Ground Source Heat Pump System Performance: Measuring the COP

Similar documents
GxTracker TM INSTALLATION AND USERS MANUAL. The Geoexchange Tracker

Welcome Everyone. Not Quite this kind! Geothermal Heat Pumps are a indirect solar heating system! Introduction to Geothermal

Introduction to Geothermal Comfort Systems in INDIA

Ground Source Heat Pumps

Alaska Geothermal LLC Geothermal Heat Pumps. Alternatives for Heating, Cooling & Domestic Hot Water Production

For more information about Ground Source Heat Pumps, call the Member Service Department at or visit our website at

Geothermal Alliance of Illinois Sales and Marketing for Technicians

Introduction to Geothermal Comfort Systems in INDIA

Evaluation of Vertical and Horizontal Geoexchange Systems

White Paper. Geothermal Heating and Cooling

What is a ground source heat pump?

NYSERDA CHP Assessment Report A S S E S S I N G T H E C H P P L A N T A T C L A R K S O N U N I V E R S I T Y

ASSESSMENT OF NATIONAL BENEFITS OF RETROFITTING EXISTING SINGLE-FAMILY HOMES IN UNITED STATES WITH GROUND-SOURCE HEAT PUMP SYSTEMS 1

Geothermal Heat Pump Systems Being Green by using the Ground

Performance enhancement of a photovoltaic thermal (PVT) and ground-source heat pump system

Measurement of COPs for Ground Source Heat Pump (GSHP) System in Heating and Cooling Mode

The American Council for an Energy-Efficient Economy Emerging Technologies Report. Residential Ground-Source Heat Pumps July, 2007

Cares renewable ENERGY

DIRECTIONAL-BORE GROUND SOURCE HEAT PUMP FIELD REPORT

DOE Webinar Residential Geothermal Heat Pump Retrofits

Meeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It

Field Test of Cold Climate Air Source Heat Pumps

Geothermal Heat Pump Systems Being Green by using the Ground. Presented by: Warren (Trey) Austin, PE, CEM, CGD, LEED-AP Geo-Energy Services, LLC

HVAC Real-time Remote Monitoring 4 year Case Study Delivering Value

3/6/2017 Past president & currently on the board of directors for the Wisconsin Geothermal Association

G eothermal. S ystems. The Earth Connection

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Measurement & Verification Report for Alltemp Refrigerant: Preliminary Results Macy s Department Store Manhattan Beach, CA

WaterFurnace Explains

GEOTHERMAL OVERVIEW. Presented by John Cole East Coast Account Rep. for RENEWABLE ENERGY. Construction Automotive Industry

Initial Commissioning of a Water to Water GHP system in KIER

EnergyPro Building Energy Analysis. Nine-story Office Building

FIRST LARGE-SCALE SOLAR SEASONAL BOREHOLE THERMAL ENERGY STORAGE IN CANADA

Performance of Ductless Heat Pumps in the Northeast

Ground Source Heat Pumps (AKA Geothermal Heat Pump or Geoexchange): E3A Folder Forthcoming. Milton Geiger, CEM, REP Fairbanks, AK April 15, 2014

EnergyPro Building Energy Analysis. Single-story School Building

Supplemental Data for California Smart Thermostat Work Paper

Residential Swimming Pool Heating with Geothermal Heat Pump Systems

The Participants in this GreenON Rebates Program are homeowners and landlords.

DOE Task 99-4 Extension of Design and Simulation Models 3/24/00 EXTENSION OF EXISTING DESIGN AND SIMULATION MODELS

Comprehensive Compressed Air Assessments

D DAVID PUBLISHING. Optimizing Thermal Energy Storage Systems in the Hospitality Industry. 1. Introduction

Field Test of Cold Climate Air Source Heat Pumps

2. Ground Source Heat Pumps Invitations to complete questionnaire Responses received... 7

MEMORANDUM. The Massachusetts and Rhode Island Program Administrators (PAs) commissioned Cadmus and its

In-Depth Exploration of Ground Source Heat Pump Technologies

Customer guide. Residential Dual Energy

Heat Pump Assisted Solar Thermal System

Retro-commissioning and on-going commissioning 23 November 2016

Ground-Coupled Heat Pump And Energy Storage

A new application of an old idea

FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC MANGUM ROAD HOUSTON, TEXAS. performed by:

NEW TECHNOLOGIES THAT ARE INCREASING SYSTEM EFFICIENCIES. Tom Wyer Director of Engineering

RESIDENTIAL Q&A IS GEOEXCHANGE HEATING & COOLING RIGHT FOR YOU?

a comparative study of secondary glycol and direct expansion refrigeration systems

Geothermal Heat Pumps: Harnessing On-Site Renewable Energy to Meet Energy-Efficiency and Climate Change Goals

Energy Savers: Air-Source Heat Pumps

22 DIGITAL SERIES CLIMATEMASTER GEOTHERMAL HEATING AND COOLING

HIGH EFFICIENCY SHOWERS WASTE WATER HEAT RECOVERY UNIT. Saved power 80kW. Showers waste water 9 C Power consumption 3,1kW. Showers waste water 31 C

1. How the research adds to the understanding of the area investigated

WaterFurnace Explains GEOTHERMAL HEATING & COOLING

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE

Enhancement of Heat Exchange Capacity of Ground Heat Exchangers by Injecting Water into Wells

Value of Air Source Heat Pumps in Light of Variable Energy Prices. Jeff Haase. Energy Design Conference February 27, 2013

The impact of the work under partial load on the energy efficiency of an air-to-water heat pump

GHP Data Collection and Monitoring System at the SRRL

Inverter Drive Control and Seasonal Performance Analysis of a Single Speed Unitary Air-Source Split-System Heat Pump

Heat exchanger performance of ground source heat pump by water cooling method

Design and development of a residential gas-fired heat pump

This article appeared in a journal published by Elsevier. The attached copy is furnished to the author for internal non-commercial research and

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

WT Model Water-to-Water Heat Pump

COPs, EERs, and SEERs

Recent U. S. R&D results from IEA HPP Annex 41

NORTH AMERICAN MONITORING OF A HOTEL WITH ROOM SIZE GSHPS

geoexchange as an alternative energy source DESIGN APPROACHES

Evaluating Environmental Benefits of Ground Source Heat Pumps: The Strengths and Weaknesses of COP and SCOP i

RESTORE 1030TM Testing Protocol

Connecticut Residential Ground Source Heat Pump Impact Evaluation & Market Assessment

BETTER BUILDINGS BY DESIGN Sheraton Conference Center Burlington, Vermont. February 8, 2012

LEADER IN SUSTAINABLE TECHNOLOGIES HVAC LIGHTING ENERGY SOLUTIONS MIDDLE EAST

Research on Ground Source Heat Pump Design

Go Green, Get Geo! GEOTHERMAL SYSTEMS GEOEXCEL: ULTIMATE PERFORMANCE AND RELIABILITY GEO-411. Geothermal Loop Types

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

Geothermal Alliance of IL ComEd trade ally event January 9 and 11, 2018

Adam Alaica, M.A.Sc., E.I.T.

Field Commander. Overview. Operations. Custom Solution. Building Startup/Shutdown

Farm Energy IQ. Farms Today Securing Our Energy Future

Appendix B. Glossary of Steam Turbine Terms

REFRIGERATED WAREHOUSES AND DEMAND RESPONSE

Intelligent Process Cooling Technology Saves on Water and Energy, Improves Productivity

Geothermal HVAC Systems - The Basics and Applications (Draft) George Hu, P.E., LEED AP Air Water Energy Engineers, Inc.

Future changes in the carbon intensity of grid electricity and its effect on the carbon emissions from domestic electric heating solutions

Performance and Applications of Cold- Climate Air Source Heat Pumps

Residential HVAC Rebate Program Manual

Wakulla Chamber of Commerce July Place your cover photo here. Size and crop it to 4 high x 9.6 wide. Presented by Derick Farfan

Geothermal Comfort Systems

2. Chilled Water Storage: A 4.4-million gallon chilled water storage tank improves Cornell s ability to meet peak cooling needs.

