SUPPLY AND EXHAUST VENTILATION SYSTEM WITH HEAT RECOVERY IN COMPARISON TO A DEMAND-BASED (MOISTURE-CONTROLLED) EXHAUST VENTILATION SYSTEM

Similar documents
INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS

The reasons for this approach are different. So

Buildings XI Conference Workshop 2: Thermal Mass IV Assessing Thermal and Moisture Control Benefits of PCM Components by Hygrothermal Simulation

Hygrothermal Evaluation of Icynene Spray Foam Insulation Installed Between Roof Rafters on Pitched Roofs

Comparative evaluation of the predictions of two established mould growth models

Influence of night ventilation on the cooling demand of typical residential buildings in Germany

COMBINED EFFECT OF TEMPERATURE AND HUMIDITY ON THE DETORIATION PROCESS OF INSULATION MATIRIALS IN ETICS

Design of Mineral Fibre Durability Test Based on Hygrothermal Loads in Flat Roofs.

Energy Efficient Buildings in Germany An Introduction

Low-Energy Industrial Buildings for Climates of Emerging Countries

Available online at ScienceDirect. Energy Procedia 78 (2015 )

VALIDATION OF A HYGROTHERMAL WHOLE BUILDING SIMULATION SOFTWARE

Hygrothermal Calculations applied to water-repellent surfaces - Validation and Application -

Condensation Problems in Cool Roofs

Proceedings Cold Climate HVAC Sisimiut, Greenland, March 2009

Ventilation in residential buildings: A comparison of different calculation methodologies in the context of the EPBD

A NEW MODEL FOR PREDICTION AND ITS APPLICATION IN PRACTICE

Limits and potentials of office building climatisation with ambient air

P177. Germany: Impact, compliance and control of legislation. [European projects]

Interior climate in German houses (Investigation funded by the German Federal Ministry of Economics and Labour)

Thermal Performance Degradation of Foam Insulation in Inverted Roofs Due to Moisture Accumulation

THE HYGROTHERMAL BEHAVIOUR OF ROOMS: COMBINING THERMAL BUILDING SIMULATION AND HYGROTHERMAL ENVELOPE CALCULATION

Concept of a New Airing Strategy and Simulation of the Expected Indoor Climate in Linderhof Palace

Control of Moisture Safety Design by Comparison between Calculations and Measurements in Passive House Walls Made of Wood

Available online at ScienceDirect. Energy Procedia 70 (2015 )

Hygrothermal Performance of Flat Roofs with Construction Moisture

PROPOSAL FOR A BUILDING ENERGY EFFICIENCY CERTIFICATE. H.-P. Leimer, Prof. Dr.-Ing.1,*

IEA HPP Annex 28 Uniform testing and seasonal performance calculation of combined operating heat pump systems

ENVIRONMENTAL ASSESSMENT OF A LOW-ENERGY HOUSE

Solar-active-houses analysis of the building concept based on detailed measurements

Derivation of algorithms for the climate correction of heating energy parameters

Passive houses for the Northern climate

Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001

Effects of Air Leakage of Residential Buildings in Mixed and Cold Climates

Hygrothermal Simulation of ventilated pitched roofs with effective transfer parameters

Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

DIN V Date:2007 February

Heat, Air and Moisture (HAM) modeling of historic windows

Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood

FORMULATING A BUILDING CLIMATE CLASSIFICATION METHOD

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

Available online at ScienceDirect. Energy Procedia 78 (2015 )

See how to use WUFI in conjunction with ASHRAE s New Standard 160, Design Criteria for Moisture Control in Buildings.

Trends in National Nearly Zero-Energy Building Approaches Erhorn-Kluttig, Heike; Erhorn, Hans; Thomsen, Kirsten Engelund; Nyffenegger, Ulrich

Built examples and project certification. Zeno Bastian, Passive House Institute

IEA Annex 41 MOIST-ENG Whole Building Heat, Air and Moisture Response Comparison of measured and simulated moisture buffering results

INTEGRAL BUILDING AND ENERGY DESIGN OF AN OFFICE BUILDING COMPARISON OF INITIAL DESIGN IDEAS WITH MONITORED RESULTS

Verified net Zero Energy Building with air source heat pumps for SME

Flexible Vapor Control Solves Moisture Problems of Building Assemblies - Smart Retarder to Replace the Conventional PE-Film

See how to use WUFI in conjunction with ASHRAE s New Standard 160, Design Criteria for Moisture Control in Buildings.

