Inspection Requirements For Anchors in Concrete in Accordance With ACI and

Similar documents
Bonded (Adhesive) Anchors

Chapter 1: Application and Administration

REVISIONS TO ICC-ES ACCEPTANCE CRITERIA AC308 (JUNE 2013)

PROCEDURE SPECIAL INSPECTIONS PROGRAM OP PURPOSE: POLICY: SCOPE: Michael Fink. Deputy Commissioner

CALIFORNIA BUILDING CODE

STRUCTURAL MASONRY SPECIAL INSPECTOR. Study Guide

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

Statement of Special Inspections

Advancements in Adhesive Anchor Technology

The installation of adhesive anchors (post-installed

CAMA Position on AC502

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

WACEL STUDY GUIDE. Reinforced Concrete Special Inspector (Concrete II)

International Building Code/International Residential Code Inspection & Quality Assurance Requirements for Metal Plate Connected Wood Trusses

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER:

Subject: Proposed Revisions to the Acceptance Criteria for Mechanical Anchors in Concrete Elements, Subject AC R1 (KS/ME).

The primary needs for electrical power after such an event is for the continuing operation of essential. The IBC has been updated on a threeyear

Student Services & Classroom Addition SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: MMFX TECHNOLOGIES A COMMERCIAL METALS COMPANY

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE

A. Section includes Sprayed Fire-Resistive Materials: (SFRM) A. Pre-Installation Conference: Conduct conference at Project Site.

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

Session: Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports

2639 North Monroe Street, Suite B-112 Tallahassee, FL Application for Special Inspector Certification. Rule 61G Form FBPE/006 12/17

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS SECTION: PRECAST STRUCTURAL CONCRETE SECTION: SITE CAST CONCRETE

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PEIKKO GROUP, INC.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

Introduction: Issue: Analysis/Conclusion:

SPECIAL INSPECTION PROCEDURE IBC CHAPTER 17

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

SECTION NON-STRUCTURAL SEISMIC DESIGN CRITERIA PART 1 - GENERAL 1.1 RELATED DOCUMENTS

GENERAL CHAPTER 1. SCOPE AND ADMINISTRATION 101 GENERAL SCOPE

Statement of Special Inspection Requirements

Originally Issued: 09/16/2010 Revised: 09/15/2017 Valid Through: 09/30/ Design:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Snow load design using the 2003 International Building Code

SECTION ANCHOR SYSTEMS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

Engineering judgement on the use of American s anchor performance provisions along with the European seismic action definition

Best practice specification, design and installation for post-installed anchors in safety-critical applications

SECTION SEISMIC CONTROL OSHPD

Originally Issued: 11/24/2010 Revised: 01/20/2017 Valid Through: 11/30/ Design

Special Inspections Instructions

THE ABC S OF IBC COMPLIANCE

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

FROM: PROPOSED SUBSTITUTION: Use HILTI X-CW Ceiling Wire for Suspended Ceiling Systems

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS LLC

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: PJ S REBAR INC.

VMA C (Revision 2)

Fast Cure Anchoring Adhesive

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: MITEK USA, INC.

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

PICKENS COUNTY BUILDING CODES SPECIAL INSPECTION PROCEDURE IBC CHAPTER EDITION

Special Inspections. Topics for Today. What are Special Inspections. Presented by -Chris Kehl, PE Braun Intertec Corporation

STATEMENT OF SPECIAL INSPECTION FORM

Statement. Special Inspection

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: TENDON SYSTEMS, LLC

REVISIONS. App Sud. App PC. App Thom 2011/12/31 AA 2011/12/31 NK 2012/08/09 N/A AA 2015/07/20

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

Report of Special Inspections

Quality Control and Quality Assurance for Installation of Steel Deck

Washington Association of Building Officials. Standard 1702 Steel Fabricator Registration Program

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICE EVALUATION CRITERIA FOR

The installation of adhesive anchors in horizontal to

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

3.1 General. 3.2 Materials. 4.1 General. Page 1 of 6

2/16/17. Copyright Material. A Repair Technician s Guide to the ACI Chapter 10 Quality Assurance. The Big Picture. Who is a Repair Technician?

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: DEXTRA MANUFACTURING CO., LTD.

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

ESR-3574* Issued December 1, 2013 This report is subject to renewal August 1, 2014.

Originally Issued: 07/25/2014 Revised: 07/31/2018 Valid Through: 07/31/2019

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

AC R1 # Triangle Parkway Suite 100 Norcross, Ga Phone: Fax: AC R1. September 11, 2012

High performance, 2 component adhesive anchor system use in cracked & uncracked concrete. Storage Conditions. Working & Loading Times

Post-installed reinforcement bars in structural connections

SECTION COLD-FORMED METAL TRUSSES

IBC Section references ACI 318. includes. Copyright ACI 318-D. magazine

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

Originally Issued: 02/11/2011 Revised: 02/23/2018 Valid Through: 02/28/2019

Originally Issued: 09/16/2010 Revised: 05/17/2018 Valid Through: 09/30/2019. ACI , -08, or -05, the head is considered part of the bar.

