Automated weighing and moisture sensor system to assess the hygrothermal response of wood sheathing and combined membrane-sheathing wall components

Similar documents
Field assessment of the hygrothermal performance of innovative wall and window systems. Prepared by :

Performance Evaluation of Proprietary Drainage Components and Sheathing Membranes when Subjected to Climate Loads

A Methodology to develop moisture management strategies for wood-frame walls in North America: application to stucco-clad walls

National Research Council Canada. Conseil national de recherches Canada. Canada

Adhered Veneers and Inward Vapor Drives: Significance, Problems and

Adhered Veneers and Inward Vapor Drives: Significance, Problems and

Model TEM Mill. Tabletop precision preparation for producing high-quality TEM specimens from a wide variety of materials EXCELLENCE MAGNIFIED

ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS

Experimental Hygrothermal Study in Wood and Wood-based Materials

Performance of wood stud shear walls exposed to fire. Kodur, V.R.; Sultan, M.A. NRCC-41733

Date: November 21, 2007 By: Lonnie Haughton Subject: Significance and Proper Use of Pin-Style Moisture Meters

Validation of Heating 7.2 Simulations Using Hot Box Test Data for RASTRA Wall Form System with Expanded Polystyrene Beads

ScienceDirect. Comparison of steady-state and in-situ testing of high thermal resistance walls incorporating vacuum insulation panels

Module - CE 3132 Geotechnical Engineering Assignment Triaxial Test Marks 10% Learning Outcome

Relationship between Moisture Content and Mechanical Properties of Gypsum Sheathing Phase 2 Research

THE EFFECT OF WINDOW-WALL INTERFACE DETAILS ON WINDOW CONDENSATION POTENTIAL

Performance Evaluation of Proprietary Drainage Components and Sheathing Membranes when Subjected to Climate Loads

Evaluating effectiveness of window/wall interface details to manage rainwater Selected Results from US Window Installation Practice

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS

AMERICAN INSTITUTE OF TIMBER CONSTRUCTION AITC

Breaking Strength and Elongation of Pressure Sensitive Tapes

Use of salt solutions for assuring constant relative humidity conditions in contained environments

Wind pressure measurements on full scale flat roofs. Baskaran, A.; Savage, M.G.

BULK SPECIFIC GRAVITY OF COMPACTED HOT MIX ASPHALT (HMA) USING SATURATED SURFACE-DRY SPECIMENS FOP FOR AASHTO T 166 (11)

MODEL SEM Mill. Two independently adjustable TrueFocus ion sources

Thermostat setback effect in whole building performance NRCC Tariku, F.; Kumaran, M.K.; Fazio, P.

NRCC Guarded Hot Box Testing (ASTM C ) for Energy Efficiency of a Total Roof Assembly

Role of vapor barrier in wood-frame stucco wall in various North. American climates - observations from hygrothermal simulation

Evaluation Report CCMC R ZIP System Sheathing and Tape

DEVELOPMENT OF ENERGY RATINGS

Product certification HEAT-TREATED TIMBER TR

Experimental Assessment of Hygrothermal Performance of Wood Frame Wall System in Suzhou's Lake Tai Climate Zone

Preventive Maintenance and Calibration Program: IDM provides OEM services:

Thermal insulation performance of reflective foils in floor cavities - Hot box measurements and calculations

SELECTION TOOL FOR WATER-RESISTIVE BARRIERS WITH SUITABLE VAPOUR PERMEABILITY

Determination and use of moisture diffusion coefficient to characterize drying of northern red oak (Quercus rubra) *

ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;

OVERVIEW OF PROCEDURE 2A

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels ( )

Moisture Content Specific Gravity Relationships for Clear Southern Pine

MODEL TEM Mill. Two independently adjustable TrueFocus ion sources

PERFORMANCE OF AN IN-KILN MOISTURE METER - PRELIMINARY RESULTS -

Thermal properties of components of lightweight wood-framed assemblies at elevated temperatures. Bénichou, N. ; Sultan, M. A.

