DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

Similar documents
DIVISION: DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI

DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC.

DIVISION: CONCRETE SECTION: CAST-IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER:

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: MASON WEST, INC.

ICC-ES Evaluation Report. ESR-3707 Issued October 2014 This report is subject to renewal November 2015.

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS DIVISION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

Trusted ICC ES CONCRETEE SECTION: TOMARCO STREET. Look. Conformity! Evaluation. ICC-ES Evaluation

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

ESR-2713 Reissued August 1, 2013 This report is subject to renewal September 1, 2014.

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Trusted ICC ES. Issued 02/2018 SECTION: HILTI, INC. KCM MD. Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

ESR-2202 Issued May 1, 2009 This report is subject to re-examination in one year.

Product Submittal/Substitution Request

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

ICC-ES Evaluation Report. ESR-1917 Reissued May 2015 This report is subject to renewal May * * *Deleted by the City of Los Angeles

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

CITY OF LOS ANGELES CALIFORNIA

ICC-ES Evaluation Report

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Trusted. Issued 03/2015 SECTION: SECTION: 05 ITW ITW BUILDEX FOR. Conformity! ICC-ES Evaluation. Copyright 2015

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

ESR-1545 Reissued February 1, 2014 This report is subject to renewal March 1, 2016.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

Blue Banger Hanger Cast-In-Place, Internally Threaded Insert. Mechanical Anchors. Cracked. Concrete. Features. Installation. Installation Sequence

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

CALIFORNIA ERIC GARCETTI MAYOR

To: Firm: Project: Product Specified: Specified Location:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW BUILDEX 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

Trusted ICC ES CONCRETE SECTION: SECTION: 05 HILTI, INC. Look. Conformity! ICC-ES Evaluation

CITY OF LOS ANGELES CALIFORNIA

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.1.

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

APPENDIX A: Strength Design Performance Values

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Powers Fasteners, Inc. RESEARCH REPORT: RR Powers Lane (CSI # ) Brewster, New York BASED UPON ICC ES EVALUATION SERVICE

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST-INSTALLED CONCRETE ANCHORS

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 17.

Product Submittal/Substitution Request

Product Submittal/Substitution Request

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

Originally Issued: 07/07/2017 Revised: 05/03/2018 Valid Through: 07/31/2018

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Strong Bolt 2 Wedge Anchor for Cracked and Uncracked Concrete

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code.

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

DDI + (DECK INSERT) Threaded Insert for Metal Deck

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 100 PLANO, TEXAS 75024

CITY OF LOS ANGELES CALIFORNIA

Product Submittal/Substitution Request

DDI + (DECK INSERT) Threaded Insert for Metal Deck

Trusted ICC ES HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

Transcription:

0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4006 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 03 00 00 CONCRETE SECTION: 03 15 19 CAST IN CONCRETE ANCHORS SECTION: 03 16 00 CONCRETE ANCHORS REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 EVALUATION SUBJECT: HILTI KWIK CAST KCS WF AND KCS MD HEADED CAST IN SPECIALTY INSERTS IN CRACKED AND UNCRACKED CONCRETE Look for the trusted marks of Conformity! 2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2017 ICC Evaluation Service, LLC. All rights reserved.

ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-4006 Reissued November 2017 This report is subject to renewal November 2019. A Subsidiary of the International Code Council DIVISION: 03 00 00 CONCRETE Section: 03 15 19 Cast-in Concrete Anchors Section: 03 16 00 Concrete Anchors REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 (800) 879-8000 www.us.hilti.com HiltiTechEng@us.hilti.com EVALUATION SUBJECT: HILTI KWIK CAST KCS-WF AND KCS-MD HEADED CAST-IN SPECIALTY INSERTS IN CRACKED AND UNCRACKED CONCRETE 1.0 EVALUATION SCOPE Compliance with the following codes: 2015, 2012, 2009, and 2006 International Building Code (IBC) 2015, 2012, 2009, and 2006 International Residential Code (IRC) Properties evaluated: Structural 2.0 USES The Hilti Kwik Cast KCS-WF Headed Cast-In Specialty Insert is used to resist static, wind, and seismic (Seismic Design Categories A through F) tension and shear loads in cracked and uncracked normal-weight or lightweight concrete having a specified compressive strength, f c, of 2,500 psi to 10,000 psi (17.2 MPa to 68.9 MPa). The Hilti Kwik Cast KCS-MD Headed Cast-In Specialty Insert is used to resist static, wind, and seismic (Seismic Design Categories A through F) tension and shear loads in the soffit of cracked and uncracked normal-weight concrete and sand-lightweight concrete on steel deck having a specified compressive strength, f c, of 3,000 psi to 10,000 psi (20.7 MPa to 68.9 MPa). Reference to inserts in this report refers to the proprietary specialty anchorage products (KCS-WF and KCS-MD) used in concrete; reference to steel insert elements refers to threaded rods or bolts; reference to anchors or insert anchor system in this report refers to the installed inserts in concrete with threaded rods or bolts. The insert anchor system is an alternative to cast-in anchors described in Section 1901.3 of the 2015 IBC, Sections 1908 and 1909 of the 2012 IBC, and Sections 1911 and 1912 of the 2009 and 2006 IBC. The insert anchor system may be used where an engineered design is submitted in accordance with Section R301.1.3 of the IRC. 3.0 DESCRIPTION 3.1 Kwik Cast KCS-WF and KCS-MD: Hilti Kwik Cast KCS-WF and KCS-MD are steel internally threaded headed cast-in specialty inserts which receive threaded steel insert elements such as threaded rods and bolts in 1 / 4 -inch (KCS-WF only), 3 / 8 -inch, 1 / 2 -inch, 5 / 8 -inch, and 3 / 4 -inch thread diameters. The KCS-WF and KCS-MD inserts are manufactured from carbon steel and have a minimum 5.1 μm (0.0002 inch) zinc coating. The KCS-WF steel outer shell is covered in a thin plastic housing up to the steel head bearing surface. The KCS-MD has a plastic shell below the bottom steel flange which extends below the steel deck panels once installed. The KCS-MD has a spring around the shaft from the underside of the head to the metal tab area just above the plastic covering. The KCS-WF is illustrated in Figure 1 and KCS-MD is illustrated in Figure 2. The KCS-WF insert is installed into the wood-form for a concrete member using the attached nails prior to the casting of the concrete. The inserted threaded rod or bolt can be installed into the internally threaded section of the KCS-WF after the wood-form is removed from the concrete. The KCS-MD insert is installed into a hole cut into steel deck panels from the top-side that will be filled with a concrete topping slab. The inserted threaded rod or bolt can be installed from the underside of the steel deck panel in the internally threaded section of the KCS-MD. The inserts are color coded as indicated in Tables 1 and 2 for each diameter of threaded rod or other steel element that is threaded into the insert. Figure 3 shows a diagram of the installed KCS-WF in a concrete member and Figure 4 shows a diagram of the installed KCS-MD in a concrete over steel deck member. 3.2 Steel Insert Elements: 3.2.1 Threaded Steel Rods and Bolts: Threaded steel rods (all-thread) or bolts must be threaded into the KCS-WF or KCS-MD. Table 5 includes design information ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2017 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 14