Evaluation of the hygrothermal performance of a concrete wall construction with Icynene open cell insulation

Simplified Calculation Method for the Energetic Assessment of Glass Double Skin Façades

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

Coupled windows in the current guise

LOW ENERGY CERTIFICATE - PROPOSAL FOR A BUILDING ENERGY EFFICIENCY CERTIFICATE

Available online at ScienceDirect. Energy Procedia 48 (2014 )

A well-planned building envelope is a requirement for achieving high user comfort and low energy costs.

Advanced Building Systems Dirk Müller, Azadeh Badakhshani, Alexander Hoh

Thermal Rehabilitation of Existing Building Enclosures by Using VIP (Vacuum Insulation Panel) Sandwich and Timber Based Panels

Application of a Computer Model for Integrated Hygrothermal Building Analysis

Potential of ventilative cooling in German residential buildings

A Brief Journey Through Building Physics / Science: Research, Standards, and Education

Improving the Energy Performance of Museum Buildings Development and Evaluation of Sustainable Refurbishment Strategies

WUFI COMPUTER MODELING WORKSHOP FOR WALL DESIGN AND PERFORMANCE (HEAT AND MOISTURE TRANSFER IN BUILDING ENVELOPES) Boston, MA - October 11-12, 2016

1. Introduction. Carl-Magnus Capener, Ph.D. 1 Stephen Burke, Ph.D. 2 Simon Le Roux, Architect 3 Stephan Ott, Architect 4

This is the published version of a paper presented at CLIMA 2013, Prague, June 16-19,

THERMAL STORAGE TANKS AND THE BUILDING AS STORAGE FOR LOCALLY GENERATED RENEWABLE ELECTRICITY

Potential of natural ventilation in shopping centres

Effects of the use of DIN on the energetic assessment of residential buildings reflection on the calculation

What does»healthy Building«mean in terms of energy efficiency?

Postprint.

Chapter 6. Space heating load

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Survey of the Climatic Behavior of Motor Homes

Adapted vapour control for durable building enclosures

Summer season temperature control in Finnish apartment buildings

ENERGY PERFORMANCE OF FACADES AND BUILDINGS IEA AS SUPPORT FOR THE EUROPEAN DIRECTIVE?

Measurements of Energy Performance and Indoor Environmental Quality in 10 Danish Passive Houses Larsen, Tine Steen; Jensen, Rasmus Lund

CASE STUDIES - CENTRE FOR SUSTAINABLE BUILDING (ZUB) KASSEL, GERMANY

DIN V Date: 2007 February

Author(s): Hollberg, Alexander; Tschetwertak, Julia; Schneider, Sven; Habert, Guillaume

In general, passive-solar components can be described by the U-value (heat loss coefficient) and

Deakin Research Online

Impact of ventilation heat recovery on primary energy use of apartment buildings built to conventional and passive house standard

INDOOR AIR POLLUTION BY FUNGUS OF HIGHLY INSULATED HOUSES BIOLOGICAL ASPECTS - Hans-Peter Leimer and Ilka Toepfer

The Passive House technology a solution to the global problem of space heating

The Gate Hall of Lorsch Comprehensive Assessment Methods to calibrate Simulation Models and adapt Conservation Strategies

Solar Architecture of Low-Energy Buildings for Industrial Applications

IBP. akustik Hygrothermics

The Centre for Sustainable Building (ZUB) * A Case Study

Ongoing Commissioning of a high efficiency supermarket with a ground coupled carbon dioxide refrigeration plant

A sustainable Energy Use Plan with special emphasis on historic preservation by the example Iphofen

The Importance of Slab Edge & Balcony Thermal Bridges

MEASURING AND TESTING FACILITIES

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Technological and Economical Potentials to Save End-Use Energy

Investigation of indoor climate in a naturally ventilated building

Potential of Natural Ventilation in Shopping Centres Diederichsen, Alice; Friis, Kristina; Brohus, Henrik; Tranholm, Gitte T.