Elcometer 118/2. Moisture Meter. Operating Instructions

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

Liquid Metal Cleanliness Analyzer for Continuous Monitoring

P Forsmark site investigation. Drill hole KFM01A: Indirect tensile strength test (HUT)

Airspace R-Values. Educational Overview. Revised 12/6/2016

Fire Testing Laboratory

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

Innovating Continuous Exterior Insulation. Theresa A. Weston, PhD. 1

Dematic Modular Conveyor System

Determining Asphalt Binder Bond Strength by Means of the Binder Bond Strength (BBS) Test

Field Determination of Water Penetration of Windows using Blowerdoor and Infrared Camera

SCC & AAMA Accredited Laboratory, ISO CAN-BEST SCC & AAMA Accredited Laboratory, ISO CAN-BEST 2006

REPORT ON COMPARATIVE AIR LEAKAGE PERFORMANCE:

TECHNICAL SPECIFICATION SDI C. Automated Ultrasonic Heavy Duty Cylinder Inspection System

Laboratory Manual. Concrete and aggregate. Content

Concrete Field Testing Technician Study Guide

CRD-C Standard Test Method for Comparing Concretes on the Basis of the Bond Developed with Reinforced Steel

Processor Performance, Packaging and Reliability Utilizing a Phase Change Metallic Alloy Thermal Interface System

PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( )

Full automatic AMADA bending cell

Hydraulic systems Quality without cutting corners

Heat Flow Meter HFM 436 Lambda. Analyzing & Testing

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.

Wind Uplift Capacity of Foam-Retrofitted Roof Sheathing Subjected to Water Leaks

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( )

Development of Non-contact Ultrasound as a Sensor for Wood Moisture Content

Mechatronics Installer

THERMAL CONDUCTIVITY TESTS OF LIQUIDS USING FOX50 HEAT FLOW METER INSTRUMENT (Amendment the FOX50 Instrument Manual)

Developing Durable CLT Building Enclosure Assemblies

Drainage Capacity Evaluation of EIFS / Wood Substrate By Elie Alkhoury, M.Eng. (Building Science), P.Eng.

Low Temperature Testers

Incorporating Insulating Sheathing into the Design of the Thermal and Moisture Management System of the Building Enclosure

TEMPERATURE EFFECT ON TDR MEASUREMENT OF WATER CONTENT OF UNBOUND MATERIALS ABSTRACT

2013 Technical Review Dwayne McDaniel Florida International University

Permalog Plus User Manual

EVALUATION OF THE LONG-TERM PERFORMANCE OF WATER REPELLANTS ON RENDERED AUTOCLAVED AERATED CONCRETE Performance of water repellants

Eclipse Energy Guard. Product Information & Installation Manual General Installation Requirements

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

T 402. WORKING GROUP CHAIRMAN Janice Trotter RELATED

CREEP BEHAVIOR OF WOOD I-JOISTS WITH WEB OPENINGS EXPOSED TO NORMAL AND LOW RELATIVE HUMIDITY CONDITIONS

Servo-hydraulic Universal Testing Machine HUT Type B

NRC Publications Archive Archives des publications du CNRC

Metal-plate connections loaded in combined bending and tension

Bagged stonedust barriers

BUREAU OF INDIAN STANDARDS Draft Indian Standard

Title: Wind uplift pressures of 2001 Company Wind Vented/ Negative Pressure Roofing System according to CSA A Report No: B1456.

Moisture assessment by fast and non-destructive in- situ measurements

SPECIAL SPECIFICATION 4401 Prestressed Ground Anchors

Tex-424-A, Obtaining and Testing Drilled Cores of Concrete

TORQUE TESTING & INSTALLATION INSPECTION OF DRILLED - IN ANCHORS

AUTOMATION IN AGRICULTURE FIELD USING ARM 7 BASED ROBOT

Compression test of fiberboard shipping containers

Improving the hygrothermal properties of clay plasters

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER

DAMPNESS MEASUREMENT IN CONCRETE FLOORS.

