This paper was presented at 12th REHVA World Congress (Clima 2016).

Similar documents
Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields

Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers

A SIMPLE TOOL FOR SIMULATION OF GROUND SOURCE HEAT PUMP SYSTEMS

Multi injection rate Thermal response test

A SIMPLE MODEL TO ACCOUNT FOR THERMAL CAPACITY IN BOREHOLES

PRELIMINARY INTERMODEL COMPARISON OF GROUND HEAT EXCHANGER SIMULATION MODELS

INCORPORATION OF GROUNDWATER FLOW INTO NUMERICAL MODELS AND DESIGN MODELS

PREPROCESSOR FOR THE GENERATION OF G-FUNCTIONS USED IN THE SIMULATION OF GEOTHERMAL SYSTEMS

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

APPLICATIONS OF A DYNAMIC THREE-DIMENSIONAL NUMERICAL MODEL FOR BOREHOLE HEAT EXCHANGERS. M. He, S.J. Rees, L. Shao

Parametric Study for Evaluation of Design Parameters of Standing Column Well

IMPROVED DESIGN METHODS FOR GROUND HEAT EXCHANGERS RACHEL MARIE GRUNDMANN. Bachelor of Science in Mechanical Engineering. Oklahoma State University

A quasi-two-dimensional standing column well model for ground source heat pump systems

First Thermal Response Test in Libya Abstract 1. Introduction 2. Background

Available online at ScienceDirect. Energy Procedia 78 (2015 )

A Novel Coaxial Borehole Heat Exchanger: Description and First Distributed Thermal Response Test Measurements

Numerical and analytical analysis of groundwater influence on the pile ground heat exchanger with cast-in spiral coils

February 20, 2014: The attached paper was presented at the 2014 ASHRAE Winter Meeting in New York City. It was published as a conference paper.

This is a repository copy of The Average Temperature of Energy Piles.

Experimental Validation of a Numerical Model for the Thermal Response of a Borehole Field

Nanocomposite materials used for ground heat exchanger pipes

This is a repository copy of Validation of vertical ground heat exchanger design methodologies.

Simulation of 2D Heat Transfer in a Horizontal Plane with Thermal Resistance-Capacitance Model

DISTRIBUTED TEMPERATURE MEASUREMENTS ON A MULTI-PIPE COAXIAL BOREHOLE HEAT EXCHANGER

TEMPERATURE STRATIFICATION OF CIRCULAR BOREHOLE THERMAL ENERGY STORAGES

A Model for Annual Simulation of Standing Column Well Ground Heat Exchangers

Comparison of Borehole Heat Exchangers (BHEs): State of the Art vs. Novel Design Approaches

Combination of solar collectors and ground-source heat pump for small buildings

NUMERICAL MODELLING OF MULTIPLE STANDING COLUMN WELLS FOR HEATING AND COOLING BUILDINGS

Study on Heat Exchange Characteristics for PHC Energy Piles

Modeling of Usage of Air Injection Well in a Geothermal System

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

Nanocomposite Materials Used for Ground Heat Exchanger Pipes

Modeling of Standing Column Wells in Ground Source Heat Pump Systems

Improvement of a Two-Dimensional Borehole Heat Exchanger Model

Pitfalls of Rules of Thumb in Geothermal Heat Pump Design

Hafiz M K U Haq 1, Birgitta J. Martinkauppi 1, and Erkki Hiltunen 1 1 Department of Energy Technology

Field Validation of a Short Time Step Model for Vertical Ground-Loop Heat Exchangers

Optimal Design for a Hybrid Ground-Source Heat Pump

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

ENERGY SAVINGS, SIMULATIONS AND ECONOMIC ANALYSIS OF A GROUND SOURCE HEAT PUMP WITH VERTICAL BOREHOLE HEAT EXCHANGERS FOR A BELGIAN OFFICE BUILDING

