil will almost always be close to 100%, so unless the ambient indoor RH in the building is 100% the drive of moisture will always be into the structure. Floor moisture issues can be avoided with proper planning, good design, implementation of moisture control measures (e.g. foundation drainage, vapor retarder), extensive moisture testing, and the specification and application of appropriate installation materials. However, there is always the potential for conditions and circumstances which are beyond the control of designers, building owners and contractors which can have a direct effect on the moisture level in a slab. CONCRETE MOISTURE For the purposes of this technical data sheet, the term concrete moisture means the total water used in the concrete batch, plus curing water, minus the water used to hydrate the cement. A typical cubic yard of concrete with a water/cement ratio of 0.5 contains 275 lbs. (125 kg) of water. Approximately half of that water will be used to hydrate the cement, while the other half, which comprises approximately 3.2% of the weight of the concrete is considered free water or water of convenience. This water must evaporate to reduce the RH in the concrete to an acceptable level for the floor covering. If the concrete is moist cured, the additional water can raise the free water to 7% of the weight of the concrete. Based on the 3.2% figure, it would be necessary for several pounds of water to evaporate from every square foot (kg/m 2 ) for the slab to be considered adequately dry for many floor finishes. Factors which affect the time needed for concrete to dry to required moisture levels include; Type of cement Type and amount of aggregate Water/cement ratio Presence of a vapor barrier (slab-on-grade) Curing and drying conditions Thickness of the concrete slab Specified moisture condition set forth by flooring material manufacturer Typically, the water/cement ratio is the single most important determining criteria for the drying of concrete. For a concrete with a water/cement ratio of 0.50 to 0.70, the drying time to reach 90% RH is anywhere from 3 to 9 months, under suitable drying conditions. Concrete utilizing a water/cement ratio of 0.38 0.5 typically take 2 to 3 months to reach 90% RH under suitable drying conditions. Keep this in mind: it took 3 months for concrete, with a water/cement ratio of 0.38 0.5 to get to 90% RH!! Many moisture sensitive flooring materials and adhesives can require as low as 75% 1

RH as tested per ASTM F2170 Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes prior to installation!! For more information on moisture vapor transmission and test methods, please refer to TDS 166 LATICRETE and Moisture Vapor Emission Rates. Over the years, the flooring industry has come up with a rule of thumb which states that the time necessary for concrete floors to reach an acceptable content is: 1 month of drying for each inch of concrete or 1mm per day. MOISTURE MOVEMENT THROUGH CONCRETE Moisture can move through concrete slabs as water vapor or as liquid water. Concrete which is not saturated with liquid water will transmit moisture as vapor (gas) by diffusion through the capillaries of the cement paste. This moisture vapor is driven to the surface by the difference in RH at the bottom and at the top of the slab. This is how moisture can accumulate under a floor covering even though the concrete does not appear to be saturated with water. This is also why concrete, poured in a building which is not completely enclosed and in which the HVAC system is not turned on, will not begin to dry until such time as the building is enclosed and the HVAC is turned on. Relative humidity in concrete and in the air work toward a state of equilibrium, so, at any time the concrete will actually be pulling moisture out of the air if the humidity of the air is greater than the concrete. The same is true in reverse. Once the building is enclosed and the HVAC system is turned on, the RH within the air in the building can be controlled and the concrete can actually begin to dry. It is at this point that the clock (actually calendar) begins. All too often, someone in the decision making team feels that drying of concrete begins as soon as it is poured and installation of flooring will proceed based on this false belief. For concrete which is saturated with water, the driving force for moisture movement is capillary action, and, when the concrete is exposed to air, the driving force is evaporation from the surface. The drying process begins (under ideal conditions) when water is no longer available at the exposed surface, so concrete cured by sealing in the original mix water with wet burlap or plastic sheets, drying will begin when these covers are removed. Spray applied membranes (curing compounds) reduce the rate of moisture evaporation and help retain moisture in the concrete; thus expediting the hydration (curing) process. But, curing compounds are somewhat breathable and drying begins shortly after the membrane is applied (under ideal conditions). However, curing compounds significantly reduce the drying rate and significantly extend the drying period. Curing compounds must be physically removed from the concrete before a normal curing period can begin. Therefore, a moisture sensitive material cannot immediately be applied to a concrete slab from which curing compounds have been removed. Once the curing compound has been removed, it will still be necessary to wait an extended period of time to allow the concrete to reach a suitable moisture level for the floor covering. Concrete is a porous material which experiences three distinct stages of drying; a constant rate period followed by two falling rate periods; Stage 1 During the first drying stage, liquid water is present at the surface which evaporates into the air above the concrete. The rate of evaporation depends upon the temperature, RH and air flow over the concrete surface. Warm, rapidly moving air will cause faster evaporation than cool, stagnant air. As water moves from within the concrete to replace water which has evaporated at the surface, the concrete will shrink to make up for the volume of water which has now left. If the evaporation rate is very high, the concrete can shrink excessively before the cement paste has developed sufficient strength. This is the cause of plastic shrinkage which may occur within the first few hours of placement. See Figure 1. Stage 2 The second stage of concrete drying begins when the concrete can no longer shrink due to liquid water evaporation. Water recedes from the exposed surface of the concrete into the pores where it clings to the sidewalls and forms a curved surface (meniscus). Water evaporates from the meniscus in each pore into the air over the concrete. The rate of evaporation is still mostly dependent upon temperature, RH and air flow over the concrete surface. The surface may appear to be dry, but the concrete is just beginning to dry in a very thin layer. It is during Stage 2 that the drying rate steadily decreases. See Figure 2. Stage 3 The third stage of drying begins when enough water has evaporated from just below the surface that the pores are no longer continuously filled with water. Pockets of liquid will still exist, but moisture must now move by vapor diffusion within the body of the concrete before arriving at the surface where it can evaporate. This is the second falling rate stage, 2

