Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

Similar documents
CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

This is a repository copy of Application of a Passive Cooling Wind Catcher within the Built Environment: Numerical and Experimental Analysis.

The Nottingham eprints service makes this work by researchers of the University of Nottingham available open access under the following conditions.

Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher.

This is a repository copy of A study of passive ventilation integrated with heat recovery.

Numerical Investigation of the Air Flow in a Novel PV-Trombe Wall Based on CFD Method

This is a repository copy of The influence of structural morphology on the efficiency of building integrated wind turbines (BIWT).

Changing the geometry of the Wind Tower and its Influence on Aerodynamic Behavior and Natural Ventilation

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Computational and field test analysis of thermal comfort performance of user-controlled thermal chair in an open plan office

Numerical Simulation of Spray Cooling Gas with High Temperature and Velocity in Compressor Inter-Stage

Vipac Engineers & Scientists Ltd

ADVANCES in NATURAL and APPLIED SCIENCES

Semi-Empirical Computational Tool for Design of Air-Cooled Condensers

Numerical Analysis of the Integration of Wind Turbines into the Design of the Built Environment

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

Design and aerodynamic investigation of dynamic architecture

Numerical Investigation of Air Flow and Temperature Distribution in a Trombe Wall System: A CFD Study

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

BOUNDARY SETTING IN SIMULATING GREENHOUSE VENTILATION BY FLUENT SOFTWARE

Numerical Study on the Effects of Flue-Gas Inlet Type for the Flue-Gas-Desulfurization Wet Scrubber

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Three-Dimensional Numerical Simulation of a Model Wind Turbine

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

Indoor Airflow Modeling and Data Assimilation. Hengye Yang Ph.D. Student, LISC Dec. 21, 2018

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

COMPUTATIONAL ANALYSIS ON THE EFFECTS OF FAÇADE MODIFICATIONS ON WIND-DRIVEN NATURAL VENTILATION PERFORMANCE OF A SINGLE-CELL ROOM

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K.

Wind driven flow through building openings

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings

Using Experimental Measurements of the Concentrations of Carbon Dioxide for Determining the Intensity of Ventilation in the Rooms

An Investigation of GDL Porosity on PEM Fuel Cell Performance

Numerical Analysis of Solar Updraft Tower with Solar Load applied to Discrete Ordinate Model

WIND FLOW IN THE RECESSED CAVITIES OF A TALL

Heat transfer enhancement in fire tube boiler using hellically ribbed tubes

INVESTIGATION OF FLOW CHARACTERISTICS OF HELLER-TYPE COOLING TOWERS WITH DIFFERENT COOLING DELTA ANGLES

Targeting and Design of Evacuated-Tube Solar Collector Networks

Numerical analysis of eccentric orifice plate using ANSYS Fluent software

CFD ANALYSIS OF SOLAR HEATER WATER PIPE WITH DIFFERENT INCLINATION

Thermal Management of Densely-packed EV Battery Set

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

VI.3 Application of Computational Fluid Dynamics to Simulate the Behaviour of Fluids inside Vertical Stack of Building Drainage System

Design and development of an Earth Air Tube Heat Exchanger

H POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH. Colman C.C. Wong and Chun-Ho Liu*

CFD Simulation Studies on Integrated Approach of Solar Chimney and Earth Air Tunnel Heat Exchanger for Building Space Conditioning

A numerical investigation of the influence of wind on multiple short natural draft dry cooling towers

EasyChair Preprint. Resolving the Non-Productive Periods of Solar Chimney by Integrating with Waste-to-Energy Plant

NUMERICAL SIMULATION OF AIR NATURAL CIRCULATION AND THERMAL RADIATION IN PASSIVE CONTAINMENT COOLING SYSTEM

Numerical Simulation of the Thermal Performance of a Dry Storage Cask for Spent Nuclear Fuel Chi-Ming Lai, University Distinguished Professor Departme

By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY. May ALDEN RESEARCH LABORATORY, INC. 30 Shrewsbury Street Holden, MA 01520

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas

APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

FLUID STRUCTURE INTERACTION MODELLING OF WIND TURBINE BLADES BASED ON COMPUTATIONAL FLUID DYNAMICS AND FINITE ELEMENT METHOD

Analysis of Lecturing Room using Computational Fluid Dynamics Natural and Forced Ventilation