SIMULATION AND OPTIMIZATION OF GROUND SOURCE HEAT PUMP SYSTEMS

Distributed Thermal Response Test on a Grouted U-pipe Borehole Heat Exchanger

H.J.L. Witte, A.J. van Gelder. Groenholland BV Valschermkade 26, 1059 CD Amsterdam, The Netherlands Tel:

SIMULATION OF A DOMESTIC GROUND SOURCE HEAT PUMP SYSTEM USING A TRANSIENT NUMERICAL BOREHOLE HEAT EXCHANGER MODEL

Performance investigation of multiple-tube ground heat exchangers for ground-source heat pump

DOE Task 99-4 Extension of Design and Simulation Models 3/24/00 EXTENSION OF EXISTING DESIGN AND SIMULATION MODELS

Research on Ground Source Heat Pump Design

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

A review on heat transfer enhancement of borehole heat exchanger

EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS

Horizontal Borehole Study

This is the published version of a paper presented at European Geothermal Congress 2016 Strasbourg, September 2016.

FIRST THERMAL RESPONSE TEST IN BULGARIA

Determination of Thermal Conductivity of Soil Using Standard Cone Penetration Test

Numerical Modelling of Geothermal Borehole Heat Exchanger Systems Miaomiao He

The influence of the ground parameters assumptions on the low enthalpy heat pump s energy source simulation s results

Simulation and data based identification of parameters affecting seasonal ATES efficiency

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Finite Volume Based Computer Programs for Ground Source Heat Pump Systems

A Simple Engineering Analysis Method to Evaluate the Geothermal Potential from a Hot Water Aquifer

An evaluation of ground thermal properties measure accuracy by thermal response test of horizontal ground heat exchangers

1 INTRODUCTION. Keywords: ground source heat pump; energy pile; geothermal; geophysics; ground temperature

Enhancement of Heat Exchange Capacity of Ground Heat Exchangers by Injecting Water into Wells

The Superposition Borehole Model for TRNSYS (TRNSBM)

THERMAL RESPONSE TEST, A ROUTINE METHOD TO DETERMINE THERMAL GROUND PROPERTIES FOR GSHP DESIGN

REGRESSION ANALYSIS ON INFLUENCE OF VARIOUS FACTORS ON HEAT TRANSFER OF VERTICAL GROUND HEAT EXCHANGER

This paper was presented at 12th REHVA World Congress (Clima 2016).

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

Ground-source Heat Pumps State of the Art

Model development of a blast furnace stove

IMPROVEMENTS IN DESIGN PROCEDURES FOR GROUND SOURCE AND HYBRID GROUND SOURCE HEAT PUMP SYSTEMS JAMES R. CULLIN

Effect of Vibration on Heat Transfer Enhancement in a Rectangular Channel Heat Exchanger

Technology, development status, and routine application of Thermal Response Test

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

Efficiency Increase of Soil Heat Exchangers due to Groundwater Flow and Air Injection Wells

Energy and geotechnical behaviour of energy piles for different design solutions

Thermal Performances Of Three Types Of Ground Heat Exchangers In Short-Time Period Of Operation

Thermal Response Test Current Status and World-Wide Application

Citation for the original published paper (version of record):

In-situ measurements of ground thermal properties around borehole heat exchangers in Plovdiv, Bulgaria

Modeling a Novel Shallow Ground Heat Exchanger

LICENTIATE THESIS. Thermal Response Test - In Situ Measurements of Thermal Properties in Hard Rock. Signhild Gehlin.

FLOW PATTERN IN CO 2 -LUBURICANT TWO-PHASE FLOW AT SUPERCRITICAL PRESSURE

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

MODELING THE VIABILITY OF UNDERGROUND COAL FIRES AS A HEAT SOURCE FOR ELECTRICAL POWER GENERATION

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Experimental Analysis of Heat Transfer Enhancement Using Fins in Pin Fin Apparatus

Course syllabus Fluid Mechanics

Deep borehole heat exchangers

Bore field sizing : Theory and applications

DESIGN AND OPTIMUM CONTROL OF A SWEDISH DUAL- SOURCE (AIR AND GROUND) HEAT PUMP SYSTEM

An Analysis on Cost Reduction Potential of Vertical Bore Ground Heat Exchangers Used for Ground Source Heat Pump Systems

Numerical Prediction of Thermodynamics and Heat Transfer Characteristics of Nano Fluid.