ESR-4006 Most Widely Accepted and Trusted Page 2 of 14 for several grades of common threaded rod or bolts for the applicable diameters. Carbon steel threaded rods or bolts must be furnished with a minimum 5.1 μm (0.0002 inch) zinc plating. 3.2.2 Ductility: In accordance with ACI 318-14 2.3 or ACI 318-11 D.1, as applicable, in order for a steel anchor element to be considered ductile, the tested elongation must be at least 14 percent and the reduction of area must be at least 30 percent. Steel elements with a tested elongation of less than 14 percent or a reduction of area less than 30 percent, or both, are considered brittle. Values for common steel threaded rod insert elements are provided in Table 5 of this report. The Hilti KCS-WF and KCS-MD Headed Cast-In Specialty Insert steel bodies are considered brittle elements. Where values are nonconforming or unstated, the steel element must be considered brittle. 3.3 Concrete: Normal-weight and lightweight concrete must conform to Sections 1903 and 1905 of the IBC. 3.4 Steel Deck Panels: Steel deck panels must be in accordance with the configuration in Figures 6, 7 and 8 and have a minimum base steel thickness of 0.035 inch (0.899 mm). Steel must comply with ASTM A653/A653M SS Grade 50 minimum and have a minimum yield strength of 50,000 psi (345 MPa). 4.0 DESIGN AND INSTALLATION 4.1 Strength Design: 4.1.1 General: Design strength of anchors complying with the 2015 IBC as well as Section R301.1.3 of the 2015 IRC, must be determined in accordance with ACI 318-14 Chapter 17 and this report. Design strength of anchors complying with the 2012 IBC as well as Section R301.1.3 of the 2012 IRC, must be determined in accordance with ACI 318-11 Appendix D and this report. Design strength of anchors complying with the 2009 IBC and Section R301.1.3 of the 2009 IRC must be determined in accordance with ACI 318-08 Appendix D and this report. Design strength of anchors complying with the 2006 IBC and Section R301.1.3 of the 2006 IRC must be in accordance with ACI 318-05 Appendix D and this report. Design parameters provided in this report are based on the 2015 IBC (ACI 318-14) and the 2012 IBC (ACI 318-11) unless noted otherwise in Sections 4.1.1 through 4.1.13. The strength design of anchors must comply with ACI 318-14 17.3.1 or ACI 318-11 D.4.1, except as required in ACI 318-14 17.2.3 or ACI-11 318 D.3.3, as applicable. Strength reduction factors, φ, as given in ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, for cast-in headed anchors, must be used for load combinations calculated in accordance with Section 1605.2 of the IBC, Section 5.3 of ACI 318-14, or Section 9.2 of ACI 318-11, as applicable. Strength reduction factors,φ, as given in ACI 318-11 D.4.4 must be used for load combinations calculated in accordance with ACI 318-11 Appendix C. An example calculation in accordance with the 2015 IBC is provided in Figure 11 of this report. The value of f c used in the calculations must be limited to a maximum of 10,000 psi (68.9 MPa), in accordance with ACI 318-14 17.2.7 or ACI 318-11 D.3.7, as applicable. 4.1.2 Requirements for Static Steel Strength in Tension: The nominal static steel strength in tension, N sa, of a single anchor must be calculated in accordance with ACI 318-14 17.4.1 or ACI 318-11 D.5.1, as applicable, for the threaded steel insert element, N sa,rod, as illustrated in Table 5 of this report. The lesser of φn sa,rod in Table 5 or φn sa,insert provided in Tables 3 and 4 shall be used as the steel strength in tension. 4.1.3 Requirements for Static Concrete Breakout Strength in Tension: The nominal concrete breakout strength of a single anchor or group of anchors in tension, N cb or N cbg, respectively, must be calculated in accordance with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, for cast-in headed bolts, with modifications as described in this section, and with Figures 4, 5, 6, 7 and 8 of this report, as applicable. The basic concrete breakout strength in tension, N b, must be calculated in accordance with ACI 318-14 17.4.2.2 or ACI 318-11 D.5.2.2, as applicable, using the values of h ef given in Tables 1 and 2, and with k c = 24. The nominal concrete breakout strength in tension in regions where analysis indicates no cracking in accordance with ACI 318-14 17.4.2.6 or ACI 318-11 D.5.2.6, as applicable, must be calculated with Ψ c,n = 1.25. For the KCS-MD installed in the soffit of sand-lightweight or normal-weight concrete filled steel deck assemblies, the contribution of the steel deck strength must be ignored and the calculation of A Nc / A Nco in accordance with ACI 318-14 17.4.2.1 or ACI 318-11 D.5.2.1, as applicable, and c a,min (minimum edge distance) must be based on Figures 5, 6, 7 and 8. 4.1.4 Static Pullout Strength in Tension: The Static Pullout Strength in Tension for the KCS-WF does not control design, and need not be calculated. For the KCS-MD, N pn,deck for installations in the underside of lightweight concrete over metal deck assemblies is given in Table 4 of this report. 4.1.5 Requirements for Static Side-Face Blowout Strength in Tension: For the KCS-WF, the nominal side-face blowout strength of a headed insert, N sb, must be calculated in accordance with ACI 318-14 17.4.4.1 or ACI 318-11 D.5.4.1, as applicable, for the cast-in headed insert, using the values of A brg as given in Tables 1 and 2 of this report, as applicable. For the KCS-MD metal deck inserts installed in the soffit of sand-lightweight or normal-weight concrete on steel deck floor and roof assemblies as shown in Figures 6, 7 and 8, calculation of the concrete side blowout strength is not required. 4.1.6 Requirements for Static Steel Strength in Shear: For the KCSI-WF, the nominal static steel strength of a single anchor in shear, V sa, must be taken as the threaded steel insert element strength, V sa,rod, given in Table 5 of this report. The lesser of φv sa,rod in Table 5 or φv sa,insert in Table 3 must be used as the steel strength in shear, and must be used in lieu of the values derived by calculation from ACI 318-14 Eq. 17.5.1.2a or ACI 318-11, Eq. D-28, as applicable. For the KCS-MD, the nominal static steel strength in shear, V sa,deck, of a single KCS-MD insert, in the lower flute and upper flute of concrete filled steel deck assemblies, must be taken as the threaded steel insert element strength, V sa,rod, given in Table 5 of this report. The lesser of φv sa,rod in Table 5 or φv sa,insert,deck in Table 4 shall be used as the steel strength in shear, and must be used in lieu of the values derived by calculation from ACI 318-14 Eq. 17.5.1.2a or ACI 318-11, Eq. D-28, as applicable.