STUDY REPORT SR234 (2010) Investigation into the Performance of Brick Veneer Walls Installed with Urea Formaldehyde Foam Insulation A Case Study

On-line corrosion mapping of industrial plant using advanced electrical resistance techniques

Transcription:

Automated weighing and moisture sensor system to assess the hygrothermal response of wood sheathing and combined membrane-sheathing wall components Maref, W.; Lacasse, M.A.; Booth, D.; Nicholls, M.; O'Connor, T. NRCC-45696 A version of this document is published in / Une version de ce document se trouve dans : 11 th Symposium for Building Physics Proceedings, Dresden, Germany, Sept. 26-30, 2002, pp. 595-604 www.nrc.ca/irc/ircpubs

Automated weighing and moisture sensor system to assess the hygrothermal response of wood sheathing and combined membrane-sheathing wall components W. Maref *, M. A. Lacasse, D. Booth, M. Nicholls and T. O'Connor National Research Council Canada, Institute for Research in Construction, Ottawa, ON, Canada, K1A 0R6 Abstract A weighing system was devised to conduct drying experiments on wood based products that could be used to compare results with those derived from simulation. The experiments were designed to retrieve data on the change in weight of specimens continuously over time from which the hygrothermal response of the specimens could then be determined. Specimens consisting of saturated wood sheathing board products of approximately 0.8-m by 1-m size and weighing 5-kg, were wrapped in different types of sheathing membrane and subjected to uniform environmental conditions in a climate chamber. A description is provided of the development of the weighing system, requirements for load cells and their calibration as well as technical features of the data acquisition system. Additionally, an example of a typical weight-in-time plot, obtained from one set of experiments, is given and compared to that derived from simulation. Experimental results are also provided that show the moisture content distribution within the sheathing board over time. Keywords: Benchmarking, Building System, Drying, Envelope, Heat Transfer, Mass Transfer, experiment, Moisture, and Wood Product. * Corresponding author. Tel.: + 1-613-993-5709; Fax: +1-613-998-6802 E-mail address: Wahid.maref@nrc.ca

Introduction 11 th Symposium for Building Physics, September, 26-30, 2002, Dresden, DE Recent research on assessing hygrothermal response of wall systems and components has focused on either laboratory experimentation or hygrothermal modelling, but less work has been reported in which both aspects are combined. Such type of studies can potentially offer useful information regarding the benchmarking of models. Acceptance of results derived from simulation models is contingent upon acquiring evidence of a response comparable to that obtained from experimental work when the simulation is carried out under the same nominal environmental loads. Studies that incorporate both laboratory experimentation and simulation thus offer possibilities to compare results and hence benchmark the response of the model to known conditions. Results from related benchmarking exercises recently have been reported by Maref [Maref et al. 2002a, Maref et al. 2002b]. This paper provides information on the development of an automated weighing and moisture sensor system to conduct drying experiments on wood based products. The system is devised to collect data that can be used to compare results with those derived from simulation. The experiments were designed to retrieve data continuously over time on the change in weight of specimens as well as the moisture content of wood-based components. These specimens consisted of saturated wood sheathing board products of approximately 0.8-m by 1-m size, wrapped in different types of sheathing membrane. Using this data, the drying rates of wood sheathing alone or in combination with several sheathing membranes were systematically measured. Results from these experiments are compared with those derived from hygrothermal simulations and subsequently used to help benchmark the model. Approach to benchmarking trials on mid-scale specimens Mid-scale experiments were used to assess the drying rates of saturated oriented strand board (OSB) sheathing in contact with, or in proximity to, other OSB sheathing, and in contact with various water resistive barriers when subjected to controlled environmental conditions. These results were then compared to those obtained through simulation with the use of an advanced hygrothermal model, hygirc, such that predictive capabilities of hygirc could be ascertained. A description of the model and its capabilities have been provided in [Maref et al. 2002a, 2002b]. The mid-scale experiments were carried out in controlled laboratory conditions on panels and assemblies having nominal dimensions of 0.8-m (W) x 1.0-m (L). This size was deemed a reasonable compromise between small (0.15-m by 0.15-m) and full-scale experiments (2.43-m by 2.43-m). The experiments were conducted in a closed chamber providing a steady state and controlled laboratory environment. Drying rates were resolved based on gravimetric analysis for which a set of nine weighing systems was devised. The bulk moisture