Magda Kaczmarczyk and Michał Kaczmarczyk

HEAT TRANSFER ANALYSIS OF GEOTHERMAL HEAT EXCHANGERS IN GROUND-COUPLED HEAT PUMP SYSTEMS. Abstract. 1. Introduction

New Large Geothermal Storage Project in Zurich/Switzerland for Heating and Cooling

Simulation of a Geothermal Bridge Deck Anti-icing System and Experimental Validation

Transcription:

This paper was presented at 12th REHVA World Congress (Clima 2016). The correct citation for the paper is: Spitler, J. Javed, S. and Grundmann, R. 2016. Calculation Tool for Effective Borehole Thermal Resistance. In Proceedings of the 12th REHVA World Congress (Clima 2016), Aalborg, Denmark, May 22 25, 2016.

Calculation Tool for Effective Borehole Thermal Resistance Jeffrey D. Spitler #1, Rachel Grundmann #2, Saqib Javed *3 # Mechanical and Aerospace Engineering, Oklahoma State University 218 EN, Stillwater, OK 74078 1 spitler@okstate.edu 2 Rachel.grundmann@okstate.edu * Building Services Engineering, Chalmers University of Technology SE-412 96 Gothenburg, Sweden 3 saqib.javed@chalmers.se Abstract This paper presents a tool for computing thermal resistance of single U-tube ground heat exchangers placed in vertical boreholes. The tool is complete in the sense that it can compute both local and effective thermal resistances for either grouted or groundwater-filled boreholes. For grouted boreholes, it utilizes the highly accurate multipole method. For groundwater-filled boreholes, it utilizes recently-published convection correlations. Thermal property routines for water and water-antifreeze mixtures allow calculation of the interior convective thermal resistance for a wide range of cases. Keywords ground source heat pumps, ground heat exchangers, borehole thermal resistance 1. Introduction Ground source heat pump systems are energy-efficient and environmentallyfriendly means of providing building heating and cooling. Design of the ground heat exchangers for these systems can be challenging for several reasons including estimation of the borehole thermal resistance. The borehole thermal resistance is the thermal resistance between the fluid in the U-tube and the borehole wall. Lower borehole thermal resistance leads to more favorable entering heat pump fluid temperatures and better heat pump performance. Mogensen [1] first identified the borehole thermal resistance as a parameter of interest in ground heat exchanger design. Since that time, there have been numerous methods proposed for calculating borehole thermal resistance in the case of grouted boreholes. Either a single or double U-tube heat exchanger involves multiple eccentrically placed cylinders within another cylinder and therefore leads to difficulties in analyzing the conduction heat transfer problem. Therefore, a number of simplified methods, which are usually accurate only over a narrow range of geometries, have been developed. The multipole method developed by Claesson and Bennet [2] is accurate over a wide range of geometries, but is mathematically challenging to implement. In Scandinavia, it is common practice to construct borehole heat exchangers by lowering a U-tube in a groundwater-filled borehole. Where the bedrock and