CFD Study of Biomass Cooking Stove using Autodesk Simulation CFD to Improve Energy Efficiency and Emission Characteristics

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment

CFD Modelling of an Aerosol Exposure Chamber for Medical Studies G. Manenti, M. Derudi, G. Nano, R. Rota

MODERN PRACTICES FOR MEASUREMENT OF GAS PATH PRESSURES AND TEMPERATURES FOR PERFORMANCE ASSESSMENT OF AN AXIAL TURBINE

Numerical Investigation of Swirl's Effects in the Outer Annulus of a Reverse-flow Gas Turbine Combustor

Stress Study on Different Designs of Ceramic High Temperature Heat Exchangers

Available online at ScienceDirect. Energy Procedia 61 (2014 )

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Cold Plane Innovative Method for Humidity Condition Control

Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies

ICMIEE-PI Experimental and Numerical Investigation of an Air to Water Heat Exchanger

A TRNSYS-FLUENT COUPLED SIMULATION OF THE THERMAL ENVIRONMENT OF AN AIRPORT TERMINAL SPACE WITH A MIXING AND DISPLACEMENT AIR CONDITIONING SYSTEM

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Design and distribution of air nozzles in the biomass boiler assembly

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

u and Yoshie (2013) investigate the effect of building geometry and they revealed that the ventilation efficiency strongly depended on the level of bu

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

FAST EVALUATION OF SUSTAINABLE HEATING AND COOLING STRATEGIES FOR SOLAR HOMES WITH INTEGRATED ENERGY AND CFD MODELING

Evaluating the Flow Inside of Portable Wind Tunnels for Odour Measurements

Numerical Simulation of the Aerodynamic Performance of a H-type Wind Turbine during Self-Starting

Utilizing Solar Energy in Order to Reduce Energy Loads of Building

Shell Side CFD Analysis of a Model Shell-and-Tube Heat Exchanger

The Pennsylvania State University. The Graduate School. Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

ENVIRONMENT DEVELOPMENT OF A CFD MODEL FOR IMPROVEMENT OF AN INTERIOR ENVIRONMENT IN METALLURGICAL INDUSTRIES: MODELING

Computational Modeling of Counter Flow Heat Exchanger for LMTD Analysis

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Sustainable Designed Air-Conditioned Mosque For Thermal Comfort

BUILDING INTEGRATED VENTILATION SYSTEMS MODELLING AND DESIGN CHALLENGES

Numerical Analysis of Two-phase Flow and Heat Transfer in External Cyclic Purification Hot-dip Galvanizing Bath

ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Analysis on the influence of rotational speed to aerodynamic performance of vertical axis wind turbine

Heat Integration Across Plants Considering Distance Factor

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

Selecting nozzle arrangement of a chimney tower to reduce temperature and to increase entrainment mass flow

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Transcription:

A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 34, 2013 Guest Editors: Neven Duić, Petar Sabev Varbanov Copyright 2013, AIDIC Servizi S.r.l., ISBN 978-88-95608-25-9; ISSN 1974-9791 The Italian Association of Chemical Engineering Online at: www.aidic.it/cet DOI: 10.3303/CET1334008 Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers John Kaiser Calautit a, Ben Richard Hughes a, Saud Ghani*,b a School of Civil Engineering, University of Leeds, Leeds, LS2 9JT, United Kingodm b Department of Industrial and Mechanical Engineering, Qatar University, Doha, Qatar cnjksc@leeds.ac.uk The purpose of this study is to incorporate heat transfer devices inside the passive terminal of a wind tower unit, highlighting the potential to achieve minimal restriction in the external air flow stream while ensuring maximum contact time, thus optimising the cooling duty of the device. Computational Fluid Dynamics (CFD) was used to develop a numerical model of a wind tower system and simulate the air flow pattern around and through the device to the test room. Results have indicated that the average internal airflow rate was reduced following the integration of the vertical and horizontal heat transfer device configuration, reductions of 4.11 % and 8.21 % was obtained respectively. Furthermore, the proposed cooling system was capable of reducing the air temperatures by up to 15 K. The technology presented here is subject to IP protection under the QNRF funding guidelines. 1. Introduction In hot and arid regions such as the Middle East, there is a large dependence on electricity to run mechanical systems for providing ventilation and thermal comfort. During the summer months more than 50 % of the electrical demand comes from HVAC loads (Lombard et al., 2008). As stated by (WBCSD, 2011), commercial and residential buildings accounts for almost 40 % of the world energy usage. The resulting carbon emissions are substantially more than those in the transportation sector. This represents a significant opportunity for reducing the buildings energy consumption and greenhouse gas emissions. Natural ventilative methods such as wind towers are increasingly being employed in new buildings to reduce the energy consumption and carbon foot print. Wind towers have been in existence in various forms for centuries as a non-mechanical means of providing indoor ventilation, energy prices and climate change agendas have refocused engineers and researchers on the low carbon credentials of modern equivalents. Conventional and modern wind towers architecture can be integrated into the designs of new buildings, to provide thermal comfort without the use of electrical energy (Hughes et al., 2011). A wind tower system is divided by partitions to create different shafts. One of the shafts functions as inlet to supply the wind and the other shafts works as outlet to extract the warm and stale air out of the living space as shown in Figure 1 (Jones and Kirby, 2008). Experimental and numerical studies (Hughes and Cheuk-Ming, 2011) have shown that wind driven force is the primary driving force for the wind tower device, providing 76 % more indoor ventilation than buoyancy driven forces. The cooling capabilities of wind towers which depend mainly on the structure design itself are inadequate. A recent study by (Calautit et al., 2012) investigated the ventilation and thermal performance of a row house model integrated with a traditional and modern four-sided wind tower. Both systems were capable of supplying the required internal air supply rates however the reductions in internal temperature were insignificant (1-2 K). Therefore it is essential to cool the air in order to reduce the building heat load and improve the thermal comfort of its occupants during the summer months (Kalantar, 2009). Traditional wind Please cite this article as: Calautit J. K., Hughes B. R., Ghani S., 2013, Numerical investigation of the integration of heat transfer devices into wind towers, Chemical Engineering Transactions, 34, 43-48 DOI:10.3303/CET1334008 43

tower systems were integrated with evaporative cooling devices to increase its thermal performance. The induced warm air is passed through cooling tubes or moist surfaces, which allows for the cooling of the air stream before entering the living spaces (Bouchahm, 2011). However, the addition of these cooling devices may reduce the air flow rate inside the channel and reduce the overall efficiency of the wind tower. Another disadvantage of this configuration is the requirement of taller towers to have sufficient contact time between the air flow and cooling surfaces (Calautit et al., 2013). (Hughes et al., 2012) reviewed different types of wind tower designs and cooling methods which have been studied using numerical CFD analysis. Furthermore, several works have also used analytical methods (Jones and Kirby, 2009), wind tunnel (Montazeri et al., 2010) and far-field testing (Hughes and Ghani, 2009) to validate the results. The good correlation between different methods of analysis suggests that the CFD techniques in use were suitable for this type of device and such have been used for the purpose of this research. Figure 1: A flow diagram representing ventilation through a multi-direction wind tower A wind tower system incorporating heat transfer devices was designed to meet to lower the internal temperatures in hot and humid condtions. Heat transfer devices were installed inside the passive terminal of the wind tower unit, highlighting the potential to achieve minimal restriction in the external air flow stream while ensuring maximum contact time, thus optimsing the cooling duty of the device. A standard roof-mounted wind tower was used as a benchmark for the comparison of the two different heat transfer device orientations. Exhaust Supply Supply Exhaust Figure 2: Wind tower systems incorporating (a) vertical HTD arrangement (b) horizontal HTD arrangement 2. CFD Setup A four-sided square wind tower with an internal diameter of 1 m and height of 1.5 m is used for the numerical analysis. The vertical HTD arrangement is identical to the standard wind tower model, the heat transfer devices are closely arranged in an x-shaped vertical pattern positioned next to the cross-dividers inside the passive terminal. A one-sided circular wind tower is used for the analysis of the horizontal heat pipe configuration, while retaining the physical parameter and standard components of the benchmark model. A total of 70 copper HTDs with an internal diameter and length of 0.015 m and 0.9 m were used in the simulation. Figure 2 displays the proposed configurations. The proposed wind tower system with the heat transfer devices is incorporated to a test room (micro climate) with the height, width, and length of 3, 6, and 6 m (Building Bulletin, 2012). An enclosure was created to represent the external wind environment (macro climate). The enclosure with a height, width, 44