because the rate of drying continuously decreases over time and is slower than the previous stage of drying. The rate of drying depends less on temperature, RH and air flow above the concrete surface because moisture must evaporate and diffuse within the body of the concrete before arriving at the surface. This is the stage that causes extended cure time for concrete to reach acceptable moisture levels prior to installation of moisture sensitive materials. The rate of drying during Stage 3 is determined by the quality of the cement paste: low water to cement paste offers more resistance to vapor diffusion than high water/cement ratio paste. While it may sound good to have a low quality cement paste, to allow the moisture in the concrete to evacuate more quickly, the increased water content of low quality cement paste can extend the drying time significantly. See Figure 3. ESTIMATION OF DRYING TIME The chart below shows the average expected drying time of an interior 4 (100mm) thick concrete slab which is drying from one side when the building is enclosed and the HVAC system is operating normally. This chart graphically shows how important the initial water/cement ratio is to the expected drying time of concrete. Concrete mixed with a water/cement ratio of 0.4 can achieve 5 lbs/1,000 ft 2 /24 hours in 28 days per ASTM F1869 (under ideal conditions) while concrete mixed at a water/cement ratio of 0.8 may take a s long as a year to achieve the same level. Thicker pours will require longer expected cure times. The Swedish Concrete Association describes a method to estimate drying times for concrete slabs. Correction factors make it possible to allow for deviations from a known set of base conditions. The purpose of this calculation is to enable the estimation of a minimum drying time(s) for concrete slabs (under conditions stated below) during the planning stage. This calculation can be useful for general planning but should not be relied upon to determine precise drying times due to variability of actual concrete composition and jobsite conditions. Factors used in this calculation include: Portland cement concrete slab measuring 7.2 (180mm) thickness Drying temperature of 64 F (18 C) Relative humidity of the air of 60% Drying from both sides of the slab (elevated) Curing conditions prior to drying 2 weeks of rain and 2 weeks of high RH Water/cement ratio is the parameter used to characterize the concrete 85% and 95% RH are used to characterize the moisture condition of the concrete after drying Standard Drying Time 3

The standard drying time is based on the actual water/cement ratio and the RH of the concrete. Table 1 - Standard Drying Time RH% w/c = 0.4 w/c = 0.5 w/c = 0.6 w/c = 0.7 85 50 days 90 days 135 days 180 days 90 20 days 45 days 65 days 95 days Dimensional Correction Factor The thickness of the slab will have an effect on the drying time. Use the correction factor as shown in Table 2 using the appropriate water/cement ratio and actual thickness of the concrete slab. Table 2 Correction Factor for Different Slab Thickness Thickness w/c = 0.4 w/c = 0.5 w/c = 0.6 w/c = 0.7 4 (100mm) 0.4 0.4 0.4 0.4 6 (150mm) 0.8 0.8 0.8 0.7 7 (180mm) 1.0 1.0 1.0 1.0 8 (200mm) 1.1 1.1 1.1 1.2 10 (250mm) 1.3 1.4 1.5 1.8 One- or Two-Sided Drying Drying from two sides requires a shorter time than drying from one side only. Use the correction factor as shown in Table 3 using the appropriate water/cement ratio and drying condition. Note that elevated concrete poured over steel pan is considered one sided drying. Table 3 Correction Factor for One-Sided or Two Sided Drying Drying Condition w/c = 0.4 w/c = 0.5 w/c = 0.6 w/c = 0.7 One-Sided 2.0 2.3 2.6 3.2 Two-Sided 1.0 1.0 1.0 1.0 Temperature and Humidity Lower humidity and higher temperature during drying will increase the rate of drying. Use the correction factors using the appropriate RH and temperature of the ambient air. Table 4 Correction Factor for Temperature and Humidity RH% 50 F (10 C) 64 F (18 C) 77 F (25 C) 86 F (30 C) 35 1.2 0.8 0.7 0.6 50 1.2 0.9 0.7 0.6 60 1.3 1.0 0.8 0.7 70 1.4 1.1 0.8 0.7 80 1.7 1.2 1.0 0.9 Variations for Curing Conditions Variations in concrete mix and curing conditions can affect the drying time of concrete. Use the correction factors in Table 5 using the appropriate conditions shown. Table 5 Correction Factors for Variations in Curing Conditions Curing Condition (drying to 90% RH) w/c = 0.5 w/c = 0.6 w/c = 0.7 Dry 0.5 0.5 0.7 4 weeks of high moisture (tight cover) 0.5 0.7 0.8 4 weeks of rain 1.0 1.3 1.3 The estimated drying time for a given concrete slab is obtained by multiplying the five factors selected from the above tables. Adding 10% silica fume to the concrete reduces the drying time by approximately 50%. For concrete with a water/cement ratio less than 0.5 and the addition of 5% silica fume can reduce the drying time approximately 50%. 4