Transcription:

SUPPLY AND EXHAUST VENTILATION SYSTEM WITH HEAT RECOVERY IN COMPARISON TO A DEMAND-BASED (MOISTURE-CONTROLLED) EXHAUST VENTILATION SYSTEM 1 Abstract M. Krus, D. Rösler, A. Holm Fraunhofer-Institut for Building Physics, 83626 Valley, Germany As a countermeasure to global warming, the energy demand of buildings is to be reduced by specific measures, for example thermal insulation or intelligent ventilation systems. A demand-based (moisture-controlled) exhaust ventilation system is assessed in comparison to a supply and exhaust ventilation system with heat recovery by means of computational investigations. This assessment of different ventilation systems is performed by means of the newly developed hygrothermal indoor climate simulation model WUFI -Plus. By implementing the individual ventilation systems the energy demand, especially the primary energy consumption on the basis of applying various fuels, as well as the effects on the indoor climate and the CO 2 content of the indoor air are calculated and compared. Moreover, air change rates are investigated resulting from the use of a demand-based exhaust ventilation system. The calculations are based on a model apartment with a ground floor of 75 m 2 and an assumed 3-person household. These investigations comprise 3 different climates in Germany (cold, medium and hot climate). Despite the high heat recovery coefficient of the supply and exhaust ventilation system an only slightly higher energy use occurred for the demand-based exhaust ventilation system. If regenerative energy sources such as wood are used, primary energy consumption of the demand-based exhaust ventilation system is even lower in comparison to the supply and exhaust ventilation system with heat recovery. With demand-based exhaust ventilation system, the CO2 concentration of the indoor air remains permanently below 1200 ppm. 2 Investigations Modern supply and exhaust ventilation systems with their high heat recovery coefficients of 80 % or even more create the impression, that the energy demand for ventilation heat loss may be negligible and that systems without heat recovery are far inferior concerning the energy demand. This results in an increasing sale of expensive and complex systems with high heat recovery (Albers et al (2002), Schmidt 2002). The efficience of airing systems have been examinated by different authors (i.e. Reiß et Erhorn (1995), Wirth (2004)) mostly by in situ measurements of the energy consumption under the influence of the users behaviour. Fortunately in common standards like EnEV 2009 or DIN V 4108-8 the use of a supply and exhaust ventilation system with heat recovery is not required and even natural ventilation is allowed. To approve or disprove the impression, that the complex supply and exhaust ventilation system show much higher energy efficiency, calculative investigations have been performed. To assess the different ventilation systems calculations are performed by means of the hygrothermal indoor climate model WUFI -Plus. The software tool WUFI -Plus allows the calculation of the hygrothermal conditions of the enclosure surfaces (walls and ceilings), the indoor air as well as the energy demand under transient boundary conditions (Holm et al (2004); Lengsfeld, Holm (2007)). The calculations consider besides the materials used in the individual building components also boundary conditions such as air change rate, moisture generation as well as the performance of heating and cooling in the room to be analyzed. The hygrothermal indoor climate simulation model WUFI -Plus is a 1-zone model, which differentiate individual rooms. The model was successfully validated by means of investigations in an appropriately equipped test building on