groundwater levels are close to the surface, this can be a very effective design with relatively low borehole thermal resistance on the order of 0.05-0.06 K/(W/m) [3] for typical conditions. Several authors have shown that the borehole thermal resistance can vary with both heat transfer rate and annulus temperature due to variations in the buoyancy-driven flow and heat transfer. Convection correlations [4] have recently been published that take into account the temperature and heat transfer effects on the buoyancy-driven flow in the borehole annulus. When a thermal response test is used to measure borehole thermal resistance it inherently includes the effects of internal heat transfer between tubes ( shortcircuiting ) in the ground heat exchanger, and is referred to as the effective borehole thermal resistance. Hellström [5] developed analytical relationships between the local borehole thermal resistance (R b) and the effective borehole thermal resistance (R b * ). For many boreholes, particularly those of depths less than 100 m, there is little effect of short-circuiting and it may be neglected. However, the short-circuiting effect increases as either the depth or conductance between the legs increases and/or as the mass flow rate in the heat exchanger decreases. As there are some trends towards increasing borehole depth, it is important to be able to account for short-circuiting in the calculation of effective borehole thermal resistance. This paper reports on an Excel/VBA spreadsheet that calculates borehole thermal resistance for both grouted and groundwater-filled boreholes with single U-tubes. 2. Methodology An Excel/VBA spreadsheet was developed that calculates both borehole thermal resistance and effective thermal resistance for grouted or ground-water-filled boreholes with single U-tubes. The inputs are summarized in Table 1; some inputs apply to grouted or groundwater-filled boreholes only and are marked parenthetically to that effect. Each aspect of the calculation is described briefly below. a. Interior convective resistance and pipe resistance Properties (dynamic viscosity, density, specific heat, thermal conductivity) for pure water and mixtures of water with propylene glycol, ethylene glycol, ethyl alcohol and methyl alcohol are provided by routines described by Khan [6]. For Reynolds number of 2300 or above, the Gnielinski [7] correlation is used; below 2300 the Nusselt number is set to 4. The conductive resistance is readily determined from the pipe dimensions and conductivity. b. Multipole algorithm grouted boreholes The multipole method is a mathematically-complex algorithm which can be used to calculate conductive thermal resistance for any number of arbitrarily placed pipes in a borehole. The multipole method solves the conduction heat transfer problem using line sources and multipoles. Derivation of the multipole method is described in [8]. The multipole method has been compared with several numerical methods with remarkable accuracy [9-11] and is often used as a reference method. There has been some confusion in the literature between 0 th and 1 st order closed form expressions that can be

derived from the multipole method and the full implementation of the method which can use additional multipoles to better account for the composite geometry. Our implementation can calculate any order, though little accuracy is gained for most cases in going beyond the 3 rd or 4 th order calculation. The multipole method is implemented in about 1000 lines of VBA code, adapted from the original [12] Fortran code. c. Natural convection - groundwater-filled boreholes In order to calculate borehole thermal resistance for a groundwater-filled borehole, it is necessary to find the convective resistances in the annulus between the pipe outer wall and the annulus water temperature (R poc) in Figure 1 and between the annulus and the borehole wall (R BHWc). The convection correlations developed by Spitler, et al. [4] are based on experimental measurements of a single borehole in Gothenburg and were validated by comparisons to measurements of effective borehole thermal resistance for 30 other boreholes in Norway and Sweden. They were tested under both heat extraction and heat injection conditions and a range of heat transfer rates and annulus temperatures. Higher heat transfer rates lead to higher temperature differences and hence higher differences in density. In turn, the higher differences in density lead to increased velocity of the recirculating flow within the annulus and decreased thermal resistances. Annulus temperature also has an influence on the natural convection. As water temperature approaches the maximum density point near 4 C, the derivative of density with respect to temperature approaches zero, resulting in reduced effect of buoyancy and increased thermal resistances. These effects have been demonstrated in both field [13, 14] and laboratory [15] experiments. The correlations used in the calculation tool account for these effects and use hydraulic diameter as a scaling parameter. Table 1. Summary of user inputs Input Units Weight concentration of antifreeze % Antifreeze type - Volume flow rate m 3 /hr Heat transfer rate (Groundwater-filled BH) W/m Outside diameter of U-pipe m Inside diameter of U-pipe m Thermal conductivity of U-pipe W/m K Roughness ratio of U-pipe - Height of borehole m Shank spacing (Grouted BH) m Borehole diameter m Backfill: grout or groundwater - Grout thermal conductivity (Grouted BH) W/m K Ground thermal conductivity (Grouted BH) W/m K Calculation option for R * b : uniform T or q -

