SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

Similar documents
SECTION TRANSLUCENT PANEL SYSTEM

SECTION FIBERGLASS SANDWICH PANEL ASSEMBLIES

SECTION FIBERGLASS SANDWICH PANEL SKYLIGHTS

1.2 RELATED REQUIREMENTS

Job No Division 07 Section "Sheet Metal Flashing and Trim" for metal flashings installed at perimeters of assemblies.

LOG COLLEGE MIDDLE SCHOOL

PART 1 GENERAL 1.1 SECTION INCLUDES A. Translucent sandwich panel window wall systems utilizing fiber reinforced thermoset profiles.

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.

SECTION Structured Polycarbonate Panel Assemblies. Series 3500 BPC System with 40mm Tongue and Groove

SECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS

SPECIFICATIONS FOR. CEI Composite Materials, LLC Featuring R4000 Rear Back Ventilated Rainscreen System. Section Aluminum Composite Panels

SECTION ALUMINUM WINDOWS

SoCal Dynamic Dome Skylight SECTION UNIT SKYLIGHTS

Series B450 Guide Specification

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

SECTION STAINLESS STEEL WALL PANELS

SECTION / METAL FRAMED SKYLIGHTS (TRANSLUCENT PANEL SYSTEM)

Corium Brick Rainscreen System Specifications

Heavy Commercial / Architectural Projected Windows Series L900T AW150

C. All anchors, brackets, and hardware attachments necessary to complete the specified structural assembly, when included within project scope.

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION

COLLEGE OF STATEN ISLAND

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>.

North Hanover Township School District North Hanover Township, New Jersey

A. Pre-Installation Conference: Conduct conference at [project site] <insert location>.

Signature Series 5 Lap SECTION ALUMINUM WINDOWS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS. A. This Section includes fixed and operable aluminum-framed windows.


CS-100 Guide Specifications

P R O D U C T - S P E C

Series 4900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction

SECTION ALUMINUM WINDOWS

SILVER LINE BUILDING PRODUCTS. Series 1700 Heavy Commercial Aluminum Double Hung. HC65 48 x84 / HC50 60 x96 Replacement Window

TRUMAN STATE UNIVERSITY GREENWOOD SCHOOL WINDOW REPLACEMENT

Series 2900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction

SECTION MANUFACTURED ROOF EXPANSION JOINTS

Division 8 Section "Flush Wood Doors" for louvers in wood doors. Division 15 Sections for louvers that are a part of mechanical equipment.

SILVER LINE BUILDING PRODUCTS

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

A. Section includes conventionally glazed aluminum curtain walls installed as stick assemblies.

SECTION METAL ROOF AND SOFFIT PANELS

SECTION / METAL FRAMED SKYLIGHTS

SECTION EXTERIOR GRILLS AND SCREENS

SERIES STB30 STEEL FIXED THERMAL BREAK DETENTION WINDOWS SECTION 08651

SECTION ALUMINUM GLASS FLOOR SKYLIGHT SYSTEMS

Alply CLASSIC WALL Architectural Insulated Panel Wall System

PART 1 / GENERAL SECTION ALUMINUM PLATE PANEL SYSTEM. ALPLY Insulated Panels. Alply TECH WALL Aluminum Plate System 2002

SERIES SA30 STEEL/ALUMINUM FIXED DETENTION WINDOWS SECTION 08651

SECTION C. Water Infiltration: Provide manufactured cupolas and dormers that do not allow water infiltration to cupola and dormer interiors.

FIXED SERIES 6200 AAMA/WDMA/CSA 101/I.S.2/A Structural Performance: Thermal Break: Main Frame Depth: 3 1/4. Glazing Thickness (Maximum): 1

