Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, Green & Energy saving concept of ABB MV apparatus For a better tomorrow.

Similar documents
INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES

Gas-insulated medium-voltage switchgear. for wind parks. Answers for energy.

General CIRCUIT BREAKER WITH SF6 GAS

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

Product Environmental Profile Premset 15 kv D02N, D06H and I06T functional units

Gas-insulated medium-voltage switchgear. for marine and offshore applications. Answers for energy.

Metal-enclosed single busbar, Solid and Air-Insulated switchgear

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

UPS installation safety requirements

Smart Integration of LV MCC to Improve Plant efficiency and Reduce life cycle cost

Medium Voltage Service Maintenance and refurbishment

Recent Technical Trends of Vacuum Circuit-Breakers (VCBs)

Proposal for amendment to the legal inspection regulation for electrical products

SECTION SECONDARY UNIT SUBSTATIONS

ABSORPTION FILTERS FAP SERIES

DISTRIBUTION SYSTEM ASSET CONDITION ASSESSMENT UPDATE

Complete Electrical Engineering Solutions. The Hospital Solution. Prevent Hospital Power Interruptions Improve Energy and Reduce Operating Costs

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

A SUBSTATION CONCEPT FOR CHANGEABLE LOAD CONDITIONS

Carry out routine inspection and service on high voltage indoor metal clad circuit breakers and bus

SECTION SECONDARY UNIT SUBSTATIONS SECONDARY LESS THAN 1000 V

The switchboard with a lot more. sivacon

It is standard practice and all manufacturers to abide by this. It is standard practice and all manufacturers to abide by this.

Pre-Qualification Certificate

IMPLEMENTATION RULES FOR COMPULSORY CERTIFICATION OF ELECTRICAL AND ELECTRONIC PRODUCTS

OPERATION & MAINTENANCE. Preventive & Predictive Quality Services

Name: Phil Langlois Position: Lead Electrical Engineer, Ontario Operations

Gas-insulated medium-voltage switchgear 8DJH 36 siemens.com/8djh36

Air-Insulated Medium-Voltage Switchgear NXAIR Totally Integrated Power NXAIR siemens.com/nxair

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS

INFLUENCE OF HEAT SOURCE LOCATION ON AIR TEMPERATURES IN SEALED MV SWITCHGEAR

Switchboards Division

4.1 Reduction/elimination of environmentally sensitive materials

Focus on Medium Voltage Value for the customer Solutions Ormazabal

Friday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

EL405. Kimchi Refrigerators [EL /4/ ]

DESIGN. DEVELOP. DELIVER. CAPABILITY STATEMENT

SWITCH GEAR SERVICE AND MAINTAINNANCE SAFETY MEASURES AND REQUIREMENTS

Certificate of non-use of The Controlled Substances

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENTS AND QUANTITIES

Your Reliable Service Partner in Scotland for Rotating Equipment

ELECTRICAL INSPECTION BULLETIN (Effective )

Totally Integrated Power NXAIR. Flexible in Application, Consistent in Safety. Air-Insulated Medium-Voltage Switchgear NXAIR.

PRIMARY UNIT SUBSTATIONS SECONDARY 1000 V AND ABOVE SECTION SECTION

Subject: China RoHS Presented By: Homi Ahmadi Venue: IEEE- PSES-Orange County, CA Date: January 2008

Desktop computer power profile settings of the Energy Star. Period of Inactivity System State program within the

sivacon Safety Embedded in Supreme Design: The Power Distribution Board, that sets new standards.

Reliable and economical power supply for industrial plants

33-SDMS-02 SPECIFICATIONS FOR

Environmental Product Declaration Registration number: S-P Rev. 0 22/12/05. Tmax T2. Low voltage circuit breaker

Prisma Plus enclosures up to 630 A

IEC Oil Filled & SF 6 Gas Current Transformers

Optimize the Performance of New Electrical Equipment Installations

Green Label Product Room Air Conditioner (TGL- 7- R3-14)

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

Type THP Serial No Rated voltage 145 kv Rated normal current 2500 A Rated short-circuit current 40 ka Rated frequency 50/60 Hz

PT100MC0MPx. Surface Mount Type, Transparent Resin Phototransistor. PT100MC0MPx. Agency Approvals/Compliance. Features. Model Line-up.