T BHW R BHWc T ann R poc R poc R pc T po T po Rpc R pic T pi T pi R pic T f T f Fig. 1 Thermal resistance network for groundwater-filled borehole d. Short-circuiting Several methods [16, 17] for treating short-circuiting in ground heat exchangers, based on an improved calculation of mean fluid temperature, have been proposed. We use the method described by Hellström [5] that gives the effective borehole thermal resistance that can be used with the simple mean fluid temperature. This method is consistent with estimates of borehole thermal resistance made with thermal response tests. Hellström gave two expressions based on idealized temperature profiles one for uniform borehole wall temperature and one for uniform heat flux; for the few cases in [4] where the short-circuiting is significant, the uniform temperature approximation gave better accuracy in predicting the effective borehole thermal resistance. Both methods are implemented in the spreadsheet and the user may pick either one. Both methods also require knowledge of the internal thermal resistance. For grouted boreholes, it is determined with the multipole method; for groundwater-filled boreholes it may be determined with the thermal resistance network shown in Figure 1. 3. Results and Discussion Sample results and validation against experimental measurements from several boreholes are presented. The effect of thermal short-circuiting is proportional to the ratio of the tube-to-tube conductance to the thermal capacitance of the working fluid and is more important as borehole depth significantly exceeds 100 m.

Rb, Rb* (K/(W/m)) a. Grouted borehole sensitivity to depth For grouted boreholes, the thermal resistance is not directly affected by the depth, but the short-circuiting increases with depth and, hence, the effective borehole thermal resistance is affected by depth. Figure 2 shows the borehole thermal resistance and effective thermal resistance for a grouted borehole as a function of borehole depth and two grout thermal conductivities corresponding to bentonite grout and a moderately enhanced grout. The other parameters are given in Table 2. Table 2. Grouted borehole parameters for Figure 2 Parameter Value Weight concentration of antifreeze 23% Antifreeze type Ethyl alcohol Volume flow rate 3.1 m 3 /hr Outside diameter of U-pipe 0.04 m Inside diameter of U-pipe 0.0352 m Thermal conductivity of U-pipe 0.48 W/m K Shank spacing 0.01 m Borehole diameter 0.11 m Ground thermal conductivity 3.0 W/m K 0.18 0.16 0.14 0.12 0.10 0.08 0.06 0.04 0.02 0.00 Grout conductivity = 0.7 W/m K Rb Rb* Grout conductivity = 1.5 W/m K 0 100 200 300 400 500 Borehole Depth (m) Fig. 2 Borehole thermal resistance and effective borehole thermal resistance for grouted borehole As shown in Figure 2, the borehole thermal resistance does not depend on depth, but increasing the grout conductivity significantly reduces the borehole thermal resistance. The effective borehole thermal resistance, shown as a dashed line, is approximately the same as the borehole thermal resistance at depths of 100 m or less. But increasing the depth leads to more short-circuiting and higher effective borehole

thermal resistance. This effect is more pronounced for the cases with higher grout conductivity as the internal resistance between the tubes is lower. b. Groundwater-filled borehole sensitivity to depth For the grouted borehole, the resistances are not affected by power input. But for the groundwater-filled borehole, the buoyancy-driven convection depends on the power input. For this section, it has been fixed at 15 kw of heat extraction. Therefore, the heat extraction rate per unit length of borehole varies between 150 W/m for a 100 m borehole and 37.5 W/m for a 400 m borehole. The mean fluid temperature inside the U-tube is held constant at 15 C. Other parameters are as shown in Table 2. Figure 3 shows that the borehole thermal resistance increases with depth this is due to the decreasing heat extraction rate per unit length which leads to lower buoyancy-driven convection rates. The effective borehole thermal resistance increases even more rapidly with depth due to the increased short circuiting. 0.12 Rb, Rb* (K/(W/m)) 0.10 0.08 0.06 0.04 Rb Rb* 0.02 0.00 0 50 100 150 200 250 300 350 400 450 Borehole Depth (m) Fig. 3 Borehole thermal resistance and effective borehole thermal resistance for ground-water filled borehole c. Grouted borehole sensitivity to flow rate The thermal resistance of grouted boreholes is not greatly affected by the flow rate as long as the flow is in the turbulent regime. Figure 4 shows the thermal resistances of a grouted borehole with three different flow rates as solid lines. The resistances are determined with a grout conductivity of 1.5 W/m K, mean fluid temperature of 20 C and other parameters of Table 2. The minor differences in borehole thermal resistances are due to small variations in convective flow resistances inside the U-tube due to different flowrates. On the other hand, the effective borehole thermal resistance, shown as dashed lines, increase significantly with decreasing flowrates. The effective borehole thermal resistances are significantly higher for deeper boreholes. For example, the