APPLICATION OF CORRECTION FACTORS Below is an example of how to use the standard time and correction factors for estimating the approximate time for drying of a concrete slab during the planning stage. During the planning stage, it was estimated that the time between pouring a concrete slab and the installation of a floor covering would be 3 months for a 4 (100mm) slab. It was also estimated that it would be a month before the building was enclosed and the HVAC turned on, effectively allowing for a 2 month drying period. It was specified that the floor slab must attain a maximum relative humidity of 85% at the equivalent depth, and drying would be one-sided. The water/cement ratio was to be 0.4 and the construction was going to take place during the rainy season. Once the building is enclosed, the drying climate will be 64 F (18 C). From Table 1, the standard time is 50 days From Table 2, the correction factor for thickness is 0.4 From Table 3, the correction factor for one-sided drying is 2.0 From Table 4, the correction factor for temperature and humidity is 0.9 From Table 5, the correction factor for a rainy season is 1.4 (not shown in table) The total time is determined by the following calculation: 50 x 0.4 x 2 x 0.9 x 1.4 = 50 days, which is acceptable compared to the 2 months available. However, this apparently short drying time is possible only if the concrete has the specified low water/cement ratio and the building is enclosed, with the HVAC running to provide 50% RH and the proper temperature. If these parameters, or others as estimated, are incorrect then the drying time will be considerably longer. CONCRETE DRYING AND TILE As stated earlier, unlike many floor coverings, ceramic tile, stone and the majority of their adhesives are not sensitive to the affects of moisture and high ph. Tile and stone can be installed on concrete, with certain cement based setting material (e.g. LATICRETE 254 Platinum, 257 TITANIUM or 211 Powder gauged with 4237 Latex Additive) directly to concrete with a 5 7 day cure time. It will be necessary to allow for additional movement joints to compensate for excessive concrete shrinkage. However, the use of a waterproofing/anti-fracture membrane (e.g. HYDRO BAN, HYDRO BAN Sheet Membrane, or 9235 Waterproofing Membrane) will require that the concrete reach moisture conditions of 5 lb / 1,000 ft 2 / 24 hours (283µg / sec m 2 ) or 75% RH prior to installation. Please consult the data sheet for the particular LATICRETE product(s) to determine acceptable concrete cure time or moisture levels prior to installation. LATICRETE Moisture Vapor Membranes For cases where the MVER or RH exceeds the recommended levels for the type of finish material being installed, NXT TM Vapor Reduction Coating and SUPERCAP (TM) Moisture Vapor Control can be used to minimize the moisture allowed to pass through to the flooring layer. These membranes are a single-coat, 100% solids, liquid applied 2-part epoxy coating specifically designed for controlling the moisture vapor emission rate from new or existing concrete slabs. These products reduce MVER from > 20 lbs/1000 ft2/24hr (1,133 μg/(s m) to below 3 lbs/1000 ft2/24hr (170 μg/(s m) in a single coat. These membranes allow for the installation of vinyl, rubber, VCT, carpet, wood, ceramic tile, stone and other moisture sensitive floor coverings and floor adhesives. Please refer to the respective product data sheets www.laticrete.com, drytek.com, www.laticretesupercap.com. The information contained in this document should be used as a guideline only, and should not be used as part of any construction document. Actual field concrete installation drying time calculations must be conducted by qualified personnel, based on actual jobsite conditions. 5

The basis for, and much of the content, of this Technical Data Sheet was taken from the outstanding resource, Concrete Floors and Moisture by Howard Kanare and is available for purchase from the Portland Cement Association at www.cement.org. Please refer to LATICRETE TDS 166 LATICRETE and Moisture Vapor Emission Rate, Relative Humidity and Moisture Testing of Concrete for more information. Technical Data Sheets are subject to change without notice. For latest revision, check our website at www.laticrete.com TDS 183.doc R 6 November 2017 6