content of at different locations on the specimens was determined using moisture pin pairs. Continuous monitoring of the temperature and relative humidity in the chamber as well the bulk moisture content of materials being evaluated was undertaken using various devices, including self contained and autonomous data loggers as well as computer controlled fully automated data acquisition (D/A) systems. A typical experiment consisted of assessing the bulk dry density of the panels, following by preconditioning the specimens such that they reached a state of equilibrium at a known moisture content. They were then assembled according to the requirements set out for the specific experimental sets (i.e. coupled to other panels or brought into contact with water resistive barriers) and then placed in the test chamber in which the weighing systems were located. Moisture pins and other sensors were then attached to the specimens and linked to the D/A system. Changes in moisture content, temperature and relative humidity were recorded as a function of time. Test series were conducted until moisture contents of the OSB panels reach pre-set equilibrium conditions. Equipment A description of the equipment to carry out the benchmarking trials is provided below and includes information on the automated weighing system and load cells, data acquisition and control system, moisture pin sensors and their calibration, and the environmental chamber. Weighing system and load cells Three weighing systems were fabricated (Figure 1), each consisting of an A-frame structure across which rested a support beam. To this beam were affixed three load cells each accommodating a specimen. The automated operation of beam insured that weight changes could be recorded over extended periods of time. Hence the weight of a total of nine different specimens could be simultaneously monitored from which a gravimetric analysis on individual specimens could then be completed. The need for intermittent weighing of specimens was brought about by the expected zero drift of load cells if subjected to continuous measurements over periods exceeding a few days. Given that the anticipated drying periods for these tests could extend to several days, if not weeks in certain instances, it was decided that to mitigate the possible load cell effects a system would be devised that permitted weighing specimens on an intermittent basis. This was achieved by having the specimens engage and disengage from the load cells at predetermined time intervals through the action of servo-controlled, time-actuated, pneumatic pistons. The pistons, placed at either end of a support beam, regulate the movement of the beam to which the load cells are attached. Each support beam is equipped with three variable resistance load cells having a nominal capacity of 50 ± 0.2-kg. Changes in weigh are recorded from load cell measurements on the D/A system.

Each individual load-cell was calibrated against an Instron type UTM by taking simultaneous readings of tensile load and voltage measurements from the load-cell using a digital multimeter. Data acquisition and control system The data acquisition (D/A) and control system (Figure 2) consists of three basic hardware modules. A command module, a data multiplexer and a digital mulitmeter. The command module is housed within a modular power supply unit. The command module transfers software instructions from a local computer (central processing unit - CPU) to the automated data logging multiplexer to collect and measure data on the digital multimeter. Readings were taken every 10 seconds and directly downloaded to the hard drive where access to the data could be made on a continual basis. Outputs from each of the load-cells (Figure 2), affixed to the central beam, are connected to a multiplexer unit (HP-E1476A) that is linked to a timer relay; this relay activates the upward and downward motion of the pneumatically driven central beam. The relay signal is connected to the D/A system such that the readings are only taken when the timer relay is activated and the load-cells are under tension. The relay timer was set such that the load cells are operative for 20 minutes of every forty minutes and when operative, the load cell outputs are scanned and recorded by the D/A every two minutes. The software program is used to collect data from both the moisture pins and loadcells. It also permits the configuration of operation parameters such as the frequency of acquisition cycles, the duration of the test, file name were the data is recorded. Data loggers were used to acquire the temperature and relative humidity profile of the chamber. The data was reconciled with the gravimetric and other sensor data following the completion of an experiment. The data was acquired every 10 minutes and held in the local memory until retrieved by downloading to another computer. Moisture pins Moisture pin pairs, DELMHORST type, were used to assess the bulk moisture content of wood-based materials (Figure 3). Calibration techniques used to determine the moisture content as a function of material resistance are described below. Calibration of moisture pin sensors The procedure for determining the moisture content in OSB specimens calibrated to readings taken from electrical resistance measurements using moisture content gauges is described this report. The procedure essentially consists of saturating a series of specimens of known size and weight and thereafter slowly drying these such that moisture contents based on weight changes can readily be correlated to corresponding measurements using moisture content (resistance) gauges.