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES SECTION: REINFORCING STEEL REPORT HOLDER: SRL INDUSTRIES LTD.

2015 IBC Chapters 1 and 35

Trusted ICC ES SECTION: Conformity! Look. Evaluation. ICC-ES Evaluation

NFPA 13 Standard for the Installation of Sprinkler Systems 2016 Edition

Originally Issued: 05/20/2013 Revised: 07/07/2017 Valid Through: 05/31/ Design

PE1000+ Epoxy Injection Adhesive Anchoring System

INSPECTION REQUIREMENT ACKNOWLEDGEMENTS. Job Site Address:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF UNDERPASS LUMINAIRES

Nonstructural Components

Statement of Special Inspections

Transcription:

Delaware Valley Association of Structural Engineers Seminar Inspection Requirements For Anchors in Concrete in Accordance With ACI 318 11 and the 2012 IBC January 14, 2015 J. Silva, PE, SE, F. ACI, F. SEI Director of Codes and Standards for Hilti North America 1 Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 2 1

Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 3 What is special inspection? 1. It is NOT structural observation 2009 IBC 4 2

What is special inspection? 2. It is defined in the code. 2009 IBC 5 What is special inspection? 2. It is defined in the code. 2009 IBC 6 3

What is special inspection? 4. It can only be performed by a approved inspector NOT employed or retained by the contractor. 2009 IBC 7 Continuous or periodic? 2009 IBC Continuous inspection is often viewed as uninterrupted observation of the work in progress. 8 4

Continuous or periodic? 2012 IBC The definitions changed materially in the 2012 IBC. 9 Where is it called out? The submission of a special inspection schedule is a mandatory part of the permit process. City of San Jose Statement of Special Inspections Form 10 5

Where is it called out? The submission of a special inspection schedule is a part of the permit process. excerpted fro m Model Program for Special Inspection, ICC/IAS 11 Special inspection forms Jurisdictions develop their own requirements for how this information is to be submitted. excerpted from City of San Jose Statement of Special Inspections Form 12 6

Special inspection forms Jurisdictions develop their own requirements for how this information is to be submitted. excerpted from City of Richmond, Schedule of Chapter 17 Inspections 13 Special inspection forms Jurisdictions develop their own requirements for how this information is to be submitted. excerpted from City of Philadelphia, Statement of Special Inspections Schedule 14 7

Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 15 In the beginning......where special inspection is provided values may be increased 100 percent. 1976 Uniform Building Code 16 8

2006 IBC Note that as recently as the 2006 code, inspection was only for cast in anchors and then only if you were using increased allowable loads for design (i.e., using a FS of 4 instead of 8!). Per the code inspection was not required for post installed anchors or for anchors designed using strength design provisions, e.g., of ACI 318. 17 2009 IBC This was corrected in the 2009 IBC through the addition of a new entry for anchors installed in hardened concrete. However, note that continuous inspection for cast in anchors was still required, even for strength design, whereas post installed anchors required only periodic. 18 9

2012 IBC In the 2012 IBC, both cast in and post installed anchors require periodic inspection, unless otherwise noted as per footnote b. 19 2012 IBC Footnote b. b. Specific requirements for special inspection shall be included in the research report for the anchor issued by an approved source in accordance with ACI 355.2 or other qualification procedures. Where specific requirements are not provided, special inspection requirements shall be specified by the registered design professional and shall be approved by the building official prior to the commencement of the work. Sources of additional inspection requirements for anchors: ACI 318 code (2011 and later) ACI 355.4 Evaluation reports (i.e., ESRs) 20 10

Summary of special inspection requirements Code Anchor design 2006 IBC 2009 IBC 2012 IBC CAST IN ASD FS = 8 NOTREQUIRED NOT REQUIRED NOT REQUIRED CAST IN ASD FS = 4 CONTINUOUS CONTINUOUS PERIODIC CAST IN STRENGTH DESIGN (e.g. ACI 318 Appendix D) NOT REQUIRED CONTINUOUS PERIODIC POST INSTALLED NOT REQUIRED PERIODIC PERIODIC POST INSTALLED ADHESIVE QUALIFIED AT A LOWER LEVEL ADHESIVE ANCHORS NOT INCLUDED ADHESIVE ANCHORS NOT INCLUDED CONTINUOUS WITH PROOF LOADING POST INSTALLED ADHESIVE FOR SUSTAINED TENSION OVERHEAD TO HORIZONTAL ADHESIVE ANCHORS NOT INCLUDED ADHESIVE ANCHORS NOT INCLUDED CONTINUOUS AND CERTIFIED INSTALLERS 21 ACI 318-11 and the 2012 IBC 22 11