the outdoor testing site of the Fraunhofer Institute for Building Physics in Holzkirchen (Rösler, Krus (2008)). 2.1. Model apartment Comparative calculations of the ventilation systems are carried out on the basis of a model apartment with a ground floor of 75 m 2. The apartment is located in a multi-storey building in one of the middle storeys. The U-value of the external walls is 0.25 W/m 2 K, the percentage of the windows in the facade amounts to 20 % with a U-value of the windows of 1.1 W/m 2 K. Material data necessary for wall, ceiling and window constructions are taken from WUFI material database. The minimum indoor air temperature is 21 C. Internal heat sources are disregarded. The moisture and CO 2 input are oriented on a time and quantity basis of a 3-person household. The calculations are based on the typical internal moisture load of a 3-person household in such an apartment. According to Hartmann et al (2001) the moisture input amounts to 9 kg/d based on the assumption that laundry is dried in the apartment and 6.5 kg/d without drying of laundry. The moisture input (Fig. 1 left) as well as the CO 2 input is based on the typical course of the day. To assess the effectiveness of the different ventilation systems at various external climates calculations are performed with a cold (Hof), medium (Würzburg) and a hot (Freiburg) test reference year. Figure 1. Daily course of moisture generation (left) in the model apartment without (above) and with drying of laundry (below), as well as the course of CO2 production (right). 2.2. Ventilation Systems A commercial supply and exhaust ventilation system with a constant air change rate of 0.4 h -1 and an integrated heat recovery with a energy efficiency of 80 % or 60 % respectively was used as ventilation system technology. Furthermore, the supply and exhaust ventilation system was also investigated without heat recovery for better comparison. The dew point temperature of the air in the room varies between about 5 C and 15 C, resulting in a condensation within the heat exchanger during winter time. To avoid problems due to condensation and the freezing of the heat exchanger in the system at low temperatures in winter especially with high heat recovery coefficients the ambient air has to be heated. When the exhaust air temperature falls below 1 C the exhaust air temperature is heated up to at least 3 C by means of a preheating unit. The typical power consumption of the ventilator amounts to 35 W. In addition to the constant air change rate of the ventilation system of 0.4 h -1 an air change by infiltration and user behaviour, e.g. window ventilation, is to be fixed at a value of 0.2 h -1 for supply and exhaust ventilation systems with heat recovery according to DIN V 4701-10.

The demand-based exhaust ventilation system investigated consists of moisture-controlled supply and exhaust ventilation elements and a central ventilator, which is controlled in a way that it has an approximately constant pressure difference of 100 Pa independent of the flow rates. By moving the opening valves the exhaust ventilation elements vary the flow rate in dependence of the relative indoor humidity. By enlarging the opening of the valves, the difference pressure at the ventilator drops and the fan must be operated at a higher performance to regain the reference pressure difference. The moisture-controlled supply ventilation elements provide for a demand-based distribution of the air (zoning) in the apartment. Calculating the heat losses of the ventilation system the changing power consumption of the ventilator is considered. The additional air change rate due to infiltration and user behavior is to be fixed at 0.15 h -1 for demand-based exhaust ventilation systems according to DIN V 4701-10. 2.3. Calculations Calculations are carried out in 1 h-steps over a period of three years, whereby the heating period of the third year is evaluated. According to DIN V 4108-6 the periods presented in Table 1 are used as heating period at a heating limit temperature of 10 C for the three climates. The energy consumption for ventilation heat loss and the electrical energy for the operation of the ventilators and, if necessary, the preheating units are determined for both ventilation systems. The primary energy demand for ventilation heat is determined for three different energy sources for heating respectively (fuel oil and natural gas with a PE factor of 1.1; cogeneration of heat and electricity with fossil fuel with a PE factor of 0.7; heating by burning wood (pellets) with a PE factor of 0.2). The part of electricity is weighted by the PE factor of 2.7. The total primary energy demand results from adding the PE demand for ventilation heat and the PE demand for electricity. Table 1: Periods and duration of the heating periods for three climates. Heating period start end Duration [days] Hof September 15 May 08 235 Würzburg October 15 April 26 193 Freiburg October 20 April 08 169 3 Results 3.1. Calculated Energy Demand Table 2 and Table 3 show the calculated energy demand for ventilation heat loss for both ventilation systems as well as the power demand for the ventilator and the preheating unit. The PE factors still remain unconsidered. It is obvious from Table 2 that with an increasing heat recovery coefficient the total energy demand for ventilation heat loss declines, but the part of energy necessary for the preheating unit increases. This effect is still enhanced the colder the outdoor climate is. It is also obvious that a heat recovery coefficient of 80 % for example does not at all mean a 80 % reduction of the total energy demand for ventilation heat loss but only energy savings of less than 40 %. The cause of this fact is on the one hand the ventilation heat losses by infiltration and user behavior, which do not pass the heat exchanger, and on the other hand the electrical power demands for ventilator and preheating unit.