Support beam Load cells Pneumatic piston Figure 1 Automated-weighing system for mid-scale specimens showing load cell support beams, load cells, pneumatic pistons and specimen holders. Support beam CPU LC: Load Cell(s) LC S LC Specimen S LC S Command module Digital MultiMeter D/A Multiplexer Figure 2 Schematic of the Data Acquisition set-up

Specimen Preparation A series of 15 specimens of nominal size 11.5 x 150 x 150-mm were cut from a standard sheet of 1220 x 2440-mm OSB. Note was taken of the orientation of strands on the surfaces of the specimens such that moisture pins could subsequently be oriented in the direction of the strands, as required for the test procedure. The initial thickness of each specimen was then measured at its four extremities, 12-mm from the outside edges, to the nearest 0.001-mm using precision callipers. Pairs of insulated moisture pins of 28-mm length were then inserted into pre-drilled holes spaced ca. 25-mm apart (Figure 3). The holes were bored to varying depths. One specimen was instrumented with moisture pins inserted to ¼, ½, and ¾ specimen depth and the remaining 15 specimens instrumented with moisture pins inserted to ½, and ¾ specimen depth. Each pair of pins was located on the specimen such that the line between pin pairs was parallel to the principal strand (wafers) orientation in the layer to which they were subsequently inserted. Calibration procedure The specimens were weighed and the laboratory conditions recorded (i.e. temperature and relative humidity) such that the moisture content could subsequently be determined. (Note that this weight is not necessarily the equilibrium MC of the material at these conditions). The specimens were then immersed in water to achieve saturation insuring that all free surfaces were completely immersed. An initial three-day immersion period was used following which confirmation that saturation has been attained was determined by monitoring the weight change of several specimens at 4-hour intervals over the fourth day. Moisture measurements were taken on all specimens (Figure 4) and the differences between the ¼ depth readings and the core moisture readings examined to determine evidence of any significant moisture gradient and hence to verify if the specimens have achieved a uniform moisture contents. If a gradient was found to exist, then more time was required for the specimens to reach the desired conditions, otherwise the calibration procedure could proceed as shown in Figure 4. Under conditions of uniform moisture content, specimens weights are determined, and moisture content values (using Delmhorst meter), and the resistance of each moisture pin pair was obtained. The calibration curve, for which moisture content was correlated to resistance measurements, was derived using 15 square OSB specimens of the same type and thickness as that used in the mid-scale experiments. Chamber A climatic chamber, referred to as the Envelope Environmental Exposure Facility (EEEF), was used to subject the specimens to simulated climatic conditions over extended periods of time. The climatic conditions within the chamber can be varied over a range of -47 to + 48 0.5 C with the capability of either, maintaining a steady state set point, or executing a temperature ramping regime. Humidity control is achieved through a pneumatically actuated fogger coupled to a set point controller and can maintain humidities ranging from 10 to 100 % RH within 3 % RH in steady state conditions.

Figure 3 Moisture pins inserted in OSB sample Figure 4 Calibration of the Moisture Pins on the OSB Water Specimens 1-m Figure 5 Cross section of immersion bath 0.8-m Figure 6 Locations on OSB board where moisture measurements are taken

Assembly of mid-scale specimens Pre-conditioning Specimens were immersed in a water bath (Figure 5) for a period of 5 days in order to saturate the specimens. Aluminum angles of 1-m length are used to separate the stacked specimens from on another and from the bottom of the immersion bath to insure that water was in contact with all surfaces of the OSB specimens. This helped hasten the process of saturating the samples. Given that the fully immersed specimens had a tendency to float, bricks were placed on the upper most specimens to weigh these down and insure that these were kept submerged. After five days, water in the bath was drained and the specimens then remained in the bath for another two days to allow moisture to re-distribute itself evenly within the OSB. The boards were prevented from drying out by sealing the bath lid with adhesive tape. Following this two-day period, each sample was then removed and moisture content measurement taken with a Delmhorst moisture meter. Weights as well as specimen thickness were recorded for each specimen. The readings were used to determine if the moisture distribution in the specimens was reasonably uniform. Specimens would, upon removal from the bath, immediately start to loose moisture to the surrounding air. Hence in order to maintain specimens at close to saturated conditions and minimise the loss in moisture prior to the start of the experiment, specimens were assembled as quickly as possible. Specimen assembly, in instances where results were being sought for OSB in combination with any of three membrane types, consisted of wrapping the sheathing with the membrane, setting the moisture pins to their predetermined locations (Figure 6) on the board, affixing the specimen to the load cell and thereafter, connecting each pin pair to the D/A lead. Comparative results between experiment and simulation Nominal results for these mid-scale experiments are provided in Figures 7 to 10. They include environmental conditions (provided in Figure 7) to which the specimens were subjected as well as the weights of individual specimens together with resistance measurements taken across each pair of moisture pins as a function of time. Moisture contents at a given pin-pair location were determined by associating the resistance to a specific moisture content based on the resistance-mc calibration curve obtained from previous experiments. For this study, hygirc was used to estimate the drying response of nine specimens of OSB (see Table adjoining Figure 10). The total moisture content as function of time of the nine (9) specimens, as determined by gravimetric analysis, is provided in Figure