ESR-4006 Most Widely Accepted and Trusted Page 3 of 14 The values given in Tables 3 and 4 are for the insert only. Determination of the shear capacity of the threaded rod or other material inserted into the cast-in insert is the responsibility of the design professional. Shear values for common threaded rods are given in Table 5. 4.1.7 Requirements for Static Concrete Breakout Strength in Shear: For the KCS-WF, the nominal static concrete breakout strength of a single anchor or group of anchors in shear, V cb or V cbg, respectively, must be calculated in accordance with ACI 318-14 17.5.2 or ACI 318-11 D.6.2, as applicable. The basic concrete breakout strength, V b, must be calculated in accordance with ACI 318-14 17.5.2.2 or ACI 318-11 D.6.2.2 based on the values provided in Table 1. The values of l e (=h ef) and d a used in ACI 318-14 Eq. 17.5.2.2a or ACI 318-11 Eq. D-33, as applicable, are provided in Table 1 of this report. For the KCS-MD installed in the soffit of sand-lightweight or normal-weight concrete on steel deck floor and roof assemblies, as shown in Figures 4, 6, 7 and 8, calculation of the concrete breakout strength in shear is not required. 4.1.8 Requirements for Static Concrete Pryout Strength in Shear: For KCS-WF inserts, the nominal concrete pryout strength of a single anchor or group of anchors, V cp or V cpg, respectively, must be calculated in accordance with ACI 318-14 17.5.3 or ACI 318-11 D.6.3, as applicable. For the KCS-MD inserts installed in the soffit of sandlightweight or normal-weight concrete filled steel deck assemblies, as shown in Figures 4, 6, 7 and 8, calculation of the concrete pry-out strength in accordance with ACI 318-14 17.5.3 or ACI 318-11 D.6.3, as applicable is not required. 4.1.9 Requirements for Seismic Design: 4.1.9.1 General: For load combinations including seismic, the design must be performed in accordance with ACI 318-14 17.2.3 or ACI 318-11 D.3.3, as applicable. Modifications to ACI 318-14 17.2.3 shall be applied under Section 1905.1.8 of the 2015 IBC. For the 2012 IBC, Section 1905.1.9 shall be omitted. Modifications to ACI 318 D.3.3 shall be applied under Section 1908.1.9 of the 2009 IBC, or Section 1908.1.16 of the 2006 IBC. The anchors may be installed in Seismic Design Categories A through F of the IBC. The KCS-WF and KCS-MD inserts comply with ACI 318-14 2.3 or ACI 318-11 D.1, as applicable, as non-ductile steel elements. For the KCS-WF inserts, the nominal steel strength, nominal concrete breakout strength and nominal concrete side-face blowout strength for anchors in tension; and the nominal concrete breakout strength and pryout strength in shear, must be calculated in accordance with ACI 318-14 17.4 and 17.5 or ACI 318-11 D.5 and D.6, as applicable, using the values in Table 1 and Table 3, as applicable. For KCS-MD inserts, the nominal steel strength and nominal concrete breakout strength for anchors in tension; and the nominal concrete breakout strength and pryout strength in the upper flute of concrete filled steel deck assemblies for anchors in shear, must be calculated in accordance with ACI 318-14 17.4 and 17.5 or ACI 318-11 D.5 and D.6, as applicable, using the values in Table 2 and Table 4, as applicable. 4.1.9.2 Seismic Tension: For KCS-WF inserts, the nominal steel strength in tension, N sa, of a single anchor must be calculated in accordance with ACI 318-14 17.4.1 or ACI 318-11 Section D.5.1, as applicable, for the threaded steel element, N sa,rod,eq, as given in Table 5, not to exceed the corresponding values of N sa,insert,eq in Table 3 of this report; the nominal concrete breakout strength for anchors in tension must be calculated in accordance with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, as described in Section 4.1.3 of this report; the nominal pullout strength in accordance with ACI 318-14 17.4.3 or ACI 318-11 D.5.3, as applicable, need not be considered as noted in Section 4.1.4 of this report; the nominal concrete side-face blowout strength must be calculated in accordance with ACI 318-14 17.4.4.1 and 17.4.4.2 or ACI 318-11 D.5.4.1 and D.5.4.2, as applicable, and Section 4.1.5 of this report. For KCS-MD inserts, the nominal steel strength in tension, N sa, of a single anchor must be calculated in accordance with ACI 318-14 17.4.1 or ACI 318-11 D.5.1, as applicable, for the threaded steel element, N sa,rod,eq, as given in Table 5, not to exceed the corresponding values of N sa,insert,eq in Table 4 of this report; the nominal concrete breakout strength for anchors in tension must be calculated in accordance with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, as described in Section 4.1.3 of this report; the nominal concrete pullout strength in given in Table 4, and must be used in lieu of calculations in accordance with ACI 318-14 17.4.3 or ACI 318-11 D.5.3, as applicable. 4.1.9.3 Seismic Shear: For KCS-WF inserts, the nominal concrete breakout strength and pryout strength in shear must be calculated in accordance with ACI 318-14 17.5.2 and 17.5.3 or ACI 318-11 D.6.2 and D.6.3, as applicable, as described in Sections 4.1.7 and 4.1.8 of this report. In accordance with ACI 318-14 17.5.1.2 or ACI 318-11 D.6.1.2, as applicable, the nominal steel strength for seismic loads, V sa,eq, must be taken as the threaded steel element strength, V sa,rod,eq, given in Table 5 of this report, not to exceed the corresponding values of V sa,insert,eq, in Table 3. For KCS-MD inserts, the nominal concrete breakout strength and pryout strength in shear, calculations in accordance with ACI 318-14 17.5.2 and 17.5.3 or ACI 318-11 D.6.2 and D.6.3, as applicable, as described in Sections 4.1.7 and 4.1.8 of this report, are not required. In accordance with ACI 318-14 17.5.1.2 or ACI 318 D.6.1.2, as applicable, the nominal steel strength for seismic loads, V sa,eq, must be taken as the threaded steel element strength, V sa,rod,eq, given in Table 5 of this report, not to exceed the corresponding values of V sa,insert,deck,eq, in Table 4, for lower flute or upper flute of the concrete filled steel deck assembly, as applicable. 4.1.10 Requirements for Interaction of Tensile and Shear Forces: For designs that include combined tension and shear, the interaction of tension and shear loads must be calculated in accordance with ACI 318-14 17.6 or ACI 318-11 D.7, as applicable. Due to the projection of the internally-threaded end of the KCS-MD insert when installed in concrete filled steel deck assemblies, for anchors or groups of anchors that are subject to the effects of combined tension and shear forces, the design engineer must take into consideration the effect of bending and verify the validity of the interaction equation in ACI 318-14 17.6 or ACI 318-11 D.7, as applicable. 4.1.11 Requirements for Minimum Member Thickness, h min, Minimum Anchor Spacing, s min, and Minimum Edge Distance, c min: Requirements on headed cast-in specialty anchor edge distance, spacing, member thickness, and concrete strength must be in accordance

