NERC Reliability Initiatives and Smart Grid

Similar documents
Primary Frequency Response Stakeholder Education Part 1 of 2

Primary Frequency Response Stakeholder Education Part 2 of 2

Frequency Response Assessment and Improvement of Three Major North American Interconnections due to High Penetrations of Photovoltaic Generation

Plant-level Control and Protection Modeling Task Force Task Force Report

Inverter-Based Resources During a Cascading Failure: Present State and Future State

BPS Reliability Risks and NERC RISC. Ryan D. Quint, Advanced Analytics & Modeling, NERC WECC RAC Meeting October 2017

Accommodating High Levels of Distributed Energy Resources

Project Generator Verification and Implementation Plan for PRC-019-2, PRC and MOD Compliance Fall Workshop October 12, 2017

Approved RMWG Discussion was held. ??? John Simpson need to assign SMART rating

NERC Lessons Learned and Industry Recommendation

Frequency Response. Straw Proposal

Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System

Texas Reliability Entity Event Analysis. Event: December 11, 2010 Loss of Multiple Generators Category 3 Event

Essential Reliability Services Task Force Measures Framework Report

Reliability and the Future of the Electricity Grid: A North American Bulk Power System Perspective

Standard MOD Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:

Public Utility District Number 1 of Snohomish County

Standard Development Timeline

PRC-006, PRC-007, and PRC-009 Mapping to Proposed Continent-Wide Standard

Post SAR July day Formal Comment Period with Parallel Ballot July 2013

Integrating High Levels of Variable Renewable Energy Sources

WebEx May 18 th Meeting WebEx URL: Join WebEx meeting

Mapping Document for FAC-010-3

Supporting Documentation for Volume 1, Chapter 11. Table 12-1 Definition of key ancillary services

Reliability Compliance and Monitoring Tools

Essential Reliability Services

Standard Development Timeline

2017 Assessment of Reliability Performance Summary Report April 2018

Grid Planning - Program 40

by the Transmission Planner or Planning Coordinator.

PRC Under Voltage Load Shedding

Standard Development Timeline

Frequency Response Phase 2

Essential Reliability Services

Standard Development Timeline

Briefing on using renewables to integrate renewables

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA

MOD Steady-State and Dynamic System Model Validation

A separate notification will be provided to NPCC Members announcing the start of the formal 10 day ballot period.

CENTRE FOR WIND ENERGY TECHNOLOGY CHENNAI INDIAN WIND GRID CODE

Toward Ensuring Reliability: Reliability Performance Metrics. A NERC Staff White Paper

Appendix 5B Statement of Compliance Registry Criteria Revision 5.2 Effective: October 15, 2015

Revised Draft Final Proposal for Participation of Non-Generator Resources in California ISO Ancillary Services Markets

Public Utility District Number 1 of Snohomish County. Facility Connection Requirements February 9, 2018

Proposed Revisions to the Applicability of NERC Reliability Standards NERC Standards Applicability to Dispersed Generation Resources

A. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements

WWSIS - 3: Western Frequency Response and Transient Stability Study

Proposed Definitions for the NERC Glossary of Terms Project : Emergency Operations

804 OFF-NOMINAL FREQUENCY LOAD SHEDDING AND RESTORATION

2015 Operational Practices Survey Questions

Standard TPL-004-0a System Performance Following Extreme BES Events

Transfer Capability Methodology. for the Near-Term. Transmission Planning Horizon

Proposed Revisions to the Applicability of NERC Reliability Standards NERC Standards Applicability to Dispersed Generation Resources

MOD Data for Power System Modeling and Analysis

A. Introduction 1. Title: Automatic Underfrequency Load Shedding Requirements

Table of Issues and Directives Project Relay Loadability: Stable Power Swings

August 1, ReliabilityFirst Compliance Contacts ReliabilityFirst Compliance Program Update Letter August Update

Collaborative Approach for Wind Power Plant Model Data and Validation

Standard TPL Transmission System Planning Performance Requirements

Reference Document. Interconnected Operations Services

Essential Reliability Services Task Force (ERSTF)

Renewables in Hawaii. Mr. Dick Rosenblum President and CEO Hawaiian Electric Company NERC Board of Trustees Meeting Phoenix, Arizona February 6, 2014

Table of Contents. To provide a methodology for determining the System Operating Limits (SOL) for the Planning Horizon at the California ISO.

STATE OF THE INTERCONNECTION DIGEST

Bulk Power System Integration of Variable Generation - Program 173

Seminar on African Electrical Interconnection. Module 8 - Interconnected Systems Operating Conditions

EAPP interconnection readiness workshop

Investigating Power System Primary and Secondary Reserve Interaction under High Wind Power Penetration Using Frequency Response Model

Regional Impact of Renewables: ERCOT

Recent US Wind Interconnection Experience

Data Visualization, Daily Operations Review and Event Analysis. Fabian Robinson PMU Program Lead PJM Interconnection NASPI Houston, TX - October 2014

Reliability Standard Audit Worksheet 1

Special Protection Systems (SPS) / Remedial Action Schemes (RAS): Assessment of Definition, Regional Practices, and Application of Related Standards

Renewable energy connection requirements in Spain April 2012

NERC Planning Committee Report

NERC Standard BAL Frequency Response & Frequency Bias Setting

Standard TPL-003-0b System Performance Following Loss of Two or More BES Elements

Standard MOD Verification of Generator Gross and Net Real Power Capability

Meeting Agenda Adequate Level of Reliability Task Force

Essential Reliability Services Task Force

GUIDE. Part 11.1: Applicability Criteria for Compliance with NERC Reliability Standards and NPCC Criteria PUBLIC

Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection

Mapping Document. Project Phase 2 of System Protection Coordination. Revisions or Retirements to Already Approved Standards

Full electrical LNG-plant: Highest availability and energy efficiency trough overall system design

GRID OPERATIONS AND PLANNING

Performance Standards Issues. Donald Lamontagne Principal Engineer Arizona Public Service

Standard MH-TPL Transmission System Planning Performance Requirements

Reliability Standards Development Plan:

Reading, Understanding, and Following NERC Standards

Standard TPL-003-0b System Performance Following Loss of Two or More BES Elements

Technical Report Supporting Definition of Adequate Level of Reliability

Renewable Integration at ERCOT

Integration of Renewable Generation in ERCOT

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. Electricity Market Design and Structure ) Docket No.

Educating System Operators in the New Millennium! Background. Course Level. Target Audience. NERC Continuing Education Hours

RENEWABLE ENERGY INTEGRATION: VARIABILITY & UNCERTAINTY IMPACTS AND MITIGATION OPTIONS BRENDAN KIRBY

What makes a Wind Plant Grid Friendly?

PRC and EOP Effective 10/1/13

Meeting Notes Project System Protection Coordination Standard Drafting Team December 1-4, 2014

Transcription:

NERC Reliability Initiatives and Smart Grid IEEE PES Late Breaking News July 28, 2009 Robert W. Cummings Director of Event Analysis & Information Exchange

System Protection and Control Performance Improvement Initiative

Protection & Controls Initiative Announced at February Board meeting Letter to industry to come out shortly NERC Board recognition of the importance of system protection to reliability Goal: Improve BES reliability Purpose: Improve the performance of power system Protection Systems through fostering technical excellence in protection and control system design, coordination, and practices.

Protection & Controls Initiative Elevate System Protection and Control Task Force to Subcommittee status Increased emphasis on the importance of protection Collaborative efforts with: IEEE Power & Energy Society IEEE Power System Relay Committee Bridge between IEEE standards and NERC system performance requirements (in NERC standards) Coordinate Protection Standards Philosophies and Standards Work Reduce discrepancies Technical basis for all protection standards changes

Initial Targeted Areas PRC Standards Technical Support SPCS to provide technical SME support to Standards process Relay Loadability Standard PRC-023 Relay Loadability passed by NERC Board, awaiting FERC approval Protection System Reliability (redundancy) SPCS Technical Reference Document & SAR Posted for comments 1/20 2/18 Generator Frequency and Voltage Protective Relay Coordination Standards Project 2007-09 Generator Verification Drafting of Standard PRC-024-1 Generator Frequency and Voltage Protective Relay Settings

Initial Targeted Areas Transmission and Generation Protection System Misoperations Technical review of PRC-004 -- Analysis and Mitigation of Transmission and Generation Protection System Misoperations Includes NERC-wide definition of protection misoperations for NERC reporting and system performance metrics Protection System Maintenance SPCTF 2007 Technical Reference Standards on Protection System maintenance Project 2007-17 Transmission and Generation Protection System Maintenance and Testing, PRC-005 in re-drafting phase

Initial Targeted Areas Protection System Coordination Transmission Protection Coordination Support for revisions to PRC-001 Trans & Gen Protection Coordination IEEE collaboration SPCS Technical Reference Power Plant and Transmission System Protection Coordination support for revisions to PRC-001 BES System Performance & Protection Coordination with Generator Controls Improved modeling of governors and other generator controls New control models need to be applied Model validation to actual system performance essential

Initial Targeted Areas BES System Performance & Protection Coordination with Turbine/Boiler Controls Response to leading trend in system disturbances Largely uncharted area for modeling by planners Discussions with industry experts and turbine control manufacturers on appropriate level of modeling (detailed modeling not appropriate)

System Modeling Improvement Initiative

NERC Modeling Initiative Purpose to improve powerflow and dynamics modeling across North America Planning models As-built models for operations planning Forensic analysis models Improve MOD series of standards Cross-program model flexibility Problems with user-models Validate dynamics models for new equipment

Basis in Blackout Recommendations Improve quality of system modeling data and data exchange practices NERC Recommendation 14 US-Canada TF Recommendation 24 Generation and Transmission Performance Report Recommendations Background of original recommendations Strengthened recommendations

TR-4 Powerflow Modeling A. Modeling Groups should reinvestigate feasibility of a CIM capable powerflow creation database B. NERC should create initiative to improve overall powerflow modeling techniques C. Powerflow cases should be periodically benchmarked to actual system conditions at various load levels D. All generators should be periodically tested to ensure that their claimed MW and Mvar ratings are accurate and realizable Testing should also be done to confirm the performance of generator dynamic controls and that their respective models in the System Dynamics Databases are accurate.

TR-12 Improve & Validate Dynamic Models A. Create a feedback loop in modeling process CIM compatible B. Initiate dynamic model validation in EI for generators and dynamic responsive equipment C. Codify (with IEEE) new standard for powerflow and dynamics data formats D. Provide forum for ongoing development, testing, and validation of new and improved dynamic models E. Improve load modeling for more accurate powerflow and dynamics analysis

Modeling Issues If something in not modeled, how can you predict system behavior or interaction???? Dynamics Modeling Issues Missing models Data errors Models may not match field equipment and settings Issue of proprietary models Modeling of wind farms Common-mode failures same make and model Registrations issues not collecting all needed data Proprietary models

Need for New Modeling Turbine / boiler control models needed Units may remain stable, but ramp to zero and trip Far more complex dynamic load models needed to analyze and predict FIDVR (Fault- Induced Delayed Voltage Recovery) behavior More load composition data needed to do this Better governor models Better SPS/RAS models Models for new power electronic devices

Intelligent Integration of ElectronicallyCoupled Resources and Demand

Smart Grids a Reliability Perspective Defined from a Reliability Perspective Two-way flow of energy and communications enabling new technologies to supply, deliver and consume electricity. Functions Enhanced flexibility and control Balancing variable demand & resources Demand Response Large deployment of sensor & automation technologies etc.

Smart Grid Integration Reliability Considerations to Plan a System that Operators can Reliably Operate Design Large-Scale, Non-Linear Control (new tools?) Large & Small Signal Stability maintained (new tools?) Coordination of controls (centralized/decentralized) Device interconnection standards dependent on function System sensitivity analyses must be expanded Cyber security considerations in planning, design and operations Operations will change (new tools?)

Renewables and Smart Grid Intelligently integrate renewable resources Intelligent integration of smart grid technologies to take advantage of tremendous potentials while maintaining reliability Overall Reliability Concerns System inertia maintaining system stability Ability to maintain voltage and frequency control Interactions of myriad of control systems

Electronically-Coupled Demand Issues Modeling Information on harmonics power quality concerns Frequency response behavior during off-nominal frequency conditions Controls and protection characteristics Schizophrenic load behavior (human reaction-based) Disturbance ride-through Potential for wide-spread common-mode disconnections Intelligent reconnection (i.e., do not automatically reconnect if underfrequency or under-voltage conditions exist) Avoid motor stalling

Electronically-Coupled Resource Issues Disturbance ride-through Stay connected through off-nominal frequency (over- and under-frequency) events, including coordination with utilities Under-Frequency Load Shedding programs Stay connected through off-nominal voltage events, including coordination with utilities Under-Voltage Load Shedding program Potential common-mode failures Intelligent reconnection (i.e., do not automatically restart/reconnect if over-frequency or over-voltage conditions exist)

Electronically-Coupled Resource Issues Voltage Stability Provide primary voltage control for transient stability Provide secondary voltage control for post-transient stability Carry (or have a linkage to) reactive reserves Be capable of a two-quadrant operation, delivering leading and lagging power factor through the entire power output range

Electronically-Coupled Resource Issues Frequency Control Primary frequency control for arresting system frequency deviations Secondary frequency control, participation in AGC Ability to dispatch and follow power schedule Ability to carry Frequency Responsive Reserves Oscillation Damping Contribute to positive damping of power oscillatory modes

Electronically-Coupled Resource Issues Additional requirements Make generic powerflow and dynamic models, and associated data sets available for power system studies prior to interconnection. These must be validated by measured performance in operation Provide self-protection and control parameters for power system studies necessary for evaluation of potential common-mode failures based on controls or performance parameters Disturbance data recorders 30+ samples per second, time synchronized needed to validate performance and models Participate in monitoring systems, remedial action schemes, and other reliability schemes as identified in regional planning process

Smart Grid Integration Task Force NERC Staff Proposal: Task Force formed to evaluate reliability considerations to integrate Smart Grids in Planning, Design and Operations Coordinated Effort between PC/OC/CIP, lead by PC Evaluate Changes in Planning, Design & Operations Make Recommendations for next steps Complete Report by December 2009

Frequency Response Initiative

Frequency Response Basics Frequency Response, termed beta (β), is a fundamental reliability service a combination of governor and load response Inversely related to frequency excursions Frequency Response is declining Should be increasing with load & generation growth Part of the decrease may be better measurement Performance-based standards quite possibly on the horizon (FERC Order No. 693)

Typical WECC Frequency Excursion 60.02 60 59.98 Point A Point B 59.96 Point C 59.94 59.92 59.9 0 6 12 18 24 30 36 42 48 54 60 Seconds

Typical ERCOT Frequency Excursion 60 59.95 59.9 Point A Point B β Int = Δ MW/(10* Δf) β BA = Δ N ia /(10* Δf) β Gen = Δ MW/(10* Δf) 59.85 59.8 0 6 12 18 24 30 36 42 48 54 60 Seconds

Typical Eastern Interconnection Frequency Excursion 60.02 60.01 60 59.99 No Point C to Point B Recovery 59.98 59.97 Response Withdrawal 59.96 59.95 59.94 0 6 12 18 24 30 36 42 48 54 60 Seconds

Eastern Interconnection Frequency Response Trend Decline of 72MW/0.1Hz/year * Ingleson and Nagle Study

Recent Frequency Response Easter Interconnection Beta 3500 3400 3300 3200 MW/0.1Hz 3100 3000 2900 2800 2700 2600 2500 2000 2001 2002 2003 2004 2005 2006 * Mean Median 2007-2008 Response = -2550MW/0.1Hz * Ingleson and Ellis/NERC Resources Subcommittee/Virginia Tech

Small Excursions (>28mHz) Follows a seasonal pattern, # are increasing 28mHz represented loss of about 1000MW in 1994 Change believed to be primarily due to decline in frequency response (70 MW per 0.1Hz /year since 94) Pumped storage and interchange schedule changes now causing excursions of this size Small excursions are a symptom, not necessarily a problem themselves Patterns give a clue to sampling techniques needed to objectively calculate Balancing Authority and Generator Frequency Response

Frequency Response Initiative Employ Frequency Monitoring and Analysis tool to look at all FTL excursions Sample events being used for shakedown NERC Advisory Alert to be issued on maintaining better frequency response One target to improve modeling of actual response in studies Stay Tuned still being developed!

Questions?