difference in effective thermal resistances values of a 100 m borehole with flowrates of 1 m 3 /hr and 3.1 m 3 /hr is over 20 %, whereas for a 400 m deep borehole the difference is over 150 % with the same flowrates. The three flowrates of Figure 4 all represent turbulent flow in the U-tube, with Reynolds numbers of approximately 4100, 8300, and 13000 for the three flowrates of 1 m 3 /hr, 2 m 3 /hr, and 3.1 m 3 /hr, respectively. 0.30 0.25 1.0 m 3 /hr Rb, Rb* (K/(W/m)) 0.20 0.15 0.10 Rb Rb* 2.0 m 3 /hr 3.1 m 3 /hr 0.05 0.00 0 100 200 300 400 500 Borehole Depth (m) Fig. 4 Borehole thermal resistance and effective borehole thermal resistance for grouted borehole with changing flow rates d. Groundwater-filled borehole sensitivity to annulus temperature For the cases shown in Figure 3, the annulus groundwater temperature and the heat extraction rate per unit length both varied over the depth. With the new convection correlations implemented in the tool, it is possible to isolate the effects of heat transfer rate and annulus temperature. For Figure 5, the heat rejection rate was kept constant at 35 W/m for a 200 m deep borehole. However, the mean fluid temperature was varied so that the annulus temperature varies between 2 C and 21 C. The shape of the curves in Figure 5 is notably non-linear. The hump near 4 C is caused by the maximum density point of water in this range, the partial derivative of density with respect to temperature is very low, resulting in a low buoyant driving force and higher thermal resistances.

Rb, Rb* (K/(W/m)) 0.12 Rb, Rb* (K/(W/m)) 0.10 0.08 0.06 0.04 0.02 Rb Rb* 0.00 0 5 10 15 20 25 Annulus Temperature ( C) Fig. 5 Borehole thermal resistance and effective borehole thermal resistance for ground-water filled borehole with fixed heat rejection rate, but changing mean fluid temperature e. Groundwater-filled borehole sensitivity to heat transfer rate In this section, we have varied the heat transfer rate, but contrived to keep the annulus groundwater temperature constant at 8.9 C. As shown in Figure 6, the borehole thermal resistance increases with decreasing heat transfer rate. Again, as the heat transfer rate decreases, the buoyant forces driving flow and convection heat transfer are lower, resulting in lower heat transfer coefficients and higher borehole thermal resistance. 0.12 0.10 0.08 0.06 0.04 0.02 0.00 Rb Rb* 0 10 20 30 40 50 60 70 80 Heat rejection rate (W/m) Fig. 6 Borehole thermal resistance and effective borehole thermal resistance for ground-water filled borehole with fixed annulus groundwater temperture