ESR-4006 Most Widely Accepted and Trusted Page 4 of 14 with the requirements in ACI 318-14 17.7 or ACI 318-11 D.8, as applicable, for cast-in bolts. For KCS-MD inserts installed in the soffit of sandlightweight or normal-weight concrete over profile steel deck floor and roof assemblies, the anchors must be installed in accordance with Figures 6, 7 and 8, and shall have a minimum axial spacing along the flute equal to 3h ef. 4.1.12 Requirements for Critical Edge Distance: The calculation of the critical edge distance, c ac, is not required, since the modification factor Ψ cp,n = 1.0 for cast-in anchors in accordance with ACI 318-14 17.4.2.5 or ACI-11 318 D.5.2.5, as applicable. 4.1.13 Lightweight Concrete: For the KCS-WF in lightweight concrete, the modification factor λ, for concrete breakout strength must be in accordance with ACI 318-14 17.2.6 (2015 IBC), ACI 318-11 D.3.6 (2012 IBC), ACI 318-08 D.3.4 (2009 IBC), or ACI 318-05 D.3.4 (2006 IBC). For KCS-MD inserts in the soffit of sand-lightweight concrete-filled steel deck, this reduction is not required. Values shown in Table 4 are based on use in sandlightweight concrete and are also valid for normal weight concrete. Installation details are shown in Figures 6, 7 and 8. 4.2 Allowable Stress Design (ASD): 4.2.1 General: Design values for use with allowable stress design (working stress design) load combinations calculated in accordance with Section 1605.3 of the IBC, must be established as follows: T allowable,asd = φn n α V allowable,asd = φv n α where: T allowable,asd = Allowable tension load (f or kn). V allowable,asd = Allowable shear load (f or kn). φn n = Lowest design strength of an anchor or anchor group in tension as determined in accordance with ACI 318-14 17.3.1 and 2015 IBC Section 1905.1.8, ACI 318-11, -08 D.4.1, and 2009 IBC Section 1908.1.9 or 2006 IBC Section 1908.1.16, as applicable (f or N). φv n = Lowest design strength of an anchor or anchor group in shear as determined in accordance with ACI 318-14 17.3.1 and 2015 IBC Section 1905.1.8, ACI 318-11, -08 D.4.1, and 2009 IBC Section 1908.1.9 or 2006 IBC Section 1908.1.16, as applicable (f or N). α = Conversion factor calculated as a weighted average of the load factors for the controlling load combination. In addition, α must include all applicable factors to account for non-ductile failure modes and required over-strength. The requirements for member thickness, edge distance and spacing, described in this report, must apply. Examples of allowable stress design value determination for illustrative purposes are shown in Table 6. 4.2.2 Interaction of Tensile and Shear Forces: For designs that include combined tension and shear, the interaction of tension and shear loads must be calculated in accordance with ACI 318-14 17.6 or ACI 318-11 D.7, as applicable, as follows: For shear loads V applied 0.2V allowable,asd, the full allowable load in tension must be permitted. For tension loads T applied 0.2T allowable,asd, the full allowable load in shear must be permitted. For all other cases: TT aaaaaaaaaaaaaa + TT aaaaaaaaaaaaaaaaaa,aaaaaa VV aaaaaaaaaaaaaa VV aaaaaaaaaaaaaaaaaa,aaaaaa 1.2 (Eq-1) Due to the projection of the internally-threaded end of the KCS-MD insert when installed in concrete filled steel deck assemblies, for anchors or groups of anchors that are subject to the effects of combined tension and shear forces, the design engineer must take into consideration the effect of bending and verify the validity of the interaction equation in ACI 318-14 17.6 or ACI 318-11 D.7, as applicable. 4.3 Installation: For the KCS-WF inserts, installation parameters are provided in Table 1 and in Figures 3 and 9. KCS-WF inserts must be positioned on wood or similar formwork with all nails in contact with the form. The head of the KCS-WF must be impacted with sufficient force to drive nails all the way into the formwork until the plastic base sits flush and tight against the form. From beneath the deck, following the concrete pour and form removal, the three nails may be broken off, and a threaded rod or bolt element must be screwed into the internal threads of the KCS-WF until fully seated in the insert, which will result in a thread engagement equal to one diameter. The threaded steel rod or bolt element must have a minimum thread engagement equal to one steel element diameter. For the KCS-MD inserts, installation parameters are provided in Table 2 and in Figures 4, 6, 7, 8 and 10. A hole must be made in the steel deck using a hole saw in accordance with the corresponding hole diameters shown in Table 2. From the topside of the deck, the KCS-MD plastic sleeve must be placed in the hole, and following this, the head of the insert must be stepped on or impacted with sufficient force to compress the outer spring and drive the flared plastic fins of the sleeve completely through the hole in the steel deck. The KCS-MD metal base plate may be screwed to the deck for additional stability (optional). After insertion in deck, a threaded rod or bolt element must be inserted through the plastic thread protector nozzle until contact is made with the inner steel barrel. The threaded rod or bolt element must then be screwed into the KCS-MD internal threads. The rod or bolt must be tightened until fully seated in the insert, which will result in a thread engagement equal to a minimum of one rod diameter. The plastic sleeve must be cut and trimmed to the surface of the insert following the concrete pour if the insert is intended to resist shear loads. KCS-MD inserts are permitted to be installed in either the upper or lower flute of the steel deck. Installation of KCS-WF and KCS-MD inserts must be in accordance with this evaluation report and the manufacturer s published installation instruction (MPII) as provided in Figures 9 and 10 of this report. In the event of a conflict between this report and the MPII, this report governs. 4.4 Special Inspection: Periodic special inspection is required in accordance with Section 1705.1.1 and Table 1705.3 of the 2015 or 2012

