SECTION 07 72 36 (1995-07725) JL Fire Vents - Guide Submittal / Specifications PART 1: GENERAL 1.01 RELATED DOCUMENTS A. Conditions of the Contract and portions of Division One of this Project Manual apply to this Section as though repeated herein. 1.02 SUMMARY Select one or more of the following subparagraphs as required by the Project. A. Section Includes: 1. FM Approved/UL Listed Double Leaf Fire Vent. 2. FM Approved Double Leaf Domed Fire Vent. 3. Gravity Ventilator Curb Mounted Fire Vent. 4. Domed Fire Vent. 1.03 SUBMITTALS A. Product Data: For each type of fire vent indicated. Include manufacturer's model number and accessories and requirements for roughing-in dimensions. 1.04 DELIVERY, STORAGE AND HANDLING A. Packing, Shipping, Handling and Unloading: Deliver fire vent as a factory assembled unit in manufacturer s original packaging. B. Store materials in a dry, protected, well-vented area. The contractor shall thoroughly inspect product upon receipt and report damaged material immediately to delivering carrier and note such damage on the carrier s freight bill of lading. PART 2: PRODUCTS 2.01 MANUFACTURER A. J L Industries, Incorporated 4450 West 78th Street Circle Bloomington, MN 55435 Telephone: (952) 835-6850/(800) 554-6077 FAX: (952) 837-1222 WEB: JLindustries.com 2.02 MANUFACTURED UNITS A. FM Approved/UL Listed Double Leaf Fire Vent. Select one or more of the following for each FM approved/ul listed double leaf fire vent size. If more than one size is required for the project, identify each type on a schedule located on the drawings and identify each type in the specification section. Custom sizes are available.
1. Model: UFV-1; 48 inches by 48 inches clear opening. 2. Model: UFV-2; 48 inches by 72 inches clear opening. 3. Model: UFV-3; 48 inches by 90 inches clear opening. 4. Model: UFV-4; 48 inches by 96 inches clear opening. 5. Model: FFV-1; 48 inches by 48 inches clear opening. 6. Model: FFV-2; 48 inches by 72 inches clear opening. 7. Model: FFV-3; 48 inches by 90 inches clear opening. 8. Model: FFV-4; 48 inches by 96 inches clear opening. 9. Model: FFV-5; 60 inches by 60 inches clear opening. 10. Model: FFV-6; 60 inches by 96 inches clear opening. 11. Model: FFV-7; 60 inches by 120 inches clear opening. 12. Model: FFV-8; 60 inches by 144 inches clear opening. 13. Model: FFV-9; 66inches by 144 inches clear opening. 14. Model: FFV-10; 72 inches by 72 inches clear opening. 15. Characteristics: a. Curbs and Curb Frame: 14 gauge galvanized steel; fully welded; gasketed; insulated. b. Covers: 11 gauge aluminum with heavy gauge 3/16 inch aluminum pivot hinges; insulated. c. Finish: Factory primed. Higher temperature fusible links are available upon request. d. Fusible Link: 165 F; UL listed. e. Drives: Torsion springs. f. Speed Control: Shock absorbers. g. Manual Operation: Interior and exterior pull handles. B. FM Approved Double Leaf Domed Fire Vent. Select one or more of the following for each FM approved double leaf domed fire vent size. If more than one size is required for the project, identify each type on a schedule located on the drawings and identify each type in the specification section. Custom sizes are available. 1. Model: FDFV-1; 48 inches by 48 inches clear opening. 2. Model: FDFV-2; 48 inches by 72 inches clear opening.