SECTION FOLDING ALUMINUM FRAMED WALL SYSTEM

Guide Specifications ADP Series SECTION SHEET METAL ROOFING

THE EDGE SYSTEMS 1. TRANSLUCENT GLAZING SYSTEM Guide Specification PART 1 GENERAL 1.01 SECTION INCLUDES

Guideline Specifications

SECTION METAL FRAMED SKYLIGHTS

EC-250 AAMA Pressure-Equalized Aluminum Plate Rainscreen East Coast Metal System

Page 1 of 5

PART 1 - GENERAL. Pinnacle Glass Glazed Skylights SECTION RELATED DOCUMENTS

08620 UNIT SKYLIGHTS Tufflite double polycarbonate glazed Frb

NRM-7000 Guide Specifications

PRODUCT SPECIFICATION UNITIZED CURTAIN WALL THERMALLY BROKEN ALUMINUM AWNING/ FIXED WINDOW

Architectural Wall Products Guide Specifications

SECTION PRE-ENGINEERED EXTRUDED ALUMINUM DECKING WALKWAY COVERS SPECIFICATION

SECTION (10705) EXTERIOR SUN CONTROL DEVICES

SECTION ALUMINUM-FRAMED ENTRANCES AND CURTAINWALL

A. Omega-Lite aluminum-faced composite panels, air and vapor barrier, attachments and sealants.

FL200 13/4 x41/2 GUIDE SPECIFICATION. Non-Thermal Storefront

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1

PRODUCT SPECIFICATION SERIES 4500T THERMALLY BROKEN ALUMINUM SLIDING BALCONY DOOR

SECTION ALUMINUM STORM WINDOWS

SECTION ALUMINUM CURTAIN WALL PART 1 - GENERAL

SECTION EXTERIOR SOLID PHENOLIC RAINSCREEN PANELS

ST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

First Class Building Products, Inc.

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION METAL ROOF PANELS

Phenolic Exterior Wall Cladding

NOTICE TO BIDDERS OF RECORD

SECTION COLD-FORMED METAL TRUSSES

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION / TRANSLUCENT WALL AND ROOF ASSEMBLIES (WINDOW WALL SYSTEMS)

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.

T700 SERIES(AW50)-Impact (Formerly 8050 series) SINGLE HUNG 3 1/4 FRAME DEPTH (SIDE LOAD)

Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS

SERIES 8510 AW-PG85-FW FIXED WINDOW

FL550T 21/2 x5. GUIDE SPECIFICATION Series FL550T Thermal (21/2 x 5 ) Impact-Resistant Storefront. Thermal Impact-Resistant Storefront

SPECIFICATIONS SECTION 08600

SECTION STRUCTURAL INSULATED PANELS

SECTION PREHUNG WOOD DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

Guide Specification for Pre-Engineered Skylight System. A. Engineering, design and drafting of the entire skylight system.

Product Guide Specification

SECTION mm METAL COMPOSITE MATERIAL (MCM) RAINSCREEN SYSTEM SPECIFICATION

SERIES 5100 AW-PG100-FW FIXED WINDOW

SECTION METAL WALL PANEL SYSTEM

SECTION CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SOTA THERMO 3 SERIES SPECIFICATION FOR PREGLAZED & UNITIZED THERMO 3 CURTAINWALL SYSTEM

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

Product Guide Specification

Transcription:

PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls. 2. Aluminum installation system. 3. Aluminum flashing. B. Related Sections: 1. Masonry: Division 4. 2. Structural steel: Division 5. 3. Wood blocking: Division 6. 4. Joint sealants: Division 7. 5. Glazing for endwalls: Elsewhere in Division 8. 1.2 SUBMITTALS A. Product Data: Submit manufacturer's product data. Include construction details, material descriptions, profiles and finishes of components. C. Shop Drawings: Submit shop drawings. Include elevations and details. D. Color Charts: Submit manufacturer's color charts showing the full range of colors available for factoryfinished aluminum. E. Samples: Submit samples for each exposed finish required, in same thickness and material indicated for the work and in size indicated below. If finishes involve normal color variations, include sample sets consisting of two or more units showing the full range of variations expected. 1. Sandwich panels: 14-inch x 28-inch units. 2. Factory finished aluminum: 5 inch long sections. F. Certificates: Submit Installer Certificate, signed by installer, certifying compliance with project qualification requirements. G. Product Reports: Submit product reports from a qualified independent testing agency indicating each type and class of panel system complies with the project performance requirements, based on comprehensive testing of current products. Previously completed reports will be acceptable if for current manufacturer and indicative of products used on this project. 14.14.001 SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 084523-1

1 Reports required are: a. International Building Code Evaluation Report. b. Flame Spread and Smoke Developed (UL 723) - Submit UL Card. c. Burn Extent (ASTM D 635). d. Color Difference (ASTM D 2244). e. Impact Strength (UL 972). f. Bond Tensile Strength (ASTM C 297 after aging by ASTM D 1037). g. Bond Shear Strength (ASTM D 1002). h. Beam Bending Strength (ASTM E 72). i. Fall Through Resistance (ASTM E 661). j. Insulation U-Factor (NFRC 100). k. NFRC System U-Factor Certification (NFRC 700). 1. Solar Heat Gain Coefficient (NFRC or Calculations). m. Condensation Resistance Factor (AAMA 1503). n. Air Leakage (ASTM E 283). o. Structural Performance (ASTM E 330). p. Water Penetration (ASTM E 331). q. Class A Roof Covering Burning Brand (ASTM E 108). r. Daylight Autonomy. 1.4 QUALITY ASSURANCE A. Manufacturer's Qualifications: 1. Material and products shall be manufactured by a company continuously and regularly employed in the manufacture of specified materials for a period of at least ten consecutive years and which can show evidence of those materials being satisfactorily used on at least six projects of similar size, scope and location. At least three of the projects shall have been in successful use for 10 years or longer. 2. Panel system must be listed by an ANSI accredited Evaluation Service, which requires quality control inspections and fire, structural and water infiltration testing of sandwich panel systems by 14.14.001 SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 084523-2