A. Cornell s district energy systems include the following components:

Danish Development Center for District Energy

Transcription:

Ground Source Heat Pump System Performance: Measuring the COP Ground Energy Support, LLC June 2013 1 Introduction This article is the second in a three-part series prepared by Ground Energy Support LLC (GES) that will highlight some of the lessons learned from over 100,000 hours of real-time ground source heat pump (GSHP) monitoring data. This is written for GSHP installers of residential and light commercial systems who want to learn how to leverage real-time Performance Monitoring to build better GSHP systems, reduce their risk and callbacks, and ensure customer satisfaction. The previous article focused on showing how data from real-time monitoring can be used to assess how the ground loop is performing relative to both the installed capacity and the measured heating load. The daily load profiles presented in that article are now available to GxTracker TM users as part of their Performance screens (login required to view Load Profile graph). This article focuses on the overall system performance, factors that affect performance, how real-time monitoring can be used to evaluate performance of installed equipment, and identify and address issues before they become problems. The number of sites represents a relatively small sample size and the different measurement techniques used at the sites result in different levels of accuracy. In spite of these limitations, we are able to identify and illustrate several factors that affect system performance. 2 Measuring GSHP System Performance GSHP systems have the potential to significantly reduce the energy needs for space heating and cooling (an estimated 4 Quadrillion BTUS in the US) and reduce green- 1

house gas emissions. However, these benefits will only be realized if the systems operate efficiently. Efficient operation requires proper design, installation, and maintenance. One common method for assessing system performance of residential systems is to review the customer s electric bills on a regular basis. While lower electric bills are a clear indication that the systems are operating efficiently, it is often difficult to parse out other factors that contribute to the overall electrical consumption. Additional challenges to using a customer s electric bill to assess system performance include: new construction has no baseline for comparison; retrofits will often combine the addition of a heat pump with other efficiency measures, making it difficult to attribute the savings to the GSHP; and finally, when an electric bill is higher than expected, the cause may be unrelated to the GSHP system. One of the biggest disadvantages of relying on electric bills as a measure of system performance is that the homeowner is left to identify and report GSHP performance problems. In short, the most effective way to demonstrate that a GSHP system is performing efficiently, and thus ensure customer satisfaction, is to monitor the system in real-time so as to assess key performance metrics. Many factors contribute to the overall performance of a GSHP system. Through our monitoring activities to date, we have found the main factors to be: Heat pump performance and loop temperature Pumping energy necessary to circulate loop fluid Heat pump cycling patterns Auxiliary electric heat One of the key metrics of assessing how a GSHP system is performing in heating mode is the Coefficient of Performance (COP). The COP is the ratio of useable thermal energy to the thermal equivalent of the electricity used to operate the system. While measuring the COP is not always the primary objective, all of our real-time monitoring systems include, at a minimum, measurements of entering and leaving water temperature (EWT and LWT), heat pump status, and an estimate of fluid flow. When power measurements are not available, power consumption is modeled using the heat pump specifications, a pump penalty based on type of system and flowrate, and measured runtimes. These methods provide representative values of COP with an error of +/- 20% and are intended to show overall trends in system behavior. 2

In some installations, a higher level of accuracy is desired and additional measures of power consumption and, if necessary, flowrate can be included. When accurate measures of both flow and power consumption are available, the accuracy of the COP improves to approximately +/-5%. Because the accuracy of the computed COP varies from site to site and quality assurance measures are necessary to insure the values are representative, COPs are not computed automatically as part of our performance metrics. Rather, the necessary components are available by downloading either the minute-resolution observations or integrated daily values. 3 Daily Average System COPs The Daily COP values presented in Figure 1 and summarized in Table 1 illustrate some of the main factors that affect performance. Overall, there is an upward trend in performance as heat pump technology has gone from single stage to multi-stage compressors. The system with the lowest performance (Site A) has single stage heat pumps using a standing column well. The two-stage heat pump on a standing column well (Site B) has a higher COP, but is adversely affected by the power required for fluid pumping. The COP of the two-stage system on the closed vertical loop (Site C) varies more through the year due to both the change in EWT and the use of the auxiliary electrical heat in late February. The performance of the two-stage system using two well groundwater loop (Site D) is comparable to, and slightly higher than, the other two-stage heat pump systems. The system with a variable stage heat pump (Site E) has the highest average COP. This is likely due to a combination of the variable-stage technology and its geographic location which enabled it to maintain higher EWTs throughout the winter. These COP values are consistent with those reported by Puttagunta and others in their 2010 study of residential ground-source heat pumps. We have also found that, while the in-field performance is typically less than the AHRI rating, the systems are seen to provide a reliable technology for heating and cooling at consistently lower cost than most conventional systems. 4 Factors Affecting System COP There are several factors that affect the overall GSHP system performance. Because of the wide range in GSHP system designs and equipment available, there is not a 3