3. Model: FDFV-3; 48 inches by 90 inches clear opening. 4. Model: FDFV-4; 48 inches by 96 inches clear opening. 5. Model: FDFV-5; 60 inches by 60 inches clear opening. 6. Model: FDFV-6; 60 inches by 96 inches clear opening. 7. Model: FDFV-7; 72 inches by 72 inches clear opening. 8. Characteristics: a. Curbs and Curb Frame: 14 gauge galvanized steel; fully welded; gasketed; insulated. b. Covers: 11 gauge aluminum with heavy gauge 3/16 inch aluminum pivot hinges; insulated. c. Dome Frame: 0.072 inch aluminum with self-contained sloping condensation and weepage gutter. d. Dome: One piece [clear] [translucent] acrylic dome. e. Finish: Factory primed. Higher temperature fusible links are available upon request. f. Fusible Link: 165 F; UL listed. g. Drives: Torsion springs. h. Speed Control: Shock absorbers. i. Manual Operation: Interior and exterior pull handles. C. [Aluminum] [Galvanized Steel] Gravity Ventilator Curb Mounted Fire Vent. Select one or more of the following for each gravity ventilator curb mounted fire vent size. If more than one size is required for the project, identify each type on a schedule located on the drawings and identify each type in the specification section. Custom sizes are available. The first option for each model size is fabricated from aluminum, the second option for each model size is fabricated from galvanized steel. 1. Model: [GVFVA-1] [GVFVG-1]; 48 inches by 48 inches clear opening. 2. Model: [GVFVA-2] [GVFVG-2]; 48 inches by 60 inches clear opening. 3. Model: [GVFVA-3] [GVFVG-3]; 48 inches by 72 inches clear opening. 4. Model: [GVFVA-4] [GVFVG-4]; 48 inches by 90 inches clear opening. 5. Model: [GVFVA-5] [GVFVG-5]; 48 inches by 96 inches clear opening. 6. Characteristics: a. Retaining and Curb Frame: [Aluminum] [Galvanized steel]. b. Dome Frame: Extruded aluminum with self-contained sloping condensation and weepage gutter. c. Louver Blades: [Aluminum] [Galvanized steel].
d. Dome: One piece [clear] [translucent] acrylic dome. e. Finish: Factory primed. f. Louver Height: 9 inches. g. Louver Width: 2 inches. h. Hardware: Safety stops, heavy duty 3/16 inch aluminum hinges, chrome vanadium torsion springs and lifting arms. D. [Aluminum] [Galvanized Steel] Domed Fire Vent. Select one or more of the following for each domed fire vent size. If more than one size is required for the project, identify each type on a schedule located on the drawings and identify each type in the specification section. Custom sizes are available. The first option for each model size is fabricated from aluminum, the second option for each model size is fabricated from galvanized steel. 1. Model: [DFVA-1] [DFVG-1]; 48 inches by 48 inches clear opening. 2. Model: [DFVA-2] [DFVG-2]; 48 inches by 60 inches clear opening. 3. Model: [DFVA-3] [DFVG-3]; 48 inches by 72 inches clear opening. 4. Model: [DFVA-4] [DFVG-4]; 48 inches by 90 inches clear opening. 5. Model: [DFVA-5] [DFVG-5]; 48 inches by 96 inches clear opening. 6. Characteristics: a. Retaining and Curb Frame: [Aluminum] [Galvanized steel]. b. Dome Frame: 0.070 inch extruded aluminum with self-contained sloping condensation and weepage gutter. c. Dome: One piece [clear] [translucent] acrylic dome. d. Finish: Factory primed. e. Hardware: Safety stops, heavy duty 3/16 inch aluminum hinges, chrome vanadium torsion springs and lifting arms. E. [Aluminum] [Galvanized Steel] Fire Vent. Select one or more of the following for each fire vent size. If more than one size is required for the project, identify each type on a schedule located on the drawings and identify each type in the specification section. Custom sizes are available. The first option for each model size is fabricated from aluminum, the second option for each model size is fabricated from galvanized steel. 1. Model: [FVA-1] [FVG-1]; 48 inches by 48 inches clear opening. 2. Model: [FVA-2] [FVG-2]; 48 inches by 60 inches clear opening. 3. Model: [FVA-3] [FVG-3]; 48 inches by 72 inches clear opening. 4. Model: [FVA-4] [FVG-4]; 48 inches by 90 inches clear opening. 5. Model: [FVA-5] [FVG-5]; 48 inches by 96 inches clear opening.
6. Characteristics: a. Lid, Curb and Curb Frame: [Aluminum] [Galvanized steel]. b. Hardware: Safety cable, heavy duty 3/16 inch aluminum hinges, chrome vanadium torsion springs and lifting arms. PART 3: EXECUTION 3.01 EXAMINATION A. Examine areas and conditions affecting installation. Do not proceed with installation until unsatisfactory conditions have b 3.02 INSTALLATION A. Install system level and plumb, and in accord with manufacturer s written instructions, original design and referenced standards. 3.03 ADJUSTING A. Adjust for proper operation. Replace any parts that prevent the fire vent from operating properly. 3.04 CLEANING A. Remove all debris caused by installation of the fire vent. Clean all exposed surfaces to as fabricated condition and appearance. 3.05 PROTECTION A. Provide protection of the completed installation until completion of the project. Repair any damage at no additional cost. 3.06 SCHEDULES If more than one type of fire vent is required, provide a schedule similar to the following example below. Use the corresponding type designations here and on the drawings, A. Type 1: [Describe by model]. B. Type 2: [Describe by model]. C. Type 3: [Describe by model].