an accredited agency. 3. Quality control inspections shall be conducted at least once each year and shall include manufacturing facilities, sandwich panel components and production sandwich panels for conformance with AC 177 "Translucent Fiberglass Reinforced Plastic (FRP) Faced Panel Wall, Roof and Skylight Systems" as issued by the ICC-ES. B. Installer's Qualifications: Installation shall be by an experienced installer, which has been in the business of installing specified panel systems for at least two consecutive years and can show evidence of satisfactory completion of projects of similar size, scope and type. 1.5 PERFORMANCE REQUIREMENTS A. The manufacturer shall be responsible for the configuration and fabrication of the complete panel system. 1. When requested, include structural analysis data signed and sealed by the qualified professional engineer responsible for its preparation. 2. Standard panel system shall have less than 0.01 cfm/ft 2 air leakage by ASTM E 283 at 6.24 PSF (50 mph) and no water penetration by ASTM E 331 at 15 PSF; and structural testing by ASTM E 330. 3. Structural Loads: Provide skylight system capable of handling the following loads, with L/60 deflection: a. 30 PSF live load. b. 30 PSF snow load. c. 30 PSF wind load. d. 0 PSF drift load. 1.6 DELIVERY, STORAGE AND HANDLING A. Deliver panel system, components and materials in manufacturer's standard protective packaging. B. Store panels on the long edge; several inches above the ground, blocked and under cover in accordance with manufacturer's storage and handling instructions. 1.7 WARRANTY A. Submit manufacturer's and installer's written warranty agreeing to repair or replace panel system work, which fails in materials or workmanship within 5 years of the date of delivery. Failure of materials or workmanship shall include leakage, excessive deflection, deterioration of finish on metal in excess of normal weathering and defects in accessories, insulated translucent sandwich panels and other components of the work. PART 2 - PRODUCTS 14.14.001 SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 084523-3

2.1 MANUFACTURER A. The approved manufacturer and basis of design are for products manufactured by Kalwall Corporation. Other manufacturers may submit bids for their products/systems provided they comply with all of the performance requirements of this specification and submit evidence thereof. 2.2 PANEL COMPONENTS A. Face Sheets: 1. Translucent faces: Manufactured from glass fiber reinforced thermoset resins, formulated specifically for architectural use. a. Thermoplastic (e.g. polycarbonate, acrylic) faces are not acceptable. b. Face sheets shall not deform, deflect or drip when subjected to fire or flame. 2. Interior face sheets: a. Flame spread: Underwriters Laboratories (UL) listed, which requires periodic unannounced retesting, with flame spread rating no greater than 50 and smoke developed no greater than 250 when tested in accordance with UL 723. b. Burn extent by ASTM D 635 shall be no greater than 1 inch. 3. Exterior face sheets: a. Color stability: Full thickness of the exterior face sheet shall not change color more than 3 CIE Units DELTA E by ASTM D 2244 after 5 years outdoor South Florida weathering at 5 degrees facing south, determined by the average of at least three white samples with and without a protective film or coating to ensure long-term color stability. Color stability shall be unaffected by abrasion or scratching. b. Strength: Exterior face sheet shall be uniform in strength, impenetrable by hand held pencil and repel an impact minimum of 70 ft. lbs. without fracture or tear when impacted by a 3-1/4- inch diameter, 5 lb. free-falling ball per UL 972. 4. Appearance: B. Grid Core: a. Exterior face sheets: Smooth 0.070 inch thick and super-weathering Crystal in color. b. Interior face sheets: Smooth 0.045 inch thick and Crystal S-171 in color. c. Face sheets shall not vary more than ± 10% in thickness and be uniform in color. 1. Thermally broken I-beam grid core shall be of 6063-T6 or 6005-T5 alloy and temper with provisions for mechanical interlocking of muntin-mullion and perimeter. Width of I-beam shall be no less than 7/16 inch. 14.14.001 SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 084523-4