ESR-4006 Most Widely Accepted and Trusted Page 5 of 14 IBC, or Section 1704.15 and Table 1704.4 of the 2009 IBC, or Section 1704.13 of the 2006 IBC, as applicable. The special inspector must make periodic inspections during installation of the headed cast-in specialty inserts to verify insert type, insert dimensions, concrete type, concrete compressive strength, insert spacing, edge distances, concrete member thickness, insert embedment, threaded rod fully seated into insert, and adherence to the manufacturer s printed installation instructions. The special inspector must be present as often as required in accordance with the statement of special inspection. Under the IBC, additional requirements as set forth in Sections 1705, 1706 and 1707 must be observed, where applicable. 5.0 CONDITIONS OF USE The KCS-WF and KCS-MD concrete inserts described in this report are acceptable alternatives to what is specified in the codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 Specialty inserts are limited to dry interior locations. 5.2 Specialty insert sizes, dimensions, minimum embedment depths, and other installation parameters are as set forth in this report. 5.3 Specialty inserts must be installed in accordance with the manufacturer s printed installation instructions (MPII) and this report. In case of conflict, this report governs. 5.4 Specialty inserts must be limited to use in cracked and uncracked normal-weight concrete, and lightweight concrete having a specified compressive strength, f' c, of 2,500 psi to 10,000 psi (17.2 MPa to 68.9 MPa) for the KCS-WF inserts, and in cracked and uncracked normal-weight or sand-lightweight concrete filled steel deck assemblies having a specified compressive strength, f' c, of 3,000 psi to 10,000 psi (20.7 MPa to 68.9 MPa) for the KCS-MD inserts. 5.5 The values of f' c used for calculation purposes must not exceed 10,000 psi (68.9 MPa). 5.6 Strength design values must be established in accordance with Section 4.1 of this report. 5.7 Allowable design values are established in accordance with Section 4.2. 5.8 Specialty insert spacing and edge distance as well as minimum member thickness must comply with ACI 318-14 17.7 or ACI 318-11 Section D.8 requirements, as applicable, for cast-in-place headed anchors, and Table 1 and Table 2, and Figures 6, 7 and 8 of this report. 5.9 Prior to installation, calculations and details demonstrating compliance with this report must be submitted to the code official. The calculations and details must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 5.10 Since an ICC-ES acceptance criteria for evaluating data to determine the performance of the specialty inserts subjected to fatigue or shock loading is unavailable at this time, the use of these inserts under such conditions is beyond the scope of this report. 5.11 Specialty inserts may be installed in regions of concrete where analysis indicates cracking may occur (f t > f r ), subject to the conditions of this report. 5.12 Specialty inserts may be used to resist short-term loading due to wind or seismic forces in locations designated as Seismic Design Categories A through F of the IBC, subject to the conditions of this report. 5.13 Where not otherwise prohibited in the code, inserts are permitted for use with fire-resistance-rated construction provided that at least one of the following conditions is fulfilled: Headed cast-in specialty inserts that support a fireresistance-rated envelope or a fire- resistancerated membrane are protected by approved fireresistance-rated materials, or have been evaluated for resistance to fire exposure in accordance with recognized standards. Headed cast-in specialty inserts are used to resist wind or seismic forces only. Headed cast-in specialty inserts are used to support nonstructural elements. 5.14 Special inspection must be provided in accordance with Section 4.4. 5.15 Specialty inserts are manufactured under an approved quality control program with inspections by ICC-ES. 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Headed Cast-in Specialty Inserts in Concrete (AC446), dated February 2015, editorially revised January 2016. 6.2 Quality-control documentation. 7.0 IDENTIFICATION The KCS-WF and KCS-MD inserts are identified by packaging labeled with the manufacturer s name (Hilti, Inc.) and contact information, insert name, insert size, lot number and evaluation report number (ESR-4006). The inserts have various colored plastic housings to identify the product size.

ESR-4006 Most Widely Accepted and Trusted Page 6 of 14 TABLE 1 HILTI KWIK CAST KCS-WF CAST-IN INSERT INSTALLATION INFORMATION 2,3 DESIGN INFORMATION SYMBOL UNITS 1 / 4 Nominal anchor diameter () 3 / 1 8 / 5 2 / 8 3 / 4 Plastic housing color - - Green Red Orange Yellow Black Insert thread size d UNC Effective embedment 1 h ef 1 / 4-20 1.11 (28) 3 / 8-16 1 / 2-13 1.63 (42) 5 / 8-11 1.90 (48) 3 / 4-10 1.83 (46) M member thickness h min 2 1 / 2 (64) 3 3 / 4 (95) Outside anchor diameter d a 0.51 (13) 0.67 (17) 0.87 (22) 1.00 (25) Bearing area A brg 2 (mm 2 ) 0.935 (603) 0.780 (503) 0.969 (625) 0.993 (641) For SI: 1 inch = 25.4 mm. For pound-inch units: 1 mm = 0.03937 inch. 1 See figure 1. 2 Reference ACI 318-14 17.3.1.1 or ACI 318-11 D.4.1.1, as applicable. The controlling strength is decisive from all appropriate failure modes (i.e. steel, concrete breakout, pryout and side-face blowout, as applicable) and design assumptions. The pullout strength in tension is not decisive for design and does not need to be evaluated. 3 See Section 4.1.9 for requirements for seismic design, where applicable. TABLE 2 HILTI KWIK CAST KCS-MD CAST-IN INSERT INSTALLATION INFORMATION 5,6 DESIGN INFORMATION SYMBOL UNITS 3 / 8 Nominal anchor diameter () 1 / 2 5 / 8 3 / 4 Plastic section color - - Red Orange Yellow Black Insert thread size d UNC 3 / 8-16 1 / 2-13 5 / 8-11 3 / 4-10 Effective embedment 1 h ef 1.95 (50) Metal hole saw diameter d bit M concrete cover over metal deck - upper flute install 2,3,4 hupper,min M. concrete cover over metal deck lower flute install 2,3,4 hlower,max 7 / 8 1 3 / 16 1 3 / 16 1 1 / 4 2 1 / 2 (64) 1 1 / 2 (38) M metal deck gauge - - 20 M offset from lower flute edge 2,3,4-1 3 / 8 (35) Outside anchor diameter d a 0.67 (17) 0.87 (22) 0.87 (22) 1.00 (25) Bearing area M edge distance 2,3,4 M anchor spacing 2,3,4 A brg c a,min s min 2 (mm 2 ) 1.14 (735) 1.11 (717) 1 1 / 2 (38) 5.85 (149) 1.11 (717) For SI: 1 inch = 25.4 mm, 1 pound = 0.00445 kn, 1 in 2 = 645.2 mm 2. For pound-inch unit: 1 mm = 0.03937 inches. 1.15 (742) 1 See Figure 2. 2 See Figure 6. 3 See Figure 7. 4 See Figure 8. 5 Reference ACI 318-14 17.3.1.1 or ACI 318-11 D.4.1.1, as applicable. The controlling strength is decisive from all appropriate failure modes (i.e. steel, concrete breakout, pryout and side-face blowout, as applicable) and design assumptions. The pullout strength in tension is not decisive for design and does not need to be evaluated. 6 See Section 4.1.9 for requirements for seismic design, where applicable.