8. Results for one of these specimens (No. 5) in which the hygrothermal response to drying at different pin pairs located in a single sheathing of OSB board in given in Figure 9. Figure 10 shows a comparison between simulated and measured total MC of the OSB board (per 0.8 meter of specimen width) as a function of time (specimen 5). The total MC in the system initially is ca. 58 % and after 30 days it reaches a value of 5%. These results indicate a very good agreement between results of simulation and those derived from experiment. As was mentioned previously, OSB boards were immersed in water for 5 days and then allowed to stabilise in a sealed tank. Thus for the simulation, it was assumed that at the start of the experiment all specimens had a uniform MC through the thickness of the material as determined from MC measurements. In a hygrothermal simulation, the boundary nodes are critical to the analysis in particular if the surface being modelled is saturated and in contact with air. In this instance, the mass transfer at the boundary layer is very sensitive because the very thin layer of air at the surface represents a certain resistance where a high rate of moisture transfer occurs. The results shown in Figure 10 suggest that for OSB sheathing directly exposed to the surrounding air (i.e. free surface ), the simulated drying rate is in good agreement with the results obtained in the experiments. Concluding remarks These results obtained from gravimetric analysis derived from experimental work indicate a very good agreement with those obtained from simulation. As well, the results obtained from moisture content changes as monitored by the moisture pins pairs is consistent with that observed for the loss in weight over time. References W. Maref, M. A. Lacasse, M. Kumar Kumaran, Michael C. Swinton, (2002), Advanced Hygrothermal Model HygIRC: Laboratory Measurements and Benchmarking, 12th International Heat Transfer Conference (18-23 August 2002, Grenoble, France) W. Maref, M. A. Lacasse, M. Kumar Kumaran, Michael C. Swinton, (2002), Benchmarking of the Advanced Hygrothermal Model HygIRC with Mid Scale Experiments, esim Conference-IBPSA-Canada- Montreal (Sept. 12-13, 2002).

Temperature (C) 50 45 40 35 30 25 20 15 10 5 0 11/21/99 11/26/99 Conditions in the Guarded Hot Box 12/1/99 %RH T 12/6/99 12/11/99 12/16/99 12/21/99 50 45 40 35 30 25 20 15 10 5 0 12/26/99 Figure 7 - Boundary conditions for the experiment showing the recorded temperature (T) and relative humidity (RH) in the climatic chamber as a function of time conducted over 30 days. Relative Humidity (%) Total Moisture Content (kgw / kgd) 110% 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% Specimen 1 Specimen 2 Specimen 3 Specimen 4 Specimen 5 Specimen 6 Specimen 7 Specimen 8 Specimen 9 0.00 5.00 10.00 15.00 20.00 25.00 30.00 Time (Days) Figure 8 - Total moisture content as function of time of 9 test specimens as determinded by gravimetric anlaysis Moisture Content (kgw / kgd) 40% 35% 30% 25% 20% 15% 10% 5% MC1 MC2 MC3 MC4 MC5 MC6 MC7 MC8 1 2 3 6 5 4 7 8 0.8 m 1 m Total Moisture Content (kgw / kgd) 70% 60% 50% 40% 30% 20% 10% Simulation Experiment Spec. No. Combination of Materials Membr. OSB Membr. 1 VII + Wet OSB + VII 2 III + Wet OSB + III 3 V + Wet OSB + V 4 Wet OSB + MP @ ½ D 5 Wet OSB + MP @ ¾ D 6 Wet OSB + NO MP 7 VII + Wet OSB + VII 8 III + Wet OSB + III 9 V + Wet OSB + V 0% 0 5 10 15 20 25 Time (Days) Figure 9 - Drying distribution Specimen 5 Figure 10 - Total moisture content as function of time of OSB layer specimen 5 (Experiment / Simulation) 0% 0 5 10 15 20 25 30 Time (Days)