Distributing electrical power safely and economically

ABB drives for water Medium voltage drives for energy savings and life-cycle improvements

Product-related services for switchgear, transformers, and cables

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4

Project Procedure 1.0 PURPOSE 2.0 SCOPE 3.0 REFERENCES. No.: P /19/2011 PAGE 1 OF 4 FACILITY LIGHTING SYSTEMS INSTALLATION

HONG KONG GREEN BUILDING COUNCIL

INTER PLANT STANDARD STEEL INDUSTRY

Green Switching. Is about making responsible choices for energy distribution

WEST ZONE POWER DISTRIBUTION CO. LTD. (WZPDCL) TENDER DOCUMENT FOR

RL SERIES. Two Stage Light Oil Burners FIRING RATES LIGHT OIL

Thermal Recovery Characteristics of a CO 2 Mixture Gas Circuit Breaker

Welding Machines for shipboard use

Study Committee A3. High Voltage Equipment. Action Plan

Prefabrication & Distribution A Global Solution GRC. Prefabricated Substation PARS TABLEAU

SECTION REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

Also includes - Auxiliary Contacts & Shunt Trip - RCCB and - Distribution Boards

Product Environmental Profile

1. INTRODUCTION. Operational Excellence Model. 1.1 Purpose. 1.2 Scope. 1.3 Rate Schedule. 1.4 Cooperation

Temporary Wiring. Low-Voltage Electrical Safety Orders

Environmental Pollution Caused by Electrical Power Devices

Siemens Controls. The power distribution board that sets new standards. SIVACON S4 safe, cost-efficient and flexible SIVACON

THE ENERGY ENGINEERING COMPANY. E²CON-GE ENGINE CONTROLLER Retrofit system based on openecs for modernizing GE Jenbacher gas engines.

ABSORPTION HYBRID FILTER FAR-Q TYPE

Product brochure Multi Functional Switchgear PASS M kv Flexible and compact switchgear solutions for windfarms

BILL OF QUANTITIES - PROJECT ELECTRICAL WORK OF PH-I FOR ASSAM RIFLES, DWARKA, NEW DELHI

FURUKAWA ELECTRIC TAPE FOR ELECTRICAL USES

SF6 Gas Free MV Switchgear 25.8kV Solid Insulated Switchgear

Houston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

TECHNICAL SPECIFICATION OF HORIZONTAL MILLING MACHINE

End-winding vibration monitoring: Pivotal in preventing major damage on a large turbo-generator

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Medium Voltage Switchgear. Basis of Design.

SECTION PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS

Environmental Product Declaration

Your partner for the right solution

Item Description Qty Unit Rate (Kshs) Amount (Kshs) 1 item

ECP SECONDARY COMMISSIONING REQUIREMENTS

RL SERIES. Two Stage Light Oil Burners FIRING RATES LIGHT OIL

Circuit Breaker Asset Management Using Intelligent Electronic Device (IED)- Based Health Monitoring

Product Environmental Profile

SUMMARY OF PRICES FOR 30MVA 161/24/36 kv MOBILE SUBSTATION ACCORDING to SR-152

EDS GAS ZONE IDENTIFICATION AND ALARMS ON GAS INSULATED SWITCHGEAR

Transcription:

Alvin.Xu, ABB Xiamen Switchgear Co,Ltd, 2014-11 Green & Energy saving concept of ABB MV apparatus For a better tomorrow Slide 1

VD4 vacuum circuit-breaker in China Inheritance and innovation Y1992 Y2003 Y2006 Y2010 Y2014 2003 Modular solution 2006 2014- Environmentfriendly 2010- PT poles Full performance improvement To provide the most advanced solutions for MV switchgear 1992 Embedded poles First to introduce the mid-set switchgear to China Slide 2

Our understanding of medium voltage switchgear What kind of MV switchgear is the best to meet market? Safety and reliable as the base Green Smart Smart is the core Oriented towards green Safety Reliable Slide 3