ESR-4006 Most Widely Accepted and Trusted Page 7 of 14 FIGURE 1 HILTI KWIK CAST KCS-WF ANCHOR FIGURE 2 HILTI KWIK CAST KCS-MD ANCHOR TABLE 3 HILTI KWIK CAST KCS-WF INSERT DESIGN INFORMATION 1,2,3,4,5,6,7 DESIGN INFORMATION SYMBOL UNITS 1 / 4 Nominal anchor diameter () 3 / 1 8 / 5 2 / 8 3 / 4 Characterization of insert per D.1 - - Non-Ductile Effective Embedment h ef Outside anchor diameter d a Nominal steel strength in tension as governed by the insert 2 Nsa,insert Nominal seismic steel strength in tension as governed by the insert 2 Nsa,insert,eq Nominal steel strength in shear as governed by the insert 2 Vsa,insert Nominal seismic steel strength in shear as governed by the insert 2 Vsa,insert,eq Modification factor for tension in uncracked concrete Modification factor for tension in cracked concrete Strength reduction factor ϕ for tension, steel failure of insert Strength reduction factor ϕ for shear, steel failure of insert ψ c,n ψ c,n ϕ ϕ 3,770 (16.8) 3,770 (16.8) 2,750 (12.2) 2,750 (12.2) 1.11 (28) 0.51 (13) 3,770 (16.8) 3,770 (16.8) 2,750 (12.2) 2,750 (12.2) Effectiveness factor cracked 4 k cr - 24 - - - - 1.63 (42) 0.67 (17) 13,020 (57.9) 13,020 (57.9) 3,520 (15.7) 3,520 (15.7) 1.25 1.0 0.65 0.60 1.90 (48) 0.87 (22) 14,000 (62.3) 14,000 (62.3) 8,690 (38.6) 8,690 (38.6) 1.83 (46) 1.00 (25) 14,000 (62.3) 14,000 (62.3) 9,070 (40.3) 9,070 (40.3) Coefficient for pryout strength k cp - 1.0 Strength reduction factor ϕ for tension, concrete failure modes, Condition B 5 ϕ - Strength reduction factor ϕ for shear, concrete failure modes, Condition B 5 ϕ - Concrete pullout, uncracked N p,uncr - NA Concrete pullout, cracked N p,cr - NA For SI: 1 inch = 25.4 mm. For pound-inch units: 1 mm = 0.03937 inch. 1 Installation must comply with Section 4.3 and Figure 3 of this report. 2 The design strength must be in accordance with ACI 318-14 Chapter 17 or ACI 318-11 Appendix D, as applicable, and Section 4.1 of this report. Values are for the insert only. The capacity of the threaded rod or other material threaded into the insert must be also be determined. See Table 5 for steel design information for common threaded rod elements. 3 See ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable. 4 See ACI 318-14 17.4.2.2 or ACI 318-11 D.5.2.2, as applicable. 5 For use with load combinations of ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable. Condition B applies where supplementary reinforcement in conformance with ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, is not provided. For cases where the presence of supplementary reinforcement can verified, the strength reduction factors associated with Condition A may be used. 6 Inserts must be installed in concrete with a minimum compressive strength f ' c of 2,500 psi. 7 The design professional is responsible for checking threaded rod or bolt strength in tension, shear, and combined tension and shear, as applicable. 0.70 0.70

ESR-4006 Most Widely Accepted and Trusted Page 8 of 14 FIGURE 3 KCS-WF INSTALLED IN CONCRETE FIGURE 4 KCS-MD INSTALLED IN SOFFIT OF CONCRETE FILLED STEEL DECK FLOOR AND ROOF ASSEMBLIES FIGURE 5 IDEALIZATION OF CONCRETE FILLED STEEL DECKS FOR DETERMINATION OF CONCRETE BREAKOUT STRENGTH IN ACCORDANCE WITH ACI 318

ESR-4006 Most Widely Accepted and Trusted Page 9 of 14 TABLE 4 HILTI KWIK CAST KCS-MD INSERT DESIGN INFORMATION 1,2,3,4,5,6 DESIGN INFORMATION SYMBOL UNITS Nominal anchor diameter () 3 / 1 8 / 5 2 / 3 8 / 4 Characterization of insert per D.1.1 - - Non-ductile Effective embedment h ef 1.95 (50) Outside anchor diameter d a 0.67 0.87 (17) (22) Strength reduction factor for tension, steel failure ϕ - 0.65 Strength reduction factor for shear, steel failure ϕ - 0.60 Strength reduction factor ϕ for tension, concrete failure modes, Condition B ϕ - 0.70 Strength reduction factor ϕ for shear, concrete failure modes, Condition B ϕ - 0.70 Nominal pullout resistance, cracked W deck (4-1 / 2 inch width) 1,700 1,700 1,700 N lower flute pn,deck (7.6) (7.6) (7.6) Nominal pullout resistance, cracked W deck (3-7 / 8 inch width) 1,485 1,485 1,485 N lower flute pn,deck (6.6) (6.6) (6.6) 700 700 700 Nominal pullout resistance, cracked- B deck lower flute N pn,deck (3.1) (3.1) (3.1) Nominal steel strength in tension as governed by the insert N sa,insert 13,000 13,000 13,000 (58) (58) (58) Nominal seismic steel strength in tension as governed by the insert N sa,insert,eq 13,000 13,000 13,000 (58) (58) (58) Installations in upper flute of metal deck according to Figures 6, 7 or 8 Nominal steel strength in shear as governed by the insert V sa,deck Nominal seismic steel strength in shear as governed by the insert V sa,deck,eq 2,650 (11.8) 2,650 (11.8) 2,865 (12.7) 2,865 (12.7) 2,865 (12.7) 2,865 (12.7) Installations in lower flute of 3-inch minimum flute height (i.e. W-deck with 4-1 / 2 inch lower flute width) according to Figure 6 Nominal steel strength in shear as governed by the insert Nominal seismic steel strength in shear as governed by the insert V sa,deck V sa,deck,eq 1,410 (6.3) 1,410 (6.3) 1,525 (6.8) 1,525 (6.8) 1,525 (6.8) 1,525 (6.8) Installations in lower flute of 3-inch minimum flute height (i.e. W-deck with 3-7 / 8 inch lower flute width) according to Figure 7 Nominal steel strength in shear as governed by the insert Nominal seismic steel strength in shear as governed by the insert V sa,deck V sa,deck,eq 1,410 (6.3) 1,410 (6.3) 1,525 (6.8) 1,525 (6.8) Installations in lower flute of 1 1 / 2-inch minimum flute height (i.e. B -deck) according to Figure 8 Nominal steel strength in shear as governed by the insert Nominal seismic steel strength in shear as governed by the insert For SI: 1 inch = 25.4 mm. For pound-inch units: 1 mm = 0.03937 inch. V sa,deck V sa,deck,eq 1,060 (4.7) 1,060 (4.7) 1,125 (5.0) 1,125 (5.0) 1,525 (6.8) 1,525 (6.8) 1,125 (5.0) 1,125 (5.0) 1.00 (25) 1,700 (7.6) 1,485 (6.6) 700 (3.1) 13,000 (58) 13,000 (58) 6,495 (28.9) 6,495 (28.9) 1 Inserts may be placed in the upper flute or lower flute of the steel deck assembly. Inserts in the lower flute require a minimum 1 1 / 2" of concrete topping thickness from the top of the upper flute. Upper flute installations require a minimum 2 1 / 2" concrete topping thickness from the top of the upper flute. Inserts in upper flute may be installed anywhere across upper flute. 2 Axial spacing for KCS-MD inserts along the lower flute length shall be minimum 3h ef. 3 Installation must comply with Section 4.3 and Figure 6 or Figure 7 of this report. 4 The design strength must be in accordance with ACI 318-14 Chapter 17 or ACI 318 Appendix D, as applicable, and Section 4.1 of this report. The capacity of the threaded rod or other material threaded into the insert must be also be determined. See Table 5 for steel design information for common threaded rod elements. 5 The characteristic pullout resistance for concrete compressive strengths greater than 3,000 psi may be increased by multiplying the value in the table by (f' c/3,000) 1/2 for psi or (f' c/20.7) 1/2 for MPa. 6 Evaluation of concrete breakout capacity in accordance with ACI 318-14 17.4.2, 17.5.2, and 17.5.3 or ACI 318-11 D.5.2, D.6.2, and D.6.3, as applicable, is not required for anchors installed in the deck soffit. 1,880 (8.4) 1,880 (8.4) 1,530 (6.2) 1,530 (6.2) 1,125 (5.0) 1,125 (5.0)