Table 2: Energy demand for ventilation heat loss of the supply and exhaust ventilation system with various heat recovery coefficients (HRC) as well as electrical power demand for ventilator and preheating unit (PHU). climate HRC ventilation heat losses (without PHU) PHU Ventilator part of electrical power (ventilator+phu) [%] Hof 0 3837.2 0.0 197.4 197.4 4034.6 (235 days) 60 2300.1 9.8 197.4 207.2 2507.3 80 1774.1 112.6 197.4 310.0 2084.1 90 1517.8 227.4 197.4 424.8 1942.6 Würzburg 0 3029.9 0.0 162.1 162.1 3192.0 (193 days) 60 1816.6 4.1 162.1 166.2 1982.8 80 1405.4 47.4 162.1 209.5 1614.9 Freiburg 0 2524.4 0.0 142.0 142.0 2666.4 (169 days) 60 1514.6 0.0 142.0 142.0 1656.6 80 1173.7 24.2 142.0 166.2 1339.9 total energy demand for ventilation heat loss As concerns the demand-based exhaust ventilation system (Table 3) the energy demand is clearly dependent on the moisture input ( see without drying of laundry (WDL), Hof as an example) and on the assumed air change rate by infiltration and user behavior. Table 3: Energy demand for ventilation heat loss (VH) of demand-based exhaust ventilation system and electricity demand of ventilator. climate air change rate by infiltration and user behavior [h -1 ] ventilation heat losses electrical power demand ventilator total energy demand for ventilation heat loss Hof 0.1 (WDL ) 2561.3 74.3 2635.6 (235 days) 0.1 2883.4 77.7 2961.1 0.15 3079.4 76.4 3155.8 Würzburg 0.15 2496.1 63.1 2559.2 (193 days) Freiburg (169 days) 0.15 2116.2 56.1 2172.3 Fig. 2 shows the total energy demand for ventilation by the example of Hof for both ventilation systems. In case of the supply and exhaust ventilation system with heat recovery the heat recovery coefficient is varied between 0 % and 80 %. The percentage shows the reduction of the total energy demand for ventilation heat in comparison to the supply and exhaust ventilation system without heat recovery. The Part for Electricity and the Part for Preheating Unit are evident. Both ventilation systems clearly reduce the total energy demand for ventilation heat loss in comparison to the supply and exhaust ventilation system without heat recovery.

Figure 2. Total energy demand for ventilation in case of a supply and exhaust ventilation system with a different heat recovery coefficient and in case of a demand-based exhaust ventilation system. If we consider primary energy factors, matters differ as is shown in Fig. 3. Compared to a supply and exhaust ventilation system with a heat recovery of 80 % there is only a slight difference with cogeneration of heat and electricity (PE factor 0.7). In case of heating by wood the demand-based ventilation is clearly superior to the supply and exhaust ventilation system with a heat recovery of 80 % with regard to the environment. Figure 3. Energy demand of supply and exhaust ventilation system with heat recovery of 80 % (right) compared to a demand-based exhaust ventilation system (left) by considering primary energy factors. 3.2. Calculated course of CO 2 concentration Whereas the air change rate is always constant in case of the supply and exhaust ventilation system, it decreases in case of the demand-based ventilation at a lower moisture load but also at a lower ambient air temperature. As desired, the result is lower heat losses but probably also higher concentrations of CO 2. Fig. 4 shows the annual course of calculated CO 2 concentrations using the demand-based ventilation system. To get conditions as unfavorable as possible, investigations were