4. Conclusions A tool for computing borehole thermal resistance and effective borehole thermal resistance for vertical single U-tube ground heat exchangers has been presented. One unique feature is calculation of resistance values for the annular region of groundwaterfilled boreholes using recently developed correlations. For grouted boreholes, the multipole algorithm has been utilized and any order multipole solution may be found the tool does not rely on 0 th or 1 st order multipole expressions. Besides the obvious usefulness of the tool for computing borehole thermal resistance and effective borehole thermal resistance as part of design procedures, the tool can also show the sensitivity of the thermal resistances to various parameters, such as how the depth of the ground heat exchanger or the flow rate affects the amount of short-circuiting. Use of the convection correlations for groundwater-filled boreholes also allows us to investigate the sensitivity of the borehole thermal resistance to both the heat transfer rate and the annular temperature independently. This is impossible to do experimentally with a single thermal response test as the annular temperature and heat transfer rate tend to be closely correlated. The tool at present can be used for single U-tube ground heat exchangers. Future work includes extension to double U-tube and co-axial heat exchangers. For grouted boreholes, there are no significant barriers to this extension for double U-tube heat exchangers, the multipole algorithm can be used and for co-axial heat exchangers, simple analytical expressions suffice for conductive resistance. However, for groundwater-filled boreholes with double U-tube and co-axial heat exchangers, additional experimental work leading to heat transfer correlations is still needed. Acknowledgments The support of the first author by the Fulbright Commission of Sweden and a sabbatical leave from Oklahoma State University is gratefully acknowledged. The third author s experimental work, on which the groundwater-filled-borehole convection correlations are based, was supported by the Swedish Energy Agency. References [1] Mogensen P. Fluid to Duct Wall Heat Transfer in Duct System Heat Storages. International Conference on Subsurface Heat Storage in Theory and Practice. Stockholm, Sweden. Swedish Council for Building Research; 1983. p. 652-7. [2] Claesson J, Bennet J. Multipole method to compute the conductive heat flows to and between pipes in a cylinder. Notes on Heat Transfer. Lund, Sweden. Lund University; 1987. p. 58. [3] Gehlin S. Thermal Response Test: Method Development and Evaluation [Doctoral Thesis]. Luleå: Luleå University of Technology; 2002. [4] Spitler JD, Javed S, Ramstad RK. Natural convection in groundwater-filled boreholes used as ground heat exchangers. Appl Energy. 2016;164:352-65. [5] Hellström G. Ground Heat Storage Thermal Analyses of Duct Storage Systems - Theory [Doctoral Thesis]. Lund, Sweden: University of Lund; 1991.

[6] Khan MH. Modeling, Simulation and Optimization of Ground Source Heat Pump Systems. [M.S.]. Stillwater: Oklahoma State University; 2004. [7] Gnielinski V. New equations for heat and mass transfer in turbulent pipe and channel flow. Int Chem Eng. 1976;16:359-68. [8] Claesson J, Hellström G. Multipole method to calculate borehole thermal resistances in a borehole heat exchanger. HVAC&R Res. 2011;17:895-911. [9] Lamarche L, Kajl S, Beauchamp B. A review of methods to evaluate borehole thermal resistances in geothermal heat-pump systems. Geothermics. 2010;39:187-200. [10] Go G-H, Lee S-R, Yoon S, Park H, Park S. Estimation and experimental validation of borehole thermal resistance. KSCE Journal of Civil Engineering. 2014;18:992-1000. [11] He M. Numerical Modelling of Geothermal Borehole Heat Exchanger Systems [Doctoral Thesis]. Leicester, UK: De Montfort University; 2012. [12] Bennet J, Claesson J, Hellstrom G. Multipole Method to Compute the Conductive Heat Flows to and between pipes in a composite cylinder. Notes on Heat Transfer. Dept of Building Technology and Mathematical Physics; 1987. [13] Gustafsson A, Gehlin S. Influence of Natural Convection in Water-Filled Boreholes for GCHP. ASHRAE Trans. 2008;114:416-23. [14] Javed S. Thermal response testing: Results and experiences from a ground source heat pump test facility with multiple boreholes. Proceedings of 11th REHVA World Congress (Clima 2013). Prague, Czech Republic. 2013. [15] Kjellsson E, Hellström G. Laboratory study of the heat transfer in a water-filled borehole with a single U-pipe. Megastock 1997 The 7th international conference on thermal energy storage. Sapporo, Japan. 1997. p. 509-14. [16] Marcotte D, Pasquier P. On the estimation of thermal resistance in borehole thermal conductivity test. Renew Energy. 2008;33:2407-15. [17] Beier RA, Acuña J, Mogensen P, Palm B. Vertical temperature profiles and borehole resistance in a U- tube borehole heat exchanger. Geothermics. 2012;44:23-32.