ESR-4006 Most Widely Accepted and Trusted Page 10 of 14 TABLE 5 STEEL DESIGN INFORMATION FOR COMMON THREADED ROD ELEMENTS USED WITH HILTI KWIK CAST KCS CONCRETE INSERTS 1,2,3,4 DESIGN INFORMATION SYMBOL UNITS 1 / 4-inch 3 / 8-inch 1 / 2-inch 5 / 8-inch 3 / 4-inch Threaded rod nominal outside diameter d rod Threaded rod effective cross-sectional area A se in 2 Nominal tension strength of ASTM A36 threaded rod in tension as governed by steel strength for static or seismic loading Nominal tension strength of ASTM F1554, Gr. 105 threaded rod in tension as governed by steel strength for static or seismic loading Nominal tension strength of ASTM A193 threaded rod in tension as governed by steel strength for static or seismic loading Nominal shear strength of ASTM A36 threaded rod in shear as governed by steel strength for static loading Nominal shear strength of ASTM A36 threaded rod in shear as governed by steel strength for seismic loading Nominal shear strength of ASTM F1554, Gr. 105 threaded rod in shear as governed by steel strength for static loading Nominal shear strength of ASTM F1554, Gr. 105 threaded rod in shear as governed by steel strength for seismic loading Nominal shear strength of ASTM A193 threaded rod in shear as governed by steel strength for static loading Nominal shear strength of ASTM A193 threaded rod in shear as governed by steel strength for seismic loading N sa,rod,a36 or N sa,rod,eq,a36 N sa,rod,f1554 or N sa,rod,eq,f1554 N sa,rod,a193 or N sa,rod,eq,a193 V sa,rod,a36 V sa,rod,eq,a36 V sa,rod,f1554 V sa,rod,eq,f1554 V sa,rod,a193 V sa,rod,eq,a193 (mm 2 ) 0.250 (6.4) 0.032 (21) 1,855 (8.2) 4,000 (17.7) 4,000 (17.7) 1,105 (4.9) 780 (3.5) 2,385 (10.6) 1,680 (7.5) 2,385 (10.6) 1,680 (7.5) 0.375 (9.5) 0.078 (50) 4,525 (20.0) 9,750 (43.1) 9,750 (43.1) 2,695 (12.0) 1,900 (8.4) 5,815 (25.9) 4,095 (18.2) 5,815 (25.9) 4,095 (18.2) For SI: 1 inch = 25.4 mm, 1 pound = 0.00445 kn, 1 in 2 = 645.2 mm 2. For pound-inch unit: 1 mm = 0.03937 inches. 0.500 (12.7) 0.142 (92) 8,235 (36.6) 17,750 (78.9) 17,750 (78.9) 4,940 (22.0) 3,460 (15.4) 10,640 (7.3) 7,455 (34.2) 10,640 (7.3) 7,455 (34.2) 0.625 (15.9) 0.226 (146) 13,110 (58.3) 28,250 (125.7) 28,250 (125.7) 7,860 (35.0) 5,505 (24.5) 16,950 (75.4) 11,865 (52.8) 16,950 (75.4) 11,865 (52.8) 0.750 (19.1) 0.335 (216) 19,400 (86.3) 41,875 (186.0) 41,875 (186.0) 11,640 (51.8) 8,160 (36.3) 25,085 (111.6) 17,590 (78.2) 25,085 (111.6) 1 Values provided for steel element material types, or equivalent, based on minimum specified strength; N sa,rod and V sa,rod calculated in accordance with ACI 318-14 Eq. (17.4.1.2) and Eq. (17.5.1.2b) or ACI 318-11 Eq. (D-2) and Eq. (D-29) respectively. V sa,rod,eq must be taken as 0.7V sa,rod. Materials of other strengths may be used and calculated in similar manner. 2 ϕn sa shall be the lower of the ϕn sa,rod or ϕn sa,insert for static steel strength in tension; for seismic loading ϕn sa,eq shall be the lower of the ϕn sa,rod,eq or ϕn sa,insert,eq. 3 ϕv sa shall be the lower of the ϕv sa,rod or ϕv sa,insert for static steel strength in tension; for seismic loading ϕv sa,eq shall be the lower of the ϕv sa,rod,eq or ϕv sa,insert,eq. 4 Strength reduction factors shall be taken from ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, for steel elements. Strength reduction factors for load combinations in accordance with ACI 318-14 5.3 or ACI 318-11 9.2 governed by steel strength of ductile steel elements shall be taken as 0.75 for tension and 0.65 for shear. The value of ϕ applies when the load combinations of Section 1605.2 of the IBC, ACI 318-14 5.3, or ACI 318-11 Section 9.2 are used in accordance with ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable. If the load combinations of ACI 318-11 Appendix C are used, the appropriate value of ϕ must be determined in accordance with ACI 318-11 D.4.4. 17,590 (78.2) FIGURE 6 INSTALLATION IN THE SOFFIT OF CONCRETE FILLED STEEL DECK FLOOR AND ROOF ASSEMBLIES W DECK WITH 4-1/2 INCH FLUTE WIDTH 1,2 1 Anchors may be placed in the upper or lower flute of the steel deck profile provided the minimum clearance is satisfied. Anchors in the lower flute may be installed with a min 1 1 / 8" offset from the edge of the flute. 2 Axial spacing along the flute length shall be minimum 3h ef.