2. I-beam thermal break: Minimum 1 inch, thermoset fiberglass composite. C. Laminate Adhesive: 1. Heat and pressure resin type adhesive engineered for structural sandwich panel use, with minimum 25-years field use. Adhesive shall pass testing requirements specified by the International Code Council "Acceptance Criteria for Sandwich Panel Adhesives". 2. Minimum tensile strength of 750 PSI when the panel assembly is tested by ASTM C 297 after two exposures to six cycles each of the aging conditions prescribed by ASTM D 1037. 3. Minimum shear strength of the panel adhesive by ASTM D 1002 after exposure to four separate conditions: a. 50% Relative Humidity at 680 F: 540 PSI. b. 1820 F: 100 PSI. c. Accelerated Aging by ASTM D 1037 at room temperature: 800 PSI. d. Accelerated Aging by ASTM D 1037 at 1820 F: 250 PSI. 2.3 PANEL CONSTRUCTION A. Provide sandwich panels of flat fiberglass reinforced translucent face sheets laminated to a grid core of mechanically interlocking I-beams. The adhesive bonding line shall be straight, cover the entire width of the I-beam and have a neat, sharp edge. 1. Thickness: 2-3/4 inches. 2. Light transmission: 30%. 3. Solar heat gain coefficient: 0.32. 4. Panel U-factor by NFRC certified laboratory: 2-3/4-inch thermally broken grid 0.23 "U". 5. Complete insulated panel system shall have NFRC certified U-factor of 0.31 "U". 6. Grid pattern: Nominal size 12-inch x 24-inch shoji grid pattern. B. Standard panels shall deflect no more than 1.9 inches at 30 PSF in 10 foot span without a supporting frame by ASTM E 72. C. Standard panels shall withstand 12000 F fire for minimum one hour without collapse or exterior flaming. D. Thermally broken panels: Minimum Condensation Resistance Factor of 80 by AAMA 1503 measured on the bond line. E. Skylight System: 14.14.001 SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 084523-5

1. System shall pass Class A Roof Burning Brand Test by ASTM E 108. 2. System shall meet the fall through requirements of OSHA 1910.23 as demonstrated by testing in accordance with ASTM E 661, thereby not requiring supplemental screens or railings. 2.4 BATTENS AND PERIMETER CLOSURE SYSTEM A. Closure System: 1. Extruded aluminum 6063-T6 and 6063-T5 alloy and temper clamp-tite screw type closure system. 2. Skylight perimeter closures at curbs shall be factory sealed to panels. B. Sealing tape: Manufacturer's standard, pre-applied to closure system at the factory under controlled conditions. C. Fasteners: 300 series stainless steel screws for aluminum closures, excluding final fasteners to the building. D. Finish: Manufacturer's factory applied finish, which meets the performance requirements of AAMA 2604. Color to be selected by the Architect from manufacturer's full range of standard colors. 2.5 STRUCTURAL SUPPORT A. Center Ridge Skylight: Self-supporting Center Ridge Skylight at 19 feet outside curb dimension span shall have concealed support integral with the installation system with exposed gussets at ridge. Aluminum curb cap extrusions and flashing shall be supplied by the skylight manufacturer. B. Skylight shall have gabled glass endwalls glazed with 1 inch thich tempered low E clear insulated glass (glass and glazing specified elsewhere in Division 8). PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, supporting structure and installation conditions. B. Do not proceed with panel installation until unsatisfactory conditions have been corrected. 3.2 PREPARATION A. Metal Protection: 1. Where aluminum will contact dissimilar metals, protect against galvanic action by painting contact surfaces with primer or by applying sealant or tape recommended by manufacturer for this purpose. 2. Where aluminum will contact concrete, masonry or pressure treated wood, protect against corrosion by painting contact surfaces with bituminous paint or method recommended by 14.14.001 SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 084523-6

manufacturer. 3.3 INSTALLATION A. Install the panel system in accordance with the manufacturer's installation recommendations and approved shop drawings. 1. Anchor component parts securely in place by permanent mechanical attachment system. 2. Accommodate thermal and mechanical movements. 3. Set perimeter framing in a full bed of sealant compound, or with joint fillers or gaskets to provide weather-tight construction. B. Install joint sealants at perimeter joints and within the panel system in accordance with manufacturer's installation instructions. 3.4 FIELD QUALITY CONTROL A. Water Test: Test skylight system according to procedures in AAMA 501.2. B. Repair or replace work that does not pass testing or that is damaged by testing and retest the work. 3.5 CLEANING A. Clean the panel system inside and outside, immediately after installation. B. Comply with manufacturer's written recommendations. END OF SECTION 084523 14.14.001 SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 084523-7

Essex County College - West Essex Campus Addition And Renovations dlb # 54292 / 11-14