based on a moisture input without drying of laundry and an air change by infiltration and user behavior of only 0.1 h -1. Anyway, the limit value of 1200 ppmv was never exceeded. Figure 4. Course of the CO 2 concentration in a 3-person household using the demand-based exhaust ventilation system as 1-h-values and transient daily average for Hof. 4 Summary The differences in the energy demand between a demand-based exhaust ventilation system and a supply and exhaust ventilation system with heat recovery were determined by comparative calculations for a model apartment of a 3-person household. The moisture input to the model apartment is relatively high (with drying laundry) with unfavorable results for the demand-based exhaust ventilation system due to a higher air change rate. Nevertheless the total energy demand per heating period of the demand-based exhaust ventilation system amounts only to approx. 1000 kwh higher compared to the supply and exhaust ventilation system with 80 % heat recovery (dependent on the outdoor climate). Calculating the costs for electricity on the basis of 0.19 /kwh and 0.07 /kwh for heating energy (fuel oil or natural gas) the energy costs for the demand-based exhaust ventilation system are higher by approx. 47. These costs must be compared to the investment and maintenance costs of the ventilation systems in a life cycle assessment. Matters are quite different, if we compare the primary energy demand of the two ventilation systems by means of the respective energy source. Due to the high primary energy factor of 2.7, electricity consumption is decisive for the assessment of primary energy demand. With a cogeneration of heat and electricity the primary energy demand is almost equal. If regenerative energy sources are used, the demand-based exhaust ventilation system is clearly superior with regard to the primary energy demand. Calculations of the CO 2 concentration also show that despite a lower air change rate good indoor air quality can be guaranteed.

5 References DIN V 4108-6:2003-06: Wärmeschutz und Energieeinsparung in Gebäuden, Teil. 6. DIN V 4108-6:2003-08: Vermeidung von Schimmel in Wohngebäuden, Teil. 8. DIN V 4701-10:2003-08 (2003) Energetische Bewertung heiz- und raumlufttechnischer Anlagen, Teil 10. EnEV Energieeinsparverordnung (2009) Verordnung über energiesparenden Wärmeschutz und energiesparende Anlagentechnik bei Gebäuden. Hartmann T; Reichel, D.; Richter, W. (2001) Feuchteabgabe in Wohnungen alles gesagt? Gesundheitsingenieur. 122. Jahrgang. Heft 4, s. 189-195. Holm, A.; Radon, J.; Künzel, H.M.; Sedlbauer, K. (2004) Berechnung des hygrothermischen Verhaltens von Räumen. WTA-Schriftenreihe, H. 24, S. 81 94. Hrsg.: WTA-Publications, München Lengsfeld, K.; Holm, A. (2007) Entwicklung und Validierung einer hygrothermischen Raumklima- Simulationssoftware WUFI-Plus. Bauphysik 29, Heft 3, Seite 178-186. Ernst & Sohn Verlag Berlin. Rösler, D.; Krus, M. (2008) Berechnung des Primärenergiebedarfs einer Zu- und Abluftanlage mit Wärmerückgewinnung im Vergleich zu einer bedarfsgeführten (feuchtegeführten) Abluftanlage. IBP- Bericht RKB-12-2008. Albers, K-J.; Hain, K.; Wirth, St. (2002) Gebäudetechnische Systeme für Niedrig; Ultra- und Passivhäuser; Teil 2 Lüftungstechnik und Systemintegration. Kälte-Klima-Tagung 20. -22.11.2002, Magdeburg, Band IV, S. 205-212. Reiß, J.; Erhorn, H. (1995) Effizienz von Solar-, Lüftungs- und Heizsystemen im Mietwohnungsbau. Gesundheitsingenieur gi 116, 5, S. 233-249. Wirth, St.. (2002) Ist mit der kontrollierten Wohnungslüftung eine Primärenergieeinsparung möglich? Bauphysik 24, 4, S. 236-239. Schmidt, R. (2002) Kontrollierte Lüftung. Die Energieeinsparverordnung 2002 gibt kontrollierter Wohnungslüftung Aufwind. Quadriga, Fachmagazin für den Holzhausbau, 1.. Hartmann, Th. (2002) Bedarfsgeregelte Wohnungslüftung. Heizung, Lüftung/Klima, Haustechnik (HLH), 7.