If you do work in structures assigned to SDC C, D, E or F, you should be aware of this issue. I highly recommend obtaining the article by Dr. Ghosh or contacting him directly at: skghoshinc@gmail.com 23 2015 IBC 24 12

2015 IBC 25 2015 IBC 26 13

2015 IBC 27 2015 IBC 28 14

Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 29 ACI 318-11 The 2011 edition of ACI 318 introduced adhesive anchors into the code. This was prompted by the 2006 failure of adhesive anchors securing the ceiling of the I 90 connector tunnel in Boston. The primary concern was for anchors installed overhead and resisting sustained tension loads (e.g., gravity loads). National Transportation Safety Board HAR07 02 30 15

ACI 318-11 The ACI code addresses this issue in several ways: 1. ALL adhesive anchor systems must be qualified to resist sustained tension loads. (D.2.3) 2. Adhesive anchors to be installed overhead must be qualified for overhead and horizontal installation. (D.3.4) 3. Adhesive anchors subject to sustained tension are subjected to a special design check using reduced bond values. (D.4.1.2) 4. Adhesive anchors installed overhead and subject to sustained tension must be installed by certified adhesive anchor installers (D.9.2.2/D.9.2.3) and must be installed under continuous special inspection. (D.9.2.4) 31 ACI 355.4-11 Continuous special inspection for adhesive anchors may also be triggered by the manner in which they are assessed under the ACI standard ACI 355.4 Qualification of Post Installed Adhesive Anchors in Concrete (ACI 355.4) and Commentary. In such cases, proof loading is also required. Threshold values for anchors subject to periodic special inspection only Threshold values for anchors subject to continuous special inspection and proof loading 32 16

Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 33 Proof loading Proof loading of anchors has been practiced in the western U.S. for many years as a means of ensuring enhanced quality control for structures resisting earthquakes. There are no widely recognized standards for proof loading. Proof loading was implemented in the construction of the Big Dig ceiling system but the proof loads were quite low (125% of the allowable design load) and the response to anchor failures (as many as 16% of the anchors tested prior to the start of construction failed to resist the proof load) was inadequate. Best practice has been summarized in a document issued by the Concrete Anchor Manufacturers Association. 34 17

Proof loading components 1. Proof loads should be established at a level that stresses the anchor within the elastic range and does not damage the anchor if it is not defective. Typical practice in California (OSHPD) is to require proof loads up to 50% of the permissible bond strength or 80% of anchor yield, whichever is less. 2. A representative number of anchors should be tested, depending on the criticality of the installation. OSHPD typically requires that 50% of all anchors be tested. Rates for non hospital work range from 10% to 25%. 3. The consequences of any anchor failing the proof load test should be appropriately severe. Typical language requires that the sample rate increase to 100% if any anchor fails the proof load. 4. Proof loads should be applied with a confined test set up. 5. Proof load specs should include permissible anchor deflection at proof load, if any. ( No visible movement. ) 35 Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 36 18

Certified installers The requirement for certified installers comes from the ACI code. It is intended to improve the knowledge base of construction personnel involved in the installation of adhesive anchors. ACI, in conjunction with CRSI, has developed a certification program for adhesive anchor installers. This certification program is comprised of a written exam and a hands on practice exam. The exam was developed largely on the basis of Hilti s experience with training of installers of adhesive anchor systems. There is a growing concern that there is/will be a deficit of certified installers. 37 Certified installers without piston plug with piston plug 38 19

Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 39 Evaluation Service Reports Inspection requirements for post installed anchors are given in the Evaluation Service Reports issued by ICC ES. These requirements are typically a summary of requirements found in other sections of the IBC and ACI codes, but may also include requirements or clarifying language not stated in those documents. ESR 2322 40 20

Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 41 General notes and specifications Correctly referencing quality control requirements for anchors in the construction documents can greatly enhance construction quality and prevent change orders. 42 21

General notes Basic requirements for anchoring are often placed on the S1 sheet. 43 General notes Proof load requirements are often stated in the General Notes. 44 22

General notes It is useful to emphasize that the manufacturers printed instructions (MPII) should be followed. This is also stressed in the anchor installer training. 45 General notes Proof loads are often shown in tabular form: 46 23

Specifications Anchor specifications are usually found in 03 15 00 Concrete Accessories 47 Specifications Installer training and certification is addressed under Quality Assurance. 48 24

Specifications Requirements on anchor installation are found under Execution. 49 Topics Special inspection 2009/2012 IBC inspection requirements ACI 318 11 inspection requirements Proof loading Certified adhesive anchor installers ICC ES supplemental inspection requirements General Notes sheet/specifications Q&A 50 25

For discussion 1. Do you use adhesive anchors for safety related structural applications? 2. Do you specify adhesive anchors with confidence? 3. Do you agree with the requirement for certified installers? 4. Would you require certification for all critical installations or just those mandated by the code? 5. How can the certification program be improved? 51 26