Energy-saving and green in ABB MV switchgear field Contents Advanced technology Innovation for the embedded pole - energy-saving and environment-friendly PT pole Energy saving and reliable low consumption coil Reliable low-consumption mechanism - magnetic drive Remove "SF6 gas" products - reduce the greenhouse effect Science selection of material The materials with flame retardant - reduce device loss and off-line cost Atoxic wires - reduce the impact on the environment Green manufacturing technology Trivalent chromium electroplating technique - conforms to RoHs statement. Life cycle cost (LCC) management Improve the service life - reduce energy consumption The most advanced smart solution - create the whole life cycle cost advantage Environment symbol certification product - power and productivity for a better world Slide 4

Advanced technology PT poles and VD4 The excellent technical parameters: 50,000 CO mechanical life 50 + E2 class short-circuit M&B capacity 5 times the charpy impact resistance of the epoxy resin 30,000 CO electric life 30years service life -25 ºC environmental withstand temperature Slide 5

Advanced technology Green PT poles Cycling time of epoxy embedded pole are 5 ~ 10 minutes by different variants. Demolding Embedding the vacuum interrupter Close mold Cycle time 90s! Injection Open mold Cooling/ Preparation of new material The production efficiency of PT poles is tens of times of traditional epoxy resin embedded poles; The world's leading technology not only has brought the production efficiency, but also ensure the ultra high consistency of the quality; The energy and power consumption of production are greatly reduced. Slide 6

Advanced technology Green PT poles 100% recycle Retirement cost Shut down cost Energy cost Mainten ance cost Operation cost installatio n and commissi oning cost Initia l cost 20 years later, the quantity of medium voltage circuit-breaker in the whole society will be almost 20 million. Assumes that the height of each phase epoxy resin pole is 65 cm 0.65m * 3 * 20,000,000 / 1000 = 40,000km (a circle around the earth!) Epoxy resin, as a thermosetting resin material, may not be recycled. With stable performance, insoluble and infusible, good chemical resistance. It will not be degraded after abandoned. The only recycle use: paving road after crushed? Slide 7

Advanced technology Green PT poles - 100% recycle PT materials can be 100% recycled, and the recycle process is very simple with low cost. Crush Re-inject into other products Thousands of application, for example: Tape, used for road signs Chemical high-pressure pipes, valves A variety of industrial components, such as automotive engine Slide 8

Advanced technology Green PT poles PT pole reduce emissions of CO2 more than 50% by energy-saving. The embedded poles PT1 reduce emissions of CO2 by more than 50 %. Each pole production save 105 kwh power This is equivalent to savings of over 3,000 t CO2 each year. 27,000 Equivalent to less fell of 27000 trees per year. In other words,each one circuitbreaker= less cut one tree. Slide 9

Advanced technology Energy saving and reliable low power coil Incandescent lamp Energy saving lamp LED lamp Commonly used coil on the market Power is 20W ~ 200W Existing safe double coil design The power is only 5W Each coil will save more than 50 million kwh every year. New generation of smart coil The power is only 1.5W Further to save energy Slide 10

Advanced technology VSC contactor with magnetic drive low consumption Energy consumption of VSC with permanent magnetic mechanism:5w Energy consumption of contactors with traditional mechanism:50~180 W ABB s strategy of sustainable development reduce operation cost Compared with the traditional contactor, VSC vacuum contactor could save 14,000~31,500 kwh in life cycle (20 years). By saving energy, there are less emissions of about 3000~30000 kg CO2. In power plant, as 600MW set for example, using 60 VSC vacuum contactor with a full life cycle thant could save 80~1.8 million kwh, and less emissions of 780 ~ 1800 tons CO2. Slide 11

Advanced technology Remove SF 6 gas products - reduce the greenhouse effect Why choose SF6? A synthetic noble gas; Strong electronegativity. Easy to combine with electron to form anion, weaken the ability of electron impact ionization; SF6 According to these characteristics, in the 40.5kV voltage and for capacitive load, SF6 circuit-breaker is still the best choice. Quick recombination. SF6 will be decomposed under the high temperature arc, but recombine instantly the arc disappear; Cooling effect. Heat conduction of SF6 is 2~5 times of air. Slide 12

Advanced technology The upgrade 40.5kV vacuum circuit-breaker Benefit from: The new contact material is developed by Germany ABB; Further optimization of the circuit-breaker mechanical parameters. The upgrade 40.5kV VD4 can meet: Rated breaking current of back-to-back capacitor bank 800A*; The first vacuum circuit-breaker at 40.5kV to switch 800A back-to-back capacitor bank. Note: The actual current through the type test up to 820A Slide 13