and length of 8, 26, and 46 m creates a direct interface through the geometry. The enclosure (the flow domain) was set at a distance from the geometry to avoid reversed flow in the region (Mehta, 1991). A flow domain representation of the physical geometry of the wind tower design under investigation and location of set boundary conditions are shown in Figure 3. Figure 3: Schematic of a wind tower system mounted on the test room 2.1 Grid Generation The quality of the mesh has important implication on the convergence and the level of accuracy of the achieved results (Chung, 2002). The size of the mesh element was extended smoothly to resolve the sections with high gradient mesh and to improve the accuracy of the results of the temperature fields. A non-uniform mesh was applied to the volumes of the computational model. The mesh arrangement consisted of 344,643 tetrahedral non-uniform mesh elements with 70,435 nodes, as shown in Figure 4. Figure 4: Flow domain representation of the physical geometry of the wind tower design under investigation and location of set boundary conditions 45

2.2 Boundary Conditions The basic assumptions for the CFD simulation include a three-dimensional, fully turbulent, and incompressible flow. The CFD code uses the Finite Volume Method (FVM) approach and employs the Semi-Implicit Method for Pressure-Linked Equations (SIMPLE) velocity pressure coupling algorithm with the second order upwind discretization as recommended in the literature (Saffari and Hosseinnia, 2009). The governing equations are the Navier-Stokes and energy equation which will not be repeated here but are available in detail in (Fluent, 2006). The turbulent nature of the flow was modelled by the standard k- epsilon as suggested by (Elmualim, 2006). This technique is well established in the field of research on airflow and temperature distribution in structures (Park et al., 2001). The geometry (micro climate) was modelled as an open structure with openings on the windward and leeward side which allows the incoming air to pass through it, in order to simulate and analyse the air flow pattern inside the structure. The enclosure consists of a velocity inlet (operating velocity) at the left hand side of the enclosure, and a pressure outlet (atmospheric pressure) on the opposing boundary wall of the enclosure as shown in Figure 4. The boundary conditions for the CFD model are shown in Table 1. Table 1: CFD Model Boundary Conditions Inlet velocity (m/s) Inlet temperature Pressure outlet 0.1-4 m/s 310 K Atmospheric Time Steady State Traditional evaporative cooling wind tower Injected water temperature (K) 293 Injected water mass flow rate (kg/s) 0.05 Heat transfer devices integrated wind tower HTD wall temperature (K) 293 2.3 Grid Adaptation Grid adaptation was used to validate the programming and computational operation of the computational model. The numerical grid was refined and locally enriched using the hp-method grid adaptation technique (Hughes and Ghani, 2009). This procedure of evaluation requires the use of different mesh sizes or higher order approximations by the use of a posterior error estimates. The grid was evaluated and refined until the posterior estimate error becomes insignificant between the number of nodes and elements, computational iterations and the posterior error indicator. Figure 5 shows that at 1,400,000 elements the percentage error between the grid refinements was at its lowest in the last two steps. Figure 5: Comparison of solutions from various grid adaptation methods. The variables are the average velocity at the inlet and outlet of the wind towers and interior of the test room 3. Results and Discussion Figure 6a display the velocity contour of the cross-sectional plane in the test room model. From the illustration it is observed that the air flow entering the opening of the uni-directional wind tower is directed down to the enclosed space through the floor diffuser. The airflow is accelerated as it shears across the walls and floor of the structure, reaching a maximum velocity of 3 m/s. The air stream is circulated inside the structure and exits the opening located on the other end. Figure 6b depicts the simulated temperature 46