ESR-4006 Most Widely Accepted and Trusted Page 11 of 14 FIGURE 7 INSTALLATION IN THE SOFFIT OF CONCRETE FILLED STEEL DECK FLOOR AND ROOF ASSEMBLIES W DECK WITH 3-7/8 INCH FLUTE WIDTH 1,2 1 Anchors may be placed in the upper or lower flute of the steel deck profile provided the minimum clearance is satisfied. Anchors in the lower flute may be installed with a min 3 / 4" offset from the edge of the flute. 2 Axial spacing along the flute length shall be minimum 3h ef. FIGURE 8 INSTALLATION IN THE SOFFIT OF CONCRETE FILLED STEEL DECK FLOOR AND ROOF ASSEMBLIES B DECK 1,2 1 Anchors may be placed in the upper or lower flute of the steel deck profile provided the minimum clearance is satisfied. Anchors in the lower flute may be installed with a minimum 3 / 4" offset from the edge of the flute to the edge of the insert. 2 Axial spacing along the flute length shall be minimum 3h ef. TABLE 6 EXAMPLE ASD ALLOWABLE TENSION AND SHEAR DESIGN VALUES FOR ILLUSTRATIVE PURPOSES FOR KCS- WF INSTALLED IN NORMAL WEIGHT CONCRETE AND KCS-MD INSTALLED IN LIGHTWEIGHT CONCRETE OVER METAL DECK FLOOR AND ROOF ASSEMBLIES 1,2,3,4,5,6,7,8,9 Nominal Insert Diameter (inches) KCS-WF Tension (s) Shear (s) KCS-MD W-Deck Installation B-Deck Installation 3-7 / 8 inch width 4-1 / 2 inch width Upper Flute Lower Flute Upper Flute Lower Flute Upper Flute Lower Flute Tension (s) Shear (s) Tension (s) Shear (s) Tension (s) Shear (s) Tension (s) Shear (s) Tension (s) Shear (s) Tension (s) 1 / 4 830 830 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 3 / 8 830 830 1,800 1,255 415 500 1,800 1,255 880 665 1,800 1,255 1,005 665 1 / 2 1,480 1,480 1,800 1,355 415 530 1,800 1,355 880 720 1,800 1,355 1,005 720 5 / 8 1,860 1,860 1,800 1,355 415 530 1,800 1,355 880 720 1,800 1,355 1,005 720 3 / 4 1,755 1,755 1,800 3,070 415 530 1,800 3,070 880 725 1,800 3,070 1,005 890 For SI: 1 inch = 25.4 mm, 1 pound = 0.00445 kn, 1 in 2 = 645.2 mm 2. For pound-inch unit: 1 mm = 0.03937 inches. 1 Concrete strength f c = 2500 psi for KCS-WF; f' c= 3000 psi sand-lightweight for KCS-MD. 2 Values are for single anchors with static tension or shear with no nearby edge impact. Installation must be in accordance with applicable Figure 3, 4, 6, 7 or 8. 3 Values are for uncracked concrete. 4 Load combinations as given in ACI 318-14 5.4 or ACI 318 9.2, as applicable. 5 30% dead load and 70% live load, controlling load combination 1.2D + 1.6 L. 6 Calculation of ASD conversion α = 0.3*1.2 + 0.7*1.6 = 1.48 Shear (s)

ESR-4006 Most Widely Accepted and Trusted Page 12 of 14 7 Values assume no side-face blowout in tension for KCS-WF or for KCS-MD installed in upper flute. 8 Values are for Condition B where supplementary reinforcement in accordance with ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, is not provided. 9 The allowable loads shown are for the applicable insert only. Design professional is responsible for checking capacity of threaded rod, including tension, shear, and influence of bending on tension capacity when loaded in shear, or other material placed in insert. FIGURE 9 KWIK CAST KCS-WF CONCRETE INSERTS MANUFACTUER PRINTED INSTALLATION INSTRUCTIONS (MPII)

ESR-4006 Most Widely Accepted and Trusted Page 13 of 14 FIGURE 10 KWIK CAST KCS-MD CONCRETE INSERTS MANUFACTUER PRINTED INSTALLATION INSTRUCTIONS (MPII) Given: Two ¾ ϕ KCS-WF anchor (un-torqued) with an edge distance of 2 and spacing of 12 loaded in tension, N, and shear, V. h ef= 1.83 in No supplementary reinforcement Condition B per ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3 (c), as applicable Assume normal weight concrete, f c= 3,000 psi Assume cracked concrete ASTM A36 attached steel rod insert element Needed: Using strength design provisions of ACI 318-14 Chapter 17 or ACI 318-11 Appendix D, calculate the design shear and tensile strength capacity for this configuration. Calculations per ACI 318-14 Chapter 17 or ACI 318-11 Appendix D and this report. ACI 318-14 ACI 318-11 Report Ref. Step 1. Calculate steel tensile capacity. Nsa,insert = Ase,Nfuta Given in Table 3 Nsa,insert= 14,000. ϕn sa,insert = ϕ(14,000) 2 ϕn sa,insert = 18,200. Nsa,rod,A36 = Ase,Nfuta Given in Table 5 Nsa,rod,A36= 19,400. ϕn sa,rod,a36 = ϕ(19,400) 2 ϕn sa,rod,a36 = 29,100. 17.3.3 17.4.1 D.4.4.1 D.5.1 4.1.2 Table 3 Table 5 Step 2. Calculate concrete breakout of anchor in tension. Ncb = Nb (ANc/ANco)ψ ed,nψ c,n ψ cp,n 17.4.2.1 a) D.5.2.1 a) 4.1.3 Step 2a. Check spacing and edge distance requirements. Given in Table 1 c a,min = 2 in > 1.5 in s anchor = 12 in > 4.0 in okay spacing and edge distance 17.7.1-6 D.8.1-6 4.1.11 4.1.12 Table 1 Step 2b. Determine λ. normal weight concrete λ= 1.0 Step 2c. Calculate basic concrete breakout strength in tension. Nb=24λ f c (hef) 1.5 Nb=24(1.0) 3,000(1.83) 1.5 Nb = 3,254 Step 2d. Determine effective projected concrete breakout area. A Nc = (c a1 + 1.5h ef )(2 1.5h ef ) A Nc = (2 + 1.5 1.83)(2 1.5 1.83) A Nc = 26.05 in 2 Step 2e. Determine idealized projected concrete breakout area. A Nco = 9(h ef ) 2 = 30.14 in 2 17.2.6 D.3.6 4.1.13 17.4.2.2 D.5.2.2 4.1.3 17.4.2.3 D.5.2.3 4.1.3 17.4.2.1 D.5.2.1 4.1.3 Step 2f. Determine ψ ed,n. ψ ed,n = 0.7 + 0.3 c a,min 1.5h ef 17.4.2.5 D.5.2.5 4.1.3 ψ ed,n = 0.7 + 0.3 2 1.5 1.83 Step 2g. Determine ψ c,n. cracked concrete ψ c,n = 1.0 Step 2i. Determine ψ cp,n. cast-in anchor with cracked concrete ψ cp,n = 1.0 17.4.2.6 D.5.2.6 4.1.3 17.4.2.7 D.5.2.7 4.1.12 Step 2j. Calculate ϕn cb. ϕn cb = 0.7 2 26.05 3,254 0.919 1.0 1.0 30.14 ϕn cb = 3,618 17.3.3 c) 17.4.2.1 a) D.4.3 c) D.5.2.1 a) 4.1.3 Step 3. Check pullout strength of concrete in tension. N pn = ψ c,pn p Step 3a. Determine ψ c,p. cracked concrete ψ c,p = 1.0 17.4.3.1 D.5.3.1 4.1.4 17.4.3.6 D.5.3.6 4.1.4 Step 3b. Calculate basic concrete pullout in tension. N p = 8A brg f c N p = 8 2 0.993 3,000 N p = 47,664 17.4.3.4 D.5.3.4 4.1.4 FIGURE 11 DESIGN EXAMPLE FOR KWIK CAST KCS-WF