Science selection of material Improve the safety of equipment - reduce the loss of failure Flame retardant materials Composite materials with good flame retardants; Limit the scope of accident and to prevent accident expand; Reduce the cost of customer equipment loss and off-line! Slide 14

Science selection of material Improve the safety of equipment - reduce the loss of failure The application for non flame retardant materials will expand the scope of failure. Slide 15

Science selection of material Improve the safety of equipment - reduce the loss of failure The secondary parts all use the high cost with low atoxic wire, which does not contain halogen (F, Cl, Br, I, At), and plumbum, cadmium, chromium, mercury which damage the environmental. Its combustion does not emit atoxic fumes, and has good flame retardant. Slide 16

Green manufacturing technology The commitment for environment The production process of MV products fully keep to ABB strict standards and specification, as far as possible to reduce the pollution of the environment. For example: Cr6+ Zinc plating process has been completely eliminated by Cr3+ Zinc plating, which is more difficult and high cost, but with low atoxic and no pollution. Cr6+ is easy to be absorbed and accumulated in the body, its atoxic is more 100 times than Cr3+. As the ROHS policy, the content of Cr6+ shall be under 0.1%. Slide 17

Life cycle cost (LCC) management Full life cycle for switchgear Establish the full life cycle cost management for equipment, improve the service life, reduce energy consumption Warrant y extensio n Technic al support Remote diagnosi s Cloud service protocol Mainten ance diagnosi s Patrol scheme Rapid support Reliability Operation efficiency Repair Diagnosis Original spare parts Engineering consulting Failure maintenance solution On-site inspection Maintenance Training Upgrade Period Retrofit solution Risk maintenance and condition-based maintenance solution Repair Run-in period Stable period Focus period fluctuant period Life-extension period Service life 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 30 Life cycle - Stable period Focus period Fluctuant period Life-extension period Maintenance Once a year Diagnosis Slide 18

Focus period and fluctuant period Familiar failure for switchgear Statistics show that the typical failure and rate for China power system in the 1990s as below: Mechanical fault (fail to open or close, reject, malfunction): 33.3% Dielectric fault: 37.3% Temperature rise fault and others (currentcarrying): 29.4% Mechanical fault caused by grease aging Dielectric failure between busbar and frame Temperature rise fault of the main circuit Dielectric fault caused by temperature rise Slide 19

Life cycle cost (LCC) management Smart solution based on whole switchgear Safe i-solution Smart TR online monitoring CB parameter monitoring Full motorized drive Reliable Green For tulip of CB For busbar lap surface For lap joints of outgoing cable end For LV compartment Reliable wireless RF technology Embedded design, without impact one dielectric and PD Self supply and magnetic saturation technology High quality components Charging time and average current of charging motor Tripping current of open and close coil Open and closing time and speed of circuit-breaker Non intrusive technology for voltage and current measurement Completely isolated from the control/protection system Motorized truck system Motorized earthing switch system Intelligent control and protection The turbine worm drive chain Unique intelligent motor control and protection system Tens of thousands on-site service experience Slide 20

Life cycle cost (LCC) management Help to identify the early potential failure Online monitoring is helpful to indentify the early potential failures of the circuit breakers, e.g. to a charging motor: Failure mode:gear wheel broken. Initial stage:one or two teeth broken, but motor could still be able to finish the charging After several operations the entire gear pairs damaged completely The online monitoring system could detect the abnormal current vibration, alarm is given in early stage. Replacement plan can be made before it is completely out of work. No emergency cases happened. Slide 21

Life cycle cost (LCC) management The most green energy is the energy saved To consume the resources and energy in the whole life cycle; Energy cost Ce Environment cost Cenv Recycle cost Cd The cost of energy consumption, environment, disposal, recycling and out of commission should be considered. Environmental symbol is not only the legal proof of environmental friendly for product, but also the guarantee of sustainable development for company. Product must pass the evaluation certified by the State Certification Committee of Environmental Labeling(SCCEL) of the State Environmental Protection Agency(SEPA).It can be declared as green products only after qualified. Slide 22

Slide 23