Figure 1: Daily Average Measured COP at 5 installations ranging from US Climate Zones 4 to 1. See Table 1 for site designations and seasonal average COPs. Power measurements are included for Sites B, C, and E. Table 1: Seasonal Average System COPs, Winter 2012-2013. Site System Description Average COP A Standing Column Well, 2 Heat Pumps, Single Stage 2.74 B Standing Column Well, 1 Heat Pump, Two Stage 3.15 C Closed Vertical Loop, 1 Heat Pump, Two Stage 3.27 D Open Two Well System, 1 Heat Pump, Two Stage 3.33 E Closed Horizontal Loop, 2 Heat Pumps, Variable Stage 4.18 4

single best approach to optimizing performance. Rather, we show how monitoring can help characterize the elements that affect specific installations. Again, the lessons learned and examples presented in this initial series of articles focuses on heating mode and uses examples from installations ranging from US Climate Zones 4 to 1. 4.1 Heat Pump Cycling It has long been recognized that rapid cycling of heat pumps diminishes performance and increases mechanical wear on the equipment. In recent years, more efficient dual stage heat pumps have become common that enable heat pumps to operate for longer cycles, produce lower heat output, and use less electricity. Figure 2 shows the heat pump cycle patterns for three different systems: one with two single-stage heat pumps, a two-stage heat pump, and one with a variablestage heat pump. While the single-stage heat pumps reach their expected heat of extraction ( 22MBtuH for the 3 ton and 40MBtuH for the 5 ton), the average production of the heat pumps (while running) over this same period was 17 MBtuH and 32 MBtuH, about 20% below their steady state production. In contrast, the twostage heat pump is able to maintain its steady state heat production in part load for cycles of approximately 30 minutes and then, when additional heat is necessary, switch into full load. With two-stage heat pumps there is much less efficiency lost from cycling on and off. The final example is a new variable stage heat pump that operates over extended periods of time, adjusting the heat output to meet demand. In general, the lower stages provide greater performance by varying heat output over multiple stages thereby increasing overall performance. 4.2 Loop Temperature Entering water temperature is well-recognized as one of the leading factors affecting system performance and heat pump manufacturers provide performance specifications for temperature ranging from 25 to 100 F. In the example shown below (Case A from last week s article on Loop Performance), the power consumption of the heat pump circuit (which includes the flow center), and the Auxiliary electric heat are being monitored separately with a WattNode power meter. The COP is calculated for 15-minute intervals through the 2012-2013 winter. To remove the variability of performance associated with the heat pump cycling on and off, we only include 15-minute intervals for which the heat pump was running continuously. The EWT ranges from 33 to 51 F. While there is an overall correlation between COP and EWT, there is also considerable variability 5

Figure 2: Three examples of heat pump cycling patterns. Each diagram represents the GeoExchange for a six hour period of heating (heat extraction). Top image is from a system with two single stage heat pumps (5-ton and 3-ton units). Middle image shows the GeoExchange for a two-stage (4-ton) heat pump. Bottom image is for a variable stage (3-ton) heat pump. 6

Figure 3: Measured COP for 15-minute intervals during which heat pump was running continuously. (A) Measured COP for different times of the day relative to manufacturer COP for different loop temperatures. COP values in (A) include power from both compressor and flow center. (B) Same measured COP values (green) compared to the COP in (A) with the pump power removed (yellow). 7