distribution inside the test room with a uni-directional wind tower incorporating the evaporative cooling method. Temperature reduction of 12.6 K is obtained from the CFD analysis. Figure 6: Velocity contour lines of a cross sectional plane in the test room with (a) Temperature distributions within the test room with the evaporative cooling tower (b) Figure 7 shows the flow comparisons between the air supply rates as recommended by government regulations (Building Regulations, 2000) for a room of 20 occupants based on air supply per occupant, and the air supply rates as calculated through the use of the CFD modelling of benchmark four-sided wind tower, vertical heat pipe configuration, and horizontal heat pipe configuration. Each of the wind tower systems did not meet this recommendation for an external wind velocity of 1m/s; however, for each of the following external wind velocities, each wind tower system surpasses the recommendation. Figure 7: Comparison of the air supply rates of the wind tower configurations at various external speeds Figure 8 shows the contour of static temperatures inside the test room with a wind tower incorporating the vertical and horizontal HTD arrangement. Air temperature reduction is observed inside the microclimate, average temperature of 296.2 K and 295.8 K are obtained inside the models, which is 11-12 % lower compared to the wind tower employing traditional evaporative cooling devices (Figure 6b). 4. Conclusions A wind tower system involving heat transfer devices was designed to lower the internal temperatures. A numerical analysis was carried out using CFD software to simulate and analyse the air flow pattern, pressure coefficient and temperature distribution around and through the wind tower to the test room. The work highlighted the effect of evaporative cooling and heat transfer devices on the thermal performance of the passive ventilation device. The proposed cooling system was capable of reducing the air temperatures by up to 15 K, depending on the configuration and operating conditions. Results have indicated that the internal airflow rate was slightly reduced following the integration of the vertical and heat pipe configuration, reductions of 4.11 % and 8.21 % were obtained from the achieved computational model. 47

Figure 8: Temperature distributions inside the test room with a commercial wind tower incorporating the vertical HTD arrangement (a) and horizontal HTD arrangement (b). 5. Acknowledgement This paper was made possible by a NPRP grant from the Qatar National Research Fund (A member of the Qatar Foundation). The statements made are solely the responsibility of the authors. NPRP 09-138-2-059. The technology presented is subject to IP protection under the QNRF funding guidelines. References ANSYS, 2006, Fluent User Guide <www.ansys.com>, Accessed 01.12.2011. Bouchahm Y., Bourbia F., Belhamri A., 2011. Performance analysis and improvement of the use of wind tower in hot dry climate, Renewable Energy, 36, 898-906. Building Regulations, 2000. Approved Document F1A: Means of Ventilation 2010, NBS: London, UK. Building Bulletin, 2011. Ventilation and indoor air quality in schools Market <www.education.gov.uk>, Accessed 12.09.2011. Calautit J.K., Hughes B.R., Ghani S.A., 2012. A numerical investigation into the feasibility of integrating green building technologies into row houses in the Middle East, Architecture Science Review, 1-18. Calautit J.K., Chaudhry H.N., Hughes B.R., Ghani S.A., 2013. Comparison between evaporative cooling and a heat pipe assisted thermal loop for a commercial wind tower in hot and dry climatic conditions, Applied Energy, 101, 740-755. Chung T.J., 2002. Computational fluid dynamics, Cambridge University Press, Second Edition, Cambridge, UK, 15-21. Elmualim A., 2006. Effect of damper and heat source on wind catcher natural ventilation performance, Energy and Buildings, 38, 939-948. Hughes B.R., Calautit J.K., Ghani S.A., 2012. The Development of Commercial Wind Towers for Natural Ventilation: a review, Applied Energy, 92, 606-627. Hughes B.R., Cheuk-Ming M., 2011. A Study of Wind and Buoyancy Driven Flows Through Commercial Wind Towers, Building and Environment, 43, 1784-1791. Hughes B.R. and Ghani S.A., 2010. A numerical investigation into the effect of Windvent louvre external angle. Building and Environment, 45, 1025-1036. Jones B., Kirby R., 2009. Quantifying the performance of a top down natural ventilation Windcatcher, Building and Environment, 44, 1925-1934. Kalantar V., 2009. Numerical simulation of cooling performance of wind tower (Baud-Geer) in hot and arid region, Renewable Energy, 34, 246-254. Lombard L., Ortiz J., Pout C., 2008. A review on buildings energy consumption information, Energy and Buildings, 40, 394-398. Mehta U., 1991. Some aspects of uncertainty in computational fluid dynamics results, Journal of Fluids Engineering, 113, 539-543. Montazeri J., Montazeri F., Azizian R., Mostafavi S., 2010. Two-sided wind catcher performance evaluation using experimental, numerical and analytical modelling, Renewable Energy, 35,1424-35. Saffari H., Hosseinnia S., 2009. Two-phase Euler-Lagrange CFD simulation of evaporative cooling in a Wind Tower, Energy and Buildings, 41, 991-1000. Park H., Fazio P., Holland D., 2001. The effect of location of a convective heat source on displacement ventilation: CFD study. Building and Environment, 36, 883-889. WBCSD, 2011. Enery Efficiency in Buildings: Transforming the Market <www.wbcsd.org>, Accessed 10.09.2011. 48