at a given temperature. In the article last week on Loop Performance, we conjectured that the pattern of thermostat settings (set back at night resulting in a greater call for heat in the morning) might affect the overall performance. While the average COPs for the morning period are lower than the night, the difference is not statistically significant. If any difference exists, it appears to be related more to the operation at full load rather than lower loop temperatures. 4.3 Pump Penalty One of the most notable features of Figure 3A is the departure of the measured from the manufacturer s specified COPs (dashed line). The primary factor explaining this departure is the power required to run the pump, which is included in Figure 3A. To illustrate the significance of the pump penalty, we remove a constant value of 500W from the total power measurements and recompute the COP to represent the pump penalty and re-compute the COP for just the compressor (Figure 3B). When the pump power is removed, the measured COP lines up well with the manufacturer specification for the COP based on the amount of thermal energy produced per unit of electrical energy consumed by the compressor. As noted above, the average COP of Site B (Figure 1, Table 1) is significantly reduced by the pumping penalty that has been measured and averages approximately 800W. For a 3-ton heat pump, the pumping penalty alone reduces the COP from 4.2 to 3.2. It is important to note that the high pump penalty is not indicative of the open loop, but rather the pump selection and materials used in installation. 4.4 Auxiliary Electric Heat When auxiliary electric heat is installed as part of a GSHP system it can augment the heat provided by the ground loop and compressor during times when the thermostat is calling for additional heat. In the example in Figure 1 with the closed loop vertical borehole with a two-stage heat pump, the auxiliary was used for a short period of time in late February 2013. In this example, the auxiliary heat was used for short periods of time to supplement heat provided by the heat pump; and while it had a significant effect on the daily COP, it had a relatively minor effect on the overall average COP for the winter season. In cases where the auxiliary is used more frequently throughout the day and over longer periods in the heating season, it will quickly erode the overall system performance. 8

. Figure 4: Power consumption for 24-hour period at Site C in which heat pump (blue line) cycles between part and full load and calls for auxiliary heat (orange line) to supplement. While the auxiliary heat itself has a COP of 1, its impact on the daily average COP is modest (see Figure 1) 5 Equipment Malfunctioning The analysis above focuses on how individual components contribute to overall system performance when the system is functioning properly. In addition to the benefit of helping to understand the performance of a specific installation under normal operating conditions, monitoring can also help identify when components of the system are NOT operating normally. Some specific examples of equipment malfunction that monitoring has both detected and helped to diagnose include: Faulty Expansion Valve was indicated by periods of heat rejection to the ground during heating mode. After the repair, the performance of the heat pump increased by 80%.. Low Refrigerant charge was indicated by lower-than-expected geoexchange. After a service call, the performance increased by 30%. Circulating Pump running when compressor is off, due to problems with the control board and heat pump going into freeze protection. 6 Web-Based GSHP System Monitoring There are several options for web-based ground loop monitoring on the market today, and more options will undoubtedly come onto the market in the future. The 9

following discussion pertains to GES s monitoring system, the GxTracker TM. The GxTracker TM system is modular, with components added or subtracted based on the characteristics of your GSHP system, and what your monitoring objectives are. For reference, a basic GSHP monitoring system for up to two heat pumps that can produce the data shown above can cost less than $1,000. The basic components of the GxTracker TM monitoring system include 1) sensors and optional meters that capture data about the temperatures and optionally, the flow and electrical consumption of your GSHP system; and 2) cloud-based data processing software presented in an easy-to-use online interface. 6.1 Data Capture The GxTracker TM measures entering and leaving water temperature with calibrated sensors attached to the the outside of the EWT and LWT pipes for each heat pump. The sensor design and installation instructions ensure a good thermal connection with the pipe. For example, the sensors must be attached to metal, and are equipped with special thermal pads to maximize the thermal connection. The system flow rate is either taken as constant (system design rate) or measured with a flowmeter(s). The heat pump on/off status is detected either with a current switch, current transducer, or flow meter (if installed). GSHP system kwh usage is based either on heat pump design specifications coupled with heat pump runtimes OR is captured by installing an optional power meter(s). Power meters and associated benefits are discussed in next week s article. In addition, we pull outdoor air temperature from the nearest NWS weather station every 15-minutes. 6.2 Data Analysis and Presentation At the web interface, GxTracker TM users can see a variety of useful system information, including system settings, real-time data, system performance data analyses, and cost and carbon benefit analyses. Data downloads are available through a password-protected user account. The user can download minute resolution data for the previous three months. Daily system performance metrics (total BTUs, geoexchange from each heat pump, runtimes, minimum EWT, kwh, heating and cooling degree days, and hot water generated for systems equipped with the GxTracker TM Hot Water kit) are archived and available